Not intended for use as Primary Power in place of utility
DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!
or in life-support applications.
INTRODUCTION
Thank you for purchasing this compact, high performance, air-cooled, engine-driven generator. It is
designed to automatically supply electrical power to
operate critical loads during a utility power failure.
This unit is factory installed in an all-weather, metal
enclosure that is intended exclusively for outdoor installation. This generator will operate using either
vapor withdrawn liquid propane (LP) or natural gas
(NG).
NOTE:
This generator is suitable for supplying typical
residential loads such as Induction Motors (sump
pumps, refrigerators, air conditioners, furnaces,
etc.), Electronic Components (computer, monitor,
TV, etc.), Lighting Loads and Microwaves.
READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, contact the nearest Dealer for starting, operating and
servicing procedures.
Throughout this publication, and on tags and decals
affixed to the generator, DANGER, WARNING,
CAUTION and NOTE blocks are used to alert personnel to special instructions about a particular operation that may be hazardous if performed incorrectly
or carelessly. Observe them carefully. Their definitions are as follows:
DANGER
After this heading, read instructions that, if not
strictly complied with, will result in serious personal injury, including death, in addition to property
damage.
After this heading, read instructions that, if not
strictly complied with, may result in serious personal injury or property damage.
After this heading, read instructions that, if not
strictly complied with, could result in damage to
equipment and/or property.
NOTE:
After this heading, read explanatory statements
that require special emphasis.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict
compliance with the special instructions while
performing the service are essential to preventing
accidents.
Four commonly used safety symbols accompany the
DANGER, WARNING and CAUTION blocks. The type
of information each indicates follows:
This symbol points out potential explosion haz-
ard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock
hazard.
The operator is responsible for proper and safe use
of the equipment. The manufacturer strongly recommends that the operator read this Owner's Manual
and thoroughly understand all instructions before
using this equipment. The manufacturer also strongly recommends instructing other users to properly
start and operate the unit. This prepares them if they
need to operate the equipment in an emergency.
CONTENTS
This manual contains pertinent owner’s information
for these models:
It is the operator's responsibility to perform all safety
checks, to make sure that all maintenance for safe
operation is performed promptly, and to have the
equipment checked periodically by a Dealer. Normal
maintenance service and replacement of parts are the
responsibility of the owner/operator and, as such, are
not considered defects in materials or workmanship
within the terms of the warranty. Individual operating
habits and usage contribute to the need for maintenance service.
Proper maintenance and care of the generator ensures
a minimum number of problems and keep operating
expenses at a minimum. See a Dealer for service aids
and accessories.
HOW TO OBTAIN SERVICE
When the generator requires servicing or repairs,
contact a Dealer for assistance. Service technicians
are factory-trained and are capable of handling all
service needs.
When contacting a Dealer about parts and service,
always supply the complete model number and serial
number of the unit as given on its data decal, which is
located on the generator. See section "The Generator"
for decal location.
Model No. ____________ Serial No. ______________
This symbol points out important safety infor-
mation that, if not followed, could endanger
personal safety and/or property of others.
Table of Contents
Air-cooled Generators
Introduction ........................Inside Front Cover
Read This Manual Thoroughly ........................ IFC
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation
be copied and posted near the unit’s installation site. Safety should be stressed to all opera-
tors and potential operators of this equipment.
The engine exhaust from this product•
contains chemicals known to the state
defects or other reproductive harm.
This product contains or emits chemicals•
known to the state of California to cause
cancer, birth defects or other reproductive harm.
Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become
familiar with this Owner’s Manual and with the
unit. The generator can operate safely, efficiently and
reliably only if it is properly installed, operated and
maintained. Many accidents are caused by failing to
follow simple and fundamental rules or precautions.
The manufacturer cannot anticipate every possible
circumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed
to the unit are, therefore, not all-inclusive. If using
a procedure, work method or operating technique
the manufacturer does not specifically recommend,
ensure that it is safe for others. Also make sure the
procedure, work method or operating technique utilized does not render the generator unsafe.
WARNING:•
of California to cause cancer, birth
WARNING:•
DANGER
Despite the safe design of this generator,
operating this equipment imprudently, neglecting
its maintenance or being careless can cause
possible injury or death. Permit only responsible
and capable persons to operate or maintain this
equipment.
Potentially lethal voltages are generated by
these machines. Ensure all steps are taken to
render the machine safe before attempting to
work on the generator.
Parts of the generator are rotating and/or hot
during operation. Exercise care near running
generators.
GENERAL HAZARDS
For safety reasons, the manufacturer recommends •
that the installation, initial start-up and maintenance of this equipment is carried out by a
Dealer.
The engine exhaust fumes contain carbon monox-•
ide, which can be DEADLY. This dangerous gas, if
breathed in sufficient concentrations, can cause
unconsciousness or even death. Do NOT alter or
add to the exhaust system or do anything that
might render the system unsafe or in noncompliance with applicable codes and standards.
Keep hands, feet, clothing, etc., away from drive •
belts, fans, and other moving or hot parts. Never
remove any drive belt or fan guard while the unit
is operating.
Adequate, unobstructed flow of cooling and venti-•
lating air is critical to correct generator operation.
Do not alter the installation or permit even partial
blockage of ventilation provisions, as this can seriously affect safe operation of the generator. The
generator MUST be installed outdoors.
When working on this equipment, remain alert •
at all times. Never work on the equipment when
physically or mentally fatigued.
Inspect the generator regularly, and contact the •
nearest Dealer for parts needing repair or replacement.
Before performing any maintenance on the gen-•
erator, disconnect its battery cables to prevent
accidental start up. Disconnect the cable from the
battery post indicated by a NEGATIVE, NEG or
(–) first, then remove the POSITIVE, POS or (+)
cable. When reconnecting the cables, connect the
POSITIVE cable first, the NEGATIVE cable last.
Never use the generator or any of its parts as a •
step. Stepping on the unit can stress and break
parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage,
oil leakage, etc.
2
IMPORTANT SAFETY INSTRUCTIONS
Air-cooled Generators
ELECTRICAL HAZARDS
All generators covered by this manual produce •
dangerous electrical voltages and can cause fatal
electrical shock. Utility power delivers extremely
high and dangerous voltages to the transfer switch
as does the standby generator when it is in operation. Avoid contact with bare wires, terminals,
connections, etc., while the unit is running. Ensure
all appropriate covers, guards and barriers are in
place, secured and/or locked before operating the
generator. If work must be done around an operating unit, stand on an insulated, dry surface to
reduce shock hazard.
Do not handle any kind of electrical device while •
standing in water, while barefoot, or while hands or
feet are wet. DANGEROUS ELECTRICAL SHOCK
MAY RESULT.
The National Electrical Code (NEC) requires the •
frame and external electrically conductive parts of
the generator to be connected to an approved earth
ground. Local electrical codes also may require
proper grounding of the generator electrical system.
After installing this home standby electrical sys-•
tem, the generator may crank and start at any
time without warning. When this occurs, load circuits are transferred to the STANDBY (generator)
power source. To prevent possible injury if such a
start and transfer occur, always set the generator’s
AUTO/OFF/MANUAL switch to its OFF position
before working on equipment and remove the 15A
fuse from the generator control panel.
In case of accident caused by electric shock, imme-•
diately shut down the source of electrical power. If
this is not possible, attempt to free the victim from
the live conductor. AVOID DIRECT CONTACT WITH
THE VICTIM. Use a nonconducting implement,
such as a dry rope or board, to free the victim from
the live conductor. If the victim is unconscious,
apply first aid and get immediate medical help.
Never wear jewelry when working on this equip-•
ment. Jewelry can conduct electricity resulting in
electric shock, or may get caught in moving components causing injury.
FIRE HAZARDS
For fire safety, the generator must be installed and •
maintained properly. Installation must always
comply with applicable codes, standards, laws
and regulations. Adhere strictly to local, state
and national electrical and building codes. Comply
with regulations the Occupational Safety and
Health Administration (OSHA) has established.
Also, ensure that the generator is installed in
accordance with the manufacturer’s instructions
and recommendations. Following proper installation, do nothing that might alter a safe installation
and render the unit in noncompliance with the
aforementioned codes, standards, laws and regulations.
Keep a fire extinguisher near the generator at all •
times. Extinguishers rated “ABC” by the National
Fire Protection Association are appropriate for
use on the standby electric system. Keep the extinguisher properly charged and be familiar with its
use. Consult the local fire department with any
questions pertaining to fire extinguishers.
EXPLOSION HAZARDS
Do not smoke around the generator. Wipe up any •
fuel or oil spills immediately. Ensure that no combustible materials are left in the generator compartment, or on or near the generator, as FIRE or
EXPLOSION may result. Keep the area surrounding the generator clean and free from debris.
Gaseous fluids such as natural gas and liquid pro-•
pane (LP) gas are extremely EXPLOSIVE. Install
the fuel supply system according to applicable
fuel-gas codes. Before placing the home standby
electric system into service, fuel system lines must
be properly purged and leak tested according to
applicable code. After installation, inspect the fuel
system periodically for leaks. No leakage is permitted.
STANDARDS INDEX
In the absence of pertinent standards, codes, regulations and laws, the published information listed
below may be used as installation guide for this
equipment.
1. NFPA No. 37, STATIONARY COMBUSTION
ENGINES AND GAS TURBINES, available from
the National Fire Protection Association, 470
Atlantic Avenue, Boston, MA 02210.
2. NFPA No. 76A, ESSENTIAL ELECTRICAL
SYSTEMS FOR HEALTH CARE FACILITIES,
available same as Item 1.
3. NFPA No. 54, NATIONAL FUEL GAS CODE,
available same as Item 1.
4. NFPA No. 58, AMERICAN NATIONAL STANDARD
FOR STORAGE AND HANDLING OF LIQUEFIED
PETROLEUM GAS, available same as Item 1.
5. NFPA No. 70, NFPA HANDBOOK OF NATIONAL
ELECTRIC CODE, available same as Item 1.
6. Article X, NATIONAL BUILDING CODE, available
from the American Insurance Association, 85
John Street, New York, N.Y. 10038.
7. AGRICULTURAL WIRING HANDBOOK, avail-
able from the Food and Energy Council, 909
University Avenue, Columbia, MO 65201.
8. ASAE EP-3634, INSTALLATION AND
MAINTENANCE OF FARM STANDBY ELECTRICAL
SYSTEMS, available from the American Society
of Agricultural Engineers, 2950 Niles Road, St.
Joseph, MI 49085.
9. NFPA No. 30, FLAMMABLE AND COMBUSTIBLE
LIQUIDS CODE, available same as Item 1.
3
DANGER
Section 1 — General Information
Air-cooled Generators
1.2 PROTECTION SYSTEMS
Unlike an automobile engine, the generator may have
Only qualified electricians or contractors should
attempt such installations, which must comply
strictly with applicable codes, standards and regulations.
1.1 UNPACKING/INSPECTION
After unpacking, carefully inspect the contents for
damage.
This standby generator set is ready for installa-•
tion with a factory supplied and pre-mounted base
pad and has a weather protective enclosure that is
intended for outdoor installation only.
This UL listed standby generator set may be pack-•
aged with an automatic transfer switch with built
in load center. The combination transfer switch
and load center is pre-wired with a two foot and
30 foot conduit. Circuit breakers for emergency
circuit connections are included (if equipped).
This UL listed, 2-pole switch is rated at 100 • or 200
AC amperes at 250 volts maximum. The 100 Amp
transfer switch is for indoor use only. The 200
Amp transfer switch is for indoor/outdoor use
(if equipped).
If this generator is used to power electrical load
circuits normally powered by a utility power
source, it is required by code to install a transfer
switch. The transfer switch must effectively isolate
the electrical system from the utility distribution
system when the generator is operating (NEC 700,
701 & 702). Failure to isolate an electrical system
by such means will result in damage to the generator and also may result in injury or death to
utility power workers due to backfeed of electrical
energy.
If any loss or damage is noted at time of delivery, have
the person(s) making the delivery note all damage on
the freight bill or affix their signature under the consignor's memo of loss or damage.
If a loss or damage is noted after delivery, separate
the damaged materials and contact the carrier for
claim procedures.
“Concealed damage” is understood to mean damage
to the contents of a package that is not in evidence at
the time of delivery, but is discovered later.
To properly open the roof, press down on the center top lip and release the latch. If pressure is not
applied from the top, the roof may appear stuck.
Always verify that the side lock is unlocked before
attempting to lift the roof.
to run for long periods of time with no operator present to monitor engine conditions. For that reason,
the engine is equipped with the following systems
that protect it against potentially damaging conditions:
1. Low Oil Pressure Sensor
2. High Temperature Sensor
3. Overcrank
4. Overspeed
5. RPM Sensor
6. Low Battery
There are readouts on the control panel to notify
personnel that one of these failures has occurred.
