General Specifications
Furnish CADDYAirSystems Exhaust Hood Model
SHBC-C-II-ASI as shown on the plans and as described in
the following specifications.
Baffle Cartridge Ventilator
509 Sharptown Road P.O. Box 345
Bridgeport, NJ 08014-0345
Tel: 856-467-4222 Fax: 856-467-5511
internet: www.caddycorp.com
CADDY CORPORATION
CADDY Air Systems
All specifications subject to change without notice
08/07
General
Exhaust ventilator shall be constructed of 18 gauge type 300
series stainless steel. All exposed surfaces to have a #4
finish. Construction to meet all requirements of NFPA 96
and NSF Standard No.2. To include necessary hanger
brackets at front and rear suspending from building
overhead structure.
Description
The CADDYAirSystems0RGHO³6+%&³6HULHVYHQWLODWRULV
a dry baffle cartridge type and is UL listed under the
standards as set forth in UL710 "Exhaust Hoods for
Commercial Cooking Equipment." This ventilator is 95%
grease extraction efficient when operated and maintained in
accordance with design specifications. This high efficiency
is accomplished by utilizing removable stainless steel baffle
cartridges containing a series of horizontal, self-draining
baffles. As the air is drawn around the baffles, the grease,
dust and lint particles are slung from the air stream by
centrifugal force. As the liquefied grease is extracted, it is
drained off via a trough into grease collection containers at
each end of the ventilator. At the end of the cooking day or
at scheduled intervals, the cartridges are removed for
cleaning without having to climb up or onto the cooking
equipment with the use of a baffle cartridge removal tool.
Once removed, the baffle cartridges can be washed in either
the dishwasher or soaked and rinsed off in a pot sink. Each
EDIIOHFDUWULGJHLVDPD[LPXPRI´ORQJ9HQWLODWRUFDQ
also be equipped with an optional fusible link or
thermostatically activated fire damper assembly.
Make-Up Air (Internal Discharge)
Ventilator shall have a fully insulated supply plenum with
duct collar/fire damper assemblies and air registers internally
mounted for discharging untempered make-up air directly
into canopy of ventilator. The amount of make-up air
supplied through this design is directly related to the type of
cooking equipment located beneath the hood. The
percentage of supply air distributed will vary as a function of
the thermal currents generated by each individual appliance.
When specifying this style, consult factory for specific supply
volumes. This air may be untempered in most areas,
depending upon climatic conditions and the type of cooking
equipment.
Application
Island style cooking applications for use over all types of
cooking equipment where integral MUA is required.
Light Fixtures
All light fixtures shall be pre-wired to a single connection
point. Ventilators built in multiple sections to be furnished
with junction boxes for ease of field connection by the
electrical trades. Light bulbs furnished and installed by the
Kitchen Equipment Contractor.
Exhaust Fans
Exhaust fans are to be provided and installed by others in
compliance with local codes. Fans should be induced
draft, squirrel cage design, equipped with backward
inclined blades.
Fire Protection
NFPA 96 and local codes require a fire extinguishing system
for protection of the duct collar and plenum of all ventilators,
as well as for the protection of various cooking appliances
such as deep fat fryers, griddles, ranges, and broilers, which
may be a source of ignition of grease. Consult factory and
local fire officials for exact requirements. UL Listed fire
protection systems may be pre-piped by Caddy at the time of
manufacture, assuring concealment of piping and detectors.
Approvals
Ventilator shall be UL Listed, listed by NSF and be in
accordance with all of the recommendations set forth by
NFPA 96. All ventilators must meet all applicable codes.