CAC / BDP 8kW, 10kW, 17kW, 12kW, 20kW Owner's Manual

...
Study Guide
Air-Cooled Training
SERVICE TRAINING
C
Owner’s Manual
8, 10, 12, 14, 16, 17 & 20kW Air-cooled,
Automatic Standby Generators
U
S
LISTE
D
DO NOT LIFT UNIT BY ROOF!
Not intended for use as Primary Power in place of utility
DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!
or in life-support applications.
INTRODUCTION
Thank you for purchasing this compact, high per­formance, air-cooled, engine-driven generator. It is designed to automatically supply electrical power to operate critical loads during a utility power failure.
This unit is factory installed in an all-weather, metal enclosure that is intended exclusively for outdoor installation. This generator will operate using either vapor withdrawn liquid propane (LP) or natural gas (NG).
NOTE:
This generator is suitable for supplying typical residential loads such as Induction Motors (sump pumps, refrigerators, air conditioners, furnaces, etc.), Electronic Components (computer, monitor, TV, etc.), Lighting Loads and Microwaves.
READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, con­tact the nearest Dealer for starting, operating and servicing procedures.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert person­nel to special instructions about a particular opera­tion that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their defini­tions are as follows:
DANGER
After this heading, read instructions that, if not
strictly complied with, will result in serious person­al injury, including death, in addition to property damage.
After this heading, read instructions that, if not
strictly complied with, may result in serious person­al injury or property damage.
After this heading, read instructions that, if not
strictly complied with, could result in damage to equipment and/or property.
NOTE:
After this heading, read explanatory statements
that require special emphasis.
These safety warnings cannot eliminate the haz­ards that they indicate. Common sense and strict compliance with the special instructions while performing the service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates follows:
This symbol points out potential explosion haz-
ard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock
hazard.
The operator is responsible for proper and safe use of the equipment. The manufacturer strongly recom­mends that the operator read this Owner's Manual and thoroughly understand all instructions before using this equipment. The manufacturer also strong­ly recommends instructing other users to properly start and operate the unit. This prepares them if they need to operate the equipment in an emergency.
CONTENTS
This manual contains pertinent owner’s information for these models:
7 kW NG, 8 kW LP, single-cylinder GH-410 Engine• 9 kW NG, 10 kW LP, V-twin GT-530 Engine• 12 kW NG, 12 kW LP, V-twin GT-990 Engine• 13 kW NG, 14 kW LP, V-twin GT-990 Engine• 16 kW NG, 16 kW LP, V-twin GT-990 Engine• 16 kW NG, 17 kW LP, V-twin GT-990 Engine• 18 kW NG, 20 kW LP, V-twin GT-999 Engine
OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safety checks, to make sure that all maintenance for safe operation is performed promptly, and to have the equipment checked periodically by a Dealer. Normal maintenance service and replacement of parts are the responsibility of the owner/operator and, as such, are not considered defects in materials or workmanship within the terms of the warranty. Individual operating habits and usage contribute to the need for mainte­nance service.
Proper maintenance and care of the generator ensures a minimum number of problems and keep operating expenses at a minimum. See a Dealer for service aids and accessories.
HOW TO OBTAIN SERVICE
When the generator requires servicing or repairs, contact a Dealer for assistance. Service technicians are factory-trained and are capable of handling all service needs.
When contacting a Dealer about parts and service, always supply the complete model number and serial number of the unit as given on its data decal, which is located on the generator. See section "The Generator" for decal location.
Model No. ____________ Serial No. ______________
This symbol points out important safety infor-
mation that, if not followed, could endanger personal safety and/or property of others.
Table of Contents
Air-cooled Generators
Introduction ........................Inside Front Cover
Read This Manual Thoroughly ........................ IFC
Contents .......................................................... IFC
Operation and Maintenance ............................ IFC
How to Obtain Service ..................................... IFC
Table of Contents ...............................................1
Safety Rules .........................................................2
Standards Index .................................................. 3
Section 1 – General Information ...................4
1.1 Unpacking/Inspection ....................................4
1.2 Protection Systems ........................................4
1.3 NEC Requirement for Arc Fault Circuit
Interruption Breaker for Bedrooms ...............4
1.4 Emission Information....................................5
1.5 The Generator ...............................................6
1.6 Specifications ................................................ 7
1.7 System Set LED ............................................8
1.8 Fuel Requirements and Recommendations .... 8
1.9 Fuel Consumption .........................................8
1.10 Reconfiguring the Fuel System .......................9
1.11 Location ......................................................10
1.12 Battery Requirements ..................................11
1.13 Battery Installation ......................................11
1.14 The Battery.................................................. 12
1.15 Battery Charger ........................................... 12
Section 3 – Operation .....................................16
3.1 Control Panel Interface ................................16
3.2 Automatic Transfer Operation ..................... 17
3.3 Sequence of Automatic Operation ................ 18
3.4 Manual Transfer Operation .........................19
3.5 Side Compartment (V-twin Only) .................20
3.6 Protection Systems ...................................... 20
Section 4 – Maintenance .............................. 22
4.1 Fuse ............................................................. 22
4.2 Checking the Engine Oil Level ..................... 22
4.3 Changing the Engine Oil ..............................23
4.4 Changing the Engine Air Cleaner ................. 23
4.5 Spark Plug(s) .............................................. 24
4.6 Battery Maintenance .................................... 25
4.7 Adjusting GH-410/GT-530/990/999
Valve Clearance ............................................ 25
4.8 Cooling System ............................................26
4.9 Attention After Submersion .........................26
4.10 Corrosion Protection ................................... 27
4.11 Out of Service Procedure ............................. 27
4.12 Service Schedule .........................................28
Section 5 – Troubleshooting ........................ 29
5.1 Troubleshooting Guide ................................29
Section 6 – Appendix ..................................... 30
6.1 Menu System Navigation .............................30
Section 2 – Post Installation Start-up
and Adjustments ........................13
2.1 Before Initial Startup ................................... 13
2.2 Check Transfer Switch Operation................13
2.3 Electrical Checks .........................................13
2.4 Generator Tests Under Load .......................14
2.5 Checking Automatic Operation ....................14
2.6 Engine Governor Adjustment ...................... 15
2.7 Voltage Regulator Adjustment ......................15
Section 7 – Notes ............................................ 32
Section 8 – Installation Diagrams .............. 33
Section 9 – Warranty ...................................... 36
1
IMPORTANT SAFETY INSTRUCTIONS
Air-cooled Generators
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation
be copied and posted near the unit’s installation site. Safety should be stressed to all opera-
tors and potential operators of this equipment.
The engine exhaust from this product
contains chemicals known to the state
defects or other reproductive harm.
This product contains or emits chemicals
known to the state of California to cause
cancer, birth defects or other reproductive harm.
Study these SAFETY RULES carefully before install­ing, operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The generator can operate safely, efficiently and reliably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warn­ings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive. If using a procedure, work method or operating technique the manufacturer does not specifically recommend, ensure that it is safe for others. Also make sure the procedure, work method or operating technique uti­lized does not render the generator unsafe.
WARNING:
of California to cause cancer, birth
WARNING:
DANGER
Despite the safe design of this generator,
operating this equipment imprudently, neglecting its maintenance or being careless can cause possible injury or death. Permit only responsible and capable persons to operate or maintain this equipment.
Potentially lethal voltages are generated by
these machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator.
Parts of the generator are rotating and/or hot
during operation. Exercise care near running generators.
GENERAL HAZARDS
For safety reasons, the manufacturer recommends
that the installation, initial start-up and main­tenance of this equipment is carried out by a Dealer.
The engine exhaust fumes contain carbon monox-
ide, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. Do NOT alter or add to the exhaust system or do anything that might render the system unsafe or in noncompli­ance with applicable codes and standards.
Keep hands, feet, clothing, etc., away from drive
belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
Adequate, unobstructed flow of cooling and venti-
lating air is critical to correct generator operation. Do not alter the installation or permit even partial blockage of ventilation provisions, as this can seri­ously affect safe operation of the generator. The generator MUST be installed outdoors.
When working on this equipment, remain alert
at all times. Never work on the equipment when physically or mentally fatigued.
Inspect the generator regularly, and contact the
nearest Dealer for parts needing repair or replace­ment.
Before performing any maintenance on the gen-
erator, disconnect its battery cables to prevent accidental start up. Disconnect the cable from the battery post indicated by a NEGATIVE, NEG or (–) first, then remove the POSITIVE, POS or (+) cable. When reconnecting the cables, connect the POSITIVE cable first, the NEGATIVE cable last.
Never use the generator or any of its parts as a
step. Stepping on the unit can stress and break parts, and may result in dangerous operating con­ditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
2
IMPORTANT SAFETY INSTRUCTIONS
Air-cooled Generators
ELECTRICAL HAZARDS
All generators covered by this manual produce
dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as does the standby generator when it is in opera­tion. Avoid contact with bare wires, terminals, connections, etc., while the unit is running. Ensure all appropriate covers, guards and barriers are in place, secured and/or locked before operating the generator. If work must be done around an oper­ating unit, stand on an insulated, dry surface to reduce shock hazard.
Do not handle any kind of electrical device while
standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
The National Electrical Code (NEC) requires the
frame and external electrically conductive parts of the generator to be connected to an approved earth ground. Local electrical codes also may require proper grounding of the generator electrical system.
After installing this home standby electrical sys-
tem, the generator may crank and start at any time without warning. When this occurs, load cir­cuits are transferred to the STANDBY (generator) power source. To prevent possible injury if such a start and transfer occur, always set the generator’s AUTO/OFF/MANUAL switch to its OFF position before working on equipment and remove the 15A fuse from the generator control panel.
In case of accident caused by electric shock, imme-
diately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting implement, such as a dry rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.
Never wear jewelry when working on this equip-
ment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving com­ponents causing injury.
FIRE HAZARDS
For fire safety, the generator must be installed and
maintained properly. Installation must always
comply with applicable codes, standards, laws and regulations. Adhere strictly to local, state
and national electrical and building codes. Comply with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, ensure that the generator is installed in accordance with the manufacturer’s instructions and recommendations. Following proper installa­tion, do nothing that might alter a safe installation and render the unit in noncompliance with the aforementioned codes, standards, laws and regu­lations.
Keep a fire extinguisher near the generator at all
times. Extinguishers rated “ABC” by the National Fire Protection Association are appropriate for use on the standby electric system. Keep the extin­guisher properly charged and be familiar with its use. Consult the local fire department with any questions pertaining to fire extinguishers.
EXPLOSION HAZARDS
Do not smoke around the generator. Wipe up any
fuel or oil spills immediately. Ensure that no com­bustible materials are left in the generator com­partment, or on or near the generator, as FIRE or EXPLOSION may result. Keep the area surround­ing the generator clean and free from debris.
Gaseous fluids such as natural gas and liquid pro-
pane (LP) gas are extremely EXPLOSIVE. Install the fuel supply system according to applicable fuel-gas codes. Before placing the home standby electric system into service, fuel system lines must be properly purged and leak tested according to applicable code. After installation, inspect the fuel system periodically for leaks. No leakage is permit­ted.
STANDARDS INDEX
In the absence of pertinent standards, codes, regu­lations and laws, the published information listed below may be used as installation guide for this equipment.
1. NFPA No. 37, STATIONARY COMBUSTION
ENGINES AND GAS TURBINES, available from the National Fire Protection Association, 470 Atlantic Avenue, Boston, MA 02210.
2. NFPA No. 76A, ESSENTIAL ELECTRICAL
SYSTEMS FOR HEALTH CARE FACILITIES, available same as Item 1.
3. NFPA No. 54, NATIONAL FUEL GAS CODE,
available same as Item 1.
4. NFPA No. 58, AMERICAN NATIONAL STANDARD
FOR STORAGE AND HANDLING OF LIQUEFIED PETROLEUM GAS, available same as Item 1.
5. NFPA No. 70, NFPA HANDBOOK OF NATIONAL
ELECTRIC CODE, available same as Item 1.
6. Article X, NATIONAL BUILDING CODE, available
from the American Insurance Association, 85 John Street, New York, N.Y. 10038.
7. AGRICULTURAL WIRING HANDBOOK, avail-
able from the Food and Energy Council, 909 University Avenue, Columbia, MO 65201.
8. ASAE EP-3634, INSTALLATION AND
MAINTENANCE OF FARM STANDBY ELECTRICAL SYSTEMS, available from the American Society of Agricultural Engineers, 2950 Niles Road, St. Joseph, MI 49085.
9. NFPA No. 30, FLAMMABLE AND COMBUSTIBLE
LIQUIDS CODE, available same as Item 1.
3
DANGER
Section 1 — General Information
Air-cooled Generators
1.2 PROTECTION SYSTEMS
Unlike an automobile engine, the generator may have
Only qualified electricians or contractors should
attempt such installations, which must comply strictly with applicable codes, standards and regu­lations.
1.1 UNPACKING/INSPECTION
After unpacking, carefully inspect the contents for damage.
This standby generator set is ready for installa-
tion with a factory supplied and pre-mounted base pad and has a weather protective enclosure that is intended for outdoor installation only.
This UL listed standby generator set may be pack-
aged with an automatic transfer switch with built in load center. The combination transfer switch and load center is pre-wired with a two foot and 30 foot conduit. Circuit breakers for emergency circuit connections are included (if equipped).
This UL listed, 2-pole switch is rated at 100 • or 200
AC amperes at 250 volts maximum. The 100 Amp
transfer switch is for indoor use only. The 200 Amp transfer switch is for indoor/outdoor use (if equipped).
If this generator is used to power electrical load
circuits normally powered by a utility power source, it is required by code to install a transfer switch. The transfer switch must effectively isolate the electrical system from the utility distribution system when the generator is operating (NEC 700, 701 & 702). Failure to isolate an electrical system by such means will result in damage to the gen­erator and also may result in injury or death to utility power workers due to backfeed of electrical energy.
If any loss or damage is noted at time of delivery, have the person(s) making the delivery note all damage on the freight bill or affix their signature under the con­signor's memo of loss or damage.
If a loss or damage is noted after delivery, separate the damaged materials and contact the carrier for claim procedures.
“Concealed damage” is understood to mean damage to the contents of a package that is not in evidence at the time of delivery, but is discovered later.
To properly open the roof, press down on the cen­ter top lip and release the latch. If pressure is not applied from the top, the roof may appear stuck. Always verify that the side lock is unlocked before attempting to lift the roof.
to run for long periods of time with no operator pres­ent to monitor engine conditions. For that reason, the engine is equipped with the following systems that protect it against potentially damaging condi­tions:
1. Low Oil Pressure Sensor
2. High Temperature Sensor
3. Overcrank
4. Overspeed
5. RPM Sensor
6. Low Battery
There are readouts on the control panel to notify personnel that one of these failures has occurred. There is also a System Set LED (single cylinder) or a Status message on the display (V-twins) that displays when all of the conditions described in the "System Set LED" section are true.
1.3 NEC REQUIREMENT FOR ARC
FAULT CIRCUIT INTERRUPTION BREAKER FOR BEDROOMS
In 2001, the National Electric Code (NEC) intro­duced a requirement for new construction. This new requirement indicates the need for Arc Fault Circuit Interrupters to be used to protect the complete branch circuit that feeds a dwelling bedroom. The actual NEC requirement is indicated below.
1.3.1 SECTION 210.12 ARC FAULT CIRCUIT INTERRUPTER PROTECTION
1. Definition: An arc fault circuit interrupter is a device intended to provide protection from the effects of arc faults by recognizing characteristics unique to arcing and by functioning to de-ener­gize the circuit when an arc fault is detected.
2. Dwelling Unit Bedrooms: All branch circuits that supply 125 volt, single-phase, 15 and 20 ampere outlets installed in dwelling unit bedrooms shall be protected by an arc fault circuit interrupter listed to provide protection of the entire branch circuit.
Section 210.12 requires that AFCI protection be provided on branch circuits that supply outlets (receptacle, lighting, etc.) in dwelling bedrooms. The requirement is limited to 15 and 20 ampere, 125 volt circuits. There is no prohibition against provid­ing AFCI protection on other circuits or in locations other than bedrooms. Because circuits are often shared between a bedroom and other areas such as closets and hallways, providing AFCI protection on the complete circuit would comply with 210.12.
4
Section 1 — General Information
Air-cooled Generators
If during the installation of the home standby system the decision is made to provide back up power to a bedroom branch circuit, then the circuit breaker in the transfer switch should be replaced with an Arc Fault Circuit Interrupter.
It is most important that breakers only be switched like for like. For instance, if replacing a 15A breaker, it MUST be replaced with a 15A AFCI breaker. Likewise, a 20A breaker MUST be replaced with a 20A AFCI.
These AFCI breakers are available at the nearest hardware store.
Siemens Item # Description Q115AF 15A Single Pole AFCI Q120AF 20A Single Pole AFCI
1.4 EMISSION INFORMATION
The Environmental Protection Agency requires that this generator complies with exhaust emission stan­dards. This generator is certified to meet the appli­cable EPA emission levels. Additional information regarding the requirements set by the EPA is as fol­lows:
The generator is certified for use as a stationary engine for standby power generation. Any other use may be a violation of federal and/or local laws. It is important that to follow the maintenance specifica­tions in the "Maintenance" section to ensure that the engine complies with the applicable emission stan­dards for the duration of the engine’s life. This engine is certified to operate on Liquid Propane fuel and pipeline Natural Gas. The emission control system on the generator consists of the following:
Fuel Metering System
Carburetor/mixer assembly• Fuel regulator
Air Induction System
Intake pipe/manifold• Air cleaner
Ignition System
Spark plug• Ignition module
The Emissions Compliance Period referred to on the Emissions Compliance Label indicates the number of operating hours for which the engine has been shown to meet Federal emission requirements. See the table below to determine the compliance period for the generator. The displacement of the generator is listed on the Emissions Compliance Label.
Displacement Category Compliance Period
A 300 Hours
< 66 cc
66 cc -
< 225 cc
225 cc
B 125 Hours C 50 Hours A 500 Hours B 250 Hours C 125 Hours A 1000 Hours B 500 Hours C 250 Hours
5
Section 1 — General Information
Air-cooled Generators
1.5 THE GENERATOR
Figure 1.1 – 8kW, Single Cylinder, GH-410 Engine
(door removed)
Circuit
Breaker
Air Filter
Fuel Inlet
(back)
Fuel
Regulator
Exhaust
Enclosure
Oil
Dipstick
Composite Base Oil Filter Battery Compartment
Data Label
(see sample)
Control
Panel
Figure 1.2 – 10kW, V-twin, GT-530 Engine
(door removed)
Oil
Dipstick
Exhaust
Enclosure
Composite Base Oil Filter Battery Compartment
Data Label
(see sample)
Control
Panel
Circuit
Breaker
Air
Filter
Fuel Inlet
(back)
Fuel
Regulator
Exhaust
Enclosure
Figure 1.3 – 12, 14, 16, 17 and 20kW, V-twin,
GT-990/GT-999 Engine (door removed)
Data Label
Oil
Dipstick
Composite Base Oil Filter Battery Compartment
(see sample)
Air Filter
Control
Panel
Circuit Breakers
GFCI Outlet
(All 17 & 20kW)
Fuel Inlet
(back)
Fuel
Regulator
Data Label Sample
6
Section 1 — General Information
Air-cooled Generators
1.6 SPECIFICATIONS
1.6.1 GENERATOR
Model 8kW 10kW 12kW 14kW 16kW 17kW 20kW
Rated Maximum Power Capacity (Watts*)
Rated Voltage 120/240
Rated Maximum Load Current (Amps)
120 Volts** (NG/LP) 58.3/66.6 75.0/83.3 100.0/100.0 108.3/116.6 133.3/133.3 133.3/141.6 150.0/166.6
240 Volts (NG/LP) 29.2/33.3 37.5/41.6 50.0/50.0 54.2/58.3 66.6/66.6 66.6/70.8 75.0/83.3
Main Circuit Breaker 35 Amp 45 Amp 50 Amp 60 Amp 65 Amp 65 Amp 100 Amp
Circuits*** 50A, 240V - - - 1 1 1 -
40A, 240V - - 1 1 1 1 -
30A, 240V 1 1 1 - - - -
20A, 240V - 1 - 1 1 1 -
20A, 120V 1 3 3 4 5 5 -
15A, 120V 5 3 5 4 5 5 -
Phase 1
Number of Rotor Poles 2
Rated AC Frequency 60 Hz
Battery Requirement
Weight (unit only in lbs.) 340 387 439 439 439 455/421 450
Enclosure Steel Steel Steel Steel Steel Steel/Aluminum Aluminum
Normal Operating Range -20° F (-28.8° C) to 77° F (25° C)
* Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition,
etc. Maximum power decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6 C (10 F) above 16 C (60 F) ambient temperature.
