Cal Controls 59424-6 Operation Manual

1/32 DIN TEMPERATURE CONTROLLER MANUAL
A
B
Cutout size
onnector
V
H
Example A
:
The SSd output is allocated to SP1and wired
Example B
: The relay output is allocated to SP1 and wired to
Legend
Type Description
Sensor Range (
°C)
Sensor
Range (
°F)
Linearity
tC b
Thermocouple
Pt-30% Rh/Pt
-
6%Rh
0 to 1800
°C
32 to 3272
°F
2.0*
Resistance
Displays
0 - 20mV 4 -
20mV Setpoint Limits
Linearity
Lin1
Main
Setpoint indication
Output device
Factory setting
Recommended minimum
(1.77)
unlock
thickness
5 6
Line Neutral
Line
Neutral
-
3
(59424-6)
SAFETY INFORMATION
INSTALLATION
Designed for use: UL873 - only in products where the acceptability is determined by Underwriters Laboratories Inc. EN61010-1 / CSA 22.2 No 1010.1 - 92 To offer a minimum of Basic Insulation only. Suitable for installation within Category II and III and Pollution Degree 2. SEE ELECTRICAL INSTALLATION. It is the responsibility of the installation engineer to ensure this equipment is installed as specified in this manual and is in compliance with appropriate wiring regulations.
CONFIGURATION
All functions are front selectable. It is the responsibility of the installing engineer to ensure that the configuration is safe. Use the program lock to protect critical functions from tampering.
ULTIMATE SAFETY ALARMS
Do not use SP2 as the sole alarm where personal injury or damage may be caused by equipment failure.
EN61010 - /CSA 22.2 NO 1010.1 92
Compliance shall not be impaired when fitted to the final installation.
Designed to offer a minimum of Basic Insulation only.
The body responsible for the installation is to ensure that supplementary insulation suitable for Installation Category II or III is
achieved when fully installed.
To avoid possible hazards, accessible conductive parts of the final installation should be protectively earthed in accordance with EN6010 for Class 1 Equipment.
Output wiring should be within a Protectively Earthed cabinet.
Sensor sheaths should be bonded to protective earth or not be accessible.
Live parts should not be accessible without the use of a tool.
When fitted to the final installation, an IEC/CSA APPROVED disconnecting device should be used to disconnect both LINE and
NEUTRAL conductors simultaneously.
A clear instruction shall be provided not to position the equipment so that it is difficult to operate the disconnecting device.
These products are intended for indoor use only
MECHANICAL INSTALLATION
The Controllers are designed to be mounted in a 1/32 DIN panel cutout. The units are sleeve mounted with the front bezel assembly rated NEMA4/IP66 provided that:
the panel is smooth and the panel cutout is accurate;
the mounting instructions are carefully followed.
PANEL MOUNTING: DIN PANEL CUTOUT – MM (INCH):
1. Unplug connector before installing the controller if wiring separately.
2. Check the controller is correctly orientated and then slide into the cutout.
3. Slide the panel clamp over the controller sleeve, pressing it firmly against
the panel until the controller is held firmly. Note: to remove panel clamp the two side levers should be pressed in.
4. Refit the connector if removed. To further secure the connector, slide the
green lock. Push in to lock, pull out to unlock as shown.
5. After installation remove the protective front window label.
6. When refitting the bezel assembly it is important to press it firmly into the
sleeve until the latch clicks in order to compress the gasket and seal to NEMA4X/IP66
DIMENSIONS – MM (INCH): MULTIPLE INSTALLATIONS:
CONNECTOR
22.2 (0.87)
CLEANING:
Wipe down with damp cloth (water only) Note: The controller should be isolated before removing or refitting it in the sleeve, and electrostatic precautions should be observed when handling the controller outside the sleeve.
ELECTRICAL INSTALLATION
OUTPUT DEVICES
Two output devices are fitted to the controllers,
1 Solid state relay driver (SSd) 5Vdc +0/-15%, 10mA non isolating. To switch a remote SSR (or logic) 2 Miniature power relay (rLY) 2A/250V AC resistive, Form A / SPST contacts.
OUTPUT DEVICE ALLOCATION
Either of the outputs may be allocated for the main setpoint (SP1), the remaining being automatically allocated to the second setpoint (SP2).
Designed for use with the following supply voltages:
1). 100 - 240V 50-60 Hz 3VA (nominal) +/-10% maximum permitted fluctuation
2). 12V - 24V (AC/DC) +/-20% 3VA Polarity not required
The controller is fitted with a 250mA time lag fuse
CAUTION: Supply voltage is dependent on the specific model; check the product label to establish the correct voltage.
WIRING THE CONNECTOR
Prepare the cable carefully, remove a maximum of 6mm insulation and ideally tin to avoid bridging. Prevent excessive cable strain. Maximum recommended wire size: 32/0.2mm 1.0mm2 (18AWG). Field wiring employed must be rated for a minimum of 70 deg C.
INDUCTIVE LOADS
To prolong relay contact life and suppress interference it is recommended engineering practice to fit a snubber (0.1uf/100 ohms) between terminals 5 and 6.
CAUTION: Snubber leakage current can cause some electro-mechanical devices to be held ON. Check with the
manufacturers specifications.
1/32 DIN
CUTOUT
COLLAR
unplug
45
Optional panel adaptors are available for the controllers to be mounted in a 45x45mm (1/16DIN) cutout.
102
(4.02)
48 (1.89)
10 (0.39) max panel
24 (0.95)
8
(0.31)
PANEL CLAMP press to release
Guide for vertical & horizontal spacing
Allows clamp & c
removal … Recommended
(also see important Safety Information)
22.2 +0.3 / 0.0
(0.87 +.012 / 0)
Maximum panel thickness = 10mm
1/32 DIN CUTOUT
Allows clamp removal
Minimum
45.0 +0.6 / 0.0
(1.77 +.024 / 0)
30 (1.18) 30 (1.18) 35 (1.38)
60 (2.36) 70 (2.76) 70 (2.76)
CONNECTION DIAGRAMS:
SP2
SP2
SP1
output
Relay (rLY)
AC
­4
2A 250V
Open in
Alarm state
supply
100-240V
± 10%
50-60Hz
3VA
L
7
N
8
Load
sensor
output
Solid State
Pt100 RTD
Time Lag Fuses
Sensor
to switch the load using an SSR
Drive (SSd)
5Vdc 10mA
T/C
+
-
+
1
2
3
SSR
sensor
Pt100 RTD
Time Lag Fuses
Sensor
Drive (SSd)
5Vdc 10mA
T/C
+
2
Alarm state
switch the load using a contactor
output
Solid State
+
off in
output
Relay (rLY)
2A 250V
AC
­4 5 6
Snubber
SP1
supply
100-240V
± 10%
50-60Hz
3VA
L
7
N
8
Load
SENSOR SELECTION
tC E tC J tC K tC L tC n tC r tC s tC t
RTD
Thermocouple Thermocouple Thermocouple Thermocouple Thermocouple Thermocouple Thermocouple Thermocouple
Temperature Detector
Chromel/Con Iron/Constantan Chromel/Alumel Fe/Konst NiCrosil/NiSil Pt-13% Rh/Pt Pt-10% Rh/Pt Copper/Con
0 to 600°C 0 to 800°C
-50 to 1200°C 0 to 800°C
-50 to 1200°C 0 to 1600°C 0 to 1600°C
-200 to 250°C
32 to 1112°F 32 to 1472°F
- 58 to 2192°F 32 to 1472°F
-58 to 2192°F 32 to 2912°F 32 to 2912°F
-273 to 482°F
0.5
0.5
0.25*
0.5
0.25*
2.0*
2.0*
0.25
Pt100/RTD-2 -200 to 400°C -273 to 752°F 0.25*
LINEAR PROCESS INPUTS (INPUT MV RANGE: 0 TO 50MV)
Lin2 Lin3 Lin4 Lin5 Notes: 1) Linearity: 5-95% sensor range
0 – 100
0 – 1000
0 - 2000
2) * Linearity B:5° (70º - 500°C) K/N:1° >350°C exceptions: R/S: 5°<300°C T:1° <- -25° >150°C RTD/Pt100: 0.5° <-100°C
0 – 100
0 – 1000
0 to 400
-25 to 400 0 to 3000
-250 to 3000 0 to 3000
± 0.5% ± 0.5% ± 0.5% ± 0.5% ± 0.5%
INSTRUMENT PANEL FEATURES
Process temperature (PV) or setpoint (SP)
Setpoint SP1
Second setpoint
SP2
markers
ADJUSTMENTS
To enter or exit program mode: Press To scroll through functions: Press To change levels or options: Press
To view setpoint: Press
To increase setpoint: Press To decrease setpoint: Press To reset an alarm or fault condition: Press Notes: If in difficulty by becoming “lost” in program mode, press the INSTRUMENT ADJUSTMENTS above and try again.
When in program mode, after 60 seconds of key inactivity the display will revert to either inPt : nonE or, if the initial configuration has been completed, the measured value. Any settings already completed will be retained.
▲▼
or
together together
together or
together for 3 seconds
together
together briefly
and
together for 3 seconds to return to display mode, check
GETTING STARTED
After power-up the controller requires programming with the following information:
Type of Sensor
Operating unit
Allocation of Output Device to SP1/SP2 (Relay or SSd)
Temperature Setpoint
When the above information has been programmed into the controller it will be operational with the following factory settings.
Proportional band/Gain 10ºC/18ºF Integral time/Reset 5 mins Derivative time/Rate 25 secs
Proportional cycle-time 20 secs (Typical setting for relay output) DAC Derivative approach control 1.5 (Average setting for minimum overshoot)
INITIAL SET-UP
On power-up the controller will display the self test sequence followed by the initial display inPt : none Select input sensor.
Press and hold and use the ▲ or displayed. Release the buttons. The display will now read selected sensor type e.g. inPt : tCs
Press ▲ once The display will now read unit : none
Select unit.
Press and hold and use the ▲ or ▼ buttons to scroll through the unit selection list until the correct unit is displayed. Release the buttons. The display will read selected unit e.g. unit : °C
Press ▲ once The display will now read SP1.d : nonE
buttons to scroll through the sensor selection list until the correct sensor is
Select SP1 (Main setpoint output device)
Press and hold
To enter initial configuration into controller memory
To display setpoint
To enter setpoint
THE CONTROLLER IS NOW OPERATIONAL WITH FACTORY SETTINGS
Note: For precise control of an application the controller may need to be TUNED. Please see the following section on AUTOTUNE
AUTO-TUNE
This is a single shot procedure to match a controller to the process. Select either Tune or Tune at Setpoint from the criteria below.
The Tune program should be used when the load temperature is at or near ambient. The procedure will apply disturbances when the temperature reaches 75% of the setpoint value, causing overshoot which is monitored in order to adjust the DAC overshoot inhibit feature. Care should be taken to ensure that any overshoot is safe for the process.
The Tune at Setpoint program is recommended when:
Notes: DAC is not re-adjusted by Tune at setpoint.
Hereafter in the Manual the symbol (▲▼) signifies both buttons are held pressed for 3 seconds to ENTER or EXIT program mode.
selected output device e.g. SP1.d : SSd
Press and hold both ▲ and
The display will now read ParK and measured input variable (eg. the sensor temperature ) ParK is displayed because
a setpoint has not yet been entered.
Press and hold  The display will now read unit (eg. °C ) followed by 0
Press and hold
value. (The digit roll-over rate increases with time).
The process is already at setpoint and control is poor
The setpoint is less than 100°C
Re-tuning after a large setpoint change
Tuning multi-zone and/or heat-cool applications.
Proportional Cycle Time can be pre-selected before running the Autotune program.
and use the ▲ or ▼ buttons to select SSd or rLY as required. The controller will show the
buttons for 3 seconds (settings are not implemented or stored until this is done.
and use ▲ button to increase or ▼ button to decrease the reading and scroll to required setpoint
TUNE OR TUNE AT SETPOINT PROGRAM
Enter program ( Exit program mode (
The TUNE program will now start. The display will show tunE as the process temperature climbs to setpoint. Note: During tuning, the main setpoint (SP1) LED will flash.
When the TUNE or TUNE AT SETPOINT program is complete the PID values are entered automatically. The process temperature will rise to setpoint and control should be stable. If not, this may be because optimum cycle time is not automatically implemented. To set the cycle time see PROPORTIONAL CYCLE-TIME.
) and from the display tunE : oFF press and hold  and press ▲ to display tunE : on or tunE : At.SP
).
PROPORTIONAL CYCLE-TIME
The choice of cycle-time is influenced by the external switching device or load. eg. Contactor or SSR. A setting that is too long for a process will cause oscillation or a setting that is too short will cause unnecessary wear to an electro-mechanical switching device.
Factory set - To use the 20 sec factory set cycle-time no action is needed whether autotune is used or not.
To Manually Select AUTOTUNE Calculated CYCLE-TIME
When AUTOTUNE is completed, enter program (
) and select CYC.t in Level 1. The display will read CYC.t:20 (factory setting) To view the new calculated optimum value, press and hold both  and ▼ buttons until indexing stops. The calculated value will be displayed eg. A16. If acceptable, exit program (
To Pre-select Automatic Acceptance of AUTOTUNE Calculated CYCLE-TIME
Before AUTOTUNE is initiated select CYC.t in Level1, press and hold both  and ▼ buttons until indexing stops at A – –. Exit program (
To Manually Pre-select Preferred CYCLE-TIME
) to accept calculated value automatically.
) to implement this setting.
Before AUTOTUNE is initiated select CYC.t in Level 1, press and hold both and ▲ or ▼ buttons until indexing stops at preferred value then exit program (
) to accept.
CYCLE-TIME RECOMMENDATIONS
Internal relay : 20 seconds 10 seconds
Solid state drive : 20 seconds 0.1 seconds
SECOND SETPOINT (SP2)
SECOND SETPOINT
Configure SP2 output to operate as an alarm from SP2.A in Level 2 and set the temperature alarm setting in SEt.2 Level 1. The alarm will be triggered when the process temperature changes according to the options listed below.
dV.hi The process rises above the main setpoint by the value entered at SEt.2. dV.Lo The process falls below the main setpoint by the value entered at SEt.2. Band The process rises above or falls below the main setpoint by the value inserted at SEt.2. FS.hi The process rises above the SP2 setpoint assigned in SEt.2. FS.Lo The process falls below the SP2 setpoint assigned in SEt.2.
SUBSIDIARY SP2 MODE
The following additional alarm functions can be added to the above alarm configurations using the features found in SP2.b in Level 2
LtCh Once activated, the alarms will latch and can be manually reset when the alarm condition has been removed by
Hold This prevents any alarm operation on power-up and is automatically disabled once the process reaches setpoint in
Lt.ho Combines the effects of both LtCh & Hold. nLin T his setting is used for non-linear cooling only. Do not select if SP2 is to be used as an alarm output. Remember also to set CyC.2 to on.oFF if SP2 is used for alarms.
SECOND SETPOINT
Configure in Level 1 using CyC.2 to select proportional cycle time and bnd.2 to adjust proportioning band. For Heat/Cool operation see full Operating Manual. In on/off mode, bnd.2 adjusts SP2 hysteresis.
pressing together briefly.
order to allow normal alarm operation.
(SP2) Alarm Output
(SP2) Proportional control output
SP2 OUTPUT AND LED INDICATION STATES -
IN ALARM CONDITION
ON-OFF
Operating Mode
Proportional Operating Mode
SP2 Output State
SP2 LED State
SP2 Output State
bAnd
Temperature above setpoint
When an SP2 alarm mode is selected in SP2.A the alarm annunciator
annunciator may be disabled by selecting function
The alarm will be automatically reset when the temperature returns within the
full operating m
Display Flashes
Fault Type
SENSOR FAULT
RTD/Pt100 open or short circuit.
100°C
dAtA : FAiL
NON-VOLATILE MEMORY ERROR
hAnd : FAiL
MANUAL POWER ERROR
tunE : FAiL
IMMEDIATE FAIL ON AUTOTUNE START
FAIL LATER DURING AUTOTUNE CYCLE
The thermal characteristics of the load exceed the
algorithm limits. The failure point is indicated by
-
Function
Options
[
Factory settings
]
in brackets
Description
Select Autotune
Used to switch the Autotune feature on and off, to select
temporarily turns the output(s) off. To use select
mode. To disable re
SP1 Operating Parameters
SP1 proportional band/Gain or Hysteresis
* 25% sensor maximum
control. Heater power is reduced, by time proportioning action, across the
proportional band.
SP1 integral time/reset
SP1 derivate time/rate
SP1 derivative approach control dAC
independent of normal operating conditions, by controlling when derivative
action starts during warm
SP1 proportional cycle
Determines the cycle rate of the output device for proportional control. Select
for ON/OFF mode.
SP1 offset/manual reset
of the
Applicable in proportional and ON/OFF mode with integral disable:
Lock main setpoint
SP2 O
perating Parameters
Adjust SP2 setpoint
Deviation Alarms
Full scale alarms
Adjust SP2 hysteresis or proportional band/gain
25% sensor
Do not set
=
Select SP2 ON/OFF or proportional cycle
Select on.oFF
proportional mode.
Function
Options
[
Factory settings
]
in brackets
Description
M
anual Control Modes
Read
SP1 output percentage power
SP1 manual percentage power control
fail. Record typical
Set SP1 power limit percentage
up and in proportional band.
Set SP2 percentage power limit (cooling)
SP2 O
perating Modes
Main SP2 operating mode
Subsidiary SP2 mode: latch/sequence ,
SUBSIDIARY SP2 MODE
I
nput Selection and Ranging
Select display resolution: for display of process temperature, setpoint,
Set.2, hi.SC, LoSC
sensor minimum [sensor maximum]
Set full scale
[sensor minimum] sensor maximum
Set scale minimum
Select input sensor
Select °C/°F or process units
SP2 LED State
Action
Auto-corrects proportional control offset error
Suppresses overshoot and speeds response to
Tunes warm
-
up characteristics,
-
time
(see section ab
ove)
Locks the setpoint preventing
unauthori
sed
adjustment.
(see
CyC.2
setting)
-
time
For manual control should a sensor
Limits
maximum SP1 heating power during
Non-linear cool proportional band
(default 0°C or 32°F)
(See
SENSOR SELECTION
table)
LEVEL 3
Function
O
utput Configuration
SP1.d
SP2.d
burn
Technical
rEu.d
rEu.L
SPAn
ZEro
ChEK
rEAD
dAtA
UEr
rSET
LEVEL 4
Access to level 4 is gained through
Enter level 4 at
Function
Function Options
dEr.S
di.SS
no.AL
ProG
Security
LoCK
FUNCTION
Options
[
Factory settings
]
in
brackets
Description
utput Configuration
Select SP1 output
device
Read only’ after initial configuration.
SP1.d
Read SP2 output device
(read only)
[uP.SC]
SP1
SP2
Sensor burn
-
out/break protection
Settings affect fail safe state.
SP1
SP2
Select
output modes: Direct/Reverse
on SP1 for heating
cooling
For heat & cool applications, select
Settings affect fail safe state.
SP1
SP2
Select SP1/2 LED indicator modes
Sensor span adjust
align readings with another instrument e.g. External
Meter, data logger. See Full Operating Manual (ADVANCED SETTINGS).
Zero sensor error
(see Sensor span adjust above).
Select control accuracy monitor
[
Var] hi Lo
Read control accuracy monitor
[
Ct A]; CT b; Ct 1;
Ct 2;
Ct 3;
Ct 4;
Read Autotune tuning cycle data
Software version number
Resets all functions to factory settings
This selection will lose all of the current settings.
seconds.
Options
[
Factory settings
]
in brackets
Description
= maximum,
Disable SP2 alarm
annunciator
Program mode auto
-
exit switch.
seconds of key inactivity, select
[none] LEV.3 LEV.2 ALL
Program security using Lock
locks level 3 and 4 only
locks levels 2, 3 and 4 only
LoCK ALL
(see Operating Manual)
= maximum,
AL
Select on to disable
-AL
Auto-exit returns display to normal if 60
SPECIFICATION
External resistance:
Resistance thermometer
Linear process inputs
Applicable to all inputs
Calibration accuracy:
Sampling frequency:
Common mode rejection:
Series mode rejection:
Temperature coefficient:
Reference conditions:
Miniature power relay:
LED output indicators
non
Alarm
Type
Deviation
dV.hi
dV.Lo
bAnd
Full Scale
FS.hi
FS.Lo
CooL
Strategy
SP2 ALARM ANNUNCIATOR
during alarm condition. This
Note:
SP2 in cool strategy See section on ‘Cool Strategy’ within
ERROR MESSAGES
inPt: FAiL
Thermocouple burnout; Also shown when the process is approximately above or below the selected range value.
SP1 set to ON/OFF in CYC.t
Note: To reset and clear error press
together briefly to cancel message.
autotune any display 0.0 in tech e.g. Ctb = 0.0
FUNCTION LIST (LEVELS 1 TO 4)
tunE [oFF], on, ParK, At.Sp
bAnD 0.1 to * C/°F [10ºC/18ºF]
int.t oFF, 0.1 to 60 minutes [5.0] dEr.t oFF 1 - 200 seconds [25]
dAC 0.5 - 5.0 x bAnd [1.5]
CyC.t A – –, on.oF, 0.1 - 81 sec [20]
oFSt [0] to * °C/°F
SP.LK [oFF] on
SEt.2 0 to * °C/°F [0]
bnd.2 0.1 - * °C/°F [2.0 °C/3.6°F]
CyC.2 [on.oFF] 0.1–81 seconds
setpoint.
ParK
disturbances
on.oF
* ±50%
* *
*
CAUTION
SEt.2SP2.A
LEVEL 2
Legend
bAnd : on-off mode only
-AL- is displayed, alternating with the process temperature, no.AL : on in level 4.
anual
Check sensor/wiring
De-power briefly. Replace unit if problem persists Select proportional mode
1. If display setpoint=0 then enter setpoint
2. If SP1 set to ON/OFF in CyC.t then select proportional mode
1. Change conditions. eg. raise setpoint
2. Try tunE : At.SP
3. If the error message persists, call local CAL representative for advice.
LEVEL 1
-enter program at tunE and select oFF.
Proportional control eliminates the cycling of on-off
-up (smaller dAC value = nearer setpoint).
bAnd value, but also limited to between -273 & +818.
DV.hi, DV.Lo, bAnd 25% sensor maximum. FS.hi, FS.Lo sensor range f/s
full scale.
0.5 x SEt.2 if used with a band alarm (e.g.
bAnd in level 2) as this would stop the alarm disengaging.
for ON/OFF mode, or the cycle rate of SP2 output device for
Always set to on.oFF if SP2 is used for alarms.
bnd.2 setting in Level 1.
Output ON
(relay or SSd energised)
Output OFF
(relay or SSd
de-energised)
LED ON
ParK or tune at
ParK and exit program
Int.t : oFF.
Thermocouple
Standards:
[nonE] rLY SSd
[nonE] SSd rLY
dn.SC 1u.2d 1d.2u
[1r.2d] 1d.2d 1r.2r 1d.2r
[1n.2n] 1i.2n 1n.2i 1i.2i
[0.0] to ±25% sensor maximum
[0.0] to ±25% sensor f/s
[oFF] on
oS 1; uS and oS 2
[nonE] ALL
Lock, release ▲ or
0.1 to 1.0 [0.5] Derivative sensitivity
Dir, 1 to 32 [6] Display sensitivity
[oFF] on
[Auto] StAY
Upscale Downscale Upscale Downscale
Reverse Direct Reverse Direct
Normal Invert Normal Invert
Upscale Downscal e Downscal e Upscale
Direct Direct Reverse Reverse
Normal Normal Invert Invert
UEr in level 3. Press and hold or ▼ for 10
together. Display reads LoCK nonE
Note: ‘
settings required to change
CAUTION:
Select Reverse Select Direct on SP1 for
CAUTION:
For recalibrating to
CAUTION:
dir = direct display of input 1
LEV.3 LEV.2 ALL locks all functions
rSET ALL full reset to factory
subsequently.
- output increases as process value rises
- output increases as process value falls.
1r.2d and in Level 2, set SP2.A to Cool
32 = minimum sensitivity
StAY to disable
- Technical Functions.
- Configuration and technical Functions.
CJC rejection:
Standards: Bulb current:
mV range:
Output devices
SSd :
General
Supply Voltage:
Displays: Digital range ­Hi-res mode -
Keypad:
Environmental
Humidity: Altitude: Installation: Pollution: Protection: EMC emission: EMC immunity: Ambient: Moldings: Weight:
Approvals
100maximum
9 types IPTS 68 / DIN 43710 20:1 (0.05°/°C) typical
RTD-2/Pt100 2 wire
DIN 43760 (1000°C/138.5100°C Pt)
0.2mA maximum
-10 to 50mV
(SM = sensor maximum)
±0.25%SM ±1°C
input 10Hz, CJC 2 sec.
Negligible effect up to 140dB, 240V, 50-60Hz
60dB, 50-60Hz
150ppm/°C SM
22°C ±2°C, rated voltage after 15 minutes settling time.
Solid state relay driver: To switch a remote SSR 5Vdc +0/-15% 10mA
form A / SPST contacts (AgCdO) : 2A/250ac resistive load
100-240V ±10% 50-60Hz 3VA - dependent on specific model. 24V ±20% 3VA - dependent on specific model. 12V ±20% 3VA - dependent on specific model. 4 Digits, high brightness green or red LED. 10mm (0.4”) high.
-199 to 9999
-199.9 to 999.9
- SP1 round, green or red; SP2 round, green or red 3 elastomeric buttons
Max 80% up to 2000M Categories ll and lll Degree ll NEMA 4X, lP66 EN50081-1 FCC Rules 15 subpart J Class A EN50082-2 0-50ºC (32-130°F) Flame retardant polycarbonate 100g (3.5oz),
CE, UL (file number E81867), cUL
-isolated
MENU
SPI.P 0 to 100 % ‘read only’ hAnd [oFF] 1 to 100 % (not in ON/OFF)
PL.1 100 to 0 % duty cycle [100]
PL.2 100 to 0 % duty cycle [100]
SP2.A [none] dV.hi dV.Lo bAnd FS.hi FS.Lo
SP2.b [none] LtCh hoLd nLin
di.SP [1] 0.1
hi.SC
Lo.SC
inPt [nonE] Unit [nonE] °C °F bAr Psi Ph rh
Cool
°C/°F
°C/ºF
warm-
See the “
SP1.P values beforehand.
” section on page 1 for more details.
OFSt,
Loading...