CAC / BDP 40MKCB**F/24AHA4, 40MKCB**F/124ANS, 40MKQB**F/25HHA4, 40MKQB**F/224ANS Installation Instructions Manual

40MKCB**F/24AHA4 40MKCB**F/124ANS 40MKQB**F/25HHA4 40MKQB**F/224ANS Under Ceiling/Floor Conso le Ductless Split Sizes 18 to 54
Installation Instructions
TABLE OF CONTENTS SAFETY CONSIDERATIONS 1 PARTS L IST 2 DIMENSIONS -- INDOOR 3 DIMENSIONS -- OUTDOOR 4 CLEARANCES -- INDOOR 6 CLEARANCES -- OUTDOOR 6 SYSTEM REQUIREMENTS 6 INSTALLATION 8 INSTALL INDOOR UNIT 8 INSTALL OUTDOOR UNIT 11 ELECTRICAL DATA 15 START--UP 19 TROUBLESHOOTING 22
Fig. 1 -- Indoor Unit, Outdoor Unit, and Remote Control
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury or equipment damage.
Puron refrigerant systems operate at higher pressures than standard R--22 systems. To avoid damage to the unit or possible personal injury, do not use R--22 service equipment or components on Puron refrigerant equipment.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazi ng operations. Have a fire extingui sher ava i lable. Read these instruct ions thoroughly and follow all warnings or cautions included in the unit literature and on labels attached to the unit. Consult local building codes and current editions of the National Electrical Code ( NEC ) NFP A 70. In Canada, refer to current editions of the Canadian electrical code CSA 22.1.
Recognize safet y information. This is the safety--alert symbol When you see this symbol on the unit and in instruct ions or manuals , be alert to the potential for personal inj ury. Underst and these signal words; DANGER, WARNING,andCAUTION. These words are used with the safety-- alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and propert y damage.
!
!
NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
!
CAUTION
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental pollution.
Remove and recycle all components or materials (i.e. oil, refrigerant, etc.) before unit final disposal.
INSTALLATION
IMPORTANT: Effective January 1, 2015, all split systems and
packaged air conditioners must be installed pursuant to applicable regional efficiency standards issued by the Department of Energy.
PARTS L IS T
TXV Kit
The under ceiling/ f loor console type unit and horizontal disc harge unit (24AHA/124ANS and 25HHA4/224ANS) installa t i on would not be comple t e without the addition of the TXV kit. This can be found in the packagi ng of the indoor unit. If you do not have this kit, order the kit and insta ll the outdoor and indoor units when this is a vailabl e.
Below are figures that s how how the kit looks and where it is included within the indoor unit pa ckaging.
Liquid pipe
Gas pipe
Refrigerant flow direction
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts have sharp edges or burrs, Use care and wear appropriate protective clothing and gloves when handling parts.
!
CAUTION
PERSONAL INJURY AND EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in personal injury and / or equipment damage.
DO NOT operate the unit without a filter or with grille removed.
These instructions cover the installation and the start--up of the systems listed in Table 1.
Table 1 – Matched Systems
Nominal
System Type
Coolin g
Only
Heat
Pump
Capacity
kBTU/Hr
018 24AHA418A003 124ANS018000 40MKCB18F-- -- 3
024 24AHA424A003 124ANS024000 40MKCB34F-- -- 3
030 24AHA430A003 124ANS030000 40MKCB34F-- -- 3
034 24AHA436A003/5/6 124ANS036000 40MKCB34F-- -- 3
054 24AHA448A003/5/6 124ANS048000 40MKCB54F-- -- 3
030 25HHA430A003 224ANS030000 40MKQB36C---- 3
036 25HHA436A003/5/6 224ANS036000 40MKQB36C-- --3
048 25HHA448A003/5/6 224ANS048000 40MKQB48C-- --3
Outdoor Unit Indoor Unit
A150289
Fig. 2 -- TXV Kit
TXV kit inside carton box
A150297
Fig. 3 -- TXV Kit (inside indoor unit’s packaging)
Indoor Unit
The following items are included with the indoor unit:
Table 2 – Indoor Units Parts List
Name of Part
Owner’s Manual 1 Guide for the homeowner Warranty card 1 Warranty information Installation instructions 1 Guide to install the unit
Clamp filter 2
Remote Controller 1 Controls the indoor unit
Remote Controller Holder 1