** Load current values shown for 120 volts are maximum TOTAL values for two separate circuits. The maximum current in each circuit must not exceed the
value stated for the 240 volts.
*** Circuits to be moved must be protected by same size breaker. For example, a 15 amp circuit in the main panel must be a 15 amp circuit in the transfer
switch.
7,000 NG
8,000 LP
Group 26R, 12
Volts and 350
CCA Minimum
9,000 NG
10,000 LP
12,000 NG
12,000 LP
13,000 NG
14,000 LP
Group 26R, 12 Volts and 525 CCA Minimum
16,000 NG
16,000 LP
16,000 NG
17,000 LP
18,000 NG
20,000 LP
1.6.2 ENGINE
Model 8 kW 10 kW 12/14/16/17 kW 20 kW
Type of Engine GH-410 GT-530 GT-990 GT-999
Number of Cylinders 1 2 2 2
Rated Horsepower @ 3,600 rpm 14.8 18 32 36
Displacement 410cc 530cc 992cc 999cc
Cylinder Block Aluminum w/Cast Iron Sleeve
Valve Arrangement Overhead Valves
Ignition System Solid-state w/Magneto
Recommended Spark Plug RC14YC BPR6HS RC14YC RC12YC
Spark Plug Gap 0.76 mm (0.030 inch) 0.76 mm (0.030 inch) 1.02 mm (0.040 inch) 0.76 mm (0.030 inch)
Compression Ratio 8.6:1 9.5:1 9.5:1 9.5:1
Starter 12 VDC
Oil Capacity Including Filter Approx. 1.5 Qts Approx. 1.7 Qts Approx. 1.7 Qts Approx. 1.7 Qts
Recommended Oil Filter Part # 070185F
Recommended Air Filter Part # 0G3332 Part # 0E9581 Part # 0C8127 Part # 0G5894
Operating RPM 3,600
7
Section 1 — General Information
Air-cooled Generators
1.7 SYSTEM SET LED
The “System Set” LED (single cylinder) or "Ready to Run" on the display (v-twin) is ready when all of the following conditions are true:
1. The AUTO/OFF/MANUAL switch is set to the AUTO position.
2. The utility voltage being supplied to the unit is being sensed by the PCB. If the utility sense volt­age is not connected to the unit or if it is below approximately 150-160 volts AC, then the system set light will flash rapidly (8kW). This indicates that if the AUTO/OFF/MANUAL switch is placed in the Auto position, the generator will start.
3. No alarms are present, for example, low oil pres­sure, high temperature, etc.
1.8 FUEL REQUIREMENTS
AND RECOMMENDATIONS
With LP gas, use only the vapor withdrawal sys­tem. This type of system uses the vapors formed
above the liquid fuel in the storage tank. The engine has been fitted with a fuel carburetion
system that meets the specifications of the 1997 California Air Resources Board for tamper-proof dual fuel systems. The unit will run on natural gas or LP gas, but it has been factory set to run on natural gas. Should the primary fuel need to be changed to LP gas, the fuel system needs to be reconfigured. See the reconfiguring the Fuel System section for instructions on reconfiguration of the fuel system.
Recommended fuels should have a Btu content of at least 1,000 Btus per cubic foot for natural gas; or at least 2,520 Btus per cubic foot for LP gas. Ask the fuel supplier for the Btu content of the fuel.
Required fuel pressure for natural gas is five (5)
inches to seven (7) inches water column (0.18 to
0.25 psi); and for liquid propane, 10 inches to 12
inches of water column (0.36 to 0.43 psi). The primary regulator for the propane supply is NOT INCLUDED with the generator.
NOTE:
All pipe sizing, construction and layout must com­ply with NFPA 54 for natural gas applications and NFPA 58 for liquid propane applications. Once the generator is installed, verify that the fuel pressure NEVER drops below four (4) inches water column for natural gas or 10 inches water column for liq­uid propane.
Prior to installation of the generator, the installer should consult local fuel suppliers or the fire mar­shal to check codes and regulations for proper instal­lation. Local codes will mandate correct routing of gaseous fuel line piping around gardens, shrubs and other landscaping to prevent any damage.
8
Special considerations should be given when install­ing the unit where local conditions include flooding, tornados, hurricanes, earthquakes and unstable ground for the flexibility and strength of piping and their connections.
Use an approved pipe sealant or joint compound on all threaded fitting.
All installed gaseous fuel piping must be purged and leak tested prior to initial start-up in accordance with local codes, standards and regulations.
1.9 FUEL CONSUMPTION
Unit
7/8 kW 77 140 0.94/34 1.68/62
9/10 kW 102 156 1.25/46 1.93/70
12/12 kW 152 215 1.53/56 2.08/76
13/14 kW 156 220 1.56/58 2.30/84
16/16 kW 183 261 1.59/58 2.51/91
16/17 kW 183 261 1.61/59 2.57/94
18/20 kW 206 294 1.89/69 2.90/106
* Natural gas is in cubic feet per hour. ** LP is in gallons per hour/cubic feet per hour. *** Values given are approximate.
Verify that gas meter is capable of providing enough fuel flow to include household appliances.
1.9.1 BTU FLOW REQUIREMENTS - NATURAL GAS
BTU flow required for each unit based on 1000 BTU per cubic foot.
7kW — 140,000 BTU/Hour• 9kW — 156,000 BTU/Hour• 12kW — 215,000 BTU/Hour• 13kW — 220,000 BTU/Hour• 16kW — 261,000 BTU/Hour• 18kW — 294,000 BTU/Hour
 Gaseous fuels such as natural gas and liquid
propane (LP) gas are highly explosive. Even the slightest spark can ignite such fuels and cause an explosion. No leakage of fuel is permitted. Natural gas, which is lighter than air, tends to collect in high areas. LP gas is heavier than air and tends to settle in low areas.
Nat. Gas LP Vapor
1/2 Load Full Load 1/2 Load Full Load
DANGER
Section 1 — General Information
Air-cooled Generators
NOTE:
A minimum of one approved manual shut-off valve must be installed in the gaseous fuel supply line. The valve must be easily accessible. Local codes determine the proper location.
1.10 RECONFIGURING THE FUEL SYSTEM
1.10.1 8 KW, 410CC ENGINE
To reconfigure the fuel system from NG to LP, follow these steps (Figure 1.4):
NOTE:
The primary regulator for the propane supply is NOT INCLUDED with the generator. A fuel pres­sure of 10 to 12 inches of water column (0.36 to
0.43 psi) to the fuel inlet of the generator MUST
BE SUPPLIED.
1. Turn off the main gas supply (if connected).
2. Open the roof and remove the door.
3. Remove the battery (if installed).
4. Take the plastic T-handle fuel selector in the poly
bag supplied with the generator.
5. Locate the selector knob on the air box cover,
behind the yellow air filter door and power bulge. The unit comes from the factory in the NG (Natural Gas) position. Grasping the T-handle, insert the pin end into the hole in the selector knob and pull out to overcome spring pressure and then twist clockwise 90 degrees and allow the selector to return in once aligned with the LP (Liquid Propane) position.
6. Save this tool with the Owner's Manual.
7. Install the battery, door and close the roof.
8. Reverse the procedure to convert back to natural
gas.
Figure 1.4 – Fuel Selector
NOTE:
Use an approved pipe sealant or joint compound on all threaded fittings to reduce the possibility of leakage.
1.10.2 10, 12, 14, 16, 17 AND 20KW, V-TWIN ENGINES
To reconfigure the fuel system from NG to LP, follow these steps:
NOTE:
The primary regulator for the propane supply is NOT INCLUDED with the generator. A fuel pres­sure of 10 to 12 inches of water column (0.36 to
0.43 psi) to the fuel inlet of the generator MUST BE SUPPLIED.
1. Open the roof.
2. For 10kW units: Loosen clamp and slide back
the air inlet hose.
Slide fuel selector on carburetor out towards the • back of the enclosure (Figures 1.5 and 1.6).
Return the inlet hose and tighten clamp secure-• ly.
For 12, 14, 16, 17 and 20kW units: remove the air
cleaner cover.
Slide the selector lever out towards the back of • the enclosure (Figures 1.7 and 1.8).
Return the air cleaner cover and tighten the two • thumb screws.
Figure 1.5 - 10kW, GT-530 (Inlet Hose Slid Back)
Fuel Selection
Lever - "In" Position for Natural Gas
Fuel
3. Close the roof.
4. Reverse the procedure to convert back to natural gas.
9
Section 1 — General Information
Air-cooled Generators
Figure 1.6 - 10kW, GT-530 (Inlet Hose Slid Back)
Fuel Selection
Lever - "Out"
Position for
Liquid Propane
(Vapor) Fuel
Figure 1.7 - 12, 14, 16, 17, & 20kW,
GT-990/GT-999 (Airbox Cover Removed)
Fuel Selection Lever - "In" Position for Natural Gas Fuel
Figure 1.8 - 12, 14, 16, 17, & 20kW,
GT-990/GT-999 (Airbox Cover Removed)
Fuel Selection Lever - "Out" Position for Liquid Propane
(Vapor) Fuel
1.11 LOCATION
1.11.1 GENERATOR
Install the generator set, in its protective enclosure, outdoors, where adequate cooling and ventilating air is always available (Figure 1.9). Consider these fac­tors:
The installation of the generator must comply
strictly with NFPA 37, NFPA 54, NFPA 58, and NFPA 70 standards.
Install the unit where air inlet and outlet open-
ings will not become obstructed by leaves, grass, snow, etc.. If prevailing winds will cause blowing or drifting, consider using a windbreak to protect the unit.
Install the generator on high ground where water
levels will not rise and endanger it.
Allow sufficient room on all sides of the generator
for maintenance and servicing. This unit must be installed in accordance with current applicable NFPA 37 and NFPA 70 standards; as well as any other federal, state and local codes for minimum distances from other structures. DO NOT install under wooden decks or structures unless there is at least four (4) feet of clearance above the genera­tor, three (3) feet of clearance on sides and front, and 18 inches of clearance at back of unit.
Install the unit where rain gutter down spouts,
roof run-off, landscape irrigation, water sprinklers or sump pump discharge does not flood the unit or spray the enclosure, including any air inlet or outlet openings.
Install the unit where services will not be affected
or obstructed, including concealed, underground or covered services such as electrical, fuel, phone, air conditioning or irrigation.
Where strong prevailing winds blow from one
direction, face the generator air inlet openings to the prevailing winds.
Figure 1.9 – Generator Clearances
10
Install the generator as close as possible to the fuel
supply, to reduce the length of piping.
Install the generator as close as possible to the
transfer switch. REMEMBER THAT LAWS OR CODES MAY REGULATE THE DISTANCE AND LOCATION.
The genset must be installed on a level surface.
The base frame must be level within two (2) inches all around.
The generator is typically placed on pea gravel or
crushed stone. Check local codes if a concrete slab is required. If a concrete base slab is required, all federal, state and local codes should be followed. Special attention should be given to the concrete base slab which should exceed the length and width of the generator by a minimum of six (6) inches (0.152 meters) on all sides.
The engine exhaust fumes contain carbon mon-
oxide, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. This exhaust system must be installed properly, in strict compliance with applicable codes and stan­dards. Following installation, do nothing that might render the system unsafe or in noncompli­ance with such codes and standards.
• Operate the generator outdoors ONLY.
• Keep exhaust gases from entering a confined area through windows, doors, ventilation or other openings (Figure 1.9).
1.11.2 TRANSFER SWITCH ( if included)
1.11.2.1 8, 10, 12, 14, 16, 17 and 20kW Units (if equipped)
The transfer switch that may have shipped inside the carton with the 8, 10, 12, 14, 16 or 17kW gen­erator is enclosed in a NEMA 1 (indoor rated only) enclosure. The transfer switch that may have shipped with the 20kW generator is enclosed in a NEMA 3R (indoor/outdoor rated) enclosure.
Install the transfer switch indoors on a firm, sturdy
supporting structure.
To prevent switch distortion, level the switch if
necessary. This can be done by placing washers between the switch enclosure and mounting sur­face.
Never install the switch where water or any corro-
sive substance might drip onto the enclosure.
Protect the switch at all times against excessive
moisture, dust, dirt, lint, construction grit and corrosive vapors.
Section 1 — General Information
Air-cooled Generators
If the AUTO/OFF/MANUAL switch is not set to its
OFF position, the generator can crank and start as soon as the battery cables are connected. If the utility power supply is not turned off, spark­ing can occur at the battery posts and cause an explosion.
1.12 BATTERY REQUIREMENTS
See the Specifications section for correct battery size and rating.
1.13 BATTERY INSTALLATION
Fill the battery with the proper electrolyte fluid if necessary and have the battery fully charged before installing it.
Before installing and connecting the battery, complete the following steps:
1. Set the generator's AUTO/OFF/MANUAL switch to OFF.
2. Turn off utility power supply to the transfer switch.
3. Remove the 7.5A fuse from the generator control panel.
Battery cables were factory connected at the genera­tor (Figure 1.10). Connect cables to battery posts as follows:
4. Connect the red battery cable (from starter con­tactor) to the battery post indicated by a positive, POS or (+).
5. Connect the black battery cable (from frame ground) to the battery post indicated by a nega­tive, NEG or (—).
Figure 1.10 – Battery Cable Connections
11
Section 1 — General Information
Air-cooled Generators
NOTE:
Dielectric grease should be used on battery posts to aid in the prevention of corrosion.
NOTE:
Damage will result if battery connections are made in reverse.
NOTE: In areas where temperatures regularly fall below 10° F (-12° C) it is recommended that a pad type battery heater be installed to aid in cold climate starting.
1.14 THE BATTERY
DANGER
Do not dispose of the battery in a fire. The
battery is capable of exploding.
A battery presents a risk of electrical shock
and high short circuit current. The following pre­cautions are to be observed when working on batteries:
• Remove the 7.5A fuse from the generator control
panel.
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the
battery; and
• Disconnect charging source prior to connecting or
disconnecting battery terminals.
Do not open or mutilate the battery. Released
electrolyte has been known to be harmful to the skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically conductive and corrosive.
The following procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off
immediately with water;
• Where electrolyte contacts the eyes, flush thor-
oughly and immediately with water and seek medical attention; and
• Spilled electrolyte is to be washed down with an
acid neutralizing agent. A common practice is to use a solution of 1 pound (500 grams) bicarbonate of soda to 1 gallon (4 liters) of water. The bicar­bonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.
12
Lead-acid batteries present a risk of fire because
they generate hydrogen gas. The following procedures are to be followed:
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from body before touch­ing the battery by first touching a grounded metal surface.
Be sure the AUTO/OFF/MANUAL switch is set to
the OFF position before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.
Be sure the utility power supply is turned off
and the 7.5A fuse is removed from the genera­tor control panel, or sparking may occur at the battery posts as the cables are attached and cause an explosion.
Servicing of the battery is to be performed or super­vised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized person­nel away from batteries.
See the Specifications section for the correct size and rating when replacing the battery. Have these procedures performed at the intervals specified in the “Service Schedule.” A negative ground system is used. Battery connections are shown on the wiring diagrams. Make sure the battery is correctly connect­ed and terminals are tight. Observe battery polarity when connecting the battery to the generator set.
1.15 BATTERY CHARGER
NOTE:
These generators DO NOT contain an internal bat­tery charger.
NOTE:
The manufacturer provides a battery trickle char­ger that is active when the unit is set up for auto­matic operation. With the battery installed and utility power source voltage available to the trans­fer switch, the battery receives a trickle charge to prevent self-discharge. The trickle charger is designed to help extend the life of the battery by maintaining the battery. The trickle charge feature cannot be used to recharge a discharged battery.
For units shipped with a transfer switch/load center, the battery charger is pre-installed in the transfer switch enclosure.
For units shipped without a transfer switch/load cen­ter, a separate battery charger module is included with the generator.
(For battery charger installation, see the Generator Install Guidelines and Battery Charger Instructions included with the unit.)
Section 2 — Post Installation Start-up and Adjustments
DANGER
Air-cooled Generators
2.1 BEFORE INITIAL START-UP
NOTE:
These units have been run and tested at the fac­tory prior to being shipped and do not require any type of break-in.
Before starting, complete the following:
1. Set the generator’s main circuit breaker to its OFF (or OPEN) position.
2. Set the generator's AUTO/OFF/MANUAL switch to the OFF position.
3. Turn OFF all breakers on the load center of the transfer box (T1 and T2).
4. Turn OFF all loads connected to the transfer switch terminals T1 and T2.
5. Check the engine crankcase oil level and, if neces­sary, fill to the dipstick FULL mark with the rec­ommended oil. Do not fill above the FULL mark.
6. Check the fuel supply. Gaseous fuel lines must have been properly purged and leak tested in accordance with applicable fuel-gas codes. All fuel shutoff valves in the fuel supply lines must be open.
During initial start up only, the generator may exceed the normal number of start attempts and experience an “over crank” fault (See the "Overcrank" section). This is due to accumulated air in the fuel system dur­ing installation. Reset the control board and restart up to two more times, if necessary. If unit fails to start, contact the local dealer for assistance.
Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing this could damage the engine.
2.2 CHECK TRANSFER SWITCH
2.3 ELECTRICAL CHECKS
Complete electrical checks as follows:
1. Set the generator's main circuit breaker to its OFF (or OPEN) position.
2. Set the generator's AUTO/OFF/MANUAL switch to the OFF position.
3. Turn OFF all breakers on the load center of the transfer box (T1 and T2).
4. Turn on the utility power supply to the transfer switch using the means provided (such as a utility main line circuit breaker).
DANGER
The transfer switch is now electrically “hot.”
Contact with “hot” parts will result in extremely hazardous and possibly fatal electrical shock. Proceed with caution.
5. Use an accurate AC voltmeter to check utility power source voltage across transfer switch ter­minals N1 and N2. Nominal line-to-line voltage should be 240 volts AC.
6. Check utility power source voltage across termi­nals N1 and the transfer switch neutral lug; then across terminal N2 and neutral. Nominal line-to­neutral voltage should be 120 volts AC.
7. When certain that utility supply voltage is compat­ible with transfer switch and load circuit ratings, turn OFF the utility power supply to the transfer switch.
8. On the generator panel, set the Auto/Off/ Manual switch to MANUAL. The engine should crank and start.
9. Let the engine warm up for about five minutes to allow internal temperatures to stabilize. Then, set the generator’s main circuit breaker to its ON (or closed) position.
OPERATION
Refer to the "Manual Transfer Operation" section, of the owner’s manual for procedures.
DANGER
Do not attempt manual transfer switch opera-
tion until all power voltage supplies to the transfer switch have been positively turned off. Failure to turn off all power voltage supplies will result in extremely hazardous and possibly fatal electrical shock.
Proceed with caution! Generator power voltage
is now supplied to the transfer switch. Contact with live transfer switch parts will result in dan­gerous and possibly fatal electrical shock.
10. Connect an accurate AC voltmeter and a frequen­cy meter across transfer switch terminal lugs E1 and E2. 8kW voltage should be 230-240 volts at a frequency of 61-63 Hertz. 12, 14, 16, 17 and 20kW voltage should be 247-249 at a frequency of 59.5-60.5 Hertz. 10kW voltage should be 220-230 volts at a frequency of 59.5-60.5 Hertz.
11. Connect the AC voltmeter test leads across ter­minal lugs E1 and neutral; then across E2 and neutral. In both cases, voltage reading should be 121-126 volts AC (8kW), and 125-126 volts AC (10, 12, 14, 16, 17 and 20kW).
13
Section 2 — Post Installation Start-up and Adjustments
Air-cooled Generators
12. Set the generator’s main circuit breaker to its OFF (or OPEN) position. Let the engine run at no­load for a few minutes to stabilize internal engine generator temperatures.
13. Set the generator's AUTO/OFF/MANUAL switch to OFF. The engine should shut down.
NOTE:
It is important not to proceed until certain that generator AC voltage and frequency are correct and within the stated limits. Generally, if both AC frequency and voltage are high or low, the engine governor requires adjustment* (*GH410 only). If frequency is correct, but voltage is high or low, the generator’s voltage regulator requires adjustment.
2.4 GENERATOR TESTS UNDER LOAD
To test the generator set with electrical loads applied, proceed as follows:
1. Set generator’s main circuit breaker to its OFF (or OPEN) position.
2. Turn OFF all breakers on the load center of the transfer box (T1 and T2).
3. Set the generator's AUTO/OFF/MANUAL switch to OFF.
4. Turn OFF the utility power supply to the transfer switch, using the means provided (such as a util­ity main line circuit breaker).