There is also a System Set LED (single cylinder) or a
Status message on the display (V-twins) that displays
when all of the conditions described in the "System
Set LED" section are true.
1.3 NEC REQUIREMENT FOR ARC
FAULT CIRCUIT INTERRUPTION
BREAKER FOR BEDROOMS
In 2001, the National Electric Code (NEC) introduced a requirement for new construction. This new
requirement indicates the need for Arc Fault Circuit
Interrupters to be used to protect the complete
branch circuit that feeds a dwelling bedroom. The
actual NEC requirement is indicated below.
1. Definition: An arc fault circuit interrupter is a
device intended to provide protection from the
effects of arc faults by recognizing characteristics
unique to arcing and by functioning to de-energize the circuit when an arc fault is detected.
2. Dwelling Unit Bedrooms: All branch circuits that
supply 125 volt, single-phase, 15 and 20 ampere
outlets installed in dwelling unit bedrooms shall
be protected by an arc fault circuit interrupter
listed to provide protection of the entire branch
circuit.
Section 210.12 requires that AFCI protection be
provided on branch circuits that supply outlets
(receptacle, lighting, etc.) in dwelling bedrooms. The
requirement is limited to 15 and 20 ampere, 125
volt circuits. There is no prohibition against providing AFCI protection on other circuits or in locations
other than bedrooms. Because circuits are often
shared between a bedroom and other areas such as
closets and hallways, providing AFCI protection on
the complete circuit would comply with 210.12.
4
Section 1 — General Information
Air-cooled Generators
If during the installation of the home standby system
the decision is made to provide back up power to a
bedroom branch circuit, then the circuit breaker in
the transfer switch should be replaced with an Arc
Fault Circuit Interrupter.
It is most important that breakers only be switched
like for like. For instance, if replacing a 15A breaker,
it MUST be replaced with a 15A AFCI breaker.
Likewise, a 20A breaker MUST be replaced with a
20A AFCI.
These AFCI breakers are available at the nearest
hardware store.
Siemens Item # Description
Q115AF 15A Single Pole AFCI
Q120AF 20A Single Pole AFCI
1.4 EMISSION INFORMATION
The Environmental Protection Agency requires that
this generator complies with exhaust emission standards. This generator is certified to meet the applicable EPA emission levels. Additional information
regarding the requirements set by the EPA is as follows:
The generator is certified for use as a stationary
engine for standby power generation. Any other use
may be a violation of federal and/or local laws. It is
important that to follow the maintenance specifications in the "Maintenance" section to ensure that the
engine complies with the applicable emission standards for the duration of the engine’s life. This engine
is certified to operate on Liquid Propane fuel and
pipeline Natural Gas. The emission control system
on the generator consists of the following:
Fuel Metering System•
Carburetor/mixer assembly•
Fuel regulator•
Air Induction System•
Intake pipe/manifold•
Air cleaner•
Ignition System•
Spark plug•
Ignition module•
The Emissions Compliance Period referred to on the
Emissions Compliance Label indicates the number of
operating hours for which the engine has been shown
to meet Federal emission requirements. See the table
below to determine the compliance period for the
generator. The displacement of the generator is listed
on the Emissions Compliance Label.
Normal Operating Range-20° F (-28.8° C) to 77° F (25° C)
* Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition,
etc. Maximum power decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6 C (10 F) above 16 C
(60 F) ambient temperature.
** Load current values shown for 120 volts are maximum TOTAL values for two separate circuits. The maximum current in each circuit must not exceed the
value stated for the 240 volts.
*** Circuits to be moved must be protected by same size breaker. For example, a 15 amp circuit in the main panel must be a 15 amp circuit in the transfer
switch.
7,000 NG
8,000 LP
Group 26R, 12
Volts and 350
CCA Minimum
9,000 NG
10,000 LP
12,000 NG
12,000 LP
13,000 NG
14,000 LP
Group 26R, 12 Volts and 525 CCA Minimum
16,000 NG
16,000 LP
16,000 NG
17,000 LP
18,000 NG
20,000 LP
1.6.2 ENGINE
Model8 kW10 kW12/14/16/17 kW20 kW
Type of EngineGH-410GT-530GT-990GT-999
Number of Cylinders1222
Rated Horsepower @ 3,600 rpm14.8183236
Displacement410cc530cc992cc999cc
Cylinder BlockAluminum w/Cast Iron Sleeve
Valve ArrangementOverhead Valves
Ignition SystemSolid-state w/Magneto
Recommended Spark PlugRC14YCBPR6HSRC14YCRC12YC
Spark Plug Gap0.76 mm (0.030 inch)0.76 mm (0.030 inch)1.02 mm (0.040 inch)0.76 mm (0.030 inch)
The “System Set” LED (single cylinder) or "Ready to
Run" on the display (v-twin) is ready when all of the
following conditions are true:
1. The AUTO/OFF/MANUAL switch is set to the
AUTO position.
2. The utility voltage being supplied to the unit is
being sensed by the PCB. If the utility sense voltage is not connected to the unit or if it is below
approximately 150-160 volts AC, then the system
set light will flash rapidly (8kW). This indicates
that if the AUTO/OFF/MANUAL switch is placed
in the Auto position, the generator will start.
3. No alarms are present, for example, low oil pressure, high temperature, etc.
1.8 FUEL REQUIREMENTS
AND RECOMMENDATIONS
With LP gas, use only the vapor withdrawal system. This type of system uses the vapors formed
above the liquid fuel in the storage tank.
The engine has been fitted with a fuel carburetion
system that meets the specifications of the 1997
California Air Resources Board for tamper-proof dual
fuel systems. The unit will run on natural gas or LP
gas, but it has been factory set to run on natural gas.
Should the primary fuel need to be changed to LP
gas, the fuel system needs to be reconfigured. See the
reconfiguring the Fuel System section for instructions
on reconfiguration of the fuel system.
Recommended fuels should have a Btu content of at
least 1,000 Btus per cubic foot for natural gas; or at
least 2,520 Btus per cubic foot for LP gas. Ask the
fuel supplier for the Btu content of the fuel.
Required fuel pressure for natural gas is five (5)
inches to seven (7) inches water column (0.18 to
0.25 psi); and for liquid propane, 10 inches to 12
inches of water column (0.36 to 0.43 psi). The
primary regulator for the propane supply is NOT
INCLUDED with the generator.
NOTE:
All pipe sizing, construction and layout must comply with NFPA 54 for natural gas applications and
NFPA 58 for liquid propane applications. Once the
generator is installed, verify that the fuel pressure
NEVER drops below four (4) inches water column
for natural gas or 10 inches water column for liquid propane.
Prior to installation of the generator, the installer
should consult local fuel suppliers or the fire marshal to check codes and regulations for proper installation. Local codes will mandate correct routing of
gaseous fuel line piping around gardens, shrubs and
other landscaping to prevent any damage.
8
Special considerations should be given when installing the unit where local conditions include flooding,
tornados, hurricanes, earthquakes and unstable
ground for the flexibility and strength of piping and
their connections.
Use an approved pipe sealant or joint compound on
all threaded fitting.
All installed gaseous fuel piping must be purged and
leak tested prior to initial start-up in accordance with
local codes, standards and regulations.
1.9 FUEL CONSUMPTION
Unit
7/8 kW771400.94/341.68/62
9/10 kW1021561.25/461.93/70
12/12 kW1522151.53/562.08/76
13/14 kW1562201.56/582.30/84
16/16 kW1832611.59/582.51/91
16/17 kW1832611.61/592.57/94
18/20 kW2062941.89/692.90/106
* Natural gas is in cubic feet per hour.
** LP is in gallons per hour/cubic feet per hour.
*** Values given are approximate.
Verify that gas meter is capable of providing enough
fuel flow to include household appliances.
1.9.1 BTU FLOW REQUIREMENTS -
NATURAL GAS
BTU flow required for each unit based on 1000 BTU
per cubic foot.
propane (LP) gas are highly explosive. Even the
slightest spark can ignite such fuels and cause
an explosion. No leakage of fuel is permitted.
Natural gas, which is lighter than air, tends to
collect in high areas. LP gas is heavier than air
and tends to settle in low areas.
Nat. GasLP Vapor
1/2 LoadFull Load1/2 LoadFull Load
DANGER
Section 1 — General Information
Air-cooled Generators
NOTE:
A minimum of one approved manual shut-off valve
must be installed in the gaseous fuel supply line.
The valve must be easily accessible. Local codes
determine the proper location.
1.10 RECONFIGURING THE
FUEL SYSTEM
1.10.1 8 KW, 410CC ENGINE
To reconfigure the fuel system from NG to LP, follow
these steps (Figure 1.4):
NOTE:
The primary regulator for the propane supply is
NOT INCLUDED with the generator. A fuel pressure of 10 to 12 inches of water column (0.36 to
0.43 psi) to the fuel inlet of the generator MUST
BE SUPPLIED.
1. Turn off the main gas supply (if connected).
2. Open the roof and remove the door.
3. Remove the battery (if installed).
4. Take the plastic T-handle fuel selector in the poly
bag supplied with the generator.
5. Locate the selector knob on the air box cover,
behind the yellow air filter door and power
bulge. The unit comes from the factory in the NG
(Natural Gas) position. Grasping the T-handle,
insert the pin end into the hole in the selector
knob and pull out to overcome spring pressure
and then twist clockwise 90 degrees and allow
the selector to return in once aligned with the LP
(Liquid Propane) position.
6. Save this tool with the Owner's Manual.
7. Install the battery, door and close the roof.
8. Reverse the procedure to convert back to natural
gas.
Figure 1.4 – Fuel Selector
NOTE:
Use an approved pipe sealant or joint compound
on all threaded fittings to reduce the possibility
of leakage.
To reconfigure the fuel system from NG to LP, follow
these steps:
NOTE:
The primary regulator for the propane supply is
NOT INCLUDED with the generator. A fuel pressure of 10 to 12 inches of water column (0.36 to
0.43 psi) to the fuel inlet of the generator MUST
BE SUPPLIED.
1. Open the roof.
2. For 10kW units: Loosen clamp and slide back
the air inlet hose.
Slide fuel selector on carburetor out towards the •
back of the enclosure (Figures 1.5 and 1.6).
Return the inlet hose and tighten clamp secure-•
ly.
For 12, 14, 16, 17 and 20kW units: remove the air
cleaner cover.
Slide the selector lever out towards the back of •
the enclosure (Figures 1.7 and 1.8).
Return the air cleaner cover and tighten the two •
thumb screws.
Figure 1.5 - 10kW, GT-530 (Inlet Hose Slid Back)
Fuel Selection
Lever - "In"
Position for
Natural Gas
Fuel
3. Close the roof.
4. Reverse the procedure to convert back to natural
gas.
9
Section 1 — General Information
Air-cooled Generators
Figure 1.6 - 10kW, GT-530 (Inlet Hose Slid Back)
Fuel Selection
Lever - "Out"
Position for
Liquid Propane
(Vapor) Fuel
Figure 1.7 - 12, 14, 16, 17, & 20kW,
GT-990/GT-999 (Airbox Cover Removed)
Fuel Selection Lever - "In" Position for Natural Gas Fuel
Figure 1.8 - 12, 14, 16, 17, & 20kW,
GT-990/GT-999 (Airbox Cover Removed)
Fuel Selection Lever - "Out" Position for Liquid Propane
(Vapor) Fuel
1.11 LOCATION
1.11.1 GENERATOR
Install the generator set, in its protective enclosure,
outdoors, where adequate cooling and ventilating air
is always available (Figure 1.9). Consider these factors:
The installation of the generator • must comply
strictly with NFPA 37, NFPA 54, NFPA 58, and
NFPA 70 standards.
Install the unit where air inlet and outlet open-•
ings will not become obstructed by leaves, grass,
snow, etc.. If prevailing winds will cause blowing
or drifting, consider using a windbreak to protect
the unit.
Install the generator on high ground where water •
levels will not rise and endanger it.
Allow sufficient room on all sides of the generator •
for maintenance and servicing. This unit must be
installed in accordance with current applicable
NFPA 37 and NFPA 70 standards; as well as any
other federal, state and local codes for minimum
distances from other structures. DO NOT install
under wooden decks or structures unless there is
at least four (4) feet of clearance above the generator, three (3) feet of clearance on sides and front,
and 18 inches of clearance at back of unit.
Install the unit where rain gutter down spouts, •
roof run-off, landscape irrigation, water sprinklers
or sump pump discharge does not flood the unit
or spray the enclosure, including any air inlet or
outlet openings.
Install the unit where services will not be affected •
or obstructed, including concealed, underground
or covered services such as electrical, fuel, phone,
air conditioning or irrigation.
Where strong prevailing winds blow from one •
direction, face the generator air inlet openings to
the prevailing winds.
