40MKCB**F/24AHA4
40MKCB**F/124ANS
40MKQB**F/25HHA4
40MKQB**F/224ANS
Under Ceiling/Floor Conso le Ductless Split
Sizes 18 to 54
InstallationInstructions
TABLE OF CONTENTS
SAFETY CONSIDERATIONS1
PARTS L IST2
DIMENSIONS -- INDOOR3
DIMENSIONS -- OUTDOOR4
CLEARANCES -- INDOOR6
CLEARANCES -- OUTDOOR6
SYSTEM REQUIREMENTS6
INSTALLATION8
INSTALL INDOOR UNIT8
INSTALL OUTDOOR UNIT11
ELECTRICAL DATA15
START--UP19
TROUBLESHOOTING22
Fig. 1 -- Indoor Unit, Outdoor Unit, and Remote Control
NOTE: Read the entire instruction manual before starting the
installation.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury or
equipment damage.
Puron refrigerant systems operate at higher pressures than
standard R--22 systems. To avoid damage to the unit or
possible personal injury, do not use R--22 service equipment or
components on Puron refrigerant equipment.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and
work gloves. Use quenching cloth for brazi ng operations. Have a fire
extingui sher ava i lable. Read these instruct ions thoroughly and follow
all warnings or cautions included in the unit literature and on labels
attached to the unit. Consult local building codes and current editions
of the National Electrical Code ( NEC ) NFP A 70. In Canada, refer to
current editions of the Canadian electrical code CSA 22.1.
Recognize safet y information. This is the safety--alert symbol
When you see this symbol on the unit and in instruct ions or manuals ,
be alert to the potential for personal inj ury. Underst and these signal
words; DANGER, WARNING,andCAUTION. These words are
used with the safety-- alert symbol. DANGER identifies the most
serious hazards which will result in severe personal injury or death.
WARNING signifies hazards which could result in personal injury or
death. CAUTION is used to identify unsafe practices which may
result in minor personal injury or product and propert y damage.
!
!
NOTE is used to highlight suggestions which will result in enhanced
installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF
position. There may be more than 1 disconnect switch.
Lock out and tag switch with a suitable warning label.
!
CAUTION
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental
pollution.
Remove and recycle all components or materials (i.e. oil,
refrigerant, etc.) before unit final disposal.
INSTALLATION
IMPORTANT: Effective January 1, 2015, all split systems and
packaged air conditioners must be installed pursuant to applicable
regional efficiency standards issued by the Department of Energy.
PARTS L IS T
TXV Kit
The under ceiling/ f loor console type unit and horizontal disc harge unit
(24AHA/124ANS and 25HHA4/224ANS) installa t i on would not be
comple t e without the addition of the TXV kit. This can be found in
the packagi ng of the indoor unit. If you do not have this kit, order the
kit and insta ll the outdoor and indoor units when this is a vailabl e.
Below are figures that s how how the kit looks and where it is included
within the indoor unit pa ckaging.
Liquid pipe
Gas pipe
Refrigerant
flow direction
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts have sharp edges or burrs, Use care and wear
appropriate protective clothing and gloves when handling
parts.
!
CAUTION
PERSONAL INJURY AND EQUIPMENT DAMAGE
HAZARD
Failure to follow this caution may result in personal injury
and / or equipment damage.
DO NOT operate the unit without a filter or with grille
removed.
These instructions cover the installation and the start--up of the
systems listed in Table 1.
SCenter of Gravity
SAll dimensions are in “inches” unless noted.
MINIMUM
UNIT SIZE
18,2423” x 42”
30,36,4824” x 50”
MOUNTING PAD
DIMENSIONS
Fig. 7 -- Outdoor Unit Dimensions
4
Table6–Dimensions(ACs)
Table7–DimensionsSI(ACs)
Table 8 – Dimensions (HPs)
Table9–DimensionsSI(HPs)
2
124ANS018000/
124ANS024000/
124ANS030000/
124ANS036000/
124ANS048000/
124ANS018000/
124ANS024000/
124ANS030000/
124ANS036000/
124ANS048000/
5
224ANS048000/
224ANS030000/
224ANS036000/
224ANS030000/
224ANS036000/
224ANS048000/
CLEARANCES -- INDOOR
≥35mm
≥ 35mm
Fig. 8 – 40MKCB**F, 40MKQB**F Unit Clearance
CLEARANCES -- OUTDOOR
1. Single Unit Applications: With coil facing wall: Allow 6”
(152.4mm) minimum cleara nce on coi l side and coil end and
20” (504.0 mm) minimum cl earance on fan side. Allow 24”
(609.6 mm) minimum clearance on compressor end for
service.
2. With fan facing wall: Allow 8” (203.2 mm) minimum
clearance on fan side and coil end and 20” (504.0 mm)
minimum clea r ance on coil side. Allow 24” (609.6 mm)
minimum clearance on compressor end for service when units
are stacked or there is less than 40” (1016 mm) of clea r ance
above the unit. If there is 40” (1016 mm) clearance above unit
and the top panel is accessible for removal allow 8” (203.2
mm) minimum clearance on compressor end for service.