Do not attempt manual transfer switch opera-
tion until all power voltage supplies to the transfer switch have been positively turned off. Failure to turn off all power voltage supplies will result in extremely hazardous and possibly fatal electrical shock.
5. Manually set the transfer switch to the STANDBY position, i.e., load terminals connected to the generator's E1/E2 terminals. The transfer switch operating lever should be down.
6. Set the generator's AUTO/OFF/MANUAL switch to MANUAL. The engine should crank and start immediately.
7. Let the engine stabilize and warm up for a few minutes.
8. Set the generator’s main circuit breaker to its ON (or CLOSED) position. Loads are now powered by the standby generator.
9. Turn ON the load center of the transfer switch (T1 and T2).
10. Connect an accurate AC voltmeter and a frequen­cy meter across terminal lugs E1 and E2.
8kW voltage should be greater than 230 volts and • frequency should be greater than 58 Hz.
10, 12, 14, 16, 17 and 20kW voltage should be greater than 240 volts and frequency should be 60 Hz.
11. Let the generator run at full rated load for 20-30 minutes. Listen for unusual noises, vibration or other indications of abnormal operation. Check for oil leaks, evidence of overheating, etc.
12. When testing under load is complete, turn OFF electrical loads.
13. Set the generator's main circuit breaker to its OFF (or OPEN) position.
14. Let the engine run at no-load for a few minutes.
15. Set the AUTO/OFF/MANUAL switch to OFF. The engine should shut down.
2.5 CHECKING AUTOMATIC
OPERATION
To check the system for proper automatic operation, proceed as follows:
1. Set generator’s main circuit breaker to its OFF (or OPEN) position.
2. Check that the AUTO/OFF/MANUAL switch is set to OFF.
3. Turn OFF the utility power supply to the transfer switch, using means provided (such as a utility main line circuit breaker).
4. Manually set the transfer switch to the UTILITY position, i.e., load terminals connected to the util­ity power source side.
5. Turn ON the utility power supply to the transfer switch, using the means provided (such as a util­ity main line circuit breaker).
6. Set the generator's main circuit breaker to its ON (or CLOSED) position.
7. Set the AUTO/OFF/MANUAL switch to AUTO. The system is now ready for automatic operation.
8. Turn OFF the utility power supply to the transfer switch.
With the AUTO/OFF/MANUAL switch at AUTO, the engine should crank and start when the utility source power is turned OFF after a 10 second delay. After starting, the transfer switch should connect load circuits to the standby side after a five (5) second delay. Let the system go through its entire automatic sequence of operation.
With the generator running and loads powered by generator AC output, turn ON the utility power supply to the transfer switch. The following should occur:
After about 15 seconds, the switch should transfer
loads back to the utility power source.
About one minute after re-transfer, the engine
should shut down.
14
GOVERNOR
SHAFT
PRIMARY
ADJUST
SCREW
GOVERNOR
CLAMP
BOLT
SECONDARY
ADJUST SCREW
Section 2 — Post Installation Start-up and Adjustments
Air-cooled Generators
2.6 ENGINE GOVERNOR ADJUSTMENT
If both AC frequency and voltage are correspondingly high or low, adjust the engine governor as follows:
2.6.1 8 KW UNITS
The engine must be OFF to perform steps 1 and
2.
1. Loosen the governor clamp bolt (Figure 2.1).
2. Hold the governor lever at its wide open throttle position (clockwise), and rotate the governor shaft clockwise as far as it will go. Then, tighten the governor lever clamp bolt to 70 inch-pounds (8 N-m).
Figure 2.1 — Engine Governor Adjustment
Single Cylinder Engines
2.6.3 ADDITIONAL CORROSION PROTECTION
Periodically spray all engine linkage parts and brack­ets with corrosion inhibiting spray such as WD-40 or a comparable product.
2.7 VOLTAGE REGULATOR ADJUSTMENT
2.7.1 8 & 10KW UNITS
Due to the brushless design of these two alternators, no voltage regulator is used and therefore no voltage adjustment is required.
2.7.2 12, 14, 16, 17 & 20KW UNITS
With the frequency between 59.5 -60.5 Hertz at no­load, slowly turn the slotted potentiometer (Figure
2.2) until line voltage reads 247-249 volts.
Figure 2.2 – Voltage Adjustment Potentiometer
3. Start the generator; let it stabilize and warm up at no-load.
4. Connect a frequency meter across the generators AC output leads.
5. Turn the primary adjust screw to obtain a fre­quency reading of 61.5 Hertz. Turn the secondary adjust screw to obtain a frequency of 62.5 Hz.
2.6.2 12, 14, 16, 17 & 20KW UNITS
All V-twin units DO NOT require an engine gover­nor adjustment due to their design.
NOTE:
Turn to adjust voltage.
NOTE:
The access panel on top of the control panel must be removed to adjust the voltage regulator.
NOTE:
The voltage regulator is housed behind the genera­tor's control panel. The regulator maintains a volt­age in direct proportion to frequency at a 2-to-1 ratio. For example, at 60 Hertz, line-to-neutral voltage will be 124 volts.
15
Section 3 — Operation
Air-cooled Generators
3.1 CONTROL PANEL INTERFACE
3.1.1 USING THE AUTO/OFF/MANUAL
SWITCH
1. “AUTO” Position – Selecting this switch activates fully automatic system operation. It also allows the unit to automatically start and exercise the engine every seven days with the setting of the exercise timer (see the Setting the Exercise Timer section).
2. “OFF” Position – This switch position shuts down the engine. This position also prevents automatic operation.
3. “MANUAL” Position – Set the switch to MANUAL to crank and start the engine. Transfer to standby power will not occur unless there is a utility fail­ure.
Figure 3.1 – 8kW Generator Control Panel
With the switch set to AUTO, the engine may
crank and start at any time without warning. Such automatic starting occurs when utility power source voltage droops below a preset level or during the normal exercise cycle. To prevent possible injury that might be caused by such sudden starts, always set the switch to OFF and remove the fuses before working on or around the generator or transfer switch. Then, place a “DO NOT OPERATE” tag on the genera­tor panel and on the transfer switch.
16
(FIGURES 3.1 & 3.2)
SYSTEM READY
LOW BATTERY
LOW OIL PRESSURE
HIGH OIL TEMPERATURE
OVERSPEED
RPM SENSOR LOSS
OVERCRANK
SET
EXERCISE
Figure 3.2 – 10/12/14/16/17 & 20kW Generator
Control Panel
ECS
ENTER
3.1.2 SETTING THE EXERCISE TIMER
This generator is equipped with an exercise timer. Once it is set, the generator will start and exercise every seven days, on the day of the week and at the time of day specified. During this exercise period, the unit runs for approximately 12 minutes and then shuts down. Transfer of loads to the generator out­put does not occur during the exercise cycle unless utility power is lost.
8kW
A switch on the control panel (see Figure 3.1) per­mits selection of the day and time for the system to exercise. At the chosen time, perform the following sequence to select the desired day and time of day the system will exercise. Remember seasonal time changes affect the exercise settings.
1. Verify that the AUTO/OFF/MANUAL switch is set to AUTO.
2. Press and hold the “Set Exercise” switch for sev­eral seconds. All the red LED’s will stop flashing immediately and the generator will start.
3. The generator will start and run for approximate­ly 12 minutes and then shut down. The exerciser is now set to run at this time of day each week.
Example: If the “Set Exercise” pressed on Saturday afternoon at 2:00 p.m., the generator will start and exercise for approximately 12 minutes every Saturday at 2:00 p.m.
Section 3 — Operation
Air-cooled Generators
NOTE:
The exerciser will only work in the AUTO mode and will not work unless this procedure is per­formed. The exerciser will need to be reset every time the 12 volt battery is disconnected and then reconnected, and when the fuse is removed and/ or replaced.
10 to 20 KW - INSTALLATION ASSISTANT
Upon first power up of the generator, the display interface will begin an installation assistant. The assistant will prompt the user to set the minimum settings to operate. These settings are simply: Current Date/Time and Exercise Day/Time. The maintenance intervals will be initialized when the exercise time is entered (Figure 3.2).
The exercise settings can be changed at any time via the "EDIT" menu (see Appendix, "Menu System").
If the 12 volt battery is disconnected or the fuse removed, the Installation Assistant will operate upon power restoration. The only difference is the display will only prompt the customer for the current Time and Date.
IF THE INSTALLER TESTS THE GENERATOR PRIOR TO INSTALLATION, PRESS THE “ENTER” KEY TO AVOID SETTING UP THE EXERCISE TIME. THIS WILL ENSURE THAT WHEN THE CUSTOMER POWERS UP THE UNIT, HE WILL STILL BE PROMPTED TO ENTER AN EXERCISE TIME.
NOTE:
The exerciser will only work in the AUTO mode and will not work unless this procedure is performed. The current date/time will need to be reset every time the 12 volt battery is disconnected and then reconnected, and/or when the fuse is removed.
3.1.3 DISPLAY INTERFACE
8 kW LED Display
Seven (7) LED’s are provided for user status indica­tions. The LED functions are:
1. System Ready (green)
2. Low Battery (red)
3. Low Oil Pressure (red)
4. High Oil Temperature (red)
5. Over Speed (red)
6. RPM Sensor Loss (red)
7. Over Crank (red) See the Protection Systems section for details.
10 to 20KW DISPLAY INTERFACE MENUS
The LCD display is organized as detailed below:
The “Home” page, this page is the default page
which will be displayed if no keys are pressed for 30 seconds. This page normally shows the current Status message and the current date and time. The highest priority active Alarm and/or Warning will be automatically posted on this page as well as flashing the backlight when such an event is detect­ed. In the case of multiple Alarms or Warnings, only the first message will be displayed. To clear an Alarm or Warning, see the Protection Systems section - Clear Alarm.
The display backlight is normally off. If the user
presses any key, the backlight will come on auto­matically and remain on for 30 seconds after the last key was pressed.
The “Main Menu” page will allow the user to
navigate to all other pages or sub-menus by using the Left/Right and Enter keys. This page can be accessed at any time with several presses of the dedicated Escape key. Each press of the Escape key takes you back to the previous menu until the main menu is reached. This page displays the fol­lowing options: HISTORY; STATUS; EDIT; AND DEBUG. (See the Appendix - "Menu System".)
3.2 AUTOMATIC TRANSFER
OPERATION
To select automatic operation, do the following:
1. Make sure the transfer switch main contacts are set to their UTILITY position, i.e., loads con­nected to the utility power source (Figure 3.2).
2. Be sure that normal UTILITY power source volt­age is available to transfer switch terminal lugs N1 and N2 (Refer to the Electrical Data section).
3. Set the generator’s AUTO/OFF/MANUAL switch to AUTO.
4. Set the generator’s main circuit breaker to its ON (or CLOSED) position.
With the preceding steps complete, the generator will start automatically when utility source voltage drops below a preset level. After the unit starts, loads are transferred to the standby power source. Refer to the Sequence of Automatic Operation section.
17
Section 3 — Operation
Air-cooled Generators
3.3 SEQUENCE OF AUTOMATIC OPERATION
3.3.1 UTILITY FAILURE
Initial Conditions: Generator in Auto, ready to run, load being supplied by utility source. When utility fails (below 65% of nominal), a 10 second (optionally programmable on the 17 and 20kW only) line inter­rupt delay time is started. If the utility is still gone when the timer expires, the engine will crank and start. Once started, a five (5) second engine warm­up timer will be initiated. When the warm-up timer expires, the control will transfer the load to the gen­erator. If the utility power is restored (above 75% of nominal) at any time from the initiation of the engine start until the generator is ready to accept load (5 second warm-up time has not elapsed), the control­ler will complete the start cycle and run the genera­tor through its normal cool down cycle; however, the load will remain on the utility source.
3.3.2 CRANKING
The system will control the cyclic cranking as follows: 16 second crank, seven (7) second rest, 16 second crank, seven (7) second rest followed by three (3) additional cycles of seven (7) second cranks followed by seven (7) second rests.
Choke Operation
1. The 990/999cc engines have an electric choke in
the air box that is automatically controlled by the electronic control board.
2. The 530cc engines have an electric choke on the
divider panel air inlet hose that is automatically controlled by the electronic control board.
3. The 410cc engines have a choke behind the air
box that is automatically controlled by the elec­tronic control board.
Failure to Start
This is defined as any of the following occurrences during cranking.
1. Not reaching starter dropout within the specified
crank cycle. Starter dropout is defined as four (4) cycles at 1,000 RPM.
2. Reaching starter dropout, but then not reaching
2200 RPM within 15 seconds. In this case the control board will go into a rest cycle for seven (7) seconds, then continue the rest of the crank cycle.
During a rest cycle the start and fuel outputs are de-energized and the magneto output is shorted to ground.
Cranking Conditions
The following notes apply during cranking cycle.
1. Starter motor will not engage within five (5) sec­onds of the engine shutting down.
2. The fuel output will not be energized with the starter.
3. The starter and magneto outputs will be ener­gized together.
4. Once the starter is energized the control board will begin looking for engine rotation. If it does not see an RPM signal within three (3) seconds it will shut down and latch out on RPM sensor loss.
5. Once the control board sees an RPM signal it will energize the fuel solenoid, drive the throttle open and continue the crank sequence.
6. Starter motor will disengage when speed reaches starter dropout.
7. If the generator does not reach 2200 RPM within 15 seconds, re-crank cycle will occur.
8. If engine stops turning between starter dropout and 2200 RPM, the board will go into a rest cycle for seven (7) seconds then re-crank (if additional crank cycles exist).
9. Once started, the generator will wait for a hold­off period before starting to monitor oil pressure and oil temperature (refer to the Alarm Messages section for hold-off times).
10. During Manual start cranking, if the Mode switch is moved from the Manual position, the cranking stops immediately.
11. During Auto mode cranking, if the Utility returns, the cranking cycle does NOT abort but continues until complete. Once the engine starts, it will run for one (1) minute, then shut down.
3.3.3 LOAD TRANSFER
The transfer of load when the generator is running is dependent upon the operating mode as follows:
1. Manual
Will not transfer to generator if utility is present.• Will transfer to generator if utility fails (below
65% of nominal for 10 consecutive seconds. Will transfer back when utility returns for 15 con-
secutive seconds. The engine will continue to run until removed from the Manual mode.
18
2. Auto
DANGER
Will start and run if Utility fails for 10 consecu-• tive seconds.
Will start a five (5) second engine warm-up • timer.
Will not transfer if utility subsequently returns.• Will transfer to generator if utility is still not pres-
ent. Will transfer back to utility once utility returns
(above 75% of nominal) for 15 seconds. Will transfer back to utility if the generator is
shut down for any reason (such as the switch is in the OFF position or a shutdown alarm.
After transfer, will shut down engine after one (1) • minute cool-down time.
3. Exercise Will not exercise if generator is already running
in either Auto or Manual mode. During exercise, the controller will only transfer
if utility fails during exercise for 10 seconds, and will switch to Auto mode.
Section 3 — Operation
Air-cooled Generators
Do not attempt to activate the transfer switch
manually until all power voltage supplies to the switch have been positively turned off. Failure to turn off all power voltage supplies may result in extremely hazardous and possibly fatal elec­trical shock.
4. Use the manual transfer handle inside the trans­fer switch to move the main contacts to their STANDBY position, i.e., loads connected to the standby power source (Figure 3.3).
5. To crank and start the engine, set the AUTO/OFF/ MANUAL switch to MANUAL.
6. Let the engine stabilize and warm up for a few minutes.
7. Set the generator’s main circuit breaker to its ON (or CLOSED) position. The standby power source now powers the loads.
Figure 3.3 – Manual Transfer Switch Operation
3.3.4 UTILITY RESTORED
Initial Condition: Generator supplying power to customer load. When the utility returns (above 75% of nominal), a 15 second return to utility timer will start. At the completion of this timer, if the utility supply is still present and acceptable, the control will transfer the load back to the utility and run the engine through a one (1) minute cool down period and then shut down. If utility fails for three (3) sec­onds during this cool down period, the control will transfer load back to the generator and continue to run while monitoring for utility to return.
3.4 MANUAL TRANSFER OPERATION
3.4.1 TRANSFER TO GENERATOR POWER SOURCE
To start the generator and activate the transfer switch manually, proceed as follows:
1. Set the generator’s AUTO/OFF/MANUAL switch to OFF.
2. Set the generator’s main circuit breaker to its OFF (or OPEN) position.
3. Turn OFF the utility power supply to the transfer switch using the means provided (such as a utility main line circuit breaker).
3.4.2 TRANSFER BACK TO UTILITY POWER SOURCE
When utility power has been restored, transfer back to that source and shut down the generator. This can be accomplished as follows:
1. Set the generator’s main circuit breaker to its OFF (or OPEN) position.
2. Let the engine run for a minute or two at no-load to stabilize the internal temperatures.
3. Set the generator’s AUTO/OFF/MANUAL switch to its OFF (or OPEN) position. The engine should shut down.
4. Check that utility power supply to the transfer switch is turned OFF.
19
DANGER
Section 3 — Operation
Air-cooled Generators
Do not attempt to activate the transfer switch
manually until all power voltage supplies to the switch have been positively turned off. Failure to turn off all power voltage supplies may result in extremely hazardous and possibly fatal elec­trical shock.
5. Use the manual transfer handle inside the trans­fer switch to move the main contacts back to their UTILITY position, i.e., loads connected to the util­ity power source (Figure 3.2).
6. Turn ON the utility power supply to the transfer switch using the means provided.
7. Set the system to automatic operation as outlined in Automatic Transfer Operation section.
Figure 3.4 – Side Compartment
3.5 SIDE COMPARTMENT (V-TWIN
ONLY)
Local codes may require this compartment to be locked. A hasp is provided so the owner can secure the compartment with their own padlock. Check local codes in the area.
3.5.1 MAIN CIRCUIT BREAKER
This is a 2-pole breaker rated according to the Specifications section.
3.5.2 EXTERIOR READY LIGHTS
Green LED ‘Ready’ light (10, 12, 14, 16, 17 & 20
KW) is on when utility is present and switch is in AUTO indicating the generator is ready and when the generator is running.
Red LED ‘Alarm’ light (10, 12, 14, 16, 17 & 20
KW) is on when the generator is OFF or a fault is detected. (See the Protections Systems section.)
Yellow LED ‘Maintenance’ light (17 & 20 KW) (See
the Protections Systems section.)
3.5.3 120 VAC GFCI OUTLET & 15 AMP
These models are equipped with an external, 15 amp, 120 volt, GFCI convenience outlet that is located in a compartment on the right side of generator (Figure
1.3).
When the generator is running, in the absence of util­ity power, this outlet may also be used to power items outside your home such as lights or power tools. This outlet may also be used when utility power is pres­ent by running the generator in manual mode. This outlet does not provide power if the generator is not running. This outlet is protected by a 15 amp circuit breaker in the same compartment as the outlet. (Do not use when the generator is running in exercise mode.)
20
(FIGURES 3.4 & 3.5)
BREAKER (17 & 20 KW ONLY)
Figure 3.5 – Open Side Compartment
120V GFCI Outlet 15 Amp Outlet Breaker
Main Circuit BreakerLED Indicator Lights
3.6 PROTECTION SYSTEMS
3.6.1 ALARMS
Highest Priority (Latching) Displayed on the con­trol panel and the external red LED (V-twins only). They must be cleared before the alarm message goes away. The alarm log records each occurrence (see Appendix - "Menu System").
Low Oil Pressure (Shutdown Alarm)
A five (5) second delay on start-up and seven (7) sec­ond delay once the engine is running.
This switch (Figure 3.6) has normally closed con­tacts that are held open by engine oil pressure dur­ing operation. Should the oil pressure drop below the five (5) PSI range, switch contacts close and the engine shuts down. The unit should not be restarted until oil level is verified.
Section 3 — Operation
Air-cooled Generators
 High Engine Temperature (Shutdown Alarm – Auto Reset)
A 10 second delay on start-up and one (1) second delay before shutdown. Auto reset when the condition clears and restart the engine if a valid start signal is still present.
This switch’s contacts (Figure 3.6) close if the tem­perature should exceed approximately 144° C (293° F), initiating an engine shutdown. Once the oil tem­perature drops to a safe level the switch’s contacts open again.
Over Crank (Shutdown Alarm)
This occurs if the engine has not started within the specified crank cycle. (See "Cranking" section.)
Figure 3.6 – Low Oil Pressure and
High Temperature Switches
Low Oil Switch
L
o
o
s
e
Oil Filter
Oil Drain Hose
NOTE:
The oil drain hose may be routed in the opposite direction as shown in figure.
