Cadex C4000 SERIES User Manual

CADEX C4000 SERIES
SATTERY ANALYZER
USER'S MANUAL
CADEX ELECTRONICS INC.
111- 7400 MacPherson Ave.
Burnaby, B.C. Canada V5J 5B6
Fax (604) 451-7991
Toll Free 1-800-565-5228
WARRANTY
DISCLAIMER
REVISIONS
TRADEMARK
COPYRIGHT
CADEX ELECTRONICS INC. warrants the Cadex C4000 Battery Analyzer against defective materials and workmanship for ONE YEAR from the purchase date. Service is available by returning the unit to the manufacturer. The manufacturer will assume one half of the shi in cost.
The information contained herein is accurate to the best of our knowledge and belief. Since the conditions of handling and use are beyond our control, we make no guarantee on results if equipment is improperly handled or misused.
CADEX ELECTRONICS INC.
reserves the right to revise this publication and make changes in the contents hereof without obligation to notify any person of such changes.
CADEX
is a registered trademark of CADEX ELECTRONICS
INC.
Copyright (c) 1993 by
CADEX ELECTRONICS INC.
All rights
are reserved. No part of this publication or the firmware
controlling the CADEX product(s) may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language or computer language in any form or by any means, electronic, mechanical, magnetic, optical, chemical, manual or otherwise without the written permission of CADEX ELECTRONICS INC. 111- 7400 MacPherson Ave. Burnaby, B.C., Canada V5A 3G1. Document MUC49503 Firmware Versions V3.00 &V3.00P
DO'S AND DONT'S
Do: Connect the C4000 Battery Analyzer to the correct line voltage.
The operating voltage is indicated on the instrument label on bottom of the unit.
Recharge NiCd batteries between SoC and 3S 0C (410F and 96 oF). Fast-charging outside this temperature range may cause damage
to the battery.
Note Allow cold battery to warm up before charging;
Allow hot battery to cool before charging.
Use the correct battery for which the adapter is configured to. Failure to do so may cause damage to the battery. Battery parameters
can be verified by pressing the appropriate Display Key when the Station is empty.
Don't:
Clean battery contacts before servicing
Do not short leads from one Station to another or to the case. An electrical short to any point outside the Station bypasses the current regulation loop and will cause a fuse to blow. A shorted battery will
cause no harm.
Do not transmit in close proximity. The C4000 is equipped with high frequency switch-mode power supplies. The advanced circuits may be sensitive to RF interference.
Rule of Thumb: The following distances should be observed when
transmitting:
0.5 Watt of transmit power=0.3m (1')
1 Watt of transmit power=0.6m (2') 2 Watts of transmit power=1.2m (4') 4 Watts of transmit power=204m(8')
Do-not restrict the airflow of the analyzer. Leave the fan opening
clear. Fan operation is automatic.
Do not expose LCD to direct sunlight.
