Caddy T-30 Installation Manual

Page 1
Installation instructions for Plenum-mounted add-on electric heaters
Aug. 2008
Version 4
Page 2
Page 3
Page 4
Page 5
If a cooling coil is installed in the warm air plenum a minimum distance of 3" or 7" is required between the top of the cooling coil and the add-on heater (depending from which side of the plenum the add-on heater is inserted). (Please see Fig. 4) In both cases, a minimum distance of 2" must be kept between the top of the add-on heater and the elbow, Tee or plenum-end take off of the main supply duct.
1
The heater may be installed on any available side of the plenum. An installation and service clearance of 28 inches is required from the heater control box to a wall, partition or any other obstruction.
If the heater is installed on the same side as the flue pipe a minimum clearance of 10 inches must be maintained between the flue pipe and the heater control box. (Please see Fig. 5)
Select the plenum side, which offers the most space for installation and service.
VERY IMPORTANT BAFFLES MUST ASSURE MAXIMUM AIR FLOW OVER THE HEATING ELEMENTS.
- Screw the baffles to bottom flanges of casing, as shown in Fig. 6.
- Cut baffles to size allowing only 1/8" clearance for insertion of heater.
AIR FLOW All the air from the furnace must pass through the heater element. If the heater element casing is smaller than the plenum the space between the plenum and the element casing must be blocked off with baffles. (Please see Fig. 7)
Page 4
Page 6
Page 7
Page 8
Page 9
Characteristics
Characteristics
Models kW @ 240V
T-5 5 1 20.8 30 30 10 T-9 9 2 37.5 50 50 8 T-15 15 4 62.5 80 100 4 T-18 18 4 75.0 100 100 3 T-20 20 4 83.3 110 125 3 T-25 25 4 104.0 150 150 1 T-30 30 4 124.0 175 175 0
Heating Current (Amps)
Sequences Plenum Heaters Fuses Breakers
AWG
Page 8
Loading...