High Temp Switch
n
Over Speed (Shutdown Alarm)
4320 RPM for three (3) seconds or 4500 RPM imme­diately. This feature protects the generator from dam­age by shutting it down if it happens to run faster than the preset limit. This protection also prevents the generator from supplying an output that could potentially damage appliances connected to the generator circuit. Contact the nearest Dealer if this failure occurs.
RPM Sense Loss (Shutdown Alarm)
During cranking, if the Control Board does not see a valid RPM signal within three (3) seconds, it will shut down and lock out on RPM sense loss. While engine is running, if RPM signal is lost for one (1) second the Control Board will shut the engine down, wait 15 seconds, then re-crank the engine. If no RPM signal is detected within the first three (3) seconds of cranking, the Control Board will shut the engine down and latch out on RPM sensor loss. If the RPM signal is detected, the engine will start and run nor­mally. If the RPM signal is subsequently lost again, the Control Board will try one more re-crank attempt before latching out and displaying the RPM sensor failure message.
Under-frequency (Shutdown Alarm)
After starting, if the generator stays under frequency for more than 30 seconds it will shut down. The under-frequency setting is 50 Hz.
Internal Fault (Shutdown Alarm)
This alarm cannot be cleared, call service dealer.
CLEAR ALARM
8kW — Clear the alarm by setting the AUTO/OFF/
MANUAL switch to the OFF position and back to AUTO.
10 - 20kW — Clear the alarm by setting the AUTO/
OFF/MANUAL switch to the OFF position. Press the ENTER key to unlatch any active fault and clear the corresponding alarm message.
3.6.2 WARNINGS
Second Priority (Non-latching) Displayed on the control panel and the external yellow LED (V-twins only). Warnings automatically clear when the moni­tored condition goes away. Warnings are recorded in the alarm log. Warnings cannot cause shutdowns.
Low Battery
The Control Board monitors battery voltage and dis­plays a warning if the battery voltage falls below 11.0 volts for one (1) minute. Warning is automatically cleared if the battery voltage rises above 11.0 volts. Battery voltage is not monitored during the crank cycle.
Exercise Set Error
If the exercise period becomes corrupted, a warning message will be displayed. This message will only clear when the exercise period is reset.
21
Oil Dipstick
Oil Fill
Section 4 — Maintenance
Air-cooled Generators
3.6.3 MAINTENANCE ALERTS (10 - 20KW
ONLY)
Third priority
Maintenance Message
When a maintenance period expires, a warning mes­sage will be displayed. (16 through 20kW models include an external yellow LED which will illuminate.) The alert can be reset by pressing the Enter key, which will cause the user to be prompted to confirm the action. Resetting will clear the alert and reset the maintenance counters for all conditions annunciated. The history log will record the alert. The maintenance counter will not accumulate without battery power. Once battery power is restored, the set time prompt will be displayed. The maintenance counters will be adjusted to the new time and date.
NOTE:
Since most maintenance alerts will occur at the same time (most have two (2) year intervals), only one will appear on the display at any one time. Once the first alert is cleared, the next active alert will be displayed.
4. Install the dipstick.
5. Reset the AUTO/OFF/MANUAL switch to its origi­nal position.
Figure 4.1 — Oil Dipstick and Fill, 8kW
Oil Dipstick and Fill
Figure 4.2 — Oil Dipstick, 10kW
4.1 FUSE
The 7.5 amp fuse on the control panel protects the DC control circuit against overload (Figures 3.1 and
3.2). This fuse is wired in series with the battery out­put lead to the panel. If this fuse element has melted open, the engine will not be able to crank or start. Replace this fuse using only an identical 7.5 amp replacement fuse. Whenever the fuse is removed or replaced, the exercise timer needs to be reset.
4.2 CHECKING THE ENGINE OIL LEVEL
For oil capacities, see the Specifications section. For engine oil recommendations, see the Engine Oil Recommendations section. To check the engine oil level, proceed as follows (Figures 4.1, 4.2 and 4.3):
1. Move the AUTO/OFF/MANUAL switch to the OFF
position.
2. Remove the dipstick and wipe it dry with a clean
cloth.
3. Completely insert the dipstick; then, remove it
again. The oil level should be at the dipstick “Full” mark. If necessary, add oil to the “Full” mark only. DO NOT FILL ABOVE THE “FULL” MARK.
Figure 4.3 — Oil Dipstick and Fill,
12, 14, 16, 17 & 20kW
Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing this could damage the engine.
22
SA E 30
Sy nt he ti c 5W -3 0
10 W- 30
Section 4 — Maintenance
Air-cooled Generators
4.3 CHANGING THE ENGINE OIL
4.3.1 OIL CHANGE INTERVALS
See the "Service Schedule" section.
4.3.2 ENGINE OIL RECOMMENDATIONS
All oil should meet minimum American Petroleum Institute (API) Service Class SJ, SL or better. Use no special additives. Select the oil's viscosity grade according to the expected operating temperature.
SAE 30 Î Above 32° F 10W-30 Î Between 40° F and -10° F Synthetic 5W-30 Î 10° F and below
Any attempt to crank or start the engine before
it has been properly serviced with the recom­mended oil may result in an engine failure.
SAE 30
10W-30
Synthetic 5W-30
4. Refill with the proper recommended oil (see the Engine Oil Recommendations section). See the Specifications section for oil capacities.
5. Start the engine, run for one (1) minute, and check for leaks.
6. Shutdown and recheck oil level, add as needed. DO NOT OVER FILL.
7. Reset the AUTO/OFF/MANUAL switch to the AUTO position.
Figure 4.4 – Oil Drain Hose and Filter
Oil Filter
Oil Drain Hose
Low Oil Switch
L
o
o
s
e
n
High Temp Switch
4.3.3 OIL & OIL FILTER CHANGE PROCEDURE
To change the oil, proceed as follows:
1. Start the engine by moving the AUTO/OFF/ MANUAL switch to MANUAL and run until it is thoroughly warmed up. Then shut OFF the engine by moving the switch to the OFF position.
2. Immediately after the engine shuts OFF, pull the oil drain hose (Figure 4.4) free of its retaining clip. Remove the cap from the hose and drain the oil into a suitable container.
3. After the oil has drained, replace the cap onto the end of the oil drain hose. Retain the hose in the clip.
Change the engine oil filter as follows:
1. With the oil drained, remove the old oil filter by turning it counterclockwise.
2. Apply a light coating of clean engine oil to the gas­ket of the new filter. See the Specifications section for recommended filter.
3. Screw the new filter on by hand until its gasket lightly contacts the oil filter adapter. Then, tighten the filter an additional 3/4 to one turn (Figure
4.4).
NOTE:
The oil drain hose may be routed in the opposite direction as shown in figure.
4.4 CHANGING THE ENGINE AIR CLEANER
4.4.1 12, 14, 16, 17 & 20KW GENERATORS
See "The Generator" section for the location of the air cleaner. Use the following procedures (Figure 4.5):
1. Lift the roof and remove the door.
2. Turn the two screws counterclockwise to loosen.
3. Remove the cover and air filter.
4. Wipe away dust or debris from inside of the air
box and around edges.
5. Install the new air cleaner into the air box.
6. Install the cover. Turn the two cover screws clock-
wise to tighten.
See the Service Schedule section for air cleaner main­tenance. See the Specifications section for air filter replacement part number.
23
Section 4 — Maintenance
Air-cooled Generators
Figure 4.5 — 12, 14, 16, 17 & 20kW
Engine Air Cleaner
Screw
Cover
Filter
4.4.2 10KW GENERATORS
See "The Generator" section for the location of the air cleaner. Use the following procedure (Figure 4.6):
1. Lift the roof and remove the door.
2. Turn the worm gear clamp screw counterclock­wise to loosen.
3. Pull the old filter off the divider panel hub.
4. Wipe away dust or debris from the panel hub.
5. Install the new air cleaner onto the hub.
6. Turn the worm gear clamp screw clockwise to tighten.
7. Replace door and roof.
4.4.3 8KW GENERATOR
See "The Generator" section to locate the air box. Use the following procedures to replace the dirty air filter within the air box (Figure 4.7).
1. Lift the roof and remove the door.
2. Push back on the latch of the yellow air filter access door to swing open.
3. Pull out the old air filter and discard appropri­ately.
4. Install the new filter, open end first into the air box.
5. Swing the yellow door shut and snap to close.
6. Replace door and close roof securely.
Figure 4.7 — 8kW Engine Air Cleaner Location
Air Cleaner Cover
Figure 4.6 — 10kW Engine Air Cleaner
Air Filter
24
4.5 SPARK PLUG(S)
Reset the spark plug(s) gap or replace the spark plug(s) as necessary. See the Service Schedule section for maintenance requirements.
1. Clean the area around the base of the spark plug(s) to keep dirt and debris out of the engine.
2. Remove the spark plug(s) and check the condi­tion. Replace the spark plug(s) if worn or if reuse is questionable. See the Service Schedule section for recommended inspection. Clean by scraping or washing using a wire brush and commercial solvent. Do not blast the spark plug(s) to clean.
3. Check the spark plug gap using a wire feeler gauge. Adjust the gap to 0.76 mm (0.030 inch) for 8, 10 and 20kW; and 1.02 mm (0.040 inch) for 12, 14, 16 and 17kW by carefully bending the ground electrode (Figure 4.8).
DANGER
Section 4 — Maintenance
Air-cooled Generators
Figure 4.8 – Setting the Spark Plug Gap
SET PLUG GAP AT 0.76 mm (.030 inch) - 8, 10 &
20kW; 1.02 mm (.040 inch) - 12, 14, 16 & 17kW
4.6 BATTERY MAINTENANCE
The battery should be inspected per the "Service Schedule" section. The following procedure should be followed for inspection:
1. Inspect the battery posts and cables for tightness and corrosion. Tighten and clean as necessary.
2. Check the battery fluid level of unsealed batteries and, if necessary, fill with Distilled Water Only. Do not use tap water in batteries.
3. Have the state of charge and condition checked. This should be done with an automotive-type bat­tery hydrometer.
Do not dispose of the battery in a fire. The
battery is capable of exploding.
A battery presents a risk of electrical shock
and high short circuit current. The following pre­cautions are to be observed when working on batteries:
• Remove the 7.5A fuse from the generator control
panel.
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the
battery; and
• Disconnect charging source prior to connecting or
disconnecting battery terminals.
Do not open or mutilate the battery. Released
electrolyte has been known to be harmful to the skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically conductive and corrosive. The following procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off immediately with water;
• Where electrolyte contacts the eyes, flush thor­oughly and immediately with water and seek medical attention; and
• Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of 1 pound (500 grams) bicarbonate of soda to 1 gallon (4 liters) of water. The bicar­bonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.
Lead-acid batteries present a risk of fire because
they generate hydrogen gas. The following procedures are to be followed:
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from body before touch­ing the battery by first touching a grounded metal surface.
Be sure the AUTO/OFF/MANUAL switch is set to
the OFF position before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.
Be sure the utility power supply is turned off
and the 7.5A fuse is removed from the genera­tor control panel, or sparking may occur at the battery posts as the cables are attached and cause an explosion.
4.7 ADJUSTING GH-410/GT-530/
990/999 VALVE CLEARANCE
After the first six (6) months of operation, check the valve clearance in the engine, adjust if neces­sary.
Important: If feeling uncomfortable about doing
this procedure or the proper tools are not available, please contact the Dealer for service assistance. This is a very important step to ensure longest life for the engine.
To check valve clearance:
The engine should be cool before checking. If
valve clearance is 0.002" - 0.004" (0.05 - 0.1mm), adjustment is not needed.
Remove spark plug wires and position wires away
from plugs.
Remove spark plugs.
25
Section 4 — Maintenance
Air-cooled Generators
Make sure the piston is at Top Dead Center (TDC)
of its compression stroke (both valves closed). To get the piston at TDC, remove the intake screen at the front of the engine to gain access to the flywheel nut. Use a large socket and socket wrench to rotate the nut and hence the engine in a clockwise direc­tion. While watching the piston through the spark plug hole. The piston should move up and down. The piston is at TDC when it is at its highest point of travel.
To adjust valve clearance (if necessary), (Figure
4.9):
Make sure the engine is at 60° to 80° F.• Make sure that the spark plug wire is removed
from the spark plug and out of the way. Remove the four screws attaching the valve cover.• Loosen the rocker jam nut. Use an 10mm allen
wrench to turn the pivot ball stud while checking
clearance between the rocker arm and the valve
stem with a feeler gauge. Correct clearance is
0.002-0.004 inch (0.05-0.1 mm).
Figure 4.9 - Valve Clearance Adjustment
Rocker
Jam Nut
Pivot Ball
Stud
Arm
Valve Stem
Install spark plugs.• Re-attach the spark plug wire to the spark plug.• On the GT-530 and GT-990/999, repeat the process
for the other cylinder.
4.8 COOLING SYSTEM
Air inlet and outlet openings in the generator com­partment must be open and unobstructed for con­tinued proper operation. This includes such obstruc­tions as high grass, weeds, brush, leaves and snow.
Without sufficient cooling and ventilating air flow, the engine/generator quickly overheats, which causes it to quickly shut down. (See Figure 4.10 for vent loca­tions.)
Make sure the doors and roof are in place dur­ing operation as running the generator with them removed can effect cooling air movement.
Figure 4.10 – Cooling Vent Locations
NOTE:
Hold the rocker arm jam nut in place as the pivot ball stud is turned.
When valve clearance is correct, hold the pivot ball stud in place with the allen wrench and tighten the rocker arm jam nut. Tighten the jam nut to 174 in/ lbs. torque. After tightening the jam nut, recheck valve clearance to make sure it did not change.
Install new valve cover gasket.• Re-attach the valve cover.
NOTE:
Start all four screws before tightening or it will not be possible to get all the screws in place. Make sure the valve cover gasket is in place.
26
The exhaust from this product gets extremely
hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.
The maximum ambient temperature for the gen-
erator is 25° C (77° F).
4.9 ATTENTION AFTER SUBMERSION
If the generator has been submerged in water, it must not be started and operated. Following any submer-
sion in water, have a Dealer thoroughly clean, dry and inspect the generator. If the structure (ex. home) has been flooded, it should be inspected by a certi­fied electrician to ensure there won't be any electrical problems during generator operation or when utility is returned.
Section 4 — Maintenance
Air-cooled Generators
4.10 CORROSION PROTECTION
Periodically wash and wax the enclosure using auto­motive type products. Frequent washing is recom­mended in salt water/coastal areas. Spray engine linkages with a light oil such as WD-40.
4.11 OUT OF SERVICE PROCEDURE
4.11.1 REMOVAL FROM SERVICE
If the generator cannot be exercised every seven days, and will be out of service longer than 90 days, pre­pare the generator for storage as follows:
1. Start the engine and let it warm up.
2. Close the fuel shutoff valve in the fuel supply line and allow the unit to shut down.
3. Once the unit has shut down, switch to the OFF position.
4. Set the generator’s main circuit breaker to its OFF (or OPEN) position.
5. Set the AUTO/OFF/MANUAL switch to OFF and turn off the utility power to the transfer switch. Remove the 7.5A fuse from the generator control panel. Disconnect the battery cables as outlined in “General Hazards”.
6. While the engine is still warm from running, drain the oil completely. Refill the crankcase with oil. See ”Engine Oil Recommendations".
7. Attach a tag to the engine indicating the viscosity and classification of the oil in the crankcase.
8. Remove the spark plug(s) and spray fogging agent into the spark plug(s) threaded openings. Reinstall and tighten the spark plug(s).
9. Remove the battery and store it in a cool, dry room on a wooden board. Never store the battery on any concrete or earthen floor.
10. Clean and wipe the entire generator.
4.11.2 RETURN TO SERVICE
To return the unit to service after storage, proceed as follows:
1. Verify that utility power is turned off and that the AUTO/OFF/MANUAL switch is set to OFF.
2. Check the tag on the engine for oil viscosity and classification. Verify that the correct recommend­ed oil is used in the engine (see the Engine Oil Recommendations section). If necessary, drain and refill with the proper oil.
3. Check the state of the battery. Fill all cells of unsealed batteries to the proper level with dis­tilled water. DO NOT USE TAP WATER IN THE BATTERY. Recharge the battery to 100 percent state of charge, or, if defective, replace the battery. See “Specifications,” for type and size.
4. Clean and wipe the entire generator.
5. Make sure the 7.5A fuse is removed from the generator control panel. Reconnect the battery. Observe battery polarity. Damage may occur if the battery is connected incorrectly.
6. Open the fuel shutoff valve.
7. Insert the 7.5A fuse into the generator control panel. Start the unit by moving the AUTO/OFF/ MANUAL switch to MANUAL. Allow the unit to warm up thoroughly.
8. Stop the unit by setting the AUTO/OFF/MANUAL switch to OFF.
9. Turn on the utility power to the transfer switch.
10. Set the AUTO/OFF/MANUAL switch to AUTO.
11. The generator is now ready for service.
NOTE:
If the battery was dead or disconnected, the exer­cise timer (single cylinder), current date and time (v-twin) must be reset.
4.11.3 ACCESSORIES
There are performance enhancing accessories avail­able for the air-cooled generators.
Cold Weather Kits are recommended in areas
where temperatures regularly fall below 10° F (-12° C).
Scheduled Maintenance Kits include all pieces
necessary to perform maintenance on the genera­tor along with oil recommendations.
Auxiliary Transfer Switch Lockout enables any
of the transfer switches to completely lock out one large electrical load by tying into its control system.
A Fascia Skirt Wrap is standard on all 20kW
units. It's available for all other current produc­tion air-cooled units. It snaps together to provide a smoothing, contoured look as well as rodent/insect protection.
The PowerMaster load prioritization device allows
home owners to potentially operator two (2) large electrical loads by giving one (1) priority over the other.
The Remote Monitor System is a wireless, indoor
mounted, box that indicates generator run status and allows for exercise programing as well as pro­vide maintenance reminders.
Touch-up Paint Kits are very important to main-
tain the look and integrity of the generator enclo­sure. These kits include touch-up paint and instructions if the need should arise.
For more details on accessories, please contact a Dealer.
27
Section 4 — Maintenance
Air-cooled Generators
4.12 SERVICE SCHEDULE
ATTENTION: It is recommended that all service work
be performed by the nearest Dealer.
SYSTEM/COMPONENT PROCEDURE FREQUENCY
X = Action R = Replace as Necessary
Inspect Change Clean
* = Notify Dealer if Repair is
Needed.
FUEL
Fuel lines and connections*
XM
LUBRICATION
Oil level
Oil
Oil filter
X M or 24 hours of
X 2Y or 200 hours
X 2Y or 200 hours
COOLING
Enclosure louvers
XXW
BATTERY
Remove corrosion, ensure dryness
Clean and tighten battery terminals
Check charge state Electrolyte level
XXM
XXM
X R EVERY 6 M X R EVERY 6 M
ENGINE AND MOUNTING
Air cleaner Spark plug(s)
X R 2Y or 200 hours X R 2Y or 200 hours
GENERAL CONDITION
Vibration, Noise, Leakage, Temperature*
COMPLETE TUNE-UP*
* Contact the nearest dealer for assistance if necessary. ** Change oil and fi lter after fi rst eight (8) hours of operation and then every 200 hours thereafter, or 2 years, which-
ever occurs fi rst. Change sooner when operating under a heavy load or in a dusty or dirty environment or in high ambient temperatures.
XM
TO BE COMPLETED BY A DEALER 2Y or 200 hours
W = Weekly
M = Monthly
Y = Yearly
continuous operation.
of operation.**
of operation.**
28
Section 5 — Troubleshooting
Air-cooled Generators
5.1 TROUBLESHOOTING GUIDE
Problem Cause Correction
The engine will not crank. 1. Fuse blown. 1. Correct short circuit condition,
replace 7.5A fuse in generator control panel.
2. Loose, corroded or defective 2. Tighten, clean or replace battery cables. as necessary.
3. Defective starter contactor. (8 kW) 3. *
4. Defective starter motor. 4. *
5. Dead Battery. 5. Charge or replace battery.
The engine cranks but 1. Out of fuel. 1. Replenish fuel/Turn on fuel valve. will not start. 2. Defective fuel solenoid (FS). 2. *
3. Open #14 wire from 3. * engine control board.
4. Fouled spark plug(s). 4. Clean, re-gap or replace plug(s).
5. Valve lash out of adjustment. 5. Reset valve lash.
6. Choke not operating. 6. Verify choke plate moves freely.
The engine starts hard 1. Air cleaner plugged 1. Check, replace air cleaner. and runs rough. or damaged.