Tapped Screw 2
Battery 2 Powers the remote controller
Strain Relief Bracket 1
Screws 4 To affix strain relief bracket
Qty. Usage
For conforming to EMC standards on connecting wires
Holds the remote controller on the wall
Used to fix the remote controller holder
To affix strain relief to hold wires in place
2
Outdoor Unit
The following items are included with the outdoor unit:
Fig. 4 -- 24AHA/124ANS
DIMENSIONS - INDOOR
Unit:
A09536
Fig. 5 -- 25HHA4/224ANS
Table 3 – Outdoor Unit Parts Checklist
Model
24AHA4/124ANS n 25HHA4/224ANS n n n n
Filter Drier
Piston
Cap
Pistons
Flare
Connector
H
A09537
Bracket:
D
W
W
Hook
D
A0150266
Fig. 6 -- 440MKCB**F, 40MKQB**F Unit and Bracket Dimensions
Indoor Unit Size
BTU/Hr
AC
18K 9.3 (235) 42.0 (1068) 26.6 (675) 59.7 (27.1)
24K - 34K 9.3 (235) 65.0 (1650) 26.6 (675) 91.9 (41.7)
54K 9.3 (235) 65.0 (1650) 26.6 (675) 98.8 (44.8)
HP
30K - 48K 9.3 (235) 65.0 (1650) 26.6 (675) 98.8 (44.8)
Bracket
18K AC - 38.7 (983) 8.7 (220) -
24K - 54K AC/HP - 61.6 (1565) 8.7 (220) -
Height (H)
in (mm)
Table 4 – Dimensions Indoor
Width (W)
in (mm)
3
Depth (D)
in (mm)
Operating Weight
lb (kg)
DIMENSIONS -- OUTDOOR
NOTE:
S Center of Gravity S All dimensions are in “inches” unless noted.
MINIMUM
UNIT SIZE
18,24 23” x 42”
30,36,48 24” x 50”
MOUNTING PAD
DIMENSIONS
Fig. 7 -- Outdoor Unit Dimensions
4
Table6–Dimensions(ACs)
Table7–DimensionsSI(ACs)
Table 8 – Dimensions (HPs)
Table9–DimensionsSI(HPs)
2
124ANS018000/
124ANS024000/
124ANS030000/
124ANS036000/
124ANS048000/
124ANS018000/
124ANS024000/
124ANS030000/
124ANS036000/
124ANS048000/
5
224ANS048000/
224ANS030000/
224ANS036000/
224ANS030000/
224ANS036000/
224ANS048000/
CLEARANCES -- INDOOR
≥35mm
≥ 35mm
Fig. 8 – 40MKCB**F, 40MKQB**F Unit Clearance
CLEARANCES -- OUTDOOR
1. Single Unit Applications: With coil facing wall: Allow 6” (152.4mm) minimum cleara nce on coi l side and coil end and 20” (504.0 mm) minimum cl earance on fan side. Allow 24” (609.6 mm) minimum clearance on compressor end for service.
2. With fan facing wall: Allow 8” (203.2 mm) minimum clearance on fan side and coil end and 20” (504.0 mm) minimum clea r ance on coil side. Allow 24” (609.6 mm) minimum clearance on compressor end for service when units are stacked or there is less than 40” (1016 mm) of clea r ance above the unit. If there is 40” (1016 mm) clearance above unit and the top panel is accessible for removal allow 8” (203.2 mm) minimum clearance on compressor end for service.
3. Multi--unit Applications: Allow 24” (609.6 mm) minimum clearance between fan and coil sides of multiple units. Arrange units so discharge of one does not enter inlet of another . Al low 24” (609.6 mm) minimum clea rance on compre ssor end when units are stacked or there is less than 40” (1016 mm) of clearance above the unit. If there is 40” (1016 mm) clearance above unit and the top panel is accessible for removal allow 8” (203.2 mm) minimum clearance on compressor end for service. When two units are installed end to end with the coil ends facing each other allow 12” (304.8 mm) minimum clearance between units.
IMPORTANT: When installing multiple units, ensure the discharge air from one unit is not drawn into another unit. When installing single or multiple units in an alcove, roof well, or partially enclosed area, ensure there is adequate ventilation to prevent recirculation of discharge air.
≥ 35mm
≥1000mm
A0150267
SYSTEM REQUIREMENTS
Clearances
Allow sufficient space around the indoor and outdoor unit for proper airflow circulation and servicing. Refer to Fig.8 and the outdoor unit clearance section for minimum required clearances.
Piping:Piping and insulation is field supplied.
Piping Lengths
The minimum length between the indoor and outdoor units is 10 ft (3 m). Refer to table 9 for the maximum lengths allowed.
Table 9 – Maximum Refrigerant Line Lengths
Sizes (in)
Max Elevation (OD over ID) ft
(m)ft(m)
OutdoorUnit Tube
5/8
3/8
Size (in)
5/8
Unit Size
18K -54K 250 (76.2) 65 (19.8) 200 (61)
Note:Forlengthsgreaterthan25ft(7.6m),refertotheResidential Long
Line Guide.
Max Line
Length* ft(m)
Max elevation (ID
over ODft (m)
Pipe Sizes
In some models, indoor unit and/or outdoor unit pipe sizes may differ from those in TXV connections. Coupling is required in those cases. See table below for a complete list of tube sizes to identify coupling needs. Refer to Table 10 for pipe sizes.
Table10–PipeSizes
Indoor Units OutdoorUnits
40MKCB18F-- --3
40MKCB34F-- --3
40MKCB34F-- --3
40MKCB34F-- --3
40MKCB54F-- --3
40MKQB36F-- --3
40MKQB36F-- --3
40MKQB48F-- --3
24AHA418
124ANS018
24AHA424
124ANS024
24AHA430
124ANS030
24AHA436
124ANS036
24AHA448
124ANS048
25HHA430224A
NS030
25HHA436
224ANS036
25HHA448
224ANS048
Indoor Unit Tube
Sizes (in)
Liquid Vap o r Liquid Vap o r Liquid Vap o r
3/8
TXV Kit Tube
5/8
3/4 3/4 3/4
3/4 3/4 3/4
3/4 3/4 7/8
3/8
3/4 7/8 7/8
3/4 3/4 3/4
3/4 3/4 7/8
3/4 7/8 7/8
Note:Both lines need to be insulated using at le ast 1/2 inch closed
foam insulation.
6
Condensate Drain Pipe Sizes
Refer to table 11 for the required sizes.
Table 11 – Drain Pipe Sizes
Unit Size
18K-54K 1 (25.4)
Outside Diameter
in (mm)
Refrigerant Charge
The outdoor units can be matched with multiple indoor units, and thus a different amount of charge might be required when matched with the 40MKCB**F or 40MKQB**F units. Charge to Sub--cooling Delta from Rating Plate V alue as stated below.
Table 12 – Charge Requirements
Nominal
System
Type
Cooling
Only
Heat
Pump
Capacity
kBTU/Hr
018 24AHA418A003 124ANS018000 40MKCB18F---- 3 12
024 24AHA424A003 124ANS024000 40MKCB34F---- 3 12
030 24AHA430A003 124ANS030000 40MKCB34F---- 3 12
034 24AHA436A003/5/6 124ANS036000 40MKCB34F-- --3 8
054 24AHA448A003/5/6 124ANS048000 40MKCB54F-- --3 12
030 25HHA430A003 224ANS030000 40MKQB36C-- --3 11
036 25HHA436A003/5/6 224ANS036000 40MKQB36C----3 14
048 25HHA448A003/5/6 224ANS048000 40MKQB48C----3 11
Outdoor Unit Indoor Unit
NOTE::The above additional charge is required amount for line lengths up to 25 ft (7.6 m). For line lengths exceeding 25 ft (7.6 m), additional charge will be required. Refer to the Residential Long Line Guide.
Charge to
Sub--cooling
Delta from Rating
Plate Val ue
Communication Wiring:
A separate shielded copper conductor only with a minimum 300 volt rating and 2/64 inch thick insulation must be used as the communic ation wire from the outdoor unit to the indoor unit. To minimi ze voltage drop of the communication wire, use the wire size and maximum lengths shown in table 14.
Table 14 – Maximum Wire Lengths
Wire Size Length ft. (m)
18AWG 50 ft. (15 m) 16AWG 50 ft. (15 m) to 100ft. (30 m)
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow the following caution may result in equipment damage or improper operation.
Wires should be sized based on NEC and local codes.
Use copper conductors only with a minimum 300 volt rating and 2/64 inch thick insulation.
USER INTERFACE
The indoor unit is supplied with a wireless remote control to operate the unit (an Owner’s Manual is supplied with the unit). The following accessories are available.
S Wall mounted control
Metering Device
The 40MKC(Q)*F unit uses a TXV. The outdoor unit uses a type B accurator. The cooling metering device is installed with the indoor unit, while the heating metering device is installed with the outdoor unit. One metering device is required for the cooling only system and two are required for the heat pump systems. Refer to Table 13 for a breakdown of each unit’s metering devices.
Table 13 – Metering Devices
System Size
kBTU/hr
018 TXV - ­024 TXV - ­030 TXV TXV 0.055" 034 TXV - ­054 TXV - ­036 - TXV 0.063" 048 - TXV 0.073"
Cooling Only Heat Pumps
40MKCB**C 40MKQB**C 25HHA4/224ANS
POWER AND CONNECTING CABLES -­FIELD SUPPLIED
Recommended Connection Method for Power and Communication Wiring (To minimize communication wiring interference)
Power Wiring:
The main power is supplied to both the indoor and the outdoor units. The field supplied connecting cable consists of three (3) wires. Two wires ar e high voltage AC power and one is a ground wire. Consult your loca l building codes and the NEC (National Electr ical Code) or CEC (Canadian Electrical Code) for special requirements. All wires must be sized per NEC or CEC and local codes. Use Electrical Data table MCA (minimum circuit amps) and MOCP (maxi mum over current protect ion) to correctly size the wires and the disconnect fuse or breakers respectively. Per caution note, only copper conductors with a minim um 300 volt rating and 2/64--inch thick insulat i on must be used.
OPERATING RANGE
Ensure that the system operates within the application guidelines shown in the following tables.
Table 15 – Cooling Operating Range
Maximum Minimum
Outdoor
Unit
Indoor Unit 90 (32) - 64 (18) -
DB °F (°C) WB °F (°C) DB °F (°C) WB °F (°C)
125 (51.7) - 55(12.8) -
Table 16 – Heating Opera ting Range
Maximum Minimum
Outdoor
Unit
Indoor Unit 80 (27) 32 (0) -
DB °F (°C) WB °F (°C) DB °F (°C) WB °F (°C)
75 (23.9) 67 (19.4) 17 (-8.3) -
ACCESSORIES
An extensive list of field installed accessories is available for both indoor and outdoor units. Identify what accessories, if any, are required for the application at hand and consult the separate installation instructions for the accessories. Some of the accessories, especially on the indoor units, can be installed much easier if planned ahead.
7
INSTALLATION
COMPLETE PRE--INSTALLATION CHECKS
1. Unpack Unit -- Store the indoor and outdoor units in the original packaging until it is moved to the final site for installat ion. When unpacking indoor unit, be ca reful not to lift unit by condensate drain discha rge pipe or by refrigerant connections.
2. Inspe ct Shipment -- Upon receipt of shipment, check the indoor and outdoor units for damage. If there is any damage, forwa r d claim papers directly to the transport ation company . Manufa cturer is not responsi ble for damage incurred in transi t.
3. Inspect Parts Supplied With Units – Check all items against parts list (see the PARTS LIST section). If any items are missing, notify your distributor or manufacturer office. To prevent loss or damage, leave all parts in original packages until installation.
CONSIDER SYSTEM REQUIREMENTS
1. Consult local building codes and NEC for special installation requirements.
2. When deciding the location of the indoor and outdoor units, ensure that the piping run does not exceed the allowed distances listed in Table 9.
3. Make sure the indoor and outdoor units are easily accessible to electrical power.
4. Allow sufficient clearances for airflow, wiring, refrigerant piping, and servicing the unit (see the ”CLEARANCES -­INDOOR” and “CLEARANCES -- OUTDOOR” sections).
5. Condensate piping can be directed through the inside wall to an approved drain or straight outside.
2. TXV Installation
S Location -- The TXV kit can be affixed directly to the
indoor unit or anywhere between 12 to 18 inches from the indoor unit pipe connection.
!
Failure to follow the following caution may result in equipment damage or improper operation.
The TXV kit needs to be installation at most 12 to 18 inches from the indoor unit pipe connection.
S The TXV kit contains a label specifying the allowed
flow direction. See below for allowed and not allowed flow directions.
!
Failure to follow the following caution may result in equipment damage or improper operation. One of the two arrows on the TXV part number label must point up when installed. Install unit such that the refrigerant flow directions is in any of the two allowed directions.
CAUTION
CAUTION
Outdoor unit connection
INSTALL INDOOR UNIT
Plan the installation carefully before you begin.
1. Select indoor unit location.
S A location where there are no obstacles near inlet and
outlet area.
S A location that can bear the weight of the unit.
S Do not install indoor units near a direct source of heat
such as direct sunlight or a heating appliance.
S Do not install units too close to humid conditions.
S Where an optimum air distribution is ensured. S Where the condensate can drain correctly and safely.
S Maintain sufficient clearance around the indoor unit for
maintenance and servicing.
S Where the air filter can be removed and cleaned easily.
S Where the piping between the indoor and outdoor units
is within the allowable limits.
S 1m or more away from the TV or radio to prevent the
screen from being distorted or noise from being generated.
S As far away as possible from fluorescent and incandes-
cent lights so that the remote control can be operated well.
Indoor unit connection
Outdoor unit connection
Indoor unit connection
Arrows on TXV label pointing
upward and to the right
Fig. 9 – Allowed TXV installation direction per label attached
To
indoor
unit
Fig. 10 – TXV
Arrows on TXV label pointing
upward and to the left
to TXV
Refrigerant flow direction
To
outdoor
unit
8
Loading...
+ 16 hidden pages