CADDX Ranger 9000E User Manual

Security Control System
User’s Manual
ARMED light indicates system is armed. Flashing ARMED light indicates previous alarm.
READY light indicates all zones are secure or bypassed, and system is ready to arm.
POWER light indicates AC power is present to your system.
means zone(s) open.
INSTANT light indicates no entry/exit delay is present.
FIRE light indicates a smoke or heat detector has been activated. This light is reset by pressing the
reset
button.
TROUBLE light indicates a technical problem with the fire zone. This light is reset by pressing the
reset
button.
Pressing will turn off Keypad
Pressing will turn off
backlighting.
I
STAR button is used to remove or regain entry/exit delay; also used during zone bypassing.
BELL TEST: If programmed by the installers, pressing these buttons simultaneously will activate a local test of the siren/bell. Enter your code to silence.
PULL OUT
ZONE IDENTIFICATION LABEL
POUND button is used to reset Fire Zone or code entry.
Pressing
[0] will turn off both
of the above.
PANIC/HOLD UP ALARM: If programmed by the installer, pressing the and simultaneously for one second will activate a panic/hold up transmission, and/or sound the local siren/bell.
Installing/Service Company For Service Call
SECURITY SYSTEM NOTES
SPECIAL CODES
Master Code
“Quick Arm” Digit
02 03 04 05
06 07 08 09
10
11
Duress Code
“Chime” Digit
“Entry-Guard” Digit
AUXILIARY ARM/DISARM CODES
22 23
24 25
26 27 28 29 30
--
--
12
15
19 20 21
ENTRY/EXIT DELAY TIMES
Exit Delay Time Entry Delay Time
01
02
03
04 05 06 07 08
09
10
11
Secondary Exit Delay Time Secondary Entry Delay Time
ZONE DESCRIPTIONS
12 13 14 15
18
19 20 21
22
--
23 24
25 26 27 28 29 30
32
--
THIS MANUAL IS FURNISHED TO HELP YOU UNDERSTAND YOUR SECURITY SYSTEM AND BECOME PROFICIENT IN ITS OPERATION. ALL USERS OF YOUR SECURITY
SYSTEM SHOULD READ AND FOLLOW THE INSTRUCTIONS AND PRECAUTIONS IN THIS BOOKLET. FAILURE TO DO SO COULD RESULT IN THE SECURITY SYSTEM NOT WORKING PROPERLY. THIS BOOKLET SHOULD BE KEPT IN AN ACCESSIBLE
LOCATION FOR THE LIFE OF THE SECURITY SYSTEM. IF YOU DO NOT UNDERSTAND ANY PART OF THIS MANUAL YOU SHOULD NOTIFY YOUR INSTALLING COMPANY AND ASK FOR THAT SECTION OF THE MANUAL TO BE EXPLAINED FULLY.
The SECURITY CONTROL CENTER is turned on (ARMED) and off (DISARMED) by entering a 4 digit code into the Keypad Control, which is similar to a telephone keypad. The Keypad Control includes 22 lights and a built in electronic sounder. These provide specific information
relating to the status of the security system which is described in this booklet. Understanding what the lights and sounds mean will help you easily operate your system.
SO REMEMBER, READ THE ENTIRE MANUAL AND, IF POSSIBLE, PRACTICE ON THE KEYPAD CONTROL WHILE YOUR PROFESSIONAL INSTALLER IS AT YOUR BUILDING. IF YOU HAVE ANY QUESTIONS ASK YOUR INSTALLING COMPANY.
PLEASE KEEP IN MIND THAT THE LEVEL OF SECURITY YOU WILL OBTAIN WITH THIS SYSTEM RELATES SPECIFICALLY WITH TWO MAJOR FACTORS:
1.
The quantity, quality, and placement of security devices attached to this system.
2.
The knowledge you have of the security system and how that knowledge is utilized in a weekly test of the complete system.