3. Multi--unit Applications: Allow 24” (609.6 mm) minimum
clearance between fan and coil sides of multiple units. Arrange
units so discharge of one does not enter inlet of another . Al low
24” (609.6 mm) minimum clea rance on compre ssor end when
units are stacked or there is less than 40” (1016 mm) of
clearance above the unit. If there is 40” (1016 mm) clearance
above unit and the top panel is accessible for removal allow 8”
(203.2 mm) minimum clearance on compressor end for
service. When two units are installed end to end with the coil
ends facing each other allow 12” (304.8 mm) minimum
clearance between units.
IMPORTANT: When installing multiple units, ensure the
discharge air from one unit is not drawn into another unit.
When installing single or multiple units in an alcove, roof well,
or partially enclosed area, ensure there is adequate ventilation
to prevent recirculation of discharge air.
≥ 35mm
≥1000mm
A0150267
SYSTEM REQUIREMENTS
Clearances
Allow sufficient space around the indoor and outdoor unit for
proper airflow circulation and servicing. Refer to Fig.8 and the
outdoor unit clearance section for minimum required clearances.
Piping:Piping and insulation is field supplied.
Piping Lengths
The minimum length between the indoor and outdoor units is 10 ft
(3 m). Refer to table 9 for the maximum lengths allowed.
Table 9 – Maximum Refrigerant Line Lengths
Sizes (in)
Max Elevation
(OD over ID) ft
(m)ft(m)
OutdoorUnit Tube
5/8
3/8
Size (in)
5/8
Unit Size
18K -54K250 (76.2)65 (19.8)200 (61)
Note:Forlengthsgreaterthan25ft(7.6m),refertotheResidential Long
Line Guide.
Max Line
Length* ft(m)
Max elevation (ID
over ODft (m)
Pipe Sizes
In some models, indoor unit and/or outdoor unit pipe sizes may
differ from those in TXV connections. Coupling is required in
those cases. See table below for a complete list of tube sizes to
identify coupling needs. Refer to Table 10 for pipe sizes.
Table10–PipeSizes
Indoor UnitsOutdoorUnits
40MKCB18F-- --3
40MKCB34F-- --3
40MKCB34F-- --3
40MKCB34F-- --3
40MKCB54F-- --3
40MKQB36F-- --3
40MKQB36F-- --3
40MKQB48F-- --3
24AHA418
124ANS018
24AHA424
124ANS024
24AHA430
124ANS030
24AHA436
124ANS036
24AHA448
124ANS048
25HHA430224A
NS030
25HHA436
224ANS036
25HHA448
224ANS048
Indoor Unit Tube
Sizes (in)
LiquidVap o rLiquid Vap o rLiquid Vap o r
3/8
TXV Kit Tube
5/8
3/43/43/4
3/43/43/4
3/43/47/8
3/8
3/47/87/8
3/43/43/4
3/43/47/8
3/47/87/8
Note:Both lines need to be insulated using at le ast 1/2 inch closed
foam insulation.
6
Condensate Drain Pipe Sizes
Refer to table 11 for the required sizes.
Table 11 – Drain Pipe Sizes
Unit Size
18K-54K1 (25.4)
Outside Diameter
in (mm)
Refrigerant Charge
The outdoor units can be matched with multiple indoor units, and
thus a different amount of charge might be required when matched
with the 40MKCB**F or 40MKQB**F units. Charge to
Sub--cooling Delta from Rating Plate V alue as stated below.
NOTE::The above additional charge is required amount for
line lengths up to 25 ft (7.6 m). For line lengths exceeding 25 ft
(7.6 m), additional charge will be required. Refer to the
Residential Long Line Guide.
Charge to
Sub--cooling
Delta from Rating
Plate Val ue
Communication Wiring:
A separate shielded copper conductor only with a minimum 300 volt
rating and 2/64 inch thick insulation must be used as the
communic ation wire from the outdoor unit to the indoor unit. To
minimi ze voltage drop of the communication wire, use the wire size
and maximum lengths shown in table 14.
Table 14 – Maximum Wire Lengths
Wire SizeLength ft. (m)
18AWG50 ft. (15 m)
16AWG50 ft. (15 m) to 100ft. (30 m)
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow the following caution may result in
equipment damage or improper operation.
Wires should be sized based on NEC and local codes.
Use copper conductors only with a minimum 300 volt
rating and 2/64 inch thick insulation.
USER INTERFACE
The indoor unit is supplied with a wireless remote control to
operate the unit (an Owner’s Manual is supplied with the unit). The
following accessories are available.
SWall mounted control
Metering Device
The 40MKC(Q)*F unit uses a TXV. The outdoor unit uses a type
B accurator. The cooling metering device is installed with the
indoor unit, while the heating metering device is installed with the
outdoor unit. One metering device is required for the cooling only
system and two are required for the heat pump systems. Refer to
Table 13 for a breakdown of each unit’s metering devices.