Figure 1.9 – Generator Clearances
10
Install the generator as close as possible to the fuel •
supply, to reduce the length of piping.
Install the generator as close as possible to the •
transfer switch. REMEMBER THAT LAWS OR
CODES MAY REGULATE THE DISTANCE AND
LOCATION.
The genset must be installed on a level surface. •
The base frame must be level within two (2) inches
all around.
The generator is typically placed on pea gravel or •
crushed stone. Check local codes if a concrete slab
is required. If a concrete base slab is required, all
federal, state and local codes should be followed.
Special attention should be given to the concrete
base slab which should exceed the length and
width of the generator by a minimum of six (6)
inches (0.152 meters) on all sides.
The engine exhaust fumes contain carbon mon-
oxide, which can be DEADLY. This dangerous
gas, if breathed in sufficient concentrations,
can cause unconsciousness or even death. This
exhaust system must be installed properly, in
strict compliance with applicable codes and standards. Following installation, do nothing that
might render the system unsafe or in noncompliance with such codes and standards.
• Operate the generator outdoors ONLY.
• Keep exhaust gases from entering a confined area
through windows, doors, ventilation or other
openings (Figure 1.9).
1.11.2 TRANSFER SWITCH ( if included)
1.11.2.1 8, 10, 12, 14, 16, 17 and 20kW Units
(if equipped)
The transfer switch that may have shipped inside
the carton with the 8, 10, 12, 14, 16 or 17kW generator is enclosed in a NEMA 1 (indoor rated only)
enclosure. The transfer switch that may have shipped
with the 20kW generator is enclosed in a NEMA 3R (indoor/outdoor rated) enclosure.
Install the transfer switch indoors on a firm, sturdy •
supporting structure.
To prevent switch distortion, level the switch if •
necessary. This can be done by placing washers
between the switch enclosure and mounting surface.
Never install the switch where water or any corro-•
sive substance might drip onto the enclosure.
Protect the switch at all times against excessive •
moisture, dust, dirt, lint, construction grit and
corrosive vapors.
Section 1 — General Information
Air-cooled Generators
If the AUTO/OFF/MANUAL switch is not set to its
OFF position, the generator can crank and start
as soon as the battery cables are connected. If
the utility power supply is not turned off, sparking can occur at the battery posts and cause an
explosion.
1.12 BATTERY REQUIREMENTS
See the Specifications section for correct battery size
and rating.
1.13 BATTERY INSTALLATION
Fill the battery with the proper electrolyte fluid if
necessary and have the battery fully charged before
installing it.
Before installing and connecting the battery, complete
the following steps:
1. Set the generator's AUTO/OFF/MANUAL switch to
OFF.
2. Turn off utility power supply to the transfer
switch.
3. Remove the 7.5A fuse from the generator control
panel.
Battery cables were factory connected at the generator (Figure 1.10). Connect cables to battery posts as
follows:
4. Connect the red battery cable (from starter contactor) to the battery post indicated by a positive,
POS or (+).
5. Connect the black battery cable (from frame
ground) to the battery post indicated by a negative, NEG or (—).
Figure 1.10 – Battery Cable Connections
11
Section 1 — General Information
Air-cooled Generators
NOTE:
Dielectric grease should be used on battery posts
to aid in the prevention of corrosion.
NOTE:
Damage will result if battery connections are made
in reverse.
NOTE:
In areas where temperatures regularly fall below
10° F (-12° C) it is recommended that a pad type
battery heater be installed to aid in cold climate
starting.
1.14 THE BATTERY
DANGER
Do not dispose of the battery in a fire. The
battery is capable of exploding.
A battery presents a risk of electrical shock
and high short circuit current. The following precautions are to be observed when working on
batteries:
• Remove the 7.5A fuse from the generator control
panel.
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the
battery; and
• Disconnect charging source prior to connecting or
disconnecting battery terminals.
Do not open or mutilate the battery. Released
electrolyte has been known to be harmful to the
skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically
conductive and corrosive.
The following procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off
immediately with water;
• Where electrolyte contacts the eyes, flush thor-
oughly and immediately with water and seek
medical attention; and
• Spilled electrolyte is to be washed down with an
acid neutralizing agent. A common practice is to
use a solution of 1 pound (500 grams) bicarbonate
of soda to 1 gallon (4 liters) of water. The bicarbonate of soda solution is to be added until the
evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the
area dried.
12
Lead-acid batteries present a risk of fire because
they generate hydrogen gas. The following
procedures are to be followed:
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from body before touching the battery by first touching a grounded metal
surface.
Be sure the AUTO/OFF/MANUAL switch is set to
the OFF position before connecting the battery
cables. If the switch is set to AUTO or MANUAL,
the generator can crank and start as soon as the
battery cables are connected.
Be sure the utility power supply is turned off
and the 7.5A fuse is removed from the generator control panel, or sparking may occur at the
battery posts as the cables are attached and
cause an explosion.
Servicing of the battery is to be performed or supervised by personnel knowledgeable of batteries and
the required precautions. Keep unauthorized personnel away from batteries.
See the Specifications section for the correct size
and rating when replacing the battery. Have these
procedures performed at the intervals specified in
the “Service Schedule.” A negative ground system is
used. Battery connections are shown on the wiring
diagrams. Make sure the battery is correctly connected and terminals are tight. Observe battery polarity
when connecting the battery to the generator set.
1.15 BATTERY CHARGER
NOTE:
These generators DO NOT contain an internal battery charger.
NOTE:
The manufacturer provides a battery trickle charger that is active when the unit is set up for automatic operation. With the battery installed and
utility power source voltage available to the transfer switch, the battery receives a trickle charge
to prevent self-discharge. The trickle charger is
designed to help extend the life of the battery by
maintaining the battery. The trickle charge feature
cannot be used to recharge a discharged battery.
For units shipped with a transfer switch/load center,
the battery charger is pre-installed in the transfer
switch enclosure.
For units shipped without a transfer switch/load center, a separate battery charger module is included
with the generator.
(For battery charger installation, see the Generator
Install Guidelines and Battery Charger Instructions
included with the unit.)
Section 2 — Post Installation Start-up and Adjustments
DANGER
Air-cooled Generators
2.1 BEFORE INITIAL START-UP
NOTE:
These units have been run and tested at the factory prior to being shipped and do not require any
type of break-in.
Before starting, complete the following:
1. Set the generator’s main circuit breaker to its
OFF (or OPEN) position.
2. Set the generator's AUTO/OFF/MANUAL switch to
the OFF position.
3. Turn OFF all breakers on the load center of the
transfer box (T1 and T2).
4. Turn OFF all loads connected to the transfer
switch terminals T1 and T2.
5. Check the engine crankcase oil level and, if necessary, fill to the dipstick FULL mark with the recommended oil. Do not fill above the FULL mark.
6. Check the fuel supply. Gaseous fuel lines must
have been properly purged and leak tested in
accordance with applicable fuel-gas codes. All
fuel shutoff valves in the fuel supply lines must
be open.
During initial start up only, the generator may exceed
the normal number of start attempts and experience
an “over crank” fault (See the "Overcrank" section).
This is due to accumulated air in the fuel system during installation. Reset the control board and restart
up to two more times, if necessary. If unit fails to
start, contact the local dealer for assistance.
Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing
this could damage the engine.
2.2 CHECK TRANSFER SWITCH
2.3 ELECTRICAL CHECKS
Complete electrical checks as follows:
1. Set the generator's main circuit breaker to its
OFF (or OPEN) position.
2. Set the generator's AUTO/OFF/MANUAL switch to
the OFF position.
3. Turn OFF all breakers on the load center of the
transfer box (T1 and T2).
4. Turn on the utility power supply to the transfer
switch using the means provided (such as a utility
main line circuit breaker).
DANGER
The transfer switch is now electrically “hot.”
Contact with “hot” parts will result in extremely
hazardous and possibly fatal electrical shock.
Proceed with caution.
5. Use an accurate AC voltmeter to check utility
power source voltage across transfer switch terminals N1 and N2. Nominal line-to-line voltage
should be 240 volts AC.
6. Check utility power source voltage across terminals N1 and the transfer switch neutral lug; then
across terminal N2 and neutral. Nominal line-toneutral voltage should be 120 volts AC.
7. When certain that utility supply voltage is compatible with transfer switch and load circuit ratings,
turn OFF the utility power supply to the transfer
switch.
8. On the generator panel, set the Auto/Off/ Manual
switch to MANUAL. The engine should crank and
start.
9. Let the engine warm up for about five minutes to
allow internal temperatures to stabilize. Then, set
the generator’s main circuit breaker to its ON (or
closed) position.
OPERATION
Refer to the "Manual Transfer Operation" section, of
the owner’s manual for procedures.
DANGER
Do not attempt manual transfer switch opera-
tion until all power voltage supplies to the
transfer switch have been positively turned off.
Failure to turn off all power voltage supplies
will result in extremely hazardous and possibly
fatal electrical shock.
Proceed with caution! Generator power voltage
is now supplied to the transfer switch. Contact
with live transfer switch parts will result in dangerous and possibly fatal electrical shock.
10. Connect an accurate AC voltmeter and a frequency meter across transfer switch terminal lugs E1
and E2. 8kW voltage should be 230-240 volts at
a frequency of 61-63 Hertz. 12, 14, 16, 17 and
20kW voltage should be 247-249 at a frequency
of 59.5-60.5 Hertz. 10kW voltage should be
220-230 volts at a frequency of 59.5-60.5 Hertz.
11. Connect the AC voltmeter test leads across terminal lugs E1 and neutral; then across E2 and
neutral. In both cases, voltage reading should be
121-126 volts AC (8kW), and 125-126 volts AC
(10, 12, 14, 16, 17 and 20kW).
13
Section 2 — Post Installation Start-up and Adjustments
Air-cooled Generators
12. Set the generator’s main circuit breaker to its
OFF (or OPEN) position. Let the engine run at noload for a few minutes to stabilize internal engine
generator temperatures.
13. Set the generator's AUTO/OFF/MANUAL switch to
OFF. The engine should shut down.
NOTE:
It is important not to proceed until certain that
generator AC voltage and frequency are correct
and within the stated limits. Generally, if both AC
frequency and voltage are high or low, the engine
governor requires adjustment* (*GH410 only). If
frequency is correct, but voltage is high or low, the
generator’s voltage regulator requires adjustment.
2.4 GENERATOR TESTS UNDER LOAD
To test the generator set with electrical loads applied,
proceed as follows:
1. Set generator’s main circuit breaker to its OFF
(or OPEN) position.
2. Turn OFF all breakers on the load center of the
transfer box (T1 and T2).
3. Set the generator's AUTO/OFF/MANUAL switch to
OFF.
4. Turn OFF the utility power supply to the transfer
switch, using the means provided (such as a utility main line circuit breaker).
Do not attempt manual transfer switch opera-
tion until all power voltage supplies to the
transfer switch have been positively turned off.
Failure to turn off all power voltage supplies
will result in extremely hazardous and possibly
fatal electrical shock.
5. Manually set the transfer switch to the STANDBY
position, i.e., load terminals connected to the
generator's E1/E2 terminals. The transfer switch
operating lever should be down.
6. Set the generator's AUTO/OFF/MANUAL switch
to MANUAL. The engine should crank and start
immediately.
7. Let the engine stabilize and warm up for a few
minutes.
8. Set the generator’s main circuit breaker to its ON
(or CLOSED) position. Loads are now powered
by the standby generator.
9. Turn ON the load center of the transfer switch
(T1 and T2).
10. Connect an accurate AC voltmeter and a frequency meter across terminal lugs E1 and E2.
8kW voltage should be greater than 230 volts and •
frequency should be greater than 58 Hz.
10, • 12, 14, 16, 17 and 20kW voltage should be
greater than 240 volts and frequency should be
60 Hz.
11. Let the generator run at full rated load for 20-30
minutes. Listen for unusual noises, vibration or
other indications of abnormal operation. Check
for oil leaks, evidence of overheating, etc.
12. When testing under load is complete, turn OFF
electrical loads.
13. Set the generator's main circuit breaker to its
OFF (or OPEN) position.
14. Let the engine run at no-load for a few minutes.
15. Set the AUTO/OFF/MANUAL switch to OFF. The
engine should shut down.
2.5 CHECKING AUTOMATIC
OPERATION
To check the system for proper automatic operation,
proceed as follows:
1. Set generator’s main circuit breaker to its OFF
(or OPEN) position.
2. Check that the AUTO/OFF/MANUAL switch is set
to OFF.
3. Turn OFF the utility power supply to the transfer
switch, using means provided (such as a utility
main line circuit breaker).
4. Manually set the transfer switch to the UTILITY
position, i.e., load terminals connected to the utility power source side.