WARRANTY DO'S AND DON'TS
Table of Contents
I
II
CHAPTER 1 - INTRODUCTION
1-1
1. Overview of Cadex C4000
1-2
2. Getting Started
1-3
CHAPTER 2 - BASIC OPERATION
2-1
1. Power Up
2-2
2. Analyzing Batteries
2-3
3. Evaluation of Battery Results
2-6
CHAPTER 3 - PROGRAMS
&
TARGET CAPACITY
3-1
1. Application Table
3-2
2. Prime
3-3
3. Charge
3-5
4. Auto
3-6
5. Custom
3-8
6. Standby
3-8
7. Target Selector
3-9
8. Calculation of Target Capacity
3-10
CHAPTER 4 - STATUS INDICATORS
4-1
1. LED Indicators
4-2
2. Audible Tone Signals
4-3
3. Status Indicator Tables
4-4
4. Display (LCD)
4-6
5. Display Messages
4-8
CHAPTER 5 - FAULT CODES
5-1
1. Application Tables
5-2
2. Correctable Faults
5-4
3. Voltage Faults
5-6
4. Timing Faults
5-9
5. Temperature Criteria
5-10
6. Electrical Limitations
5-11
7. Corrected Faults
5-12
CHAPTER 6 - BATTERY ADAPTERS
6-1
1. Battery Adapter Styles
6-2
2. Installation
6-4
3. Battery Adapter Errors
6-5
Table of Contents
CHAPTER 7 - PROGRAMMING BATTERY ADAPTERS
7-1
1. C-Code Definition
7-2
2. C-Code Structure
7-3
3. Quick View of Battery Parameters
7-4
4. Menu Tree
7-4
5. Menu Functions
7-6
CHAPTER 8 - UTILITIES
8-1
1. Reset to Factory Default
8-2
2. Copy Settings
8-3
3. Set Password
8-3
4. Station Target Capacity
8-5
5. Company Name
8-5
6. Calibrate Station
8-6
CHAPTER 9 - CUSTOM PROGRAMS
9-1
1. Setting up Custom Program
9-2
2. Typical Applications
9-5
3. Code Definition
9-8
4. Program Variations
9-11
CHAPTER 10 - OPTIONS
10-1
1. Data Retention
10-2
2. DatelTime
10-3
3. Printer Interface
10-4
4. Print Formats
10-5
5. Computer Interface
10-7
6. Event Log
10-8
CHAPTER 11 - C-CODE TABLES
11-1
1. Battery Type
11-7
2. Number of Cells
11-8
3. Battery Rating
11-9
4. C-Rate
11-11
5. Trickle Charge
11-13
6. Recondition Discharge
11-14
7. Capacity Offset
11-15
8. Temperature Sensor
11-17
9. Negative Slope
11-17
10. End of Discharge
11-18
11. End of Recondition (NiCd, NiMH)
11-19
12. charge method
11-19
13. Float Voltage (SLA)
11-20
14. Voltage Limit (SLA)
11-21
15. Topping Charge Plateau (SLA)
11-22
CHAPTER 12 - DIAGNOSTICS
1. RAM/Clock/LCD Check
2. Start-up Messages
CHAPTER 13 - SERVICE
1. Static Precautions
2. Replacing Fuses
3. Replacing Back-up Battery
4. Replacing the EPROM
5. Installing OPTION-P
6. Motherboard Layout
CHAPTER 14 - SPECIFICATIONS
APPENDIX GLOSSARY INDEX
Table of Contents
12-1
12-2 12-3
13-1
13-2 13-2 13-3 13-5 13-6
13-8
14-1
A-1
G-1
1-1
CHAPTER 1
CHAPTER 1
INTRODUCTION
1-1
INTRODUCTION
Introduction
1. Overview
of Cadex C4000
-ON-OFF S .
witch on the b
ack panel
Liquid Crystal Display (LCD)
Station with
out Battery Adapters
Program Selector Switch
Run Read~
Fail'Y~
LED Indicators (0
ne group
per Station)
1-2
Menu Key
Display Key
Target Selector S .
witch
Introduction
2. Getting Started
Plug in and turn on Plug and on-off switch are located on the back of the
C4000.
Select the program The Program Selector Switch is on the front of the
analyzer.
Select: PRIME for new or stored batteries prior to use
CHARGE for fast-charging only (no analysis)
AUTO to service batteries with unknown conditions.
Set Target Selector Target Selector switch is on the right hand side of the
front panel.
Select: 80% for most requirements
90% or 100% for more demanding applications
60% or 70% for less critical applications.
Battery Adapter
Insert the Battery
When battery servicing is complete
Display
Configured Battery Adapters are pre-programmed for specific battery types. To reprogram, refer to CHAPTER 7 - PROGRAMMING BATIERY ADAPTERS .
When contact is made, a "Beep" is heard and the
yellow RUN LED comes on.