2. Fouled spark plug(s). 2. Clean, re-gap or replace plug(s).
3. Fuel pressure incorrect. 3. Confirm fuel pressure to regulator
is 10-12” water column (0.36-0.43 psi) for LP, and 5-7” water column (0.18-0.25 psi) for natural gas.
4. Fuel selector in wrong position. 4. Move selector to correct position.
5. Choke remains closed. 5. Verify choke plate moves freely.
The AUTO/OFF/MANUAL 1. Defective switch. 1. * switch is set to OFF, but 2. AUTO/OFF/MANUAL switch 2. *
the engine continues wired incorrectly. to run. 3. Defective control board. 3. *
There is no AC output 1. Main line circuit breaker is in 1. Reset circuit breaker from the generator. the OFF (or OPEN) position. to ON (or CLOSED).
2. Generator internal failure. 2. *
There is no transfer to 1. Defective transfer switch coil. 1. * standby after utility 2. Defective transfer relay. 2. * source failure. 3. Transfer relay circuit open. 3. *
4. Defective control logic board. 4. *
Unit consumes large 1. Engine over filled with oil. 1. Adjust oil to proper level. amounts of oil. 2. Improper type or viscosity of oil. 2. See "Engine Oil Recommendations".
3. Damaged gasket, seal or hose. 3. Check for oil leaks.
4. Engine breather defective. 4. *
*Contact the nearest Dealer for assistance.
29
Section 6 — Appendix
Air-cooled Generators
6.1 MENU SYSTEM NAVIGATION
To get to the MENU, use the "Esc" key from any page. It may need to be pressed many times before getting to the menu page. The currently selected menu is displayed as a flashing word. Navigate to the menu required by using the +/- keys. When the menu required is flashing, press the ENTER key. Depending on the menu selected, there may be a list of choices presented. Use the same navigation method to select the the desired screen (refer to the Menu System diagram).
6.1.1 CHANGING SETTINGS (EDIT MENU)
To change a setting such as display contrast, go to the EDIT menu and use the +/- keys to navigate to the setting to change. Once this setting is displayed (e.g. Contrast), press the ENTER key to go into the edit mode. Use the +/- keys to change the setting, press the ENTER key to store the new setting.
NOTE:
If the ENTER key is not pressed to save the new setting, it will only be saved temporarily. The next time the battery is disconnected, the setting will revert back to the old setting.
30
Section 6 — Appendix
Air-cooled Generators
DEBUG
RESET
MAINTENANCE
INPUTS OUTPUTS DISPLAYS
ESC ESC
EDIT
ESC
MAIN MENU
ESC
MENU SYSTEM
17 &
STARTUP
only
20kW
DELAY
VERSIONSDISPLAY
COMMAND
CONTRAST
ESC
English
or Other
LANGUAGE
ENGINE
HOURS
17 &
20kW
ENGINE
60 Hz
FREQUENCY
only
RPM
17 &
TIME/DATE
20kW
GENERATOR
only
FREQUENCY
TIME
EXERCISE
on Line 2 of the display
are as follows:
• Switched Off
The possible commands
only
17 &
20kW
BATTERY
VO LTAGE
• Running Manually
• Stopped in Auto Mode
• Running - Utility Lost
• Running in Exercise
• Running from Radio
HISTORY STATUS
ESC
STAT E
RUN LOGALARM LOG
Press the “ESCAPE” key
to jump back up through
ESC
the menu levels.
Use the “+/-” key
to navigate through
the menu.
Use the “ENTER” key
to select items or
enter data.
The possible Status messages of the display
are as follows:
• Switched Off/Time & Date
• Ready to Run/Time & Date
• Utility Loss Delay/Pausing for X Seconds
• Cranking/Attempt # X
• Running in Exercise/Time & Date
• Running/Cooling Down
• Running - Warning/Warning Message
• Running - Alarm/Alarm Message
• Stopped - Alarm/Alarm Message
• Stopped - Warning/Warning Message
• Cranking/Pausing for X Seconds
• Running/Time & Date
• Running/Warming Up
• Cranking - Warning/Warning Message
• Cranking - Alarm/Alarm Message
+ / -
ENTER
31
31
Section 7 — Notes
Air-cooled Generators
32 32
Section 8 — Installation Diagrams
Air-cooled Generators
Circuit Breakers - Drawing No. 0G8573-A
33
Section 8 — Installation Diagrams
Air-cooled Generators Generator - Drawing No. 0G8280-D
34
Section 8 — Installation Diagrams
Air-cooled Generators
Generator - Drawing No. 0G8280-D
35
Section 9 – Warranty
Air-cooled Generators
NOTE: This Emission Control Warranty Statement pertains to this product only IF the generator size is 15 kW or below.
CALIFORNIA EMISSION CONTROL WARRANTY STATEMENT
YOUR WARRANTY RIGHTS AND OBLIGATIONS
The California Air Resources Board (CARB) and Generac Power Systems, Inc. (Generac) are pleased to explain the Emission Control System Warranty on your new engine.* In California, new utility, and lawn and garden equipment engines must be designed, built and equipped to meet the state’s stringent anti-smog standards. Generac will warrant the emission control system on your engine for the periods of time listed below provided there has been no abuse, neglect, unapproved modifica­tion or improper maintenance of your engine.
Your emission control system may include parts such as the carburetor, ignition system and exhaust system. Generac will repair your engine at no cost to you for diagnosis, replacement parts and labor, should a warrantable condition occur.
MANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE:
Emissions control systems on 1995 and later model year engines are warranted for two years as hereinafter noted. If, dur­ing such warranty period, any emission-related component or system on your engine is found to be defective in materials or workmanship, repairs or replacement will be performed by a Generac Authorized Warranty Service Facility.
PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES:
As the engine purchaser/owner, you are responsible for the completion of all required maintenance as listed in your factory supplied Owner’s Manual. For warranty purposes, Generac recommends that you retain all receipts covering maintenance on your engine. However, Generac cannot deny warranty solely due to the lack of receipts or for your failure to ensure the completion of all scheduled maintenance.
As the engine purchaser/owner, you should, however, be aware that Generac may deny any and/or all warranty coverage or responsibility if your engine, or a part/component thereof, has failed due to abuse, neglect , improper maintenance or unap­proved modifications, or the use of counterfeit and/or “grey market” parts not made, supplied or approved by Generac.
You are responsible for contacting a Generac Authorized Warranty Service Facility as soon as a problem occurs. The warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days.
Warranty service can be arranged by contacting either your selling dealer or a Generac Authorized Warranty Service Facility. To locate the Generac Authorized Warranty Service Facility nearest you, call our toll-free number:
1-800-333-1322
IMPORTANT NOTE: This warranty statement explains your rights and obligations under the Emission Control System Warranty (ECS Warranty), which is provided to you by Generac pursuant to California law. See also the “Generac Limited Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where the Generac Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac Warranty describe important rights and obligations with respect to your new engine.
Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty ser­vice, evidence must be presented showing the date of the sale to the original purchaser/owner.
If you have any questions regarding your warranty rights and responsibilities, you should contact Generac at one of the following addresses:
For Air-cooled Product ... For Liquid-cooled Product ...
ATTENTION WARRANTY DEPARTMENT ATTENTION WARRANTY DEPARTMENT GENERAC POWER SYSTEMS, INC. GENERAC POWER SYSTEMS, INC. P.O. BOX 297 211 MURPHY DRIVE WHITEWATER, WI 53190 EAGLE, WI 53119
Part 1
36
Section 9 – Warranty
Air-cooled Generators
EMISSION CONTROL SYSTEM WARRANTY
Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines:
(a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on the
date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall continue for 24 consecutive months thereafter.
(b) General Emissions Warranty Coverage: Generac warrants to the original, end-use purchaser/owner of the new engine or
equipment and to each subsequent purchaser/owner that each of its engines is ...
(1) Designed, built and equipped so as to conform with all applicable regulations adopted by the CARB pursuant to its
authority, and
(2) Free from defects in materials and workmanship which, at any time during the ECS Warranty Period, may cause a
warranted emissions-related part to fail to be identical in all material respects to the part as described in the engine manufacturer’s application for certification.
(c) The ECS Warranty only pertains to emissions-related parts on your engine, as follows:
(1) Any warranted, emissions-related parts that are not scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the ECS Warranty Period. If any such part fails during the ECS Warranty Period, it shall be repaired or replaced by Generac according to Subsection (4) below. Any such part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.
(2) Any warranted, emissions-related part that is scheduled only for regular inspection as specified in the Owner’s Manual
shall be warranted for the ECS Warranty Period. A statement in such written instructions to the effect of “repair or replace as necessary” shall not reduce the ECS Warranty Period. Any such part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.
(3) Any warranted, emissions-related part that is scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the period of time prior to the first scheduled replacement point for that part. If the part fails prior to the first scheduled replacement, the part shall be repaired or replaced by Generac according to Subsection (4) below. Any such emissions-related part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions-related part.
(4) Repair or replacement of any warranted, emissions-related part under this ECS Warranty shall be performed at no
charge to the owner at a Generac Authorized Warranty Service Facility.
(5) When the engine is inspected by a Generac Authorized Warranty Service Facility, the owner shall not be held responsible
for diagnostic costs if the repair is deemed warrantable.
(6) Generac shall be liable for damages to other original engine components or approved modifications proximately caused
by a failure under warranty of any emission-related part covered by the ECS Warranty.
(7) Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted emission-related parts sufficient
to meet the expected demand for such emission-related parts.
(8) Any Generac authorized and approved emission-related replacement part may be used in the performance of any ECS
Warranty maintenance or repairs and will be provided without charge to the owner. Such use shall not reduce Generac ECS Warranty obligations.
(9) Unapproved, add-on, modified, counterfeit and/or “grey market” parts may not be used to modify or repair a Generac
engine. Such use voids this ECS Warranty and shall be sufficient grounds for disallowing an ECS Warranty claim. Generac shall not be held liable hereunder for failures of any warranted parts of a Generac engine caused by the use of such an unapproved, add-on, modified, counterfeit and/or “grey market” part.
EMISSION RELATED PARTS INCLUDE THE FOLLOWING:
1) Fuel Metering System:
1.2) LPG/Natural Gas carburetion assembly and its internal com­ponents.
a) Fuel controller (if so equipped) b) Mixer and its gaskets (if so equipped) c) Carburetor and its gaskets (if so equipped) d) Primary gas regulator (if so equipped) e) LP liquid vaporizer (if so equipped)
2) Air Induction System including:
a) Intake pipe/manifold b) Air cleaner
* Generac engine types covered by this warranty statement include the following:
1) Prepackaged Standby Generator
2) Auxiliary Power Unit (APU) Generator
3) Standby Generator
Part 2
3) Ignition System including: a) Spark plug b) Ignition module
4) Catalytic Muffler Assembly (if so equipped) including: a) Muffler gasket b) Exhaust manifold
5) Crankcase Breather Assembly including: a) Breather connection tube
37
Part No. 0G8334 Revision D (09/16/08) Printed in U.S.A.
Catalog No. OMASPCA-S-01
RTSS Load Shed Automatic Transfer Switch
TECHNICAL MANUAL
This manual should remain with the unit.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be
followed during installation and maintenance of the generator and batteries.
SAVE THESE INSTRUCTIONS! Read the following information carefully before attempting to
install, operate or service this equipment. Also read the instructions and information on tags,
decals, and labels that may be affixed to the transfer switch. Replace any decal or label that is no longer legible.
DANGER! Connection of a generator to an electrical system normally supplied by an electric
utility shall be by means of suitable transfer equipment so as to isolate the electric system
from utility distribution system when the generator is operating (Article 701 Legally Required Standby Systems or Article 702 Optional Standby Systems, as applicable). Failure to isolate electric system by these means may result in damage to generator and may result in injury or death to utility workers due to backfeed of electrical energy.
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warn­ings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive. If using a procedure, work method or operating technique the manufacturer does not specifically recommend, ensure that it is safe for others. Also make sure the procedure, work method or operating technique cho­sen does not render the transfer switch unsafe.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert person­nel to special instructions about a particular opera­tion that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their defini­tions are as follows:
DANGER
After this heading, read instructions that, if not
strictly complied with, will result in personal inju­ry, including without limitation, death, or property damage.
After this heading, read instructions that, if not
strictly complied with, may result in personal inju­ry or property damage.
After this heading, read instructions that, if not
strictly complied with, could result in damage to equipment and/or property.
NOTE:
After this heading, read explanatory statements
that require special emphasis.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compli­ance with the special instructions while performing the service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates follows:
This symbol points out important safety infor-
mation that, if not followed, could endanger personal safety and/or property.
This symbol points out potential explosion
hazard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock
hazard.
GENERAL HAZARDS
Any AC generator that is used for backup power if
a NORMAL (UTILITY) power source failure occurs, must be isolated from the NORMAL (UTILITY) power source by means of an approved transfer switch. Failure to properly isolate the NORMAL and STANDBY power sources from each other may result in injury or death to electric utility workers, due to backfeed of electrical energy.
Improper or unauthorized installation, operation,
service or repair of the equipment is extremely dangerous and may result in death, serious per­sonal injury, or damage to equipment and/or per­sonal property.
Extremely high and dangerous power voltages are
present inside an installed transfer switch. Any contact with high voltage terminals, contacts or wires will result in extremely hazardous, and pos­sibly LETHAL, electric shock. DO NOT WORK ON THE TRANSFER SWITCH UNTIL ALL POWER VOLTAGE SUPPLIES TO THE SWITCH HAVE BEEN POSITIVELY TURNED OFF.
Table of Contents
Competent, qualified personnel should install,
operate and service this equipment. Adhere strictly to local, state and national electrical and building codes. When using this equipment, comply with regulations the National Electrical Code (NEC), CSA Standard; C22.1 Canadian Electric Code and Occupational Safety and Health Administration (OSHA) have established.
Never handle any kind of electrical device while
standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
Jewelry conducts electricity and wearing it may
cause dangerous electrical shock. Remove all jew­elry (such as rings, watches, bracelets, etc.) before working on this equipment.
If work must be done on this equipment while
standing on metal or concrete, place insulative mats over a dry wood platform. Work on this equipment only while standing on such insulative mats.
Never work on this equipment while physically or
mentally fatigued.
Keep the transfer switch enclosure door closed
and bolted at all times. Only qualified personnel should be permitted access to the switch interior.
In case of an accident caused by electric shock,
immediately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor but AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconduct­ing implement, such as a dry rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.
When an automatic transfer switch is installed for
a standby generator set, the generator engine may crank and start at any time without warning. To avoid possible injury that might be caused by such sudden start-ups, the system’s automatic start cir­cuit must be disabled before working on or around the generator or transfer switch. For that purpose, a SAFETY DISCONNECT is provided inside the transfer switch. Always set that switch to its OFF position before working on the equipment. Then place a “DO NOT OPERATE” tag on the transfer switch and on the generator. Remove the Negative (Neg) or (–) battery cable.
Safety Rules .........................................Inside Front Cover
Section 1 — General Information ...................................2
1.1 Introduction............................................................. 2
1.2 Equipment Description ........................................... 2
1.2.1 Transfer Switch Mechanism .......................... 2
1.2.2 Utility Service Disconnect Circuit Breaker .... 3
1.2.3 Load Shed Controller .................................... 3
1.2.4 Battery Charger ............................................. 3
1.3 Transfer Switch Data Decal ..................................... 3
1.4 Transfer Switch Enclosure ...................................... 3
1.5 Safe Use Of Transfer Switch .................................... 4
Section 2 — Installation ....................................................4
2.1 Introduction to Installation ...................................... 4
2.2 Unpacking ............................................................... 4
2.3 Mounting ................................................................. 4
2.4 Connecting Power Source and Load Lines ............... 4
2.5 Neutral Connections ................................................ 5
2.6 Connecting Control Wires ........................................ 5
Section 3 — Operation .......................................................5
3.1 Functional Tests & Adjustments .............................. 5
3.2 Manual Operation .................................................... 6
3.2.1 ATS Manual Operation .................................. 6
3.2.2 LSS Manual Operation .................................. 6
3.2.3 Close to Utility Source Side ........................... 7
3.2.4 Close to Generator Source Side .................... 7
3.2.5 Return to Utility Source Side ........................ 7
3.3 Voltage Checks ......................................................... 7
3.4 Generator Tests Under Load ................................... 8
3.4.1 ATS & Critical Loads ..................................... 8
3.4.2 Load Shed Functional Test ............................ 9
Section 4 – Installation Diagrams ................................10
Section 5 – Electrical Data .............................................12
Section 6 – Exploded Views & Parts Lists ..................16
Section 7 – Notes ............................................................ 20
Section 8 – Warranty ...................................... Back Cover
For authorized service, reference
the dealer locator number found
in the generator owner’s manual or
on the generator's data label.
1
Section 1 — General Information
RTSS Type Transfer Switch
1.1 INTRODUCTION
This manual has been prepared especially for the purpose of familiarizing personnel with the design, application, installation, operation and servicing of the applicable equipment. Read the manual carefully and comply with all instructions. This will help to prevent accidents or damage to equipment that might otherwise be caused by carelessness, incorrect appli­cation, or improper procedures.
Every effort has been expended to make sure that the contents of this manual are both accurate and cur­rent. The manufacturer, however, reserves the right to change, alter or otherwise improve the product at any time without prior notice.
1.2 EQUIPMENT DESCRIPTION
The PowerManager™ LTS transfer switch will provide three major functions.
The first function is to provide an automatic transfer switch. The automatic transfer switch is used for transferring electrical loads from a UTILITY (NORMAL) power source to a GENERATOR (STANDBY) power source. Such a transfer of electri­cal loads occurs automatically when (connected to a Generac engine generator) the UTILITY power source has failed or is at a substantially reduced voltage and the GENERATOR source voltage and frequency have reached an acceptable level. The transfer switch pre­vents electrical feedback between two different power sources (such as the UTILITY and GENERATOR sources) and, for that reason, codes require it in all standby electrical system installations.
The second function is to provide a means to divide up the electrical loads on the electrical system. The electrical loads are to be divided into “critical loads” and non-essential loads. The “critical” loads are con­nected to the internal 16 circuit panel board. The non-essential electrical loads are to be powered from the load shed switch (LSS).
The UTILITY source will supply all electrical loads at all times. When the transfer signal is given by the engine generator controller, all loads, both criti­cal and non-essential loads, are connected to the GENERATOR supply. If the generator is overloaded the LSS will operate and disconnect the non-essential loads which results in a reduction in the load on the generator.
The third function is a 16 circuit load center to connect the “critical loads” to. These loads will be normally powered by the UTILITY source and will be backed up by the GENERATOR source. The Siemens load center is provided with the following Siemens type QP circuit breakers; 1-50A 2-pole, 1-40A 2-pole, 1-20A 2-pole, 5-20A single pole and 5-15A 2-pole circuit breakers.
2
The PowerManager LTS transfer switch is suitable for use as SERVICE ENTRANCE EQUIPMENT – UTILITY (NORMAL) source only. The PowerManager LTS is only SERVICE ENTRANCE rated for the USA. The 200A 2-pole circuit breaker provided is the “ser­vice disconnect” and is labeled as such. An additional disconnect must be readily available for the alternate source, unless the alternate source is an accessible generator and can be shutdown.
1.2.1 TRANSFER SWITCH MECHANISM
These switches (Figure 1.1) are used with a single­phase system, when the single-phase NEUTRAL line is to be connected to a Neutral Lug and is not to be switched.
Solderless, screw-type terminal lugs are standard.
Switch Rating
200A #6-250 MCM 275 in-lbs.
This transfer switch is suitable for control of motors, electric discharge lamps, tungsten filament and elec­tric heating equipment where the sum of motor full load ampere ratings and the ampere ratings of other loads do not exceed the ampere rating of the switch and the tungsten load does not exceed 30 percent of the switch rating.
Figure 1.1 — Typical ATS Transfer Mechanism
UTILITY CLOSING COIL
GENERATOR CLOSING COIL
This transfer switch is for use in optional standby systems only (NEC® Article 702).
This transfer switch is suitable for use on a circuit capable of 22,000 rms symmetrical amperes, 240 VAC maximum.
Wire
Range
UTILITY LUGS
LOAD LUGS (T1 & T2)
Conductor Tightening
Torque
GENERATOR LUGS (E1 & E2)
Section 1 — General Information
RTSS Type Transfer Switch
1.2.2 UTILITY SERVICE DISCONNECT CIRCUIT BREAKER
The utility service disconnect circuit breaker for the 200 amp models are:
Generac, Type 225AF, 2-pole• 120/240VAC, 200A• 50/60 Hertz• Wire range: 300 MCM - 6 STR (Line), 250 MCM
- 6 STR (Load)
The conductor tightening torque is 375 in-lbs.