5. Turn ON the utility power supply to the transfer
switch, using the means provided (such as a utility main line circuit breaker).
6. Set the generator's main circuit breaker to its ON
(or CLOSED) position.
7. Set the AUTO/OFF/MANUAL switch to AUTO. The
system is now ready for automatic operation.
8. Turn OFF the utility power supply to the transfer
switch.
With the AUTO/OFF/MANUAL switch at AUTO, the
engine should crank and start when the utility source
power is turned OFF after a 10 second delay. After
starting, the transfer switch should connect load
circuits to the standby side after a five (5) second
delay. Let the system go through its entire automatic
sequence of operation.
With the generator running and loads powered by
generator AC output, turn ON the utility power supply
to the transfer switch. The following should occur:
After about 15 seconds, the switch should transfer •
loads back to the utility power source.
About one minute after re-transfer, the engine •
should shut down.
14
GOVERNOR
SHAFT
PRIMARY
ADJUST
SCREW
GOVERNOR
CLAMP
BOLT
SECONDARY
ADJUST SCREW
Section 2 — Post Installation Start-up and Adjustments
Air-cooled Generators
2.6 ENGINE GOVERNOR ADJUSTMENT
If both AC frequency and voltage are correspondingly
high or low, adjust the engine governor as follows:
2.6.1 8 KW UNITS
The engine must be OFF to perform steps 1 and
2.
1. Loosen the governor clamp bolt (Figure 2.1).
2. Hold the governor lever at its wide open throttle
position (clockwise), and rotate the governor
shaft clockwise as far as it will go. Then, tighten
the governor lever clamp bolt to 70 inch-pounds
(8 N-m).
Figure 2.1 — Engine Governor Adjustment
Single Cylinder Engines
2.6.3 ADDITIONAL CORROSION
PROTECTION
Periodically spray all engine linkage parts and brackets with corrosion inhibiting spray such as WD-40 or
a comparable product.
2.7 VOLTAGE REGULATOR
ADJUSTMENT
2.7.1 8 & 10KW UNITS
Due to the brushless design of these two alternators,
no voltage regulator is used and therefore no voltage
adjustment is required.
2.7.2 12, 14, 16, 17 & 20KW UNITS
With the frequency between 59.5 -60.5 Hertz at noload, slowly turn the slotted potentiometer (Figure
2.2) until line voltage reads 247-249 volts.
Figure 2.2 – Voltage Adjustment Potentiometer
3. Start the generator; let it stabilize and warm up
at no-load.
4. Connect a frequency meter across the generators
AC output leads.
5. Turn the primary adjust screw to obtain a frequency reading of 61.5 Hertz. Turn the secondary
adjust screw to obtain a frequency of 62.5 Hz.
2.6.2 12, 14, 16, 17 & 20KW UNITS
All V-twin units DO NOT require an engine governor adjustment due to their design.
NOTE:
Turn to
adjust voltage.
NOTE:
The access panel on top of the control panel must
be removed to adjust the voltage regulator.
NOTE:
The voltage regulator is housed behind the generator's control panel. The regulator maintains a voltage in direct proportion to frequency at a 2-to-1
ratio. For example, at 60 Hertz, line-to-neutral
voltage will be 124 volts.
15
Section 3 — Operation
Air-cooled Generators
3.1 CONTROL PANEL INTERFACE
3.1.1 USING THE AUTO/OFF/MANUAL
SWITCH
1. “AUTO” Position – Selecting this switch activates
fully automatic system operation. It also allows
the unit to automatically start and exercise the
engine every seven days with the setting of the
exercise timer (see the Setting the Exercise Timer
section).
2. “OFF” Position – This switch position shuts down
the engine. This position also prevents automatic
operation.
3. “MANUAL” Position – Set the switch to MANUAL
to crank and start the engine. Transfer to standby
power will not occur unless there is a utility failure.
Figure 3.1 – 8kW Generator Control Panel
With the switch set to AUTO, the engine may
crank and start at any time without warning.
Such automatic starting occurs when utility
power source voltage droops below a preset
level or during the normal exercise cycle. To
prevent possible injury that might be caused
by such sudden starts, always set the switch to
OFF and remove the fuses before working on or
around the generator or transfer switch. Then,
place a “DO NOT OPERATE” tag on the generator panel and on the transfer switch.
16
(FIGURES 3.1 & 3.2)
SYSTEM READY
LOW BATTERY
LOW OIL PRESSURE
HIGH OIL TEMPERATURE
OVERSPEED
RPM SENSOR LOSS
OVERCRANK
SET
EXERCISE
Figure 3.2 – 10/12/14/16/17 & 20kW Generator
Control Panel
ECS
ENTER
3.1.2 SETTING THE EXERCISE TIMER
This generator is equipped with an exercise timer.
Once it is set, the generator will start and exercise
every seven days, on the day of the week and at the
time of day specified. During this exercise period,
the unit runs for approximately 12 minutes and then
shuts down. Transfer of loads to the generator output does not occur during the exercise cycle unless
utility power is lost.
8kW
A switch on the control panel (see Figure 3.1) permits selection of the day and time for the system to
exercise. At the chosen time, perform the following
sequence to select the desired day and time of day
the system will exercise. Remember seasonal time
changes affect the exercise settings.
1. Verify that the AUTO/OFF/MANUAL switch is set
to AUTO.
2. Press and hold the “Set Exercise” switch for several seconds. All the red LED’s will stop flashing
immediately and the generator will start.
3. The generator will start and run for approximately 12 minutes and then shut down. The exerciser
is now set to run at this time of day each week.
Example: If the “Set Exercise” pressed on Saturday
afternoon at 2:00 p.m., the generator will start and
exercise for approximately 12 minutes every Saturday
at 2:00 p.m.
Section 3 — Operation
Air-cooled Generators
NOTE:
The exerciser will only work in the AUTO mode
and will not work unless this procedure is performed. The exerciser will need to be reset every
time the 12 volt battery is disconnected and then
reconnected, and when the fuse is removed and/
or replaced.
10 to 20 KW - INSTALLATION ASSISTANT
Upon first power up of the generator, the display
interface will begin an installation assistant. The
assistant will prompt the user to set the minimum
settings to operate. These settings are simply: Current
Date/Time and Exercise Day/Time. The maintenance
intervals will be initialized when the exercise time is
entered (Figure 3.2).
The exercise settings can be changed at any time via
the "EDIT" menu (see Appendix, "Menu System").
If the 12 volt battery is disconnected or the fuse
removed, the Installation Assistant will operate upon
power restoration. The only difference is the display
will only prompt the customer for the current Time
and Date.
IF THE INSTALLER TESTS THE GENERATOR
PRIOR TO INSTALLATION, PRESS THE “ENTER”
KEY TO AVOID SETTING UP THE EXERCISE
TIME. THIS WILL ENSURE THAT WHEN THE
CUSTOMER POWERS UP THE UNIT, HE WILL
STILL BE PROMPTED TO ENTER AN EXERCISE
TIME.
NOTE:
The exerciser will only work in the AUTO mode and
will not work unless this procedure is performed.
The current date/time will need to be reset every
time the 12 volt battery is disconnected and then
reconnected, and/or when the fuse is removed.
3.1.3 DISPLAY INTERFACE
8 kW LED Display
Seven (7) LED’s are provided for user status indications. The LED functions are:
1. System Ready (green)
2. Low Battery (red)
3. Low Oil Pressure (red)
4. High Oil Temperature (red)
5. Over Speed (red)
6. RPM Sensor Loss (red)
7. Over Crank (red)
See the Protection Systems section for details.
10 to 20KW DISPLAY INTERFACE MENUS
The LCD display is organized as detailed below:
The “Home” page, this page is the default page •
which will be displayed if no keys are pressed for
30 seconds. This page normally shows the current
Status message and the current date and time.
The highest priority active Alarm and/or Warning
will be automatically posted on this page as well as
flashing the backlight when such an event is detected. In the case of multiple Alarms or Warnings,
only the first message will be displayed. To clear
an Alarm or Warning, see the Protection Systems
section - Clear Alarm.
The display backlight is normally off. If the user •
presses any key, the backlight will come on automatically and remain on for 30 seconds after the
last key was pressed.
The “Main Menu” page will allow the user to •
navigate to all other pages or sub-menus by using
the Left/Right and Enter keys. This page can be
accessed at any time with several presses of the
dedicated Escape key. Each press of the Escape
key takes you back to the previous menu until the
main menu is reached. This page displays the following options: HISTORY; STATUS; EDIT; AND
DEBUG. (See the Appendix - "Menu System".)
3.2 AUTOMATIC TRANSFER
OPERATION
To select automatic operation, do the following:
1. Make sure the transfer switch main contacts are
set to their UTILITY position, i.e., loads connected to the utility power source (Figure 3.2).
2. Be sure that normal UTILITY power source voltage is available to transfer switch terminal lugs
N1 and N2 (Refer to the Electrical Data section).
3. Set the generator’s AUTO/OFF/MANUAL switch to
AUTO.
4. Set the generator’s main circuit breaker to its ON
(or CLOSED) position.
With the preceding steps complete, the generator will
start automatically when utility source voltage drops
below a preset level. After the unit starts, loads are
transferred to the standby power source. Refer to the
Sequence of Automatic Operation section.
17
Section 3 — Operation
Air-cooled Generators
3.3 SEQUENCE OF AUTOMATIC
OPERATION
3.3.1 UTILITY FAILURE
Initial Conditions: Generator in Auto, ready to run,
load being supplied by utility source. When utility
fails (below 65% of nominal), a 10 second (optionally
programmable on the 17 and 20kW only) line interrupt delay time is started. If the utility is still gone
when the timer expires, the engine will crank and
start. Once started, a five (5) second engine warmup timer will be initiated. When the warm-up timer
expires, the control will transfer the load to the generator. If the utility power is restored (above 75% of
nominal) at any time from the initiation of the engine
start until the generator is ready to accept load (5
second warm-up time has not elapsed), the controller will complete the start cycle and run the generator through its normal cool down cycle; however, the
load will remain on the utility source.
3.3.2 CRANKING
The system will control the cyclic cranking as follows:
16 second crank, seven (7) second rest, 16 second
crank, seven (7) second rest followed by three (3)
additional cycles of seven (7) second cranks followed
by seven (7) second rests.
Choke Operation
1. The 990/999cc engines have an electric choke in
the air box that is automatically controlled by the
electronic control board.
2. The 530cc engines have an electric choke on the
divider panel air inlet hose that is automatically
controlled by the electronic control board.
3. The 410cc engines have a choke behind the air
box that is automatically controlled by the electronic control board.
Failure to Start
This is defined as any of the following occurrences
during cranking.
1. Not reaching starter dropout within the specified
crank cycle. Starter dropout is defined as four (4)
cycles at 1,000 RPM.
2. Reaching starter dropout, but then not reaching
2200 RPM within 15 seconds. In this case the
control board will go into a rest cycle for seven
(7) seconds, then continue the rest of the crank
cycle.
During a rest cycle the start and fuel outputs are
de-energized and the magneto output is shorted to
ground.
Cranking Conditions
The following notes apply during cranking cycle.
1. Starter motor will not engage within five (5) seconds of the engine shutting down.
2. The fuel output will not be energized with the
starter.
3. The starter and magneto outputs will be energized together.
4. Once the starter is energized the control board
will begin looking for engine rotation. If it does
not see an RPM signal within three (3) seconds
it will shut down and latch out on RPM sensor
loss.
5. Once the control board sees an RPM signal it will
energize the fuel solenoid, drive the throttle open
and continue the crank sequence.
6. Starter motor will disengage when speed reaches
starter dropout.
7. If the generator does not reach 2200 RPM within
15 seconds, re-crank cycle will occur.
8. If engine stops turning between starter dropout
and 2200 RPM, the board will go into a rest cycle
for seven (7) seconds then re-crank (if additional
crank cycles exist).
9. Once started, the generator will wait for a holdoff period before starting to monitor oil pressure
and oil temperature (refer to the Alarm Messages
section for hold-off times).
10. During Manual start cranking, if the Mode switch
is moved from the Manual position, the cranking
stops immediately.
11. During Auto mode cranking, if the Utility returns,
the cranking cycle does NOT abort but continues
until complete. Once the engine starts, it will run
for one (1) minute, then shut down.
3.3.3 LOAD TRANSFER
The transfer of load when the generator is running is
dependent upon the operating mode as follows:
1. Manual
Will not transfer to generator if utility is present.•
Will transfer to generator if utility fails (below •
65% of nominal for 10 consecutive seconds.
Will transfer back when utility returns for 15 con-•
secutive seconds. The engine will continue to run
until removed from the Manual mode.
18
2. Auto
DANGER
Will start and run if Utility fails for 10 consecu-•
tive seconds.
Will start a five (5) second engine warm-up •
timer.