YOU SHOULD BE AWARE OF THE FOLLOWING FACTS WHEN PREPARING A SAFETY/SECURITY PLAN FOR YOUR HOME/BUSINESS.
1.
Your security system is an electronic device and is subject to failure or malfunction. Do not rely on it as your single source of security.
2.
Your system should be tested weekly.
3.
Your system will not work without power.
4.
Warning devices will need to be loud enough, wired correctly, and properly placed to provide notification of an alarm event.
5.
Smoke and heat detectors may not detect heat and smoke in all situations.
6.
Use qualified security professionals to select, install, and maintain your security system.
PLEASE READ THE FOLLOWING INFORMATION AND INSTRUCTIONS CAREFULLY BEFORE OPERATING YOUR SECURITY CONTROL SYSTEM. IF YOU DO NOT
UNDERSTAND ANY PORTION OF THIS MANUAL, OR IF YOU HAVE ANY QUESTIONS ABOUT YOUR SYSTEM CONTACT THE INSTALLING COMPANY LISTED ON PAGE 1 OF THIS BOOKLET.
Smarthome.com, Inc. (800) SMART-HOME (949) 221-9200 http://smarthome.com
HOW TO ARM YOUR SECURITY SYSTEM
To turn the security system on, close all of the protected doors and windows. The green “READY” light on the keypad control will illuminate when all of the protected areas and sensors are secure. If any of the zones are bypassed, a sensor in that zone can be violated without affecting the “READY” light. The security system will not arm if the “READY” light is not
illuminated. With the “READY” light on, you may arm the security system with your master
code or one of the auxiliary codes.
Each time a key is pressed on the keypad control, a short tone (beep) will sound. If the keypad beeps three times after the code entry or if it does not arm, it is an indication that the code has not been accepted. Press the key to reset and re-enter a valid code. If the keypad control beeps continuously after code entry, it is an indication that the “POWER” light is off, the “FIRE” and/or “TROUBLE” light is on, or a phone line fault (problem) has been detected. The keypad sounder can be silenced by re-entering your four-digit code. should restore power to the system if possible. If the “FIRE” and/or “TROUBLE” light is on,
you should press the above conditions, you should contact the installing company listed on page 1 of this booklet for service. When the security system has accepted a valid code, the red “ARMED” light will
illuminate indicating that the system has been turned on. If you choose to leave the protected
area, you must exit through a designated exit door within the exit delay time noted on page 1.
If you choose to stay within the protected area, insure that all interior zones that may be tripped
by your movement are bypassed.
key (reset), and wait 10 seconds. If you are unable to correct the
If the “POWER” light is off, you
HOW TO DISARM YOUR SECURITY SYSTEM
When you enter the protected area through one of the designated entry/exit doors, the keypad control will sound a continuous tone (beep) for the duration of the entry delay time, or until you enter a valid code, After a valid code has been entered, the red “ARMED” light the tone will stop. The security system is now DISARMED. If a valid code is n the end of the entry delay time, an alarm will occur. (NOTE: IF THE RED “ARMED” LIGHT IS FLASHING DURING THE ENTRY DELAY, THE ALARM SYSTEM HAS BEEN ACTIVATED IN YOUR ABSENCE. LEAVE THE BUILDING IMMEDIATELY AND CALL YOUR ALARM
COMPANY AND/OR THE POLICE FROM A SAFE LOCATION.)
ill turn off, and
‘entered before
HOW TO BYPASS ZONES
To bypass any of the zones, disarm the control and press zone number(s) to be bypassed, and Zone numbers less than 10 must be proceeded by a zero (for example, Zones cannot be bypassed or unbypassed while the control is in the armed state. Upon disarming, all bypassed zones will be unbypassed. As bypassed zones are not protected, the bypass procedure should only be given to authorized persons.
KEYPAD CONTROL LIGHT INDICATORS
ARMED
RED LED is on while system is armed; off otherwise. Blinks as alarm memory if alarm was activated during arming cycle.