Recommended Connection Method for Power and
Communication Wiring (To minimize
communication wiring interference)
Power Wiring:
The main power is supplied to both the indoor and the outdoor units.
The field supplied connecting cable consists of three (3) wires. Two
wires ar e high voltage AC power and one is a ground wire.
Consult your loca l building codes and the NEC (National Electr ical
Code) or CEC (Canadian Electrical Code) for special requirements.
All wires must be sized per NEC or CEC and local codes. Use
Electrical Data table MCA (minimum circuit amps) and MOCP
(maxi mum over current protect ion) to correctly size the wires and the
disconnect fuse or breakers respectively.
Per caution note, only copper conductors with a minim um 300 volt
rating and 2/64--inch thick insulat i on must be used.
OPERATING RANGE
Ensure that the system operates within the application guidelines
shown in the following tables.
Table 15 – Cooling Operating Range
MaximumMinimum
Outdoor
Unit
Indoor Unit90 (32)-64 (18)-
DB °F (°C)WB °F (°C)DB °F (°C)WB °F (°C)
125 (51.7)-55(12.8)-
Table 16 – Heating Opera ting Range
MaximumMinimum
Outdoor
Unit
Indoor Unit80 (27)32 (0)-
DB °F (°C)WB °F (°C)DB °F (°C)WB °F (°C)
75 (23.9)67 (19.4)17 (-8.3)-
ACCESSORIES
An extensive list of field installed accessories is available for both
indoor and outdoor units. Identify what accessories, if any, are
required for the application at hand and consult the separate
installation instructions for the accessories. Some of the
accessories, especially on the indoor units, can be installed much
easier if planned ahead.
7
INSTALLATION
COMPLETE PRE--INSTALLATION CHECKS
1. Unpack Unit -- Store the indoor and outdoor units in the
original packaging until it is moved to the final site for
installat ion. When unpacking indoor unit, be ca reful not to lift
unit by condensate drain discha rge pipe or by refrigerant
connections.
2. Inspe ct Shipment -- Upon receipt of shipment, check the
indoor and outdoor units for damage. If there is any damage,
forwa r d claim papers directly to the transport ation company .
Manufa cturer is not responsi ble for damage incurred in transi t.
3. Inspect Parts Supplied With Units – Check all items
against parts list (see the PARTS LIST section). If any items
are missing, notify your distributor or manufacturer office.
To prevent loss or damage, leave all parts in original
packages until installation.
CONSIDER SYSTEM REQUIREMENTS
1. Consult local building codes and NEC for special
installation requirements.
2. When deciding the location of the indoor and outdoor units,
ensure that the piping run does not exceed the allowed
distances listed in Table 9.
3. Make sure the indoor and outdoor units are easily accessible
to electrical power.
4. Allow sufficient clearances for airflow, wiring, refrigerant
piping, and servicing the unit (see the ”CLEARANCES -INDOOR” and “CLEARANCES -- OUTDOOR” sections).
5. Condensate piping can be directed through the inside wall
to an approved drain or straight outside.
2. TXV Installation
SLocation -- The TXV kit can be affixed directly to the
indoor unit or anywhere between 12 to 18 inches from
the indoor unit pipe connection.
!
Failure to follow the following caution may result in equipment
damage or improper operation.
The TXV kit needs to be installation at most 12 to 18 inches
from the indoor unit pipe connection.
SThe TXV kit contains a label specifying the allowed
flow direction. See below for allowed and not allowed
flow directions.
!
Failure to follow the following caution may result in
equipment damage or improper operation. One of the two
arrows on the TXV part number label must point up when
installed.
Install unit such that the refrigerant flow directions is in any
of the two allowed directions.
CAUTION
CAUTION
Outdoor unit
connection
INSTALL INDOOR UNIT
Plan the installation carefully before you begin.
1. Select indoor unit location.
SA location where there are no obstacles near inlet and
outlet area.
SA location that can bear the weight of the unit.
SDo not install indoor units near a direct source of heat
such as direct sunlight or a heating appliance.
SDo not install units too close to humid conditions.
SWhere an optimum air distribution is ensured.
SWhere the condensate can drain correctly and safely.
SMaintain sufficient clearance around the indoor unit for
maintenance and servicing.
SWhere the air filter can be removed and cleaned easily.
SWhere the piping between the indoor and outdoor units
is within the allowable limits.
S1m or more away from the TV or radio to prevent the
screen from being distorted or noise from being
generated.
SAs far away as possible from fluorescent and incandes-
cent lights so that the remote control can be operated
well.
Indoor unit
connection
Outdoor unit
connection
Indoor unit
connection
Arrows on TXV label pointing
upward and to the right
Fig. 9 – Allowed TXV installation direction per label attached
To
indoor
unit
Fig. 10 – TXV
Arrows on TXV label pointing
upward and to the left
to TXV
Refrigerant
flow direction
To
outdoor
unit
8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.