Will not transfer if utility subsequently returns.•
Will transfer to generator if utility is still not pres-•
ent.
Will transfer back to utility once utility returns •
(above 75% of nominal) for 15 seconds.
Will transfer back to utility if the generator is •
shut down for any reason (such as the switch is
in the OFF position or a shutdown alarm.
After transfer, will shut down engine after one (1) •
minute cool-down time.
3. Exercise
Will not exercise if generator is already running •
in either Auto or Manual mode.
During exercise, the controller will only transfer •
if utility fails during exercise for 10 seconds, and
will switch to Auto mode.
Section 3 — Operation
Air-cooled Generators
Do not attempt to activate the transfer switch
manually until all power voltage supplies to the
switch have been positively turned off. Failure
to turn off all power voltage supplies may result
in extremely hazardous and possibly fatal electrical shock.
4. Use the manual transfer handle inside the transfer switch to move the main contacts to their
STANDBY position, i.e., loads connected to the
standby power source (Figure 3.3).
5. To crank and start the engine, set the AUTO/OFF/
MANUAL switch to MANUAL.
6. Let the engine stabilize and warm up for a few
minutes.
7. Set the generator’s main circuit breaker to its ON
(or CLOSED) position. The standby power source
now powers the loads.
Figure 3.3 – Manual Transfer Switch Operation
3.3.4 UTILITY RESTORED
Initial Condition: Generator supplying power to
customer load. When the utility returns (above 75%
of nominal), a 15 second return to utility timer will
start. At the completion of this timer, if the utility
supply is still present and acceptable, the control
will transfer the load back to the utility and run the
engine through a one (1) minute cool down period
and then shut down. If utility fails for three (3) seconds during this cool down period, the control will
transfer load back to the generator and continue to
run while monitoring for utility to return.
3.4 MANUAL TRANSFER OPERATION
3.4.1 TRANSFER TO GENERATOR
POWER SOURCE
To start the generator and activate the transfer switch
manually, proceed as follows:
1. Set the generator’s AUTO/OFF/MANUAL switch to
OFF.
2. Set the generator’s main circuit breaker to its
OFF (or OPEN) position.
3. Turn OFF the utility power supply to the transfer
switch using the means provided (such as a utility
main line circuit breaker).
3.4.2 TRANSFER BACK TO UTILITY POWER
SOURCE
When utility power has been restored, transfer back
to that source and shut down the generator. This can
be accomplished as follows:
1. Set the generator’s main circuit breaker to its
OFF (or OPEN) position.
2. Let the engine run for a minute or two at no-load
to stabilize the internal temperatures.
3. Set the generator’s AUTO/OFF/MANUAL switch
to its OFF (or OPEN) position. The engine should
shut down.
4. Check that utility power supply to the transfer
switch is turned OFF.
19
DANGER
Section 3 — Operation
Air-cooled Generators
Do not attempt to activate the transfer switch
manually until all power voltage supplies to the
switch have been positively turned off. Failure
to turn off all power voltage supplies may result
in extremely hazardous and possibly fatal electrical shock.
5. Use the manual transfer handle inside the transfer switch to move the main contacts back to their
UTILITY position, i.e., loads connected to the utility power source (Figure 3.2).
6. Turn ON the utility power supply to the transfer
switch using the means provided.
7. Set the system to automatic operation as outlined
in Automatic Transfer Operation section.
Figure 3.4 – Side Compartment
3.5 SIDE COMPARTMENT (V-TWIN
ONLY)
Local codes may require this compartment to be
locked. A hasp is provided so the owner can secure
the compartment with their own padlock. Check
local codes in the area.
3.5.1 MAIN CIRCUIT BREAKER
This is a 2-pole breaker rated according to the
Specifications section.
3.5.2 EXTERIOR READY LIGHTS
Green LED ‘Ready’ light (10, 12, 14, 16, 17 & 20 •
KW) is on when utility is present and switch is in
AUTO indicating the generator is ready and when
the generator is running.
Red LED ‘Alarm’ light (10, 12, 14, 16, 17 & 20 •
KW) is on when the generator is OFF or a fault is
detected. (See the Protections Systems section.)
Yellow LED ‘Maintenance’ light (17 & 20 KW) (See •
the Protections Systems section.)
3.5.3 120 VAC GFCI OUTLET & 15 AMP
These models are equipped with an external, 15 amp,
120 volt, GFCI convenience outlet that is located in
a compartment on the right side of generator (Figure
1.3).
When the generator is running, in the absence of utility power, this outlet may also be used to power items
outside your home such as lights or power tools. This
outlet may also be used when utility power is present by running the generator in manual mode. This
outlet does not provide power if the generator is not
running. This outlet is protected by a 15 amp circuit
breaker in the same compartment as the outlet. (Do
not use when the generator is running in exercise
mode.)
20
(FIGURES 3.4 & 3.5)
BREAKER (17 & 20 KW ONLY)
Figure 3.5 – Open Side Compartment
120V GFCI Outlet15 Amp Outlet Breaker
Main Circuit BreakerLED Indicator Lights
3.6 PROTECTION SYSTEMS
3.6.1 ALARMS
Highest Priority (Latching) Displayed on the control panel and the external red LED (V-twins only).
They must be cleared before the alarm message goes
away. The alarm log records each occurrence (see
Appendix - "Menu System").
Low Oil Pressure (Shutdown Alarm)
A five (5) second delay on start-up and seven (7) second delay once the engine is running.
This switch (Figure 3.6) has normally closed contacts that are held open by engine oil pressure during operation. Should the oil pressure drop below
the five (5) PSI range, switch contacts close and the
engine shuts down. The unit should not be restarted
until oil level is verified.
Section 3 — Operation
Air-cooled Generators
High Engine Temperature (Shutdown Alarm –
Auto Reset)
A 10 second delay on start-up and one (1) second
delay before shutdown. Auto reset when the condition
clears and restart the engine if a valid start signal is
still present.
This switch’s contacts (Figure 3.6) close if the temperature should exceed approximately 144° C (293°
F), initiating an engine shutdown. Once the oil temperature drops to a safe level the switch’s contacts
open again.
Over Crank (Shutdown Alarm)
This occurs if the engine has not started within the
specified crank cycle. (See "Cranking" section.)
Figure 3.6 – Low Oil Pressure and
High Temperature Switches
Low Oil Switch
L
o
o
s
e
Oil Filter
Oil
Drain
Hose
NOTE:
The oil drain hose may be routed in the opposite
direction as shown in figure.
High Temp Switch
n
Over Speed (Shutdown Alarm)
4320 RPM for three (3) seconds or 4500 RPM immediately. This feature protects the generator from damage by shutting it down if it happens to run faster
than the preset limit. This protection also prevents
the generator from supplying an output that could
potentially damage appliances connected to the
generator circuit. Contact the nearest Dealer if this
failure occurs.
RPM Sense Loss (Shutdown Alarm)
During cranking, if the Control Board does not see
a valid RPM signal within three (3) seconds, it will
shut down and lock out on RPM sense loss. While
engine is running, if RPM signal is lost for one (1)
second the Control Board will shut the engine down,
wait 15 seconds, then re-crank the engine. If no RPM
signal is detected within the first three (3) seconds
of cranking, the Control Board will shut the engine
down and latch out on RPM sensor loss. If the RPM
signal is detected, the engine will start and run normally. If the RPM signal is subsequently lost again,
the Control Board will try one more re-crank attempt
before latching out and displaying the RPM sensor
failure message.
Under-frequency (Shutdown Alarm)
After starting, if the generator stays under frequency
for more than 30 seconds it will shut down. The
under-frequency setting is 50 Hz.
Internal Fault (Shutdown Alarm)
This alarm cannot be cleared, call service dealer.
CLEAR ALARM
8kW — Clear the alarm by setting the AUTO/OFF/•
MANUAL switch to the OFF position and back to
AUTO.
10 - 20kW — Clear the alarm by setting the AUTO/•
OFF/MANUAL switch to the OFF position. Press
the ENTER key to unlatch any active fault and
clear the corresponding alarm message.
3.6.2 WARNINGS
Second Priority (Non-latching) Displayed on the
control panel and the external yellow LED (V-twins
only). Warnings automatically clear when the monitored condition goes away. Warnings are recorded in
the alarm log. Warnings cannot cause shutdowns.
Low Battery
The Control Board monitors battery voltage and displays a warning if the battery voltage falls below 11.0
volts for one (1) minute. Warning is automatically
cleared if the battery voltage rises above 11.0 volts.
Battery voltage is not monitored during the crank
cycle.
Exercise Set Error
If the exercise period becomes corrupted, a warning
message will be displayed. This message will only
clear when the exercise period is reset.
21
Oil Dipstick
Oil Fill
Section 4 — Maintenance
Air-cooled Generators
3.6.3 MAINTENANCE ALERTS (10 - 20KW
ONLY)
Third priority
Maintenance Message
When a maintenance period expires, a warning message will be displayed. (16 through 20kW models
include an external yellow LED which will illuminate.)
The alert can be reset by pressing the Enter key,
which will cause the user to be prompted to confirm
the action. Resetting will clear the alert and reset the
maintenance counters for all conditions annunciated.
The history log will record the alert. The maintenance
counter will not accumulate without battery power.
Once battery power is restored, the set time prompt
will be displayed. The maintenance counters will be
adjusted to the new time and date.
NOTE:
Since most maintenance alerts will occur at the
same time (most have two (2) year intervals), only
one will appear on the display at any one time.
Once the first alert is cleared, the next active alert
will be displayed.
4. Install the dipstick.
5. Reset the AUTO/OFF/MANUAL switch to its original position.
Figure 4.1 — Oil Dipstick and Fill, 8kW
Oil Dipstick and Fill
Figure 4.2 — Oil Dipstick, 10kW
4.1 FUSE
The 7.5 amp fuse on the control panel protects the
DC control circuit against overload (Figures 3.1 and
3.2). This fuse is wired in series with the battery output lead to the panel. If this fuse element has melted
open, the engine will not be able to crank or start.
Replace this fuse using only an identical 7.5 amp
replacement fuse. Whenever the fuse is removed or
replaced, the exercise timer needs to be reset.
4.2 CHECKING THE ENGINE
OIL LEVEL
For oil capacities, see the Specifications section.
For engine oil recommendations, see the Engine Oil
Recommendations section. To check the engine oil
level, proceed as follows (Figures 4.1, 4.2 and 4.3):
1. Move the AUTO/OFF/MANUAL switch to the OFF
position.
2. Remove the dipstick and wipe it dry with a clean
cloth.
3. Completely insert the dipstick; then, remove it
again. The oil level should be at the dipstick “Full”
mark. If necessary, add oil to the “Full” mark
only. DO NOT FILL ABOVE THE “FULL” MARK.
Figure 4.3 — Oil Dipstick and Fill,
12, 14, 16, 17 & 20kW
Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing
this could damage the engine.
22
SA E 30
Sy nt he ti c 5W -3 0
10 W- 30
Section 4 — Maintenance
Air-cooled Generators
4.3 CHANGING THE ENGINE OIL
4.3.1 OIL CHANGE INTERVALS
See the "Service Schedule" section.
4.3.2 ENGINE OIL RECOMMENDATIONS
All oil should meet minimum American Petroleum
Institute (API) Service Class SJ, SL or better. Use
no special additives. Select the oil's viscosity grade
according to the expected operating temperature.
SAE 30 • Î Above 32° F
10W-30 • Î Between 40° F and -10° F
Synthetic 5W-30 • Î 10° F and below
Any attempt to crank or start the engine before
it has been properly serviced with the recommended oil may result in an engine failure.
SAE 30
10W-30
Synthetic 5W-30
4. Refill with the proper recommended oil (see the
Engine Oil Recommendations section). See the
Specifications section for oil capacities.
5. Start the engine, run for one (1) minute, and
check for leaks.
6. Shutdown and recheck oil level, add as needed.
DO NOT OVER FILL.
7. Reset the AUTO/OFF/MANUAL switch to the
AUTO position.
Figure 4.4 – Oil Drain Hose and Filter
Oil Filter
Oil
Drain
Hose
Low Oil Switch
L
o
o
s
e
n
High Temp Switch
4.3.3 OIL & OIL FILTER CHANGE PROCEDURE
To change the oil, proceed as follows:
1. Start the engine by moving the AUTO/OFF/
MANUAL switch to MANUAL and run until it
is thoroughly warmed up. Then shut OFF the
engine by moving the switch to the OFF position.
2. Immediately after the engine shuts OFF, pull the
oil drain hose (Figure 4.4) free of its retaining
clip. Remove the cap from the hose and drain the
oil into a suitable container.
3. After the oil has drained, replace the cap onto the
end of the oil drain hose. Retain the hose in the
clip.