The Green READY LED is on if the battery has successfully completed the program.
The red FAIL LED comes on if the battery has failed to
meet the specified requirement.
Global The status of each battery is shown on the top line of
the LCD display. The lower section of the LCD shows the relative voltage of each battery in a line-graph form.
Detailed Detailed information about the battery can be seen by
pressing the corresponding Display Key.
After completion of the program
Record the test results. The battery may be removed or left in the analyzer until needed. When the battery is
removed, the test results are canceled .
1-3
CHAPTER 2
BASIC OPERATION
CHAPTER 2
BASIC OPERATION
2-1
Basic Operation
1. Power Up
Start-up messages
Global Display
Battery Adapters
Before connecting the C4000, check for the correct line
voltage. The line voltage label is located on the bottom
of the unit. The on-oft switch is on the back panel.
When the power is turned on, the display (LCD) message briefly reads:
:,gM9!:"(ll~'.::.B.~::.eEElmgrff:!~nISi:.:::.:
:):;i }:;:),:::::::
:MeBstQN#::alQOfR:::::n::QIAGNQSTIGS}PA$$}~;tjj: :::',::::: .
The display then shows the Target Capacity setting briefly, then switches to the Global Display. If the Battery Adapters are installed in Stations 1, 2 & 3, but not 4, the display shows:
The analyzer is now ready to service batteries in Stations 1, 2&3.
Note It is advised to install a Battery Adapter in all vacant stations. This prevents damage by static electricity.
The batteries interface with the C4000 through Battery Adapters. You can install, replace and reprogram the adapters while other batteries are being serviced. For more details on the various types of Battery Adapters, refer to CHAPTER 6 - BATTERY ADAPTERS.
2-2
Basic Operation
2. Analyzing Batteries
Set Program
Before servicing a battery, select the desired program
(refer to CHAPTER 3 - PROGRAMS & TARGET
CAPACITY).
Set Target Capacity
Select the Target Capacity. If you are not certain what setting to use, select 80%. For more detail. refer to CHAPTER 3- PROGRAMS & TARGET CAPACITY.
Verify correct battery setting
Check that the Battery Adapter is set to the correct battery parameters. With the display indicating EMPTY, press the appropriate Display Key. The display now indicates the setting of the Battery Adapter in question.
STATIQII 4
ZOfE 2
VQ.TAGE
Battery rating
STATION 3
STATION 2
Battery voltage
NiCd
(STD.);
AUTO-SCALED
12 CELLS
(15.00V); 4000 mAh
Z0fE1
EN) OF
DISCHARGE
SHORT
#2
1
2 3
4
EN) OF
Number of cells
C4000 Battery Parameter Display For A NiCd Battery
Station number
STAros
VQ.TACE
Figure 2.1
Viewing different
display frames
Since not all information can be shown on one display frame, the battery parameters are contained in several frames. The basic information is shown in the first frame. followed by more detailed definitions in the subsequent frames.
To step through the frames, press the appropriate
Display Key several times. For more details on the display, refer to CHAPTER 4 - STATUS INDICATORS.
Reverse polarity and
short protection
The C4000 is electronically protected against reverse connection and short circuits. No harm is done to the equipment if the battery has a short or is accidentally connected in reverse polarity .
2-3
Basic Operation
"Dead" batteries
Connect battery
Program Sequence
PRIME and AUTO
If the battery to be serviced has no voltage reading, an
initial brief charge by a designated charger is required. The C4000 will not start the program if battery voltage is not detected.
After selecting the program and target capacity, you are
now ready to connect the battery. Battery connection is
acknowledged with a beep tone. While the battery is being serviced, the yellow RUN LED is on.
The program starts with discharge, followed by charge. If the battery has no capacity (no energy), the program
starts with charge.
CHARGE On the CHARGE program, the battery commences with
charge. No discharge is applied.