READY
INSTANT
POWER
FIRE
GREEN LED is on when all zones are secure and/or Bypassed and the system
is
ready to arm; off otherwise.
RED LED is on while the entry/exit zones are instant or the Entry Guard is on;
off otherwise. RED LED is on while AC power is on; off otherwise. Blinks when the system
standby battery is low.
;
KEYPAD CONTROL TONES (BEEPS)
A sounder is built into the keypad control and may sound for one of the following reasons:
Beeps for all keypresses. Beeps continuously during the Entry delay time. Pulses when a day zone is violated and the system is disarmed, a FIRE zone has a trouble
condition, or when the armed status changes and the AC power is off, or a FIRE/TROUBLE condition exists. When pulsing, it may be silenced by entering a valid code. The Armed state of your security system will not change when you enter a code to silence a pulsing sounder.
Pulses when a phone line fault is detected. 3 beeps for trying to arm with the “READY” light off. Beeps 1 second for the “CHIME” feature. Beeps 1 second at the end of the exit delay.
AUDIBLE ALARM SOUNDS
FIRE:
INTRUSION PANIC:
Steady Siren
(Beeping Keypad) Yelp siren
RESETTING YOUR SECURITY CONTROL CENTER
In the event of a system malfunction in the Security Control Center, press the [#] (reset) key on the keypad control. This should reset the code sequence and restore normal operation. If the problem persists, call the service number located on page 1 of this booklet for service.
ALARM MEMORY
To obtain the last alarm information, press and wait 5 seconds. All zones violated during last alarm will flash. All zones that bypassed during the last alarm will be a steady light.
QUICK-ARM FEA TURE
If checked, your security system has a “QUICK ARM” code programmed. This feature will
allow you to arm the security system by pressing one, pre-designated key on the keypad control. This “QUICK ARM” code is for ARMING ONLY, and will not disarm the security system. This makes it ideal for a maid code, babysitter code, etc. This code can only be programmed and/or changed by your installing company.
AUTOMATIC BYPASS OPTION
If checked, your installing company has selected the “AUTOMATIC BYPASS” option. With this
feature enabled, all interior zones will automatically bypass if you “ARM” your security system and do not leave through a designated entry/exit door. The “AUTOMATIC BYPASS” will occur at the end of the exit delay time. At this time, all bypassed “ZONE” lights will become illuminated. With the interior zones bypassed, occupants are allowed the freedom of
movement inside of the Home/Business white the security system is “ARMED”.
q
If checked, your installing company has selected the “GROUP option. If you wish
to bypass all zones designated as “GROUP BYPASS” zones, you may do so by pressing the
GROUP BYPASS OPTION
key during the exit delay. Once these zones have been bypassed, they will remain
q
If checked, your installing company has selected the “INSTANT” option. With this feature enabled, if you do not wish to have a delay on your entry/exit doors, this can be accomplished by pressing the key on your keypad while the system is “ARMED”. At this time, the “INSTANT” light will illuminate and there will be no entry delay when the entry/exit doors are opened. Any time the “INSTANT” light is on and the exit delay has expired, the opening of an
entry/exit door will produce an immediate alarm, making this feature ideal when a high level of security is desired, and no authorized entries are anticipated. By pressing the key again. the “INSTANT” light will turn off, and an entry delay will be present on designated entry/exit doors.
NOTE: Your installing may have programmed the “INSTANT” option to occur in conjunction with the “AUTOMATIC BYPASS” feature. In this case, the “INSTANT” light and the bypassed “ZONE” lights will become illuminated at the end of the exit delay. If this occurs, you still have the ability to turn the “INSTANT” feature off, and/or on by pressing the key.
INSTANT/DELAY OPTION
ENTRY-GUARD OPTION
If checked, your installing company has selected the “ENTRY-GUARD” option. If you wish to arm your system in a low security mode, you may do so by pressing the preset GUARD” digit (see page 1 for the selected digit). Five seconds later, the security control will bypass all non “ENTRY-GUARD” zones, and arm the system with all “Entry-Guard” zones
delayed. This mode of operation will allow you time to DISARM (turn off) the security system
in the event a zone is accidentally opened.