Change the engine oil filter as follows:
1. With the oil drained, remove the old oil filter by
turning it counterclockwise.
2. Apply a light coating of clean engine oil to the gasket of the new filter. See the Specifications section
for recommended filter.
3. Screw the new filter on by hand until its gasket
lightly contacts the oil filter adapter. Then, tighten
the filter an additional 3/4 to one turn (Figure
4.4).
NOTE:
The oil drain hose may be routed in the opposite
direction as shown in figure.
4.4 CHANGING THE ENGINE
AIR CLEANER
4.4.1 12, 14, 16, 17 & 20KW GENERATORS
See "The Generator" section for the location of the air
cleaner. Use the following procedures (Figure 4.5):
1. Lift the roof and remove the door.
2. Turn the two screws counterclockwise to loosen.
3. Remove the cover and air filter.
4. Wipe away dust or debris from inside of the air
box and around edges.
5. Install the new air cleaner into the air box.
6. Install the cover. Turn the two cover screws clock-
wise to tighten.
See the Service Schedule section for air cleaner maintenance. See the Specifications section for air filter
replacement part number.
23
Section 4 — Maintenance
Air-cooled Generators
Figure 4.5 — 12, 14, 16, 17 & 20kW
Engine Air Cleaner
Screw
Cover
Filter
4.4.2 10KW GENERATORS
See "The Generator" section for the location of the air
cleaner. Use the following procedure (Figure 4.6):
1. Lift the roof and remove the door.
2. Turn the worm gear clamp screw counterclockwise to loosen.
3. Pull the old filter off the divider panel hub.
4. Wipe away dust or debris from the panel hub.
5. Install the new air cleaner onto the hub.
6. Turn the worm gear clamp screw clockwise to
tighten.
7. Replace door and roof.
4.4.3 8KW GENERATOR
See "The Generator" section to locate the air box. Use
the following procedures to replace the dirty air filter
within the air box (Figure 4.7).
1. Lift the roof and remove the door.
2. Push back on the latch of the yellow air filter
access door to swing open.
3. Pull out the old air filter and discard appropriately.
4. Install the new filter, open end first into the air
box.
5. Swing the yellow door shut and snap to close.
6. Replace door and close roof securely.
Figure 4.7 — 8kW Engine Air Cleaner Location
Air Cleaner
Cover
Figure 4.6 — 10kW Engine Air Cleaner
Air Filter
24
4.5 SPARK PLUG(S)
Reset the spark plug(s) gap or replace the spark
plug(s) as necessary. See the Service Schedule section
for maintenance requirements.
1. Clean the area around the base of the spark
plug(s) to keep dirt and debris out of the engine.
2. Remove the spark plug(s) and check the condition. Replace the spark plug(s) if worn or if reuse
is questionable. See the Service Schedule section
for recommended inspection. Clean by scraping
or washing using a wire brush and commercial
solvent. Do not blast the spark plug(s) to clean.
3. Check the spark plug gap using a wire feeler
gauge. Adjust the gap to 0.76 mm (0.030 inch)
for 8, 10 and 20kW; and 1.02 mm (0.040 inch)
for 12, 14, 16 and 17kW by carefully bending the
ground electrode (Figure 4.8).
DANGER
Section 4 — Maintenance
Air-cooled Generators
Figure 4.8 – Setting the Spark Plug Gap
SET PLUG GAP AT 0.76 mm (.030 inch) - 8, 10 &
20kW; 1.02 mm (.040 inch) - 12, 14, 16 & 17kW
4.6 BATTERY MAINTENANCE
The battery should be inspected per the "Service
Schedule" section. The following procedure should be
followed for inspection:
1. Inspect the battery posts and cables for tightness
and corrosion. Tighten and clean as necessary.
2. Check the battery fluid level of unsealed batteries
and, if necessary, fill with Distilled Water Only. Do
not use tap water in batteries.
3. Have the state of charge and condition checked.
This should be done with an automotive-type battery hydrometer.
Do not dispose of the battery in a fire. The
battery is capable of exploding.
A battery presents a risk of electrical shock
and high short circuit current. The following precautions are to be observed when working on
batteries:
• Remove the 7.5A fuse from the generator control
panel.
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the
battery; and
• Disconnect charging source prior to connecting or
disconnecting battery terminals.
Do not open or mutilate the battery. Released
electrolyte has been known to be harmful to the
skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically
conductive and corrosive. The following
procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off
immediately with water;
• Where electrolyte contacts the eyes, flush thoroughly and immediately with water and seek
medical attention; and
• Spilled electrolyte is to be washed down with an
acid neutralizing agent. A common practice is to
use a solution of 1 pound (500 grams) bicarbonate
of soda to 1 gallon (4 liters) of water. The bicarbonate of soda solution is to be added until the
evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the
area dried.
Lead-acid batteries present a risk of fire because
they generate hydrogen gas. The
following procedures are to be followed:
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from body before touching the battery by first touching a grounded metal
surface.
Be sure the AUTO/OFF/MANUAL switch is set to
the OFF position before connecting the battery
cables. If the switch is set to AUTO or MANUAL,
the generator can crank and start as soon as the
battery cables are connected.
Be sure the utility power supply is turned off
and the 7.5A fuse is removed from the generator control panel, or sparking may occur at the
battery posts as the cables are attached and
cause an explosion.
4.7 ADJUSTING GH-410/GT-530/
990/999 VALVE CLEARANCE
After the first six (6) months of operation, check
the valve clearance in the engine, adjust if necessary.
Important: If feeling uncomfortable about doing
this procedure or the proper tools are not available,
please contact the Dealer for service assistance. This
is a very important step to ensure longest life for the
engine.
To check valve clearance:
The engine should be cool before checking. If •
valve clearance is 0.002" - 0.004" (0.05 - 0.1mm),
adjustment is not needed.
Remove spark plug wires and position wires away •
from plugs.
Remove spark plugs.•
25
Section 4 — Maintenance
Air-cooled Generators
Make sure the piston is at Top Dead Center (TDC) •
of its compression stroke (both valves closed). To
get the piston at TDC, remove the intake screen at
the front of the engine to gain access to the flywheel
nut. Use a large socket and socket wrench to rotate
the nut and hence the engine in a clockwise direction. While watching the piston through the spark
plug hole. The piston should move up and down.
The piston is at TDC when it is at its highest point
of travel.
To adjust valve clearance (if necessary), (Figure
4.9):
Make sure the engine is at 60° to 80° F.•
Make sure that the spark plug wire is removed •
from the spark plug and out of the way.
Remove the four screws attaching the valve cover.•
Loosen the rocker jam nut. Use an 10mm allen •
wrench to turn the pivot ball stud while checking
clearance between the rocker arm and the valve
stem with a feeler gauge. Correct clearance is
0.002-0.004 inch (0.05-0.1 mm).
Figure 4.9 - Valve Clearance Adjustment
Rocker
Jam Nut
Pivot Ball
Stud
Arm
Valve
Stem
Install spark plugs.•
Re-attach the spark plug wire to the spark plug.•
On the GT-530 and GT-990/999, repeat the process •
for the other cylinder.
4.8 COOLING SYSTEM
Air inlet and outlet openings in the generator compartment must be open and unobstructed for continued proper operation. This includes such obstructions as high grass, weeds, brush, leaves and snow.
Without sufficient cooling and ventilating air flow, the
engine/generator quickly overheats, which causes it
to quickly shut down. (See Figure 4.10 for vent locations.)
Make sure the doors and roof are in place during operation as running the generator with them
removed can effect cooling air movement.
Figure 4.10 – Cooling Vent Locations
NOTE:
Hold the rocker arm jam nut in place as the pivot
ball stud is turned.
When valve clearance is correct, hold the pivot ball
stud in place with the allen wrench and tighten the
rocker arm jam nut. Tighten the jam nut to 174 in/
lbs. torque. After tightening the jam nut, recheck
valve clearance to make sure it did not change.
Install new valve cover gasket.•
Re-attach the valve cover.•
NOTE:
Start all four screws before tightening or it will not
be possible to get all the screws in place. Make
sure the valve cover gasket is in place.
26
The exhaust from this product gets extremely
hot and remains hot after shutdown. High grass,
weeds, brush, leaves, etc. must remain clear of
the exhaust. Such materials may ignite and burn
from the heat of the exhaust system.
The maximum ambient temperature for the gen-
erator is 25° C (77° F).
4.9 ATTENTION AFTER SUBMERSION
If the generator has been submerged in water, it must
not be started and operated. Following any submer-
sion in water, have a Dealer thoroughly clean, dry
and inspect the generator. If the structure (ex. home)
has been flooded, it should be inspected by a certified electrician to ensure there won't be any electrical
problems during generator operation or when utility
is returned.
Section 4 — Maintenance
Air-cooled Generators
4.10 CORROSION PROTECTION
Periodically wash and wax the enclosure using automotive type products. Frequent washing is recommended in salt water/coastal areas. Spray engine
linkages with a light oil such as WD-40.
4.11 OUT OF SERVICE PROCEDURE
4.11.1 REMOVAL FROM SERVICE
If the generator cannot be exercised every seven days,
and will be out of service longer than 90 days, prepare the generator for storage as follows:
1. Start the engine and let it warm up.
2. Close the fuel shutoff valve in the fuel supply line
and allow the unit to shut down.
3. Once the unit has shut down, switch to the OFF
position.
4. Set the generator’s main circuit breaker to its
OFF (or OPEN) position.
5. Set the AUTO/OFF/MANUAL switch to OFF and
turn off the utility power to the transfer switch.
Remove the 7.5A fuse from the generator control
panel. Disconnect the battery cables as outlined
in “General Hazards”.
6. While the engine is still warm from running,
drain the oil completely. Refill the crankcase with
oil. See ”Engine Oil Recommendations".
7. Attach a tag to the engine indicating the viscosity
and classification of the oil in the crankcase.
8. Remove the spark plug(s) and spray fogging
agent into the spark plug(s) threaded openings.
Reinstall and tighten the spark plug(s).
9. Remove the battery and store it in a cool, dry
room on a wooden board. Never store the battery
on any concrete or earthen floor.
10. Clean and wipe the entire generator.
4.11.2 RETURN TO SERVICE
To return the unit to service after storage, proceed
as follows:
1. Verify that utility power is turned off and that the
AUTO/OFF/MANUAL switch is set to OFF.
2. Check the tag on the engine for oil viscosity and
classification. Verify that the correct recommended oil is used in the engine (see the Engine Oil
Recommendations section). If necessary, drain
and refill with the proper oil.
3. Check the state of the battery. Fill all cells of
unsealed batteries to the proper level with distilled water. DO NOT USE TAP WATER IN THE
BATTERY. Recharge the battery to 100 percent
state of charge, or, if defective, replace the battery.
See “Specifications,” for type and size.
4. Clean and wipe the entire generator.
5. Make sure the 7.5A fuse is removed from the
generator control panel. Reconnect the battery.
Observe battery polarity. Damage may occur if the
battery is connected incorrectly.
6. Open the fuel shutoff valve.
7. Insert the 7.5A fuse into the generator control
panel. Start the unit by moving the AUTO/OFF/
MANUAL switch to MANUAL. Allow the unit to
warm up thoroughly.
8. Stop the unit by setting the AUTO/OFF/MANUAL
switch to OFF.
9. Turn on the utility power to the transfer switch.
10. Set the AUTO/OFF/MANUAL switch to AUTO.
11. The generator is now ready for service.
NOTE:
If the battery was dead or disconnected, the exercise timer (single cylinder), current date and time
(v-twin) must be reset.
4.11.3 ACCESSORIES
There are performance enhancing accessories available for the air-cooled generators.
Cold Weather Kits• are recommended in areas
where temperatures regularly fall below 10° F (-12°
C).
Scheduled Maintenance Kits• include all pieces
necessary to perform maintenance on the generator along with oil recommendations.
Auxiliary Transfer Switch Lockout• enables any
of the transfer switches to completely lock out
one large electrical load by tying into its control
system.
A Fascia Skirt Wrap• is standard on all 20kW
units. It's available for all other current production air-cooled units. It snaps together to provide a
smoothing, contoured look as well as rodent/insect
protection.
The PowerMaster• load prioritization device allows
home owners to potentially operator two (2) large
electrical loads by giving one (1) priority over the
other.
The Remote Monitor System• is a wireless, indoor
mounted, box that indicates generator run status
and allows for exercise programing as well as provide maintenance reminders.
Touch-up Paint Kits• are very important to main-
tain the look and integrity of the generator enclosure. These kits include touch-up paint and
instructions if the need should arise.
For more details on accessories, please contact a
Dealer.
27
Section 4 — Maintenance
Air-cooled Generators
4.12 SERVICE SCHEDULE
ATTENTION: It is recommended that all service work
be performed by the nearest Dealer.