(Line), 275 in-lbs. (Non-essential Load and Generator Terminals)
1.2.3 LOAD SHED CONTROLLER
The primary function of the Load Shed Controller (LSC) is to determine when there is excess load on the generator and has the ability to disconnect the non-essential loads connected to it. Excess load is determined by monitoring the generator supply frequency, if the frequency drops below 58 Hz for more than three (3) seconds, or below 50 Hz for 1/2 second, and the generator is considered to have excess load on it. When this happens, non-essential customer loads are disconnected. The non-essential loads are supplied via the load shed switch (LSS) and the LSS is actuated to disconnect these loads.
The non-essential loads are reconnected in one of 3 ways; Utility voltage is restored and ATS transfers all load back to the Utility supply, manual operation of LOAD SHED RESET push-button on the outside of the enclosure or, automatic operation setup on the DIP switches on the LSC.
For manual operation, set DIP switch #6 to the ON position. If the generator output is overloaded and the non-essential loads are disconnected, press the LOAD SHED RESET push-button to reconnect the non-essential loads to the generator. If the overload condition still exists the LSC will turn the non-essen­tial loads off.
For automatic operation, the number of attempts to reconnect the non-essential loads can be selected. The 2 choices are one-shot or repeated. The time interval before each attempt is set on DIP switches 1-4. For “one-shot” operation mode set DIP switch #5 to ON. Reconnection of the non-essential loads will occur one time, after the time set on DIP switches 1-4. If DIP switch #5 is OFF, the LSC will attempt to reconnect the non-essential loads after the time inter­val set on DIP switches 1-4. If the overload still exists or comes back, the LSC and LSS will disconnect non-essential loads and the timer and the attempt to reconnect non-essential loads will be repeated.
DIP switch
number
1 Selects a 5 minute reconnection
time
2 Selects a 15 minute reconnection
time
3 Selects a 30 minute reconnection
time
4 Selects a 60 minute reconnection
time
1-4 all OFF Selects a 1 minute reconnection
time 5 Selects one-shot mode 6 Selects manual reconnect only 7 Selects 50 Hz units 8 Not used
Function
1.2.4 BATTERY CHARGER
The POWER MANAGER LTS transfer switch is pro­vided with a battery charger (item #44 on Generac #0G8054 assembly drawing) for charging of the engine generator 12 Vdc battery. The battery charger is powered from the load side of the transfer switch (line to neutral – 120V) and is protected by a 2A fuse on the LSC pcb. The battery charger will charge the battery at all times.
1.3 TRANSFER SWITCH DATA DECAL
A DATA DECAL is permanently affixed to the transfer switch enclosure. Use this transfer switch only with the specific limits shown on the DATA DECAL and on other decals and labels that may be affixed to the switch. This will prevent damage to equipment and property.
When requesting information or ordering parts for this equipment, make sure to include all information from the DATA DECAL.
Record the Model and Serial numbers in the space provided below for future reference.
MODEL #
SERIAL #
1.4 TRANSFER SWITCH ENCLOSURE
The standard switch enclosure is a National Electrical Manufacturer’s Association (NEMA) 3R, UL listed. NEMA 3R type enclosures primarily provide a degree of protection against falling rain and sleet and is undamaged by the formation of ice on the enclosure.
3
Section 2 — Installation
RTSS Type Transfer Switch
1.5 SAFE USE OF TRANSFER SWITCH
Before installing, operating or servicing this equip­ment, read the SAFETY RULES (inside front cover) carefully. Comply strictly with all SAFETY RULES to prevent accidents and/or damage to the equipment. The manufacturer recommends that a copy of the SAFETY RULES are posted near the transfer switch. Also, be sure to read all instructions and information found on tags, labels and decals affixed to the equip­ment.
Three publications that outline the safe use of trans­fer switches are the following:
NFPA 70; National Electrical Code• NFPA 70E; Standard for Electrical Safety in the
Workplace
UL 1008, STANDARD FOR SAFETY-AUTOMATIC
TRANSFER SWITCHES
NOTE:
It is essential to use the latest version of any stan­dard to ensure correct and current information.
2.1 INTRODUCTION TO INSTALLATION
This equipment has been wired and tested at the factory. Installing the switch includes the following procedures:
Mounting the enclosure.• Connecting power source and load leads.• Connecting non-essential loads.• Connecting "Critical Load" branch circuits to the
internal load center.
Connecting the utility sensing and transfer relay
circuits to the generator control panel. Connecting any auxiliary contact (if needed)• Testing functions.
2.2 UNPACKING
Carefully unpack the transfer switch. Inspect closely for any damage that might have occurred during shipment. The purchaser must file with the carrier any claims for loss or damage incurred while in tran­sit.
Check that all packing material is completely removed from the switch prior to installation.
2.3 MOUNTING
Mounting dimensions for the transfer switch enclo­sure are in this manual. Enclosures are typically wall-mounted. See “Installation Diagram”.
Handle transfer switches carefully when install-
ing. Do not drop the switch. Protect the switch against impact at all times, and against construc­tion grit and metal chips. Never install a transfer switch that has been damaged.
This transfer switch is mounted in a NEMA 3R alumi­num enclosure. It can be mounted outside or inside and should be based on the layout of installation, convenience and proximity to the utility supply and load center.
Install the transfer switch as close as possible to the electrical loads that are to be connected to it. Mount the switch vertically to a rigid supporting structure. To prevent switch distortion, level all mounting points. If necessary, use washers behind mounting holes to level the unit.
2.4 CONNECTING POWER SOURCE AND LOAD LINES
DANGER
Make sure to turn OFF both the UTILITY
(NORMAL) and GENERATOR (STANDBY) power supplies before trying to connect power source and load lines to the transfer switch. Supply voltages are extremely high and dangerous. Contact with such high voltage power sup­ply lines causes extremely hazardous, possibly lethal, electrical shock.
Wiring diagrams and electrical schematics are pro­vided in this manual.
NOTE:
All installations must comply with national, state and local codes. It is the responsibility of the installer to perform an installation that will pass the final electrical inspection.
Conductor sizes must be adequate to handle the max­imum current to which they will be subjected, based on the 75°C column of tables, charts, etc. used to size conductors. The installation must comply fully with all applicable codes, standards and regulations.
4
Section 3 — Operation
RTSS Type Transfer Switch
Before connecting wiring cables to terminals, remove any surface oxides from the cable ends with a wire brush. All power cables must enter the enclosure through the knockouts provided. This is necessary to maintain the NEMA/UL type 3 rating. If mounted indoors, conduits can enter the enclosure above the knockouts. If not using the knockouts, entry must be at or below knockouts.
If ALUMINUM conductors are used, apply corro­sion inhibitor to conductors. Tighten terminal lugs to the torque values as noted on the "Utility Service Disconnect Circuit Breaker", and on the decal located on the inside of the door. After tightening terminal lugs, carefully wipe away any excess corrosion inhibi­tor.
Use a torque wrench to tighten the conductors,
being sure not to overtighten, or damage to the insulating base could occur. If not tightened enough, a loose connection would result, caus­ing excess heat which could damage the switch base.
Connect power source load conductors to clearly marked transfer mechanism terminal lugs as fol­lows
1. Connect UTILITY (NORMAL) power source cables to the top of the UTILITY SERVICE DISCONNECT circuit breaker.
2. Connect GENERATOR (STANDBY) source power cables to ATS GENERATOR supply terminals, E1-E2.
3. Connect non-essential customer LOAD leads to LSS switch terminals E1, E2.
4. Connect critical customer loads to the circuit breakers on the load center provided.
Conductors must be properly supported, of approved insulative qualities, protected by approved conduit, and of the correct wire gauge size in accordance with applicable codes.
Be sure to maintain proper electrical clearance between live metal parts and grounded metal. Allow at least 1/2 inch for 100-400 amp circuits.
2.5 NEUTRAL CONNECTIONS
The main neutral block is provided for the connec­tion of the neutral (ungrounded conductors) of the Utility, Generator and non-essential load neutrals. Tighten all wires to the specified torque. Torque val­ues are given on the information decal located on the inside cover.
The main neutral block is connected (bonded) to the enclosure metal by a busbar. If bonding of the neutral is not necessary, the jumper can be removed. When the jumper bar is removed the control wires should be connected as follows:
#00 wire to the neutral block.• GRD wire to the enclosure.
The essential load neutrals are to be connected on the busbars mounted on the load center, next to the branch circuit breakers.
2.6 CONNECTING CONTROL WIRES
Control system interconnections consist of N1 and N2, and leads 0, 15B and 23. Control system inter­connection leads can be run in the same conduit as the AC power lead if the conduit length is less than 35 feet, and ALL of the wiring is rated for 600V. If the conduit length between the generator and PowerManager LTS is more than 35 feet, the control and power leads must be routed in separate con­duits. Recommended wire gauge sizes for this wiring depends on the length of the wire, as recommended in the following chart:
MAXIMUM WIRE
RUN LENGTH
35 feet (10.67m) No. 16 AWG.
60 feet (18.29m) No. 14 AWG.
90 feet (27.43m) No. 12 AWG.
RECOMMENDED WIRE
SIZE
3.1 FUNCTIONAL TESTS AND ADJUSTMENTS
Following transfer switch installation and inter­connection, inspect the entire installation care­fully. A competent, qualified electrician should inspect it. The installation should comply strictly with all applicable codes, standards, and regula­tions. When absolutely certain the installation is proper and correct, complete a functional test of the system.
Perform functional tests in the exact order pre-
sented in this manual, or damage could be done to the switch.
IMPORTANT: Before proceeding with functional tests, read and make sure all instructions and information in this section are understood. Also read the infor­mation and instructions of labels and decals affixed to the switch. Note any options or accessories that might be installed and review their operation.
5
Section 3 — Operation
RTSS Type Transfer Switch
3.2 MANUAL OPERATION
DANGER
Do NOT manually transfer under load.
Disconnect transfer switch from all power sourc­es by approved means, such as the main circuit breaker(s).
3.2.1 ATS MANUAL OPERATION
A manual HANDLE is shipped with the transfer switch. Manual operation must be checked BEFORE the transfer switch is operated electrically. To check manual operation, proceed as follows (Figure 3.1):
1. Turn the generator’s AUTO/OFF/MANUAL switch to OFF.
2. Turn OFF UTILITY SERVICE DISCONNECT cir­cuit breaker.
3. Note position of transfer mechanism main con­tacts by observing the moveable contact carrier arm. This can be viewed through the long narrow slot in the inside cover of the ATS. The top of the moveable contact carrier arm is yellow to be eas­ily identified.
Manual operation handle in the UP position - • LOAD terminals (T1, T2) are connected to UTIL­ITY terminals (N1, N2).
Manual operation handle in the DOWN posi-• tion - LOAD terminals (T1, T2) are connected to EMERGENCY terminals (E1, E2).
3.2.2 LSS MANUAL OPERATION
A manual HANDLE is shipped with the transfer switch. Manual operation must be checked BEFORE the LSS is operated electrically. To check manual operation, proceed as follows (Figure 3.2):
1. Turn the generator’s AUTO/OFF/MANUAL switch to OFF.
2. Turn OFF UTILITY SERVICE DISCONNECT cir­cuit breaker.
3. Note position of non-essential LSS main contacts by observing the moveable contact carrier arm. This can be viewed through the long narrow slot in the inside cover of the ATS. The top of the moveable contact carrier arm is yellow to be eas­ily identified.
Manual operation handle in the UP position - • non-essential loads OFF.
Manual operation handle in the DOWN position - • non-essential loads ON.
Do not use excessive force when operating the
transfer switch manually or damage could be done to the manual handle.
Attach handle to the moveable
contact carrier arm.
NOTE: Return handle to storage position in enclosure when finished with manual transfer.
Figure 3.1 — Actuating ATS Transfer Switch
Move handle UP for the
UTILITY (NORMAL) position.
Move handle DOWN for the
GENERATOR (STANDBY) position.
6
Attach handle to the moveable
contact carrier arm.
Section 3 — Operation
RTSS Type Transfer Switch
Figure 3.2 — Actuating LSS Transfer Switch
Move handle UP for the
non-essential loads OFF.
Move handle DOWN for the
non-essential loads ON.
NOTE: Return handle to storage position in enclosure when finished with manual transfer.
3.2.3 CLOSE TO UTILITY SOURCE SIDE
Before proceeding, verify the position of the switch by observing the position of manual operation handle in Figure 3.1. If the handle is UP, the contacts are closed in the UTILITY (NORMAL) position, no further action is required. If the handle is DOWN, proceed with Step
1. Step 1: With the handle inserted into the moveable
contact carrier arm, move handle UP. Be sure to hold on to the handle as it will move quickly after the center of travel.
Step 2: Remove manual operating handle from move-
able contact carrier arm. Return handle to storage bracket.
3.2.4 CLOSE TO GENERATOR SOURCE SIDE
Before proceeding, verify the position of the switch by observing the position of the manual operation handle in Figure 3.1. If the handle is DOWN, the contacts are closed in the GENERATOR (STANDBY) position. No further action is required. If the handle is UP, proceed with Step 1.
Step 1: With the handle inserted into the moveable
contact carrier arm, move the handle DOWN. Be sure to hold on to the handle as it will move quickly after the center of travel.
Step 2: Remove manual operating handle from move-
able contact carrier arm. Return handle to storage bracket.
3.2.5 RETURN TO UTILITY SOURCE SIDE
Step 1: Manually actuate switch to return manual
operating handle to the UP position.
Step 2: Remove manual operating handle from move-
able contact carrier arm. Return handle to storage bracket.
3.3 VOLTAGE CHECKS
1. Turn ON the UTILITY power supply to the PowerManager LTS using the UTILITY SERVICE DISCONNECT circuit breaker.
DANGER
PROCEED WITH CAUTION. THE TRANSFER SWITCH
IS NOW ELECTRICALLY HOT. CONTACT WITH LIVE TERMINALS RESULTS IN EXTREMELY HAZARDOUS AND POSSIBLY FATAL ELECTRICAL SHOCK.
2. With an accurate AC voltmeter, check for correct voltage. Measure across ATS terminal lugs N1 and N2. Also check N1 to NEUTRAL and N2 to NEUTRAL.
3. When certain that UTILITY supply voltage is correct and compatible with transfer switch ratings, turn OFF the UTILITY supply to the transfer switch.
4. On the generator panel, set the AUTO/OFF/ MANUAL switch to MANUAL position. The gen­erator should crank and start.
7
Section 3 — Operation
RTSS Type Transfer Switch
The voltage measurements should be as follows:
N1 - N2 240 VAC Nominal N1 - Neutral 120 VAC Nominal N2 - Neutral 120 VAC Nominal
5. Let the generator stabilize and warm up at no­load for at least five minutes.
6. Set the generator's main circuit breaker (CB1) to its ON or CLOSED position.
DANGER
PROCEED WITH CAUTION. GENERATOR
OUTPUT VOLTAGE IS NOW BEING DELIVERED TO TRANSFER SWITCH TERMINALS. CONTACT WITH LIVE TERMINALS RESULTS IN EXTREMELY DANGEROUS AND POSSIBLY FATAL ELECTRICAL SHOCK.
7. With an accurate AC voltmeter and frequency meter, check the no-load, voltage and frequency.
Measure across ATS terminal lugs E1 to E2. Also
check E1 to NEUTRAL and E2 to NEUTRAL.
a. Frequency ........................................60-62 Hertz
b. Terminals E1 to E2..........................240-246 VAC
c. Terminals E1 to NEUTRAL ..............120-123 VAC
d. Terminals E2 to NEUTRAL ..............120-123 VAC
8. Set the generator’s main circuit breaker (CB1) to its OFF or OPEN position.
9. Set the AUTO/OFF/MANUAL switch to the OFF position to shut down the generator.
NOTE:
Do NOT proceed until generator AC output volt­age and frequency are correct and within stated limits. If the no-load voltage is correct but no-load frequency is incorrect, the engine governed speed may require adjustment. If no-load frequency is correct but voltage is not, the voltage regulator may require adjustment.
3.4 GENERATOR TESTS UNDER LOAD
3.4.1 ATS & CRITICAL LOADS
1. Set the generator's main circuit breaker to its OFF or OPEN position.
2. Set the UTILITY SERVICE DISCONNECT circuit breaker to the OFF position.
3. Manually actuate the transfer switch main con­tacts to their GENERATOR (STANDBY) position. Refer to "Manual Operation".
4. Manually actuate the LSS main contacts to the UP position. Non-essential loads OFF.
5. To start the generator, set the AUTO/OFF/ MANUAL switch to MANUAL. When engine starts, let it sta­bilize for a few minutes.
6. Turn the generator's main circuit breaker to its ON or CLOSED position. The generator now pow­ers all LOAD circuits. Check generator operation under load as follows:
Turn ON electrical loads to the full rated watt-• age/amperage capacity of the generator. DO NOT OVERLOAD.
With maximum rated load applied, check volt-• age and frequency across transfer switch termi­nals E1 and E2. Voltage should be greater than 230VAC and frequency should be greater than 59 Hertz.
Let the generator run under rated load for at • least 30 minutes. With unit running, listen for unusual noises, vibration, overheating, etc., that might indicate a problem.
7. When checkout under load is complete, set main circuit breaker of the generator to its OFF or OPEN position.
8. Let the generator run at no-load for several min­utes. Then, shut down by setting the AUTO/OFF/ MANUAL switch to its OFF position.
9. Move the switch's main contacts back to their UTILITY position. For example, LOAD connected to UTILITY power supply. Refer to "Manual Operation". Handle and operating lever of trans­fer switch should be in UP position.
10. Turn on the UTILITY power supply to transfer switch, using the UTILITY SERVICE DISCONNECT circuit breaker. The utility power source now powers the loads.
11. Set the generator's AUTO/OFF/MANUAL switch to its AUTO position.
8
Section 3 — Operation
RTSS Type Transfer Switch
3.4.2 LOAD SHED FUNCTIONAL TEST
1. Set the generator’s main circuit breaker to its OFF or OPEN position.
2. Set the UTILITY SERVICE DISCONNECT circuit breaker to the OFF position.
3. Manually actuate the transfer switch main con­tacts to the GENERATOR position. Refer to “Manual Operation” section of this manual.
4. Manually actuate the LSS main contacts to the DOWN position. Non-essential loads ON.
5. To start the generator, set the AUTO/OFF/MANUAL switch to MANUAL. When engine starts, let it sta­bilize for a few minutes.
6. Turn the generator’s main circuit breaker its ON position. The generator now powers all LOAD circuits. Check generator operation under load as follows:
Turn ON electrical loads to the full rated wattage/• amperage capacity of the generator.
Increase the load to slightly overload the genera-• tor (load to draw frequency down 55-56 hz). This will require turning loads on that are connected to the LSS. Do not severely overload the genera­tor.
The LSS should actuate after three (3) seconds • to disconnect the non-essential loads. The door mounted LOAD SHED LED should be ON.
Decrease the electrical load on the generator to • allow the generator frequency to increase to 60 Hz.
7. The next step will depend on how the LSC is set up (see the "Load Shed Controller" section). If set up for:
Manual Operation — Press the door mounted LOAD SHED RESET button. The LSS will recon­nect non-essential loads.
Automatic Operation — The LSS will reconnect non-essential loads after the delay time setup on the DIP switches of the LSC.
8. Turn ON the UTILITY power supply to the transfer switch using the UTILITY SERVICE DISCONNECT circuit breaker. After the return to utility time delay, the utility power source will power the loads.
9. Set the generator's AUTO/OFF/MANUAL switch to the AUTO position.
9
Section 4 — Installation Diagrams
RTSS Type Transfer Switch Load Shed Interconnection - Drawing No. 0G8774-B
10
Section 4 — Installation Diagrams
RTSS Type Transfer Switch
200 Amp Load Shed Enclosure - Drawing No. 0G8775-B
11
Section 5 — Electrical Data
RTSS Type Transfer Switch Electrical Schematic - Drawing No. 0G7816-A
12
Section 5 — Electrical Data
RTSS Type Transfer Switch
Electrical Schematic - Drawing No. 0G7816-A
13
Section 5 — Electrical Data
RTSS Type Transfer Switch Wiring Diagram - Drawing No. 0G7817-B
14
Section 5 — Electrical Data
RTSS Type Transfer Switch
Wiring Diagram - Drawing No. 0G7817-B
15
Parts List on page 19.
Section 6 — Exploded Views & Parts Lists
RTSS Type Transfer Switch Load Shed Transfer Switch - Drawing No. 0G8054$-C
16
Section 6 — Exploded Views & Parts Lists
RTSS Type Transfer Switch
Load Shed Transfer Switch - Drawing No. 0G8054$-C
Parts List on page 19.
17
Parts List on page 19.
Section 6 — Exploded Views & Parts Lists
RTSS Type Transfer Switch Load Shed Transfer Switch - Drawing No. 0G8054$-C
18
Section 6 — Exploded Views & Parts Lists
RTSS Type Transfer Switch
Load Shed Transfer Switch - Drawing No. 0G8054$-C
ITEM PART NO. QTY. DESCRIPTION
1 0D9618 2 TRANSFER SW. HSB 200A 2P 250V 2 074908 10 SCREW HHTT M5-0.8 X 10 BP 3 0G4478 1 CIRCUIT BREAKER, 200A 2-POLE 4 053640 2 SCREW RHM #8-32 X 3-1/4 5 0F8843 2 BUSBAR, 200A LUG ADAPTER 6 0F8451 2 LUG 300 MCM-6STR 7 0G4413 4 SPACER 200 AMP TRANSFER 8 024334 4 BOLT CARR 1/4-20 X 1" 9 0G7847 1 BUSBAR, 200A TRANSFER SW T1 10 0G7848 1 BUSBAR, 200A TRANSFER SW T2 11 0G6352 2 BUSBAR, 200A TRANSFER SW
N1,N2
12 0G8413 2 BUSBAR, PANELBOARD
INTERCONNECTION 13 0G6417 1 BUSBAR, NEUTRAL BLOCK 14 0E3375 4 LUG SOLDERLESS 250-#6 AL/CU 15 0F1252 4 SCREW BHSC 1/4-20 X 3/8 16 0G78110AL14 1 ENCLOSURE,LOAD SHED
TRANSFER SWITCH 17 0G78120GS0R 1 SUBPLATE PANELBOARD 18 0G78130GS0R 1 SUBPLATE, LOADCENTER 19 0G78140AL14 1 INSIDE COVER LOAD SHED 20 0G78150AL14 1 COVER LOAD SHED ENCLOSURE 21 0G44200AL14 1 CB BRKT 200A TRANSFER SWITCH 22 022097 7 WASHER LOCK M6-1/4 23 085889 3 NUT HEX 1/4-20 SS 24 0G8574A REF. DECAL, TRANSFER SWITCH DATA 25 0G8574B 1 DECAL, TRANSFER SWITCH DATA
200 26 0G8341 1 DECAL, WARN MANUAL OPER
HANDLE 27 0F9205A 1 DECAL, FRT GTS LD CTR 16 CIR
GRY 28 0G4220 1 DECAL, NEUTRAL CONNECTION 29 0D3587 1 DECAL, FUSE REPLACEMENT 30 0G8257 1 DECAL, CUSTOMER CONNECTION 31 0G8264 1 DECAL, TEST SEQUENCE 32 067210A 1 DECAL, GROUNDING LUG 33 0G3259 1 DECAL, TERMINAL SHOCK HZD BI 34 0E4987 1 DECAL, UL PANELBOARD 35 0G3274 1 DECAL, LIVE CIRCUIT ENG/FRN/
SPN 36 0G8535 2 DECAL, TRANSFER SWITCH INFO 37 0G8536 1 DECAL, UTILITY SERVICE
DISCONNECT 38 0G8537A 1 DECAL, GENERATOR SOURCE
CONNECTION 39 0G8537B 1 DECAL, NON-ESSENTIAL LOAD
CONN 40 0G8213 1 DECAL, GENERAC POWER
SYSTEMS
ITEM PART NO. QTY. DESCRIPTION
41 066849 2 SCREW HHTT M5-0.8 X 16 42 058000E 1 NUT TRIC 1/4-20 X .525 43 0E7213 1 THUMB SCREW 1/4-20x1/2 44 0G8783 1 BATTERY CHARGER ASSEMBLY 45 0G3976 4 SCREW BHSC 1/4-20 X 3/4 46 0G6320 1 GROUND BAR (5) 2-14 AWG CONN 47 026850 2 WASHER SHAKEPROOF EXT 1/4
STL 48 0G8411 22 NUT HEX FL WHIZ 1/4-20 49 0E6193 1 BRACKET, ARM EXTENDER 50 0D6162 2 RIVET POP .156 X .362 AL 51 0E6155 1 ARM EXTENDER PIN 52 0E6303 2 WIRE-A 53 0E6303A 2 WIRE-B 54 0E6303D 1 WIRE-E1 55 0D2806 1 FUSEBLOCK 30A 600V 2 POLE 56 073590A 2 FUSE 5A X BUSS HLDR73591 57 0A1495 6 SCREW HHTT M4-0.7 X 10 BP 58 049897 4 SCREW SHC M8-1.25 X 20 G8 59 022145 6 WASHER FLAT 5/16-M8 ZINC 60 022129 6 WASHER LOCK M8-5/16 61 045771 2 NUT HEX M8-1.25 G8 CLEAR ZINC 62 043107 2 SCREW HHC M8-1.25 X 25 C8.8 63 026902 5 SCREW HHTT #8-32 X 1/4 CZ 64 0G8300 1 WIRING HARNESS HSB (NOT
SHOWN) 65 0E3717A 1 ASSY-NEUT BLK 200-400A W/TAP 66 090388 2 SCREW HHTT M6-1.0 X 12 MM 67 0G8145 1 KEYPAD, LOAD SHED 68 0G8242 1 ASSY PCB INTFC LOAD SHED
KEYPD 69 0C6748 2 NUT HEX LOCK M4-0.7 SS NYL INS 70 0F4460 2 SPACER M4/#8 X 5/16 X 1/4 NYL 71 0G8412 1 CABLE, KEYPAD INTERFACE 72 0G8534 1 NEUTRAL WIRE 73 0G7925 1 ASSY PCB 2008HSB LOAD
SHEDCTRL 74 027911 2 RELAY SOC 12VDC DPDT
10A@240VA 75 0D6511 4 SPACER .20 X .375 X .375 PL 76 0E6423 4 NUT HEX FL WHIZ M5-0.8 77 0G8293 1 16 CIR L/CENTR 200A/240V SIEMS 78 0E7888 1 CB 0020A 2P PLUG IN 79 0E7888B 5 CB 0015A 1P PLUG IN 80 0E7888C 5 CB 0020A 1P PLUG IN 81 0E7888D 1 CB 0040A 2P PLUG IN 82 0E7888E 1 CB 0050A 2P PLUG IN 83 0E6034 1 STRAIGHT SPADE CONNECTOR 84 0F6685 3 TIE-WRAP MOUNT(FIR TREE
SYTLE)
19
Section 7 — Notes
20
Section 7 — Notes
21
Part No. 0G8637 Revision D (08/27/08) Catalog No. KGALT-1SI Printed in U.S.A.
INSTALLATION GUIDE
For 100 Amp Automatic Transfer Switch/Load Center Models: 8, 10, 12, 14 and 16 Circuit. Installed with 8, 10, 12, 14, 16, 17 and 20kW Generators.
This Automatic Transfer Switch with built-in Load Center includes an Express Install Kit.
C
US
• Saves on installation time and cost, in many cases up to 50% compared to traditional transfer switch installations.
• Automatically supplies electricity to selected critical circuits.
LISTED
• Can be installed prior to, or along with generator installation.
This manual should remain with the unit.
Residential Transfer Switch Installation Guide
PLEASE NOTE:
This installation guide should be used in conjunction with the “Installation and Owner’s Manual” that is furnished with the Air-cooled Standby Generator. Please review both manuals prior to installation of the generator and transfer switch. This Automatic Transfer Switch/Load Center is not intended for use with the Liquid-cooled Generator product line. This unit is not compatible with other generator manufacturer’s products.
INTRODUCTION
Thank you for purchasing this 100 Amp Automatic Transfer Switch/Load Center with Express Install Kit. The Express Install Kit includes:
• 30 foot, five foot, and two foot pre-wired conduits for making
all required wiring runs.
• An outdoor junction box for making connections between
outdoor and indoor pre-wired conduits.
• UL listed wire nuts for reconnecting emergency circuits
within the main distribution panel.
The 100 Amp Automatic Transfer Switch/Load Center with Express Install Kit can be installed along with a 8, 10, 12, 14, 16 or 17kW Air-cooled Standby Generator, or can be used to pre­wire a home or small business in advance of generator instal­lation. In either case, the Express Install Kit saves installation time and cost, since the majority of labor involved in installing a standby power system is in wiring the generator, automatic transfer switch and emergency circuit subpanel.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates follows:
This symbol points out important safety information
that, if not followed, could endanger personal safety and/or property.
This symbol points out potential explosion hazard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock
hazard.
SAVE THESE INSTRUCTIONS – The manufacturer
suggests that these rules for safe operation be cop­ied and posted near the unit’s installation site. Safety should be stressed to all operators and potential operators of this equipment.
The manufacturer cannot anticipate every possible circum­stance that might involve a hazard. The warnings in this manual, and on tags and decals affixed to the unit are therefore, not all-inclusive. If using a procedure, work method or operating technique the manufacturer does not specifically recommend, ensure that it is safe for all personnel. Also make sure the pro­cedure, work method or operating technique chosen does not render the equipment unsafe.
DANGER
After this heading, read instructions that, if not strictly
complied with, will result in serious personal injury, including death, and/or severe property damage.
After this heading, read instructions that, if not strictly
complied with, may result in serious personal injury and/or property damage.
After this heading, read instructions that, if not strictly
complied with, could result in damage to equipment and/or property.
NOTE:
After this heading, read explanatory statements that
require special emphasis.
ELECTRICAL HAZARDS
• Utility power delivers extremely high and dangerous voltages to the transfer switch as does the standby generator when it is in operation.
• Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet.
DANGEROUS ELECTRICAL SHOCK MAY RESULT.
• In case of accident caused by electric shock, immediately shut down the source of electrical power. If this is not pos­sible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a non­conducting implement, such as a rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.
• Never wear jewelry when working on this equipment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving components causing injury.
1
Residential Transfer Switch Installation Guide
100 Amp Automatic Transfer Switch/Load Center with Express Install Kit
KIT INCLUDES:
THE OUTDOOR CONNECTION BOX WITH FIVE FOOT
A
PRE-WIRED LIQUID TIGHT CONDUIT
B
Mounted outside the home or business nearest the
planned generator location. This is for connection to gen­erator controls and main line circuit breaker.
30 FOOT FLEXIBLE CONDUIT
C
Pre-wired from the automatic transfer switch with built-in
emergency load center for connection to the outdoor con­nection box.
PRE-WIRED AUTOMATIC TRANSFER SWITCH AND
D
EMERGENCY LOAD CENTER
E
Installed within one (1) foot of the building’s main distribu-
tion panel. This transfer switch provides smooth and safe transition between utility and generator power.
Designed with installation
cost savings in mind!
A
C
B
D
F
ITEMS TO BE PURCHASED OR SUPPLIED FOR
COMPLETE INSTALLATION:
E
TWO FOOT PRE-WIRED CONDUIT FOR EASY
F
CONNECTION TO THE BUILDING’S MAIN DISTRIBUTION PANEL
UL LISTED WIRE NUTS (not shown)
G
TOOLS REQUIRED:
Drill, drill bits, hole saw (type and length will be deter­mined by the materials to be drilled and cut), open-end wrenches or adjustable wrenches, socket wrenches or nut drivers, standard and Phillips screwdrivers, sledge ham­mer, level, pencil, channel-lock pliers, spade shovel, rake and safety goggles.
; 70 amp or 40 amp (7kW) double pole circuit breaker (must
be the same type as in the main electrical distribution panel)
; Ground rod with grounding strap (for generator
installation)
; Padlock to lock outdoor connection box
; Crushed stone or pea gravel (approximately 10-12 cubic
feet) (for generator installation)
; Black poly-film or other vegetation blocking fabric (for
generator installation)
; Silicone caulk
; Fasteners (to mount outdoor connection box and
automatic transfer switch)
; Battery - 12V automotive type, group 26R, negative
ground, 350 CCA (8kW), 525 CCA (10, 12, 14, 16, 17 and 20kW) minimum capacity (required as part of generator installation).
2
Site Preparation and Standby Generator Placement
1
2
3
Residential Transfer Switch Installation Guide
5
Crushed Stone or Pea Gravel
4
1. PLAN THE LOCATION OF THE GENERATOR.
NOTE:
Do not place the generator directly under a window.
Select an area outside of the home or business nearest
the incoming gas service. Determine where the genera­tor will be placed outside of the building. Arrange for fuel piping with shut-off valve to be run to this location. Keep in mind that the manufacturer recommends placement no closer than 18 inches to any structure. Local codes may dictate placement farther from a structure. If facing the unit from the front, the generator's fuel inlet is located at the rear lower right of the unit.
2. Clear an area 62 inches by 50 inches of grass and vegeta- tion to a depth of five inches. This includes the distance the generator should be set away from a structure (18 inches) and six inches beyond the width and length of the generator mounting pad (49" L x 25" W).
3. Lay black poly-film to cover the area.
Drill Hole Through House
6
1-3/4”
Diameter Hole
7. While adhering to all local electrical codes, route the 30
foot conduit along ceiling/floor joists and wall studs to the location where the conduit will pass through the wall to the exterior of the building.
Drill Pass Through Hole
7
4. Fill the area to ground level with pea gravel or crushed
stone.
5. Drive an eight foot grounding rod into the ground to grade. Make sure grounding rod and strap are not exposed above ground level. (NEC code applies to grounding method.)
6. Determine where the flexible conduit will pass through the building from inside to outside. When certain there is clearance on each side of the wall, drill a small pilot hole through the wall to mark the location. Drill a 1-3/4” diameter hole through the sheathing and siding with hole saw.
1-3/4”
Diameter Hole
3
Residential Transfer Switch Installation Guide
8. From inside the building, feed the end of the 30-foot conduit (INCLUDED and pre-wired from transfer switch) through the wall to the outside.
Feed Conduit and Wires
8
Silicone
Caulk
The outer diameter of the conduit
connector is 1-11/16”
9. Remove the threaded lock nut from the conduit coupling.
The outer diameter of the threaded
end is 15/16 inches.
The outdoor connection box must be locked to
ensure safety and to discourage tampering.
11. Locate automatic transfer switch with built-in emergency
load center in close proximity to the main distribution panel. The transfer switch can be located to the left or right of the main distribution panel. Two (2) feet is the suggested distance (see Figure 11). The transfer switch may be located a different distance from the main panel depending on available mounting area. Using the two (2) foot conduit connected straight across to the main panel is another option. Always adhere to local electrical codes during installation. Hold transfer switch against the mounting surface. Level the transfer switch and mark the mounting holes. Drill the appropriate size pilot holes. Mount transfer switch with built-in load center to mounting surface with appropriate fasteners.
9
Threaded Lock Nut
10. Lift cover. Remove internal
cover plate screw and internal cover. Remove the knock out in the lower right corner of the external connection box. From the rear of the connection box, feed wires, 4-pin and 2-pin plugs into box. Slip the lock nut over wires and plugs and tighten securely onto conduit coupling.
10
Using appropriate fasteners, mount external connection box
over pre-drilled hole to fully con­ceal the hole. Seal around the hole and conduit with silicone caulk from both the inside and outside of the building. Also, caulk around the sides and top of the box to seal the edges to the siding or wall. Connect wires to lugs; black to black, white to white, and red to red. Torque nuts to 20 in/lbs. Snap together the 4-pin and 2-pin plug connector. Loosen nut from grounding lug and attach ground wire (green) from conduit. Reinstall nut and tighten to 45 in/lbs. Reinstall internal cover plate and screw. Close cover and install lock. This wiring is complete.
4
Mounting Automatic Transfer Switch
11
Two (2)
Feet
Suggested
Distance
The manufacturer recommends that a licensed elec-
trician or an individual with complete knowledge of electricity perform the procedures in Sections 12 and
13.
Switch service main circuit breaker to the
OFF (OPEN) position prior to removal of cover or removal of any wiring of the main electrical distribution panel. The wires con­nected to the service main circuit breaker remain LIVE or HOT. Avoid contact with these wires and the service main circuit breaker connection lugs.
OFF
Residential Transfer Switch Installation Guide
NOTE: Balance must be maintained when moving circuit loca­tions from main electrical distribution panel to emergency load center. Circuit breaker positions alternate buss bars vertically. Circuits sharing a neutral wire should either be moved together to adjacent positions in emergency load center or not moved. If unsure of the proper procedure or if the installation differs from that described in this guide, consult a licensed professional at this time.
12a. Remove the main electrical distribution panel cover.
Remove appropriate size knockout from the bottom or side of the main panel. (A two foot flexible conduit is pre­wired from the transfer switch with built-in load center). Remove threaded lock nut from conduit coupling. Feed all wires through knockout into main panel. Slip lock nut over wires and tighten securely onto conduit coupling.
Connection of Emergency Circuits
12a
Models
Circuits 50A, 240V - - - 1 1
40A, 240V - - 1 1 1
30A, 240V 1 1 1 - -
20A, 240V -1-11
20A, 120V 13345
15A, 120V 53545
Connection of Emergency Circuits
12b
UL approved wire nuts are included with installation kit.
8
Circuit
10
Circuit
12
Circuit
14
Circuit
Circuit
16
NOTE:
Circuits to be moved must be protected by same size breaker. For example, a 15 amp 120 volt circuit in emer­gency load center will replace a 15 amp 120 volt circuit in main electrical distribution panel.
12b. In the main panel, remove the black (hot) wire from the
circuit breaker that protects a circuit to be powered in the event of a power failure. Wire nut the black wire to the matching circuit lead wire from the emergency circuit breaker in the load center in the transfer switch. (All circuit wires are color coded and labeled for easy identification). UL listed wire locknuts are included in installation kit. Trace each black (hot) wire connected and wire nut the white (neutral) wire from the same Romex cable (circuit) to the matching circuit number on the white (neutral) wire from the emergency load center. Repeat for each circuit. Repeat this process with the remaining circuits to be powered by the generator.
NOTE:
Both grounded and ungrounded conductors must be moved to the emergency panel and connected to the new wiring from the emergency panel using supplied wire nuts.
13. Install the 70 amp double pole circuit breaker; 10, 12, 14, 16, 17 and 20kW units or the 40 amp double pole
breaker; 8kW units (purchased or supplied separately), into main electrical distribution panel. This circuit breaker
must be compatible with the main electrical distribu­tion panel. It may be necessary to reposition remaining
circuit breakers or remove circuit breakers that have been disconnected to accommodate the insertion of the 70 amp or 40 amp double pole circuit breaker. Connect white wire to the main distribution panel neutral bar. Connect solid green wire to main electrical panel ground bar. Connect the black and red wires to the 70 amp or 40 amp double pole circuit breaker. Reinstall the main distribution panel cover.
Install 70 Amp Circuit Breaker
13
70
70
5
Residential Transfer Switch Installation Guide
THE AUTOMATIC TRANSFER SWITCH/LOAD CENTER IS NOW INSTALLED!
If a generator is being installed at this time, proceed to step 19. If a generator will not be installed at this time, perform steps 14 through 17 to complete the pre-wiring project.
14. Open the outdoor connection box and unplug the 4-pin
and 2-pin connector. Remove the black, white, red, and green wires that lead from the five foot pre-wired conduit. Make sure the mating wires from the 30 foot conduit are on the connection box terminal lugs (or ground screw), re-install all washers and nuts and secure them in place.
15. Remove the lock nut holding the five foot pre-wired con­duit coupling to the outdoor connection box. Slip the lock nut over the wires and plug, then remove the conduit from the connection box. Use a knockout plug to close off the opening where the conduit was removed.
The external connection box must be locked to
ensure safety and to discourage tampering.
16. For pre-existing buildings, switch the service main circuit
breaker back on to provide utility power to the building.
17. Save the five foot pre-wired conduit for re-installation at time of generator installation. At that time, re-install the conduit by reversing steps 14 and 15. The grounding strap will also be installed with the generator. Save this guide for reference at time of generator installation.
DANGER
Be sure the service main circuit breaker is switched
OFF at time of generator installation.
18. Place the generator and mounting pad in the location
prepared in steps one through five.
18
19. Attach one end of the grounding strap (No. 12 AWG
stranded copper wire) to grounding rod, and the other end to the grounding lug (located at rear corner of unit). Make sure the grounding rod and strap are not exposed above ground level (NEC code applies to grounding method).
NOTE:
The generator mode switch should be placed in the OFF
position. Generator main line circuit breaker should be
switched to the OFF or OPEN position.
20. Access wiring connections for installation of five foot har-
ness at the generator. To gain access to wiring connec­tions and the circuit breaker you must remove the cover plate (black) over the control module. Remove the two screws retaining the cover plate. Lift the cover plate up and towards the front of the generator to remove.
Connect Five Foot Conduit to Generator
20
19
This completes the pre-wiring portion of the 100 Amp Automatic Transfer Switch/Load Center Installation. Proceed with step 18 for generator installation.
6
Residential Transfer Switch Installation Guide
Remove the small black cap (covering 1-1/16” diameter
hole) from back of enclosure. Remove threaded lock nut from conduit coupling (with 90° elbow) and wires. Feed wires into 1-1/16” diameter hole. Place threaded lock nut over wires and onto conduit coupling. Tighten securely with screwdriver and hammer to ensure lock nut is tight. Connect power leads (red & black) to the circuit breaker lugs. Connect the neutral wire (white) to terminal connection (NEUTRAL). Connect ground wire (green) to grounding bolt with star washer below all ground wire lugs. Tighten securely ensuring the star washer makes good contact with metal base plate. Connect sensing wires to terminal strip as follows: Blue - N1, Yellow - N2, Brown - 23 and Orange - 194.
FUEL HOOKUP AND CHECK FOR LEAKS
21a. Make the connection between the rigid fuel piping and the
generator using the supplied threaded flexible fuel line. Use a pipe sealant suitable for gaseous fuel connections. Check connections for leaks by opening manual fuel shut­off valve and swab, or spray, connections with soapy water. If a leak exists, the area will bubble with the presence of the soapy water.
21b. If a leak is located, shut off fuel and disconnect flexible
piping. Dry the threaded ends and reapply an adequate amount of pipe sealant. Reconnect flexible fuel line, open fuel supply and recheck for leaks. If leak still exists, repeat step 21b.
22. Follow all generator installation and setup instructions in the Installation and Owner’s Manual provided with the generator. During testing performed in Section 2 of the generator Installation and Owner’s Manual, utility power supply to the Automatic Transfer Switch/Load Center can be controlled using the 40 or 70 amp feeder circuit breaker located in the main distribution panel.
Grounding
Lug
19
One (1) Foot Flexible
Fuel Line
21
7
Residential Transfer Switch Installation Guide
Installation Drawing 0H0258-A
8
Residential Transfer Switch Installation Guide
Installation Drawing 0H0258-A
9
Residential Transfer Switch Installation Guide
Installation Drawing 0G8573-A
10 10
Residential Transfer Switch Installation Guide
Electrical Schematic - Drawing 0G7959-A
11
Residential Transfer Switch Installation Guide
Wiring Diagram - Drawing 0G7958-A
12
Residential Transfer Switch Installation Guide
Wiring Diagram - Drawing 0G7958-A
13
Residential Transfer Switch Installation Guide
Load Center Exploded View - Drawing 0G8786-C
14
Residential Transfer Switch Installation Guide
Load Center Exploded View - Drawing 0G8786-C
ITEM PART NO. QTY. DESCRIPTION
1 0G80700ST14 1 GTS LOAD CENTER ENCLOSURE GRAY 2 0G81010ST14 1 COVER 8 POS GTS LOAD CTR GRAY 0G81020ST14 1 COVER 10 POS.GTS LOAD CTR GRAY 0G81030ST14 1 COVER 12 POS.GTS LOAD CTR GRAY 0G81040ST14 1 COVER 14 POS.GTS LOAD CTR GRAY 0G81060ST14 1 COVER 16 POS.GTS LOAD CTR GRAY 3 0C2237 1 TRANSFER SWITCH HOME STANDBY
100A 2P 250V 3A 077220 1 COIL UTILITY 3B 077220A 1 COIL STANDBY 4 074908 4 SCREW HHTT M5-0.8 X 10 5 058443 1 SCREW CRIMPTITE 1/4-20 X 5/8 6 0A1658 1 LOCK WASHER, SPECIAL-1/4” 7 063617 1 RELAY PANEL 12VDC DPDT 10A @ 240
VAC 8 0E7889A 1 8CIR L/CNTR 125A/240V 0E7889 1 12CIR L/CENTR 125A/240V (ALSO USED
FOR 10 CIRCUIT) 0F9213 1 16CIR L/CENTR 125A/240V (ALSO USED
FOR 14 CIRCUIT) 9 0A1495 4 SCREW HHTT M4-0.7 X 10 10 0A1661 2 RIVET POP .156” X .675” 11 - - ­ 12 081108 1 PLUG PLASTIC 13 0G8095AST14 1 HARNESS ADAPTER PLATE GRAY 14 0G81300ST14 1 SUBPLATE GTS LOAD CENTER GRAY 15 0F4790 2.63” U-CHANNEL 16 - - ­ 17 022717A 1 GROMMET 3/8 X 1/16 X 1/4 18 0E6155 1 ARM EXTENDER PIN 19 0G8233A 4 CABLE TIE SELF MOUNTING 4.3LG 20 0G8138 1 HARN GTS-MAIN PNL 8CIR W/NEUT 0G8139 1 HARN GTS-MAIN PNL 10CIR W/NEUT 0G8140 1 HARN GTS-MAIN PNL 12CIR W/NEUT 0G7955 1 HARN GTS-MAIN PNL 14CIR W/NEUT 0G8141 1 HARN GTS-MAIN PNL 16CIR W/NEUT
ITEM PART NO. QTY. DESCRIPTION
21 074138 3 LUG QUICK DISCONNECT NI-S 10X45
DEG BRASS / TIN 22 0H0090A 6 SCREW PPHM #10-32X5/16 SEMS SC 23 077033 6 LUG SLDLSS 1/0-#14X9/16 AL/CU 24 0D4698 1 BLOCK TERM 20A 6 X 3 X 1100V
- - - ­ 26 0A7215 10 SCREW SW 1/4"-20 X 5/8” WITH
WASHER
- - - ­ 27 066849 2 SCREW HHTT M5-0.8 X 16 (8, 10, 12, 14,
16 CIRCUIT) 28 0G7954A 1 HARNESS LOAD CTR INT.CONN 8-16
(NOT SHOWN) 0G7954B 1 HARNESS LOAD CTR INT.CONN T1 (NOT
SHOWN) 0G7954C 1 HARNESS LOAD CTR INT.CONN T2 (NOT
SHOWN) 29 0D2572 1 FUSEBLOCK 30A 600V 3POS W/SQ 30 073590A 3 FUSE 5A 31 0G8487 1 BATTERY CHARGER ASSY 8 10 12 14 16 CIR 32 0E7888 A/R CIR BRKR 20A 2P 1 1 1 33 0E7888A A/R CIR BRKR 30A 2P 1 1 1 34 0E7888B A/R CIR BRKR 15A 1P 5 3 5 4 5 35 0E7888C A/R CIR BRKR 20A 1P 1 3 3 4 5 36 0E7888D A/R CIR BRKR 40A 2P 1 1 1 37 0E7888E A/R CIR BRKR 50A 2P 1 1 38 0G80860ST14 1 HARNESS ENTRY COVER GRAY 39 0G7951 1 HARN GTS-EXT CONN BOX 8KW 0G7952 1 HARN GTS-EXT CONN BOX 10KW 0G7953 1 HARN GTS-EXT CONN BOX 14/17KW
15
Residential Transfer Switch Installation Guide
Notes
16
Residential Transfer Switch Installation Guide
Notes
17
Part No. 0G8571 Revision D (07/31/08) Catalog No. KGATX100-1SI Printed in U.S.A.
P/N 0G6419
Installation Instructions
GenReady Load Center EZ Transfer™ Operator
Model #005447-0
DANGER
Hazardous voltage that will cause
This instruction sheet outlines the gener­al installation procedure. It is not intend­ed to cover all details or variations in equipment nor does it provide for every possible contingency to be met in con­nection with installation. If unsure of the correct procedure, have any questions, or need assistance, contact a qualified electrical contractor.
This device should be installed in accor­dance with all local electrical codes and/or the latest edition of the National Electrical Code®.
death, serious injury or substan­tial property damage. Turn off power supplying this equipment before working inside.
STEP 1:
Remove the six (6) screws that hold the trim (front cover) on. Remove the trim from the front of the panel board.
NOTE: The GenReady Panel is de­signed to be directly compatible with any Generac manufactured product. Use of another manufacturer’s generator may require the purchase and installation of additional sensing and control compo­nents.
Revision D (04/17/08) Printed in U.S.A
STEP 2:
a. Open outer trim door exposing the
upper pan (dead front).
b. Remove all twist-outs covered by
existing labels.
c. Apply one of the ATS Danger decals
to the load center as shown in the following figure.
2a.
2c.
STEP 4:
a. Add additional 125 Amp, 2-pole
switch on right. Place in OFF posi­tion. Before lowering switch on stabs install interlock bar under the exist­ing switch handle and the new switch handle as shown.
2b.
STEP 3:
Remove the RED retaining clip by unscrewing the fastener in the center of clip and discard.
b. Push both switches into the bus
stabs.
STEP 5:
a. Position operator under the hold
down bracket. Locate operator and switch tie bracket around the two 125 Amp switches.
b. Install the two (2) screws (M3 x 6mm
PPHMS) to mount the switch tie bracket to the operator mechanism.
2
5a.
5b.
STEP 7:
Install the 15 Amp 2-pole circuit breaker in the position shown.
STEP 8:
Install generator control wiring (must be installed in conduit). Install 5A fuse (if required) to the terminal strip in genera­tor and connect the control wire from the generator.
STEP 6:
Install the four (4) screws (10-32 x 5/16 HHTT) to mount operating mechanism to the back of the panel board.
Refer to the wiring diagram (P/N 0G4744) for further details. 2007 and earlier generator models – refer to 0G4744 page 1, for generator models introduced in 2008 and later- refer to 0G4744 page 2.
3
STEP 9:
Apply one of the ATS Danger decals to the load center as shown.
Danger Decal
STEP 10:
Place the front cover on the panel board. Install the six (6) screws to hold the front cover on.
STEP 11:
Apply decal 0G4742A on the left side, and decal 0G4732B on right side of the EZ Transfer™ operator box as shown.
4
REFERENCE: Items supplied in the EZ Transfer™ operator kit.
5
6
7
Part Number 0G6419 Revision D (04/17/08) Printed in U.S.A
® The National Electrical Code is a registered trademark of the National Fire Protection Association.
Air-cooled Generator
Battery Charger
Installation Guidelines
Table of Contents
Table of Contents ................................Inside Front Cover
Section 1 — General Information ............................... IFC
1.1 Introduction..........................................................IFC
1.2 Battery Charger Compatibility ................................. 1
1.2.1 Determination of Generator/Transfer
Switch Model Type ........................................ 1
Section 2 — Load Shed Transfer Switch
Installation ....................................................2
2.1 Load Shed Transfer Switch (RTSS) Installation ...... 2
2.1.1 Wiring and Connections at the
Transfer Switch ............................................. 2
2.1.2 Wiring and Connections at the Generator ...... 2
2.1.3 Operational Testing ....................................... 2
Section 3 — Standard or Service Entrance Transfer
Switch Installation ......................................3
3.1 Standard Transfer Switch (RTSN) or (RTSE) Service
Entrance Rated Transfer Switch Installation ........... 3
3.1.1 Wiring and Connections at the
Transfer Switch ............................................. 3
3.1.2 Charger Mounting.......................................... 4
3.1.3 Wiring and Connections at the Generator ...... 5
3.1.4 Operational Testing ....................................... 6
Section 4 – GenReady Installation .................................6
4.1.1 Wiring and Connections at the
Transfer Switch ............................................. 6
4.1.2 Charger Mounting.......................................... 7
4.1.3 Wiring and Connections at the Generator ...... 7
4.1.4 Operational Testing ....................................... 8
Section 5 – Interconnection Diagrams ..........................9
Section 6 – Notes .............................................................16
1.1 INTRODUCTION
This battery charger supplies a trickle charging cur­rent and voltage to maintain the charge on the gen­erator starting battery inside the generator enclosure. The charger will not replenish a fully discharged bat­tery. It is intended to be connected to a 120VAC gen­erator backed-up circuit only. If it is not connected to a generator backed-up circuit the battery could go “dead” while the generator is running for extended periods of time.
Figure 1.1 — Charger as Supplied Indicating
Input and Output Wiring
DC OutputAC Input
This battery charger must be properly installed
and wired for correct operation of all 2008 model line Air-cooled Standby Generators. Failure to do so will result in a dead battery condition at the generator.
For authorized service, reference the dealer locator number found in the generator owner’s manual
or on the generator.
NOTE:
This installation guide should be used in conjunc­tion with the “Installation and Owner’s Manual” that is furnished with the Air-cooled Standby Generator and the Installation and appropriate transfer switch manual. Please review all manuals prior to installation of the generator and transfer switch. This battery charger is not required with the Liquid-cooled Generator product line. This battery charger is not required for Air-cooled Standby Generators prior to the 2008 model line. This unit is not compatible with other generator manufacturer’s products.
Section 1 — General Information
Battery Charger Installation Guidelines
These Installation Guidelines are designed to famil­iarize personnel with the installation process for the battery charger required for the air-cooled generator only. It does not replace or supersede any information contained in any of the written documents shipped with the unit. This booklet should only be used in conjunction with the Owner’s Manual, Installation Guide and other technical documents shipped with the unit.
Future product updates and/or modifications will be reflected in the written documentation included with the equipment. Always read all accompanying docu­mentation carefully before attempting to install any generator, transfer switch or related equipment.
NOTE:
It is essential to comply with all regulations estab­lished by the Occupational Safety and Health Administration (OSHA) and strict adherence to all local, state and national codes is mandatory.
This device should be installed with all local electrical codes and/or the latest edition of the National Electrical Code. All wiring must be the correct size and type, and must conform to local codes, standards, and regulations.
1.2 BATTERY CHARGER COMPATIBILITY
This battery charger is compatible, and required with all 2008 model line Air-cooled Standby Generators. For all generators that were supplied with a transfer switch/load center, the charger is already installed in the transfer switch enclosure and this charger is not needed. For all generators that were NOT supplied with a transfer switch/load center, the charger is NOT already installed and MUST be installed according to these guidelines.
1.2.1 DETERMINATION OF GENERATOR/ TRANSFER SWITCH MODEL TYPE
The Battery charger included with this manual only needs to be used with certain transfer switch configu­rations. Some transfer switch configurations already have the battery charger installed in the transfer switch. Before proceeding it is necessary to select the transfer switch used from the following table.
Switch Type Switch Description Notes Proceed to Section
RTSD
RTSF
ST100R10C
RTSH
RTSP
ST100R14C
RTSW
ST100R16C
KGATX0216100
RTSS
KGALT0101200
SR200RDPM
RTSN
SRXXXR
KGATX
RTSE
SRXXXRD
KGATD
005448-0 005449-0
KGATD0101RSP
NOTE: Switch Type is the first four (4) digits of the model number and can be found on the data label inside the switch.
Pre-wire with 8 circuit load center
Pre-wire with 10 circuit load center
Pre-wire with 12 circuit load center
Pre-wire with 14 circuit load center
Pre-wire with 16 circuit load center
Power Manager LTS - Load Shed with 16 circuit load center
Standard
Service Entrance Rated
GenReady
Battery charger is included and pre-wired with the transfer switch. Discard this charger. No further installation is required
Battery charger is included and pre-wired with the transfer switch. Discard this charger. No further installation is required
Battery charger is included and pre-wired with the transfer switch. Discard this charger. No further installation is required
Battery charger is included and pre-wired with the transfer switch. Discard this charger. No further installation is required
Battery charger is included and pre-wired with the transfer switch. Discard this charger. No further installation is required
Battery charger is included with the transfer switch. Proceed with connections.
The included battery charger must be installed and connected
The included battery charger must be installed and connected
The included battery charger must be installed and connected
Stop Here
Stop Here
Stop Here
Stop Here
Stop Here
2
3
3
4
1
Section 2 — Load Shed Transfer Switch Installation
Battery Charger Installation Guidelines
2.1 LOAD SHED TRANSFER SWITCH (RTSS) INSTALLATION
2.1.1 WIRING AND CONNECTIONS AT THE TRANSFER SWITCH
Connect the 15B, 0, and 23 low voltage control wires to the load shed controller connector J5 per the wir­ing diagram. Wires should be sized according to the following table.
CHARGER DC OUTPUT (TRANSFER SWITCH
TO GENERATOR) WIRE SIZE CHART
Maximum Wire Run
Length 35 feet (10.67m) No. 16 AWG. 60 feet (18.29m) No. 14 AWG. 90 feet (27.43m) No. 12 AWG.
NOTE:
The charger is already mounted in the transfer switch (Figure 2.1).
NOTE:
See RTSS Installation/Wiring Diagram in the "Interconnection Diagrams" section for connec­tions.
Figure 2.1 — Wiring Connections at the Transfer
Switch
Recommended Wire
Size (stranded copper)
Connections
2.1.2 WIRING AND CONNECTIONS AT THE GENERATOR
1. Crimp spade lugs onto all three low voltage wires, 15B, 0, and 23 (Purchased or supplied separate­ly).
2. Connect the low voltage wires, 15B, 0, and 23 to the terminal strip on the controller (Figure 2.2).
Figure 2.2 — Connection of Charger DC Output
Wires in Generator Control Panel
2.1.3 OPERATIONAL TESTING
1. If already connected, disconnect the battery in the generator. Remove the negative cable first fol­lowed by the positive cable. Take care not to short the cables together.
2. Ensure power is applied to the battery charger input.
3. Connect a volt meter across the battery leads. The voltage reading should be between 12.8 VDC and 13.8 VDC (Figure 2.3).
Charger
2
Figure 2.3 — Measurement of Charger Output
with Battery Disconnected
Section 3 — Standard or Service Entrance Transfer Switch Installation
Battery Charger Installation Guidelines
4. If the voltage is within range installation of the battery charger is complete. If the voltage is not within range verify all wiring and sizing and retest.
5. Re-connect the battery cables. Positive cable first followed by the negative cable.
3.1 STANDARD TRANSFER SWITCH
(RTSN) OR (RTSE) SERVICE ENTRANCE RATED TRANSFER SWITCH INSTALLATION
3.1.1 WIRING AND CONNECTIONS AT THE
TRANSFER SWITCH
Choose the appropriate option.
NOTE:
See the appropriate RTSN or RTSE Installation/ Wiring Diagram in the "Interconnection Diagrams" section for connections.
Option 1 — Protected Load Provided in Load
Center
1. Install a 15A breaker in the load center (Purchased or supplied separately). The breaker must be on a generator backed-up circuit or the battery in the generator will not maintain its charge during extended run periods.
2. Run the 120VAC hot wire and neutral wires to the generator.
NOTE:
See the appropriate RTSN or RTSE Installation/ Wiring Diagram in the "Interconnection Diagrams" section for connections.
3. Run the other side of the fuse holder (120VAC Hot) along with the neutral from the neutral lug to the generator (see Figures 3.1 and 3.5).
NOTE:
See the appropriate RTSN or RTSE Installation/ Wiring Diagram for connections.
Figure 3.1 — RTSN Fuse Block Installation and
Neutral Connection
Figure 3.2 — RTSN Fuse Block Installation T1
Connection
Option 2 — Protected Load Provided in the RTS,
Fuse Block Installation
NOTE:
This section is only appropriate for 2008 RTSN or RTSE transfer switches.
1. Mount the optional 5amp 600V fuse and holder in the transfer switch. (Purchased or supplied separately). Pre-2008 transfer switches will not have holes pre-drilled for the fuse holder. In this case, it is necessary to drill holes in the enclosure to mount the fuse holder (see Figures 3.1 and
3.4).
2. Connect one side of the fuse to terminal (T1) of the transfer switch using a spade lug. Pre-2008 transfer switches will not have the spade lug attached to terminal T1. The spade terminal is available separately if required (see Figures 3.2 and 3.4).
3
Section 3 — Standard or Service Entrance Transfer Switch Installation
Battery Charger Installation Guidelines
Figure 3.3 — RTSN Fuse Block Installation When
Completed
Figure 3.4 — RTSE Fuse Block Installation T1
Connection
Figure 3.6 — RTSE Fuse Block Installation When
Completed
Figure 3.5 — RTSE Neutral Connection
4
3.1.2 CHARGER MOUNTING
1. Remove the cover over the controller in the gen­erator
2. The battery charger can be located anywhere within the controls area on the generator. It is convenient to mount the charger on the verti­cal surface on right-hand side of the controller (Figure 3.7).
3. Clean the surface where the charger is to be mounted prior to mounting with a damp cloth and wait for the area to dry.
4. Remove the adhesive covering on the backside of the charger and firmly press the charger into place as shown. Once mounted the charger may be removed for inspection by separating the hook & loop mounting (Figure 3.8).
Loading...