Method of battery
analysis
Definition of battery
capacity
It is not possible to obtain an immediate capacity reading by inserting a battery. The capacity is derived by discharging the battery at a calibrated current to the end-of-discharge threshold voltage. The elapsed time is measured and displayed as the derived battery
capacity.
When the batt-ery starts discharging, the Global Display
reads "CAP: 0%". The flashing capacity figure indicates that the number is counting upwards. When the battery voltage has dropped to the end-of-discharge threshold, the discharge terminates. The readings stop flashing and the true capacity is then known.
Several capacity readings may be shown. If more than five discharge-charge cycles have been applied, the 2nd, 3rd, 4th and 5th readings indicate the latest four capacities. The first reading (Residual Capacity) remains visible at all times.
The capacity reading is the percentage of the
manufacturer's battery rating. The rating is measured in
mAh (milliampere per hour). For more information, refer to CHAPTER 11, "3. Battery Rating".
2-4
Interrupt
Changing control
settings
Full Load
Basic Operation
Example
A fully-charged battery rated at 1000mAh
must be able to provide a discharge current of 1000mA for one hour. If the battery can provide this current for that time, the derived capacity is 100%. If the battery can only provide the current for 30 minutes, the capacity is 50%.
When a battery is disconnected while in service, a beep
tone sounds. If the battery is reconnected within five seconds, service resumes without interruption. If not re- connected, the Station resets to EMPTY in five seconds and the battery data is lost.
Pressing the Display Key during the five-second
interrupt resets the Station immediately.
Changing the Program Selector while a battery is
serviced does not affect the program in progress. To
restart with a different program, remove the battery and press the appropriate Display Key to reset the station. Select the new setting and re-insert the battery .
Changing the Target Selector during service is possible. Since the Target Capacity setting is read at the end of each discharge, the effect of changing the setting will
depend on the battery's position in the program
sequence at the time of change.
Batteries requiring charge or discharge power in excess
of the unit's capacity are put on a waiting queue. The display message for batteries on hold reads WAITING.
When the charge or discharge power becomes available, a battery that is waiting resumes service.
Note Energy from discharging batteries is used to charge the other batteries .
2-5
Basic Operation
3. Evaluation of Battery Results
Global Display The status of each battery in service is shown on the
first line of the display. The average cell voltages are displayed in bar-graph form on the second line.
Detailed Display Pressing the Display Key allows you to get more detail
on the battery services. Several capacity figures are shown on multi-cycle programs. Average cell voltage and battery Fault Codes (if present) are also displayed. For more information, refer to CHAPTER 5 - FAULT
CODES.
Evaluation by LEDs
PRIME and AUTO
CHARGE
Evaluation by display
Each Station is equipped with RUN, READY and FAIL
LEOs. During service, the RUN LED is on. When the program is completed and the battery has met or exceeded the Target Capacity, the READY LED lights up. If the Target Capacity has not been reached, the FAIL LED comes on. A flashing FAIL indicates incorrect
battery voltage due to defective cells.
Since no capacity reading is taken on the CHARGE program, the READY LED blinks when the battery is fully charged. For a summary of LED signals, refer to CHAPTER 4-STATUS INDICATORS.
In addition to the RUN, READY and FAIL LEOs, the
C4000 is equipped with an aO-character display.
2-6
CHAPTER 3
PROGRAMS&TARGET CAPACITY
CHAPTER 3
PROGRAMS & TARGET CAPACITY
3-1
Programs
&
Target Capacity
Introduction
Selection
Indicators
The CADEX C4000 features user-selectable programs with decision-making capabilities that evaluate the bat- tery and apply an appropriate service to improve or
restore a battery. This section explains the different applications, and recommends the best choice of program and target capacity settings to be used.
The programs are selected through the Program Selec- tor Switches on the front panel of the C4000. You can set each Station to a different program.
Important Select the correct program before connecting the
battery. Changing the setting after the battery is connected will have no effect.
While the program is running, the RUN LED for that Station is on. The program is completed when the RUN LED turns off and either the READY or FAIL LED comes on (refer to CHAPTER 4-STATUS INDICATORS).
1. Application Table
Table 3.1 summarizes the typical applications of program setting.
PRIME
CHARGE
AUTO
WHEN TO USE IT
Prepare new batteries for
Fast-charge only.
Restore batteries affected
field use.
by "memory".
Condition batteries that
Top-up charge of
Identify marginally
have been in storage.
partially discharged
performing batteries.
batteries.
Verify battery condition
Weekly or monthly routine
to support a warranty
battery maintenance.
claim.
TIME (in hours)
NiCd
l
5 to 10
1.5
2.5 to 10
NiMH2
10 to 20
3
5 to 18
SLA3
40 to 80
10
20 to 40
Table 3.1
(Time at Default C-Rate of 1C. zTime at Default C-Rate of 0.5C. 3Time at Default C-Rate of 0.3C charge and 0.1 discharge.
3-2
Programs & Target Capacity
2. Prime
When to use it
Program time
How it works
Prepare new batteries for field use.
Condition batteries that have been in storage.
Verify battery condition to support warranty
claim.
PRIME is used to condition new batteries prior to use. A
new (or stored) battery may require several charge/
discharge cycles until peak performance is reached.
The time required may vary depending on the battery type. At a C-Rate of 1C, the program time is:
NiCd 5 to 10 hours
NiMH 10 to 20 hours
SLA 40 hours or longer.
For more information on C-Rates. refer to CHAPTER 11 - C-CODE TABLES .
The battery first discharges to the end-of-discharge threshold voltage and recharges. A second discharge- charge cycle is applied and its resulting capacity is compared with the first reading.
5
% improvement
Very low-capacity
battery
If the improvement is 5 % or higher, a further charge- discharge is applied. This cycle is repeated until the improvement is less than 5 %. At this percent, it is assumed that the battery has reached the peak performance. The program concludes with a final charge.
A battery that cannot obtain a capacity of 5% is cycled
four times. This feature allows additional priming cycles
on a new battery that cannot accept a full charge at first.
Empty battery A fully-discharged battery will proceed with charge
immediately.
Trickle charge After the service is completed, trickle charge is applied.
If one or more cells within the battery are bad then the battery fails. No trickle charge is applied.
3-3
Programs & Target Capacity
Indicators
Lights
READY if the battery meets or exceeds the Target Capacity. FAIL if the battery cannot meet the Target Capacity .
Display
When the program is successfully completed, the Global Display shows the Final Capacity reading. By pressing
the appropriate Display Key, the display shows
additional information. If the battery failed, a Fail Code is
shown (refer to CHAPTER 5 - FAULT CODES).
The Global Display shows a maximum of five capacity readings on PRIME. The first reading is the Residual Capacity, the middle readings are the Transitional Capacities and the last is the Final Capacity.
Residual Capacity is the charge that is left before
Transitional Capacities are the middle readings.
Final Capacity represents the final reading.
3-4
Programs
&
Target Capacity
3. Charge
When to use it
Program Time
How
it
works
Top-up partially charged batteries.
Serves as a fast-charger.
The time required may vary depending on the battery type. At a C-Rate of 1C, the charge time is:
NiCd 90 minutes typically
NiMH 3 hours typically
SLA 10 hours typically.
For more information on C-Rates, refer to CHAPTER 11
- C-CODE TABLES.
CHARGE fully charges a battery. After full charge is
reached, trickle charge is applied to maintain full charge capacity. Full charge is detected by the Negative Slope method. Poorly matched cells that do not produce an adequate slope are timed out by the Plateau Timer. The combination of these two methods provides an accurate and safe means to terminate the fast-charge. No temperature sensing is required if the battery is serviced
within the recommended temperature range.
Partially or fully charged The analyzer recognizes a partially or fully charged
batteries battery. On these batteries, the charge time is
shortened accordingly. A shorter charge time also applies to batteries that have a low capacity.
Reverse Load Charge Reverse Load Charge is used to promote the
Method recombination of gases generated during the fast-
charge of the NiCd and NiMH batteries. The Reverse Load Charge intersperses discharge currents between the charge pulses. The results are a cooler and more effective charge than conventional chargers. In addition,
the "memory" phenomenon is reduced as the battery is
stimulated while charging. Refer to "4. Auto" for
definition of memory.
Note Reverse Load Charge is used for all charge and
trickle charge functions .
3-5
Programs & Target Capacity
Indicators
LEDs
Blinking READY if the battery is fully charged (blinking
indicates that no capacity evaluation was taken). FAIL if the voltage is too low.
Display
When the program is successfully completed, the Global Display shows "DONE". If the battery failed, a Fail Code is shown (refer to CHAPTER 5 - FAULT
-CODES).
4. Auto
When to use it
Exercises batteries to maintain peak performance. Reconditions those NiCd batteries that are unable to
reach the Target Capacity. Identifies and "weeds out" marginally performing bat-
teries.
Applies battery maintenance for battery fleet.
AUTO is the recommended program for routine
maintenance of NiCd batteries. Batteries that meet the Target Capacity are exercised to retain the optimal performance. Batteries that are unable to reach the target are reconditioned. This program is effective in
restoring batteries with "memory".
Memory
Memory is a crystalline build-up that forms when the battery is repeatedly recharged without sufficient discharge. This phenomenon occurs on NiCd batteries only and causes progressive capacity degradation.
Program Time
The time required may vary depending on the battery type. At a C-Rate of 1C, the program time is:
NiCd
2.5 to 10 hours
NiMH
5 to 18 hours
SLA
20 to 40 hours.
For more information on C-Rates, refer to CHAPTER 11
- C-CODE TABLES.
3-6
How it works
If Residual Capacity
meets target
Programs
&
Target Capacity
The battery is first discharged to one volt per cell during which the Residual Capacity is measured. If the capacity meets or exceeds the target, a final charge is applied. Typical program time is 2 to 3 hours
If Residual Capacity is If the Residual Capacity is below target, the battery is
below target fully recharged and a second discharge is applied to
measure the full-charge capacity.
If second discharge If the second discharge meets the Target Capacity, the
meets target program concludes with a final charge. The READY
LED comes on.
NiCd, NiMH If the Final Capacity meets the target, the READY LED
comes on. If below target, the FAIL LED comes on.
If second discharge
capacity is below target
Indicators
If the second discharge capacity is below target, Recondition is applied. The battery is fully recharged and discharged once more to measure the Final
Capacity. A concluding charge follows.
SLA For SLA batteries, AUTO consists of 1 or 2 discharge/
charge cycles. Recondition is omitted.
For more information on the NiCd battery, refer to a separate publication referred to as "Characteristics of
Rechargeable Batteries".
Recondition
Recondition is a controlled deep discharge that removes the crystalline build-up, or "memory", on the cell plates .
3-7
Programs
&
Target Capacity
5. Custom
The Custom Program is used if a special function or a sequence of functions is required, such as:
Discharge only for purpose of shipping or storage
Long-term reliability test by cycling the battery until the capacity drops below the set Target Capacity.
The information on this program is extensive. Refer to CHAPTER 9 - CUSTOM PROGRAMS for details.
6. Standby
Standby automatically runs 30 days after the battery has completed AUTO, PRIME or CHARGE.
Why is it needed
If a NiCd battery is left on trickle charge for prolonged periods, deterioration due to "memory" occurs (refer to "4. Auto" for definition of memory).
On the other hand, if a fully-charged battery is placed on the shelf, it is subject to significant self-discharge.
Self-discharge Approximately 10% of the battery's charge is lost in the
initial 24 hours. The self-discharge is reduced to 10% per month thereafter. At higher storage temperatures, the self-discharge rate is higher. Likewise, older bat- teries have a higher self-discharge than a newer one.
What does it do
How
it
works
Maintains batteries that must be kept charged for unscheduled use.
Makes fully-charged batteries available for equipment rental.
Verifies long-term battery performance.
Standby applies a discharge-charge cycle after the battery has been on trickle charge for 30 days. The setting of the Program Selector has no effect on the Standby operation. The capacity readings are displayed as per the PRIME program.
3-8
Programs & Target Capacity
7. Target Selector Setting
The Target Capacity is set through the Target Selector Switch. The setting is global and applies to all Stations.
Individual Target Capacity settings are possible through the menu-driven interface. Refer to CHAPTER 8 - UTILITIES, "4. Station Target Capacity".
Select 80% for most applications
The Target Selector lets you set the minimum acceptable level you must obtain from a battery. If uncertain what setting to use, select 80%.
Note The Target Capacity setting does not affect the
charge level; the batteries are always fully charged regardless of the setting.
The suggested Target Capacity settings are as follows:
60%, 70% The low-end Target Capacity settings are used for
applications where the battery power demand is not critical or is of brief duration. These settings pass the largest number of batteries when serviced.
80% This is the most common Target Capacity setting. It
satisfies the need for adequate energy reserve as well as economical use of the batterY fleet.
90%, 100% The high-end Target Capacity settings are used for
critical applications that require maximum energy reserve and high reliability. These settings pass the least number of batteries when serviced .
3-9
Programs
&
Target Capacity
8. Calculation of Target Capacity
To establish a workable target setting for your require-
ment, the following evaluation is recommended:
Use a battery with a known working-capacity reading
Fully charge the battery and use it in a normal field situation
Measure the remaining capacity after the routine shift.
Select PRIME or AUTO and insert the battery. The first discharge reveals the Residual Capacity. The second discharge is the Full Capacity.
With the Residual and Full Capacities known, the consumed energy can be calculated by deducting the Residual Capacity from the Total Capacity.
Example of Target Working Capacity of battery when fully charged
Capacity calculation Residual Capacity after a routine shift
Consumed Capacity
100%
20%
80%
Recommended Target
Capacity setting
If the Residual Capacity is less than 20%, the Target Capacity should be increased by 10%. Likewise, if the Residual Capacity is 30% and higher, the Target Capacity may be reduced by 10%.
3-10
CHAPTER 4
STATUS INDICATORS
CHAPTER 4
STATUS INDICATORS
4-1
Program in progress Program completed Test results negative.
Status Indicators
Introduction
1. LED Indicators
The light-emitting diode (LED) provides the user with a quick overview of the battery test results. The battery status is indicated for each Station by the LEOs as
follows:
RUN (yellow) READY (green) FAIL (red)
Detailed battery test results are shown on the 80-
character display.
RUN
steady Battery service in progress.
blinking"
Below temperature range for charge; will proceed automatically when temperature rises to acceptable level.
READY
steady
Battery ready; capacity not available or capacity compared to target setting
blinking
Battery ready; CHARGE mode only.
FAIL
steady
Program completed; Target Capacity not met.
blinking
Battery voltage fault; cannot be corrected.
POWER
steady
Analyzer operational; normal condition.
blinking
Analyzer is on hold because its internal temperature is above operating range; resumes when normal.
Temperature trigger point: 70°C (158°F) .
Minimum hold time: 1 minute .
READY
blinking"
Battery hot; program terminated (CHARGE program
and FAIL
only).
MENU
steady
Menu mode. Batteries in service are not disrupted by
the menu but resume service as usual.
" with temperature sensor option only
4-2
Status Indicators
2. Audible Tone Signals
The C4000 Analyzer produces a variety of audible signals to mark events such as buttons pressed or programs ending. The signals and the events are listed below.
Single beep tone:
Battery connected (long beep)
Display Key pressed (short beep)
Menu Key pressed (short beep).
PRIME/AUTO: Target Capacity met or exceeded.
Triple beep: (High pitch)
Ready
CHARGE:
Full charge done.
Continuous tone
Triple beep: (Low pitch)
Wailing sound
Ready
PRIME/AUTO: Target Capacity not met.
Shorted battery, not serviceable. Remove battery or press Display Key to stop tone .
Wrong polarity. Remove battery and reverse connection.
Fading tone (gong)
Low tone
New battery parameters stored in Battery Adapter.
New battery parameters not accepted, or invalid parameters .
4-3
Status Indicators
3. Status Indicator Tables
Table 4.1 summarizes the LED and sounder schedules.
CONDITION
LEOs
SOUNDER MODE COMMENTS
NO BATIERY
Open terminal
RUN
off
silent
reset
Station resets
READY
off
when battery
FAIL
off
removed.
BATTERY
Battery in
RUN
single beep active
Beep tone when
INSERTED
service
READY
off
service
battery inserted.
FAIL
off
BATTERY READY
Normal battery
RUN
off
triple beep trickle
Target capacity
(CHARGE)
voltage
READY ___
charge
not used in
FAIL
off
CHARGE mode.
BATTERY READY
Battery capacity
RUN
off
triple beep trickle High-pitch triple
(PRIME or AUTO)
meets target
READY
charge
beep if READY;
capacity
FAIL
off
low pitch if FAIL.
Battery fails to
RUN
off
silent
trickle If program was
meet target
READY
off
charge
PRIME, try
capacity
FAIL
AUTO.
REVERSE
Leads are
RUN
off
wailing no charge
Check leads.
POLARITY/SHORT
reversed or
READY
off
Charge battery in
battery has low
FAIL
manufacturer's
voltage
specified charger.
Do not leave battery unattended.
LOW VOLTAGE
Battery has
RUN
off
silent no charge
Partial short. low
shorted cell(s)
READY
off
voltage or
FAIL
depressed V. Discard battery.
SOFT BATTERY
Battery voltage
RUN
off
silent no charge
Charge
rises too high
READY
off
terminated,
FAIL
•••
••
discard battery.
INTERMITTENT
Unable to clamp
RUN
off
silent
no charge Check condition.
battery voltage
READY
off
FAIL
Table 4.1
4-4
CONDITION
LEOs
SOUNDER
MODE
COMMENTS
COLD BATTERY
Temperature
RUN
---
silent
trickle
Trickle charges
below +10°C
READY
off
charge
until room temp.
(+50°F)
FAIL
off
is reached, then fast charge.
HOT BATTERY
Battery reaches
RUN
off
silent
trickle
Battery is
TERMINATED
+45°C (+113°F)
READY' ___
charge
considered fully
FAIL
charged .
Temperature Sensor (optional)
Table 4.2
Thermal Protection
Status Indicators
The sensor inhibits fast charging outside the operational temperature range. Battery sensing is not required if the batteries are serviced within the specified temperature range.
The temperature sensor measures the cell temperature of the battery. The sensor may be part of the battery assembly or installed externally.
The C4000 is thermally protected by a fan and an
internal thermal cutoff.
System Fault
Fan The cooling fan engages at 45°C (113°F) and turns off
at 35°C (95°F).
Heat Rail If the internal heat rail exceed lO°C (158°F), the service
is suspended and resumes when the temperature has dropped (refer to Table 4.3).
The C4000 performs a number of diagnostic tests when turned on.
If a system fault occurs during operation, the LEDs may flash at random and the unit will not respond as usual. Turn the power off and on again. If the condition persists, do not attempt to service any batteries. Turn
the unit off and call for service .
1CHARGE mode only.
4-5
Loading...
+ 122 hidden pages