SYSTEM/COMPONENTPROCEDUREFREQUENCY
X = Action
R = Replace as Necessary
InspectChangeClean
* = Notify Dealer if Repair is
Needed.
FUEL
Fuel lines and connections*
XM
LUBRICATION
Oil level
Oil
Oil filter
XM or 24 hours of
X2Y or 200 hours
X2Y or 200 hours
COOLING
Enclosure louvers
XXW
BATTERY
Remove corrosion, ensure
dryness
Clean and tighten battery
terminals
Check charge state
Electrolyte level
XXM
XXM
XREVERY 6 M
XREVERY 6 M
ENGINE AND MOUNTING
Air cleaner
Spark plug(s)
XR2Y or 200 hours
XR2Y or 200 hours
GENERAL CONDITION
Vibration, Noise, Leakage,
Temperature*
COMPLETE TUNE-UP*
* Contact the nearest dealer for assistance if necessary.
** Change oil and fi lter after fi rst eight (8) hours of operation and then every 200 hours thereafter, or 2 years, which-
ever occurs fi rst. Change sooner when operating under a heavy load or in a dusty or dirty environment or in high
ambient temperatures.
XM
TO BE COMPLETED BY A DEALER2Y or 200 hours
W = Weekly
M = Monthly
Y = Yearly
continuous operation.
of operation.**
of operation.**
28
Section 5 — Troubleshooting
Air-cooled Generators
5.1 TROUBLESHOOTING GUIDE
Problem Cause Correction
The engine will not crank. 1. Fuse blown. 1. Correct short circuit condition,
replace 7.5A fuse in generator
control panel.
2. Loose, corroded or defective 2. Tighten, clean or replace
battery cables. as necessary.
3. Defective starter contactor. (8 kW) 3. *
4. Defective starter motor. 4. *
5. Dead Battery. 5. Charge or replace battery.
The engine cranks but 1. Out of fuel. 1. Replenish fuel/Turn on fuel valve.
will not start. 2. Defective fuel solenoid (FS). 2. *
3. Open #14 wire from 3. *
engine control board.
4. Fouled spark plug(s). 4. Clean, re-gap or replace plug(s).
5. Valve lash out of adjustment. 5. Reset valve lash.
6. Choke not operating. 6. Verify choke plate moves freely.
The engine starts hard 1. Air cleaner plugged 1. Check, replace air cleaner.
and runs rough. or damaged.
2. Fouled spark plug(s). 2. Clean, re-gap or replace plug(s).
3. Fuel pressure incorrect. 3. Confirm fuel pressure to regulator
is 10-12” water column (0.36-0.43
psi) for LP, and 5-7” water column
(0.18-0.25 psi) for natural gas.
4. Fuel selector in wrong position. 4. Move selector to correct position.
The AUTO/OFF/MANUAL 1. Defective switch. 1. *
switch is set to OFF, but 2. AUTO/OFF/MANUAL switch 2. *
the engine continues wired incorrectly.
to run. 3. Defective control board. 3. *
There is no AC output 1. Main line circuit breaker is in 1. Reset circuit breaker
from the generator. the OFF (or OPEN) position. to ON (or CLOSED).
2. Generator internal failure. 2. *
There is no transfer to 1. Defective transfer switch coil. 1. *
standby after utility 2. Defective transfer relay. 2. *
source failure. 3. Transfer relay circuit open. 3. *
4. Defective control logic board. 4. *
Unit consumes large 1. Engine over filled with oil. 1. Adjust oil to proper level.
amounts of oil. 2. Improper type or viscosity of oil. 2. See "Engine Oil Recommendations".
3. Damaged gasket, seal or hose. 3. Check for oil leaks.
4. Engine breather defective. 4. *
*Contact the nearest Dealer for assistance.
29
Section 6 — Appendix
Air-cooled Generators
6.1 MENU SYSTEM NAVIGATION
To get to the MENU, use the "Esc" key from any
page. It may need to be pressed many times before
getting to the menu page. The currently selected
menu is displayed as a flashing word. Navigate to
the menu required by using the +/- keys. When the
menu required is flashing, press the ENTER key.
Depending on the menu selected, there may be a
list of choices presented. Use the same navigation
method to select the the desired screen (refer to the
Menu System diagram).
6.1.1 CHANGING SETTINGS (EDIT MENU)
To change a setting such as display contrast, go to the
EDIT menu and use the +/- keys to navigate to the
setting to change. Once this setting is displayed (e.g.
Contrast), press the ENTER key to go into the edit
mode. Use the +/- keys to change the setting, press
the ENTER key to store the new setting.
NOTE:
If the ENTER key is not pressed to save the new
setting, it will only be saved temporarily. The next
time the battery is disconnected, the setting will
revert back to the old setting.
NOTE: This Emission Control Warranty Statement pertains to this product only IF the generator size is 15 kW or below.
CALIFORNIA EMISSION CONTROL WARRANTY STATEMENT
YOUR WARRANTY RIGHTS AND OBLIGATIONS
The California Air Resources Board (CARB) and Generac Power Systems, Inc. (Generac) are pleased to explain the Emission
Control System Warranty on your new engine.* In California, new utility, and lawn and garden equipment engines must be
designed, built and equipped to meet the state’s stringent anti-smog standards. Generac will warrant the emission control
system on your engine for the periods of time listed below provided there has been no abuse, neglect, unapproved modification or improper maintenance of your engine.
Your emission control system may include parts such as the carburetor, ignition system and exhaust system. Generac will
repair your engine at no cost to you for diagnosis, replacement parts and labor, should a warrantable condition occur.
MANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE:
Emissions control systems on 1995 and later model year engines are warranted for two years as hereinafter noted. If, during such warranty period, any emission-related component or system on your engine is found to be defective in materials or
workmanship, repairs or replacement will be performed by a Generac Authorized Warranty Service Facility.
PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES:
As the engine purchaser/owner, you are responsible for the completion of all required maintenance as listed in your factory
supplied Owner’s Manual. For warranty purposes, Generac recommends that you retain all receipts covering maintenance
on your engine. However, Generac cannot deny warranty solely due to the lack of receipts or for your failure to ensure the
completion of all scheduled maintenance.
As the engine purchaser/owner, you should, however, be aware that Generac may deny any and/or all warranty coverage or
responsibility if your engine, or a part/component thereof, has failed due to abuse, neglect , improper maintenance or unapproved modifications, or the use of counterfeit and/or “grey market” parts not made, supplied or approved by Generac.
You are responsible for contacting a Generac Authorized Warranty Service Facility as soon as a problem occurs. The
warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days.
Warranty service can be arranged by contacting either your selling dealer or a Generac Authorized Warranty Service Facility.
To locate the Generac Authorized Warranty Service Facility nearest you, call our toll-free number:
1-800-333-1322
IMPORTANT NOTE: This warranty statement explains your rights and obligations under the Emission Control System
Warranty (ECS Warranty), which is provided to you by Generac pursuant to California law. See also the “Generac Limited
Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by
Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in
terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where
the Generac Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac Warranty describe
important rights and obligations with respect to your new engine.
Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty service, evidence must be presented showing the date of the sale to the original purchaser/owner.
If you have any questions regarding your warranty rights and responsibilities, you should contact Generac at one of
the following addresses:
For Air-cooled Product ... For Liquid-cooled Product ...
ATTENTION WARRANTY DEPARTMENT ATTENTION WARRANTY DEPARTMENT
GENERAC POWER SYSTEMS, INC. GENERAC POWER SYSTEMS, INC.
P.O. BOX 297 211 MURPHY DRIVE
WHITEWATER, WI 53190 EAGLE, WI 53119
Part 1
36
Section 9 – Warranty
Air-cooled Generators
EMISSION CONTROL SYSTEM WARRANTY
Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines:
(a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on the
date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall continue
for 24 consecutive months thereafter.
(b) General Emissions Warranty Coverage: Generac warrants to the original, end-use purchaser/owner of the new engine or
equipment and to each subsequent purchaser/owner that each of its engines is ...
(1) Designed, built and equipped so as to conform with all applicable regulations adopted by the CARB pursuant to its
authority, and
(2) Free from defects in materials and workmanship which, at any time during the ECS Warranty Period, may cause a
warranted emissions-related part to fail to be identical in all material respects to the part as described in the engine
manufacturer’s application for certification.
(c) The ECS Warranty only pertains to emissions-related parts on your engine, as follows:
(1) Any warranted, emissions-related parts that are not scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the ECS Warranty Period. If any such part fails during the ECS Warranty Period, it shall
be repaired or replaced by Generac according to Subsection (4) below. Any such part repaired or replaced under the
ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.
(2) Any warranted, emissions-related part that is scheduled only for regular inspection as specified in the Owner’s Manual
shall be warranted for the ECS Warranty Period. A statement in such written instructions to the effect of “repair or
replace as necessary” shall not reduce the ECS Warranty Period. Any such part repaired or replaced under the ECS
Warranty shall be warranted for the remainder of the ECS Warranty Period.
(3) Any warranted, emissions-related part that is scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the period of time prior to the first scheduled replacement point for that part. If the part
fails prior to the first scheduled replacement, the part shall be repaired or replaced by Generac according to Subsection
(4) below. Any such emissions-related part repaired or replaced under the ECS Warranty shall be warranted for the
remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions-related part.
(4) Repair or replacement of any warranted, emissions-related part under this ECS Warranty shall be performed at no
charge to the owner at a Generac Authorized Warranty Service Facility.
(5) When the engine is inspected by a Generac Authorized Warranty Service Facility, the owner shall not be held responsible
for diagnostic costs if the repair is deemed warrantable.
(6) Generac shall be liable for damages to other original engine components or approved modifications proximately caused
by a failure under warranty of any emission-related part covered by the ECS Warranty.
(7) Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted emission-related parts sufficient
to meet the expected demand for such emission-related parts.
(8) Any Generac authorized and approved emission-related replacement part may be used in the performance of any ECS
Warranty maintenance or repairs and will be provided without charge to the owner. Such use shall not reduce Generac
ECS Warranty obligations.
(9) Unapproved, add-on, modified, counterfeit and/or “grey market” parts may not be used to modify or repair a Generac
engine. Such use voids this ECS Warranty and shall be sufficient grounds for disallowing an ECS Warranty claim.
Generac shall not be held liable hereunder for failures of any warranted parts of a Generac engine caused by the use of
such an unapproved, add-on, modified, counterfeit and/or “grey market” part.
EMISSION RELATED PARTS INCLUDE THE FOLLOWING:
1) Fuel Metering System:
1.2) LPG/Natural Gas carburetion assembly and its internal components.
a) Fuel controller (if so equipped)
b) Mixer and its gaskets (if so equipped)
c) Carburetor and its gaskets (if so equipped)
d) Primary gas regulator (if so equipped)
e) LP liquid vaporizer (if so equipped)
2) Air Induction System including:
a) Intake pipe/manifold
b) Air cleaner
* Generac engine types covered by this warranty statement include the following:
1) Prepackaged Standby Generator
2) Auxiliary Power Unit (APU) Generator
3) Standby Generator
Part 2
3) Ignition System including:
a) Spark plug
b) Ignition module
4) Catalytic Muffler Assembly (if so equipped) including:
a) Muffler gasket
b) Exhaust manifold
5) Crankcase Breather Assembly including:
a) Breather connection tube
37
Part No. 0G8334Revision D (09/16/08)Printed in U.S.A.
Catalog No. OMASPCA-S-01
RTSS Load Shed Automatic Transfer Switch
TECHNICAL
MANUAL
This manual should remain with the unit.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be
followed during installation and maintenance of the generator and batteries.
SAVE THESE INSTRUCTIONS! Read the following information carefully before attempting to
install, operate or service this equipment. Also read the instructions and information on tags,
decals, and labels that may be affixed to the transfer switch. Replace any decal or label that
is no longer legible.
DANGER! Connection of a generator to an electrical system normally supplied by an electric
utility shall be by means of suitable transfer equipment so as to isolate the electric system
from utility distribution system when the generator is operating (Article 701 Legally Required
Standby Systems or Article 702 Optional Standby Systems, as applicable). Failure to isolate
electric system by these means may result in damage to generator and may result in injury
or death to utility workers due to backfeed of electrical energy.
The manufacturer cannot anticipate every possible
circumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed
to the unit are, therefore, not all-inclusive. If using
a procedure, work method or operating technique
the manufacturer does not specifically recommend,
ensure that it is safe for others. Also make sure the
procedure, work method or operating technique chosen does not render the transfer switch unsafe.
Throughout this publication, and on tags and decals
affixed to the generator, DANGER, WARNING,
CAUTION and NOTE blocks are used to alert personnel to special instructions about a particular operation that may be hazardous if performed incorrectly
or carelessly. Observe them carefully. Their definitions are as follows:
DANGER
After this heading, read instructions that, if not
strictly complied with, will result in personal injury, including without limitation, death, or property
damage.