KEYPADACTIVATED PAN/C/HOLD-UPALARM
If checked, your installing company has selected this feature. If so, when the star and
pound keys are pressed at the same time for one second, a local audible alarm will sound.
If your system is connected to a monitoring center, an emergency report could be transmitted
to that center. These keys should only be pressed in an emergency situation requiring immediate response by law enforcement personnel.
PLEASE NOTE: Some Panic/Hold-up alarrns are programmed to be silent at the protected site while reporting an alarm to the monitoring center. Check with your installing company to determine how your security system will respond to the Panic/Hold-up activation.
KEYPAD ACTIVATED FIRE ALARM
If checked,
siren by pressing the one [I] and three keys at the same time for one second. If your system is connected to a monitoring center, an emergency report could be sent to that center. These keys should only be pressed in an emergency situation requiring response by fire
department personnel.
your installing company has selected this feature. If so, you can activate the steady
q
If checked, your installing company has selected this feature. If so, you can activate the
auxiliary alarm by pressing the four and six keys at the same time for one second. If your system is connected to a monitoring center, an emergency report could be sent to that center.
These keys should only be pressed in an emergency situation requiring response by
emergency personnel. When the “4” and
beep until a code is entered.
are pressed together, the keypad will start to
FIRE ZONE
If checked, your system has designated “FIRE” zones. When this option is selected, and approved heat or smoke detectors are attached to the selected zones, a steady audible siren can be initiated from the security system. You should familiarize yourself and your family or staff with this sound and follow an evacuation plan if this “FIRE” warning sound is heard. (See page 8 for assistance in formulating an evacuation plan). To silence the audible “FIRE” alarm, enter a valid code. To reset the “FIRE” light and /or smoke detectors, press the Reset button on the keypad. After 10 seconds, the “FIRE” light should extinguish, and the light on the affected smoke detector should go out. If you are unable to reset the “FIRE” light or smoke detector after all smoke has cleared, you should immediately call the service phone number listed on page 1 of this booklet.
DURESS CODE
If checked, your security system has a “DURESS CODE” option. If so, this code may be
programmed to send a special message to the central monitoring station if you are forced to arm or disarm your security system against your will. Check with your Installing/Servicing company to see if this option has been enabled for your system.
TURNING ON THE CHIME FEATURE
If checked, your security system will operate in the “CHIME” mode, allowing the monitoring of pre-designated zones while the security system is not armed. While in the “CHIME” mode, the opening of any of these zones will produce a l-second beep from the keypad control. To use this feature, press the “CHIME” digit (this digit has been selected by your and is noted on page 1). Five seconds after pressing the “CHIME” digit, a beep will occur indicating that this feature has been activated. Repeat this procedure to turn the “CHIME”
feature off.
company
II
If checked, your installing company has selected the MULTI-AREA option for your security
system. If so, it may be possible to ARM different areas of your building independently from each other. The system may have up to 4 independent areas. To view another area from a keypad, a special “Change Area Code” will be required. To change the current area being viewed on the keypad control, press another area). Then enter the “change area code”, for example key 1 to 4 representing the area to be viewed. For instance, to change the area to area the
sequence would be as follows:
(this tells the control you want to access
followed by the
PROGRAMMING ARM/DISARM CODES
The security system can be armed and disarmed by the Master code (User Code and up to 29 auxiliary codes. All codes must have 4 digits. These Auxiliary codes are individually
SPECIAL INSTRUCTIONS FOR MULTI-AREA SYSTEMS
numbered user code individually. Only persons knowing the master code can assign or change auxiliary codes (See
“Programming Auxiliary Codes” on page 7.
2 to 30 (NOTE: If your system is programmed for DURESS code (above),
will not be available). If Auxiliary codes are desired, they must be programmed
CHANGING THE MASTER CODE The master code is user code and must be programmed by referring to its code. For example, if the Master code is and you
want to change it to the sequence would be as follows. Press (this
enters programming for user Then press (old Master code) followed by the new master code The entire sequence would consist of pressing 11 keys as
follows:
PROGRAMMING AUXILIARY CODES In order to program Auxiliary Codes you must know
the Master code. As stated earlier, each auxiliary code has its own unique number from to and must be referred to by its number. It is programmed much like the Master Code. For example, to program Auxiliary user code
the sequence would be as follows:
REMOVING AUXILIARY CODES To remove an Auxiliary user code, simply program that code as follows:
For example, to remove user code the sequence would be as
1 1 1
TESTING YOUR SECURITY SYSTEM
There are several tests you should perform on a periodic basis (at least once a week) to insure that your Security System is functioning properly.
Enable “THE CHIME” feature and open all protected windows and doors. The Keypad Control should sound (beep) for each device and the appropriate yellow zone light should blink.
Walk into all areas protected by motion detection devices while someone observes the Keypad Control. The appropriate yellow zone light should blink for each sensor tested.
l
If your system has a “FIRE” zone, the Smoke or Heat detectors should be tested at least monthly. If your Security System is monitored by a Central Monitoring Station,
always call beforehand to let them know that you are about to conduct a test of the fire detection system. Always call after the test to ask for results and to put your fire detection system back into service.
If the Siren/Bell test option has been selected by your installing company, you may activate the siren/bell by pressing the one [I second. To silence the siren/bell, enter your 4-digit master or auxiliary code.
IF ANY OF THE ABOVE TESTS ARE NOT SUCCESSFUL OR THE RESULTS UNCLEAR, CONTACT YOUR SERVICE COMPANY AT THE PHONE NUMBER LISTED ON PAGE 1 OF
THIS SYSTEM HAS BEEN LISTED BY UNDERWRITERS LABORATORIES FOR GRADE A LOCAL, GRADE B SECURITY, GRADE A HOUSEHOLD BURGLARY
C CENTRAL STATION, POLICE CONNECT WITH BASIC LINE
and keys at the same time for one
HOUSEHOLD FIRE.
EMERGENCY EVACUATION PLANS
An emergency evacuation plan should be established for an actual fire alarm condition. For example, the following steps are recommended by the National Fire Protection Association and can be used as a guide in establishing an evacuation plan for your building.
Draw up a floor plan of your home.
Show windows, doors, stairs, and rooftops that can be used for escape. Indicate each occupant’s escape routes. Always keep these routes free from obstruction.
Determine two means of escape from each room.
One will be the normal exit from the building. The other may be a window that opens easily. An escape ladder may have to be located near the window if there is a long drop to the ground below. Set a meeting place outdoors for a headcount of the building occupants.
Practice escape procedures. your escape time.
If you suspect fire, test the door for heat. If you think it is safe, brace your
In a horne, sleep with bedroom door closed; this will increase
shoulder against the door and open it cautiously. Be ready to slam the door if smoke or heat rush in. Practice escaping to the outdoors and meeting in an assigned spot. Call the Fire Department from a neighbor’s phone.
NOTE: After the installation of your Security System has been completed, notify your local Fire and Police Departments to give them your name and address for their records.
Early warning fire detection is best achieved by the installation of fire detection equipment in
all rooms. This equipment should be installed in accordance with the National Fire Protection Association’s Standard 72 (Chapter 2). For additional information write the National Fire Protection Association, Batterymarch Park,
The following are examples of evacuation plans.
MA 02269.
A plan unique to your home or business
should be drawn and memorized by each occupant.
KITCHEN
DINING
ROOM
FIRST FLOOR
BEDROOM
LIVING ROOM
HALL
BEDROOM
BATH
BEDROOM
BEDROOM
SECOND FLOOR