After this heading, read instructions that, if not
strictly complied with, may result in personal injury or property damage.
After this heading, read instructions that, if not
strictly complied with, could result in damage to
equipment and/or property.
NOTE:
After this heading, read explanatory statements
that require special emphasis.
These safety warnings cannot eliminate the hazards
that they indicate. Common sense and strict compliance with the special instructions while performing
the service are essential to preventing accidents.
Four commonly used safety symbols accompany the
DANGER, WARNING and CAUTION blocks. The type
of information each indicates follows:
This symbol points out important safety infor-
mation that, if not followed, could endanger
personal safety and/or property.
This symbol points out potential explosion
hazard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock
hazard.
GENERAL HAZARDS
Any AC generator that is used for backup power if •
a NORMAL (UTILITY) power source failure occurs,
must be isolated from the NORMAL (UTILITY)
power source by means of an approved transfer
switch. Failure to properly isolate the NORMAL
and STANDBY power sources from each other may
result in injury or death to electric utility workers,
due to backfeed of electrical energy.
Improper or unauthorized installation, operation, •
service or repair of the equipment is extremely
dangerous and may result in death, serious personal injury, or damage to equipment and/or personal property.
Extremely high and dangerous power voltages are •
present inside an installed transfer switch. Any
contact with high voltage terminals, contacts or
wires will result in extremely hazardous, and possibly LETHAL, electric shock. DO NOT WORK ON
THE TRANSFER SWITCH UNTIL ALL POWER
VOLTAGE SUPPLIES TO THE SWITCH HAVE
BEEN POSITIVELY TURNED OFF.
Table of Contents
Competent, qualified personnel should install, •
operate and service this equipment. Adhere strictly
to local, state and national electrical and building
codes. When using this equipment, comply with
regulations the National Electrical Code (NEC),
CSA Standard; C22.1 Canadian Electric Code and
Occupational Safety and Health Administration
(OSHA) have established.
Never handle any kind of electrical device while •
standing in water, while barefoot, or while hands or
feet are wet. DANGEROUS ELECTRICAL SHOCK
MAY RESULT.
Jewelry conducts electricity and wearing it may •
cause dangerous electrical shock. Remove all jewelry (such as rings, watches, bracelets, etc.) before
working on this equipment.
If work must be done on this equipment while •
standing on metal or concrete, place insulative
mats over a dry wood platform. Work on this
equipment only while standing on such insulative
mats.
Never work on this equipment while physically or •
mentally fatigued.
Keep the transfer switch enclosure door closed •
and bolted at all times. Only qualified personnel
should be permitted access to the switch interior.
In case of an accident caused by electric shock, •
immediately shut down the source of electrical
power. If this is not possible, attempt to free the
victim from the live conductor but AVOID DIRECT
CONTACT WITH THE VICTIM. Use a nonconducting implement, such as a dry rope or board, to free
the victim from the live conductor. If the victim is
unconscious, apply first aid and get immediate
medical help.
When an automatic transfer switch is installed for •
a standby generator set, the generator engine may
crank and start at any time without warning. To
avoid possible injury that might be caused by such
sudden start-ups, the system’s automatic start circuit must be disabled before working on or around
the generator or transfer switch. For that purpose,
a SAFETY DISCONNECT is provided inside the
transfer switch. Always set that switch to its OFF
position before working on the equipment. Then
place a “DO NOT OPERATE” tag on the transfer
switch and on the generator. Remove the Negative
(Neg) or (–) battery cable.
Safety Rules .........................................Inside Front Cover
Section 1 — General Information ...................................2
Section 8 – Warranty ...................................... Back Cover
For authorized service, reference
the dealer locator number found
in the generator owner’s manual or
on the generator's data label.
1
Section 1 — General Information
RTSS Type Transfer Switch
1.1 INTRODUCTION
This manual has been prepared especially for the
purpose of familiarizing personnel with the design,
application, installation, operation and servicing of
the applicable equipment. Read the manual carefully
and comply with all instructions. This will help to
prevent accidents or damage to equipment that might
otherwise be caused by carelessness, incorrect application, or improper procedures.
Every effort has been expended to make sure that the
contents of this manual are both accurate and current. The manufacturer, however, reserves the right
to change, alter or otherwise improve the product at
any time without prior notice.
1.2 EQUIPMENT DESCRIPTION
The PowerManager™ LTS transfer switch will provide
three major functions.
The first function is to provide an automatic
transfer switch. The automatic transfer switch
is used for transferring electrical loads from a
UTILITY (NORMAL) power source to a GENERATOR
(STANDBY) power source. Such a transfer of electrical loads occurs automatically when (connected to a
Generac engine generator) the UTILITY power source
has failed or is at a substantially reduced voltage and
the GENERATOR source voltage and frequency have
reached an acceptable level. The transfer switch prevents electrical feedback between two different power
sources (such as the UTILITY and GENERATOR
sources) and, for that reason, codes require it in all
standby electrical system installations.
The second function is to provide a means to divide
up the electrical loads on the electrical system. The
electrical loads are to be divided into “critical loads”
and non-essential loads. The “critical” loads are connected to the internal 16 circuit panel board. The
non-essential electrical loads are to be powered from
the load shed switch (LSS).
The UTILITY source will supply all electrical loads
at all times. When the transfer signal is given by
the engine generator controller, all loads, both critical and non-essential loads, are connected to the
GENERATOR supply. If the generator is overloaded
the LSS will operate and disconnect the non-essential
loads which results in a reduction in the load on the
generator.
The third function is a 16 circuit load center to
connect the “critical loads” to. These loads will be
normally powered by the UTILITY source and will be
backed up by the GENERATOR source. The Siemens
load center is provided with the following Siemens
type QP circuit breakers; 1-50A 2-pole, 1-40A 2-pole,
1-20A 2-pole, 5-20A single pole and 5-15A 2-pole
circuit breakers.
2
The PowerManager LTS transfer switch is suitable
for use as SERVICE ENTRANCE EQUIPMENT –
UTILITY (NORMAL) source only. The PowerManager
LTS is only SERVICE ENTRANCE rated for the USA.
The 200A 2-pole circuit breaker provided is the “service disconnect” and is labeled as such. An additional
disconnect must be readily available for the alternate
source, unless the alternate source is an accessible
generator and can be shutdown.
1.2.1 TRANSFER SWITCH MECHANISM
These switches (Figure 1.1) are used with a singlephase system, when the single-phase NEUTRAL line
is to be connected to a Neutral Lug and is not to be
switched.
Solderless, screw-type terminal lugs are standard.
Switch
Rating
200A#6-250 MCM275 in-lbs.
This transfer switch is suitable for control of motors,
electric discharge lamps, tungsten filament and electric heating equipment where the sum of motor full
load ampere ratings and the ampere ratings of other
loads do not exceed the ampere rating of the switch
and the tungsten load does not exceed 30 percent of
the switch rating.
Figure 1.1 — Typical ATS Transfer Mechanism
UTILITY
CLOSING
COIL
GENERATOR
CLOSING
COIL
This transfer switch is for use in optional standby
systems only (NEC® Article 702).
This transfer switch is suitable for use on a circuit
capable of 22,000 rms symmetrical amperes, 240
VAC maximum.
Wire
Range
UTILITY LUGS
LOAD LUGS (T1 & T2)
Conductor Tightening
Torque
GENERATOR
LUGS (E1 & E2)
Section 1 — General Information
RTSS Type Transfer Switch
1.2.2 UTILITY SERVICE DISCONNECT CIRCUIT
BREAKER
The utility service disconnect circuit breaker for the
200 amp models are:
(Line), 275 in-lbs. (Non-essential Load and
Generator Terminals)
1.2.3 LOAD SHED CONTROLLER
The primary function of the Load Shed Controller
(LSC) is to determine when there is excess load on
the generator and has the ability to disconnect the
non-essential loads connected to it. Excess load
is determined by monitoring the generator supply
frequency, if the frequency drops below 58 Hz for
more than three (3) seconds, or below 50 Hz for
1/2 second, and the generator is considered to have
excess load on it. When this happens, non-essential
customer loads are disconnected. The non-essential
loads are supplied via the load shed switch (LSS) and
the LSS is actuated to disconnect these loads.
The non-essential loads are reconnected in one of 3
ways; Utility voltage is restored and ATS transfers all
load back to the Utility supply, manual operation of
LOAD SHED RESET push-button on the outside of
the enclosure or, automatic operation setup on the
DIP switches on the LSC.
For manual operation, set DIP switch #6 to the ON
position. If the generator output is overloaded and
the non-essential loads are disconnected, press the
LOAD SHED RESET push-button to reconnect the
non-essential loads to the generator. If the overload
condition still exists the LSC will turn the non-essential loads off.
For automatic operation, the number of attempts to
reconnect the non-essential loads can be selected.
The 2 choices are one-shot or repeated. The time
interval before each attempt is set on DIP switches
1-4. For “one-shot” operation mode set DIP switch
#5 to ON. Reconnection of the non-essential loads
will occur one time, after the time set on DIP switches
1-4. If DIP switch #5 is OFF, the LSC will attempt to
reconnect the non-essential loads after the time interval set on DIP switches 1-4. If the overload still exists
or comes back, the LSC and LSS will disconnect
non-essential loads and the timer and the attempt to
reconnect non-essential loads will be repeated.
DIP switch
number
1Selects a 5 minute reconnection
time
2Selects a 15 minute reconnection
time
3Selects a 30 minute reconnection
time
4Selects a 60 minute reconnection
time
1-4 all OFFSelects a 1 minute reconnection
time
5Selects one-shot mode
6Selects manual reconnect only
7Selects 50 Hz units
8Not used
Function
1.2.4 BATTERY CHARGER
The POWER MANAGER LTS transfer switch is provided with a battery charger (item #44 on Generac
#0G8054 assembly drawing) for charging of the
engine generator 12 Vdc battery. The battery charger
is powered from the load side of the transfer switch
(line to neutral – 120V) and is protected by a 2A fuse
on the LSC pcb. The battery charger will charge the
battery at all times.
1.3 TRANSFER SWITCH DATA DECAL
A DATA DECAL is permanently affixed to the transfer
switch enclosure. Use this transfer switch only with
the specific limits shown on the DATA DECAL and
on other decals and labels that may be affixed to the
switch. This will prevent damage to equipment and
property.
When requesting information or ordering parts for this
equipment, make sure to include all information from
the DATA DECAL.
Record the Model and Serial numbers in the space
provided below for future reference.
MODEL #
SERIAL #
1.4 TRANSFER SWITCH ENCLOSURE
The standard switch enclosure is a National Electrical
Manufacturer’s Association (NEMA) 3R, UL listed.
NEMA 3R type enclosures primarily provide a degree
of protection against falling rain and sleet and is
undamaged by the formation of ice on the enclosure.
3
Section 2 — Installation
RTSS Type Transfer Switch
1.5 SAFE USE OF TRANSFER SWITCH
Before installing, operating or servicing this equipment, read the SAFETY RULES (inside front cover)
carefully. Comply strictly with all SAFETY RULES to
prevent accidents and/or damage to the equipment.
The manufacturer recommends that a copy of the
SAFETY RULES are posted near the transfer switch.
Also, be sure to read all instructions and information
found on tags, labels and decals affixed to the equipment.
Three publications that outline the safe use of transfer switches are the following:
NFPA 70; National Electrical Code•
NFPA 70E; Standard for Electrical Safety in the •
Workplace
UL 1008, STANDARD FOR SAFETY-AUTOMATIC •
TRANSFER SWITCHES
NOTE:
It is essential to use the latest version of any standard to ensure correct and current information.
2.1 INTRODUCTION TO INSTALLATION
This equipment has been wired and tested at the
factory. Installing the switch includes the following
procedures:
Mounting the enclosure.•
Connecting power source and load leads.•
Connecting non-essential loads.•
Connecting "Critical Load" branch circuits to the •
internal load center.
Connecting the utility sensing and transfer relay •
circuits to the generator control panel.
Connecting any auxiliary contact (if needed)•
Testing functions.•
2.2 UNPACKING
Carefully unpack the transfer switch. Inspect closely
for any damage that might have occurred during
shipment. The purchaser must file with the carrier
any claims for loss or damage incurred while in transit.
Check that all packing material is completely removed
from the switch prior to installation.
2.3 MOUNTING
Mounting dimensions for the transfer switch enclosure are in this manual. Enclosures are typically
wall-mounted. See “Installation Diagram”.
Handle transfer switches carefully when install-
ing. Do not drop the switch. Protect the switch
against impact at all times, and against construction grit and metal chips. Never install a transfer
switch that has been damaged.
This transfer switch is mounted in a NEMA 3R aluminum enclosure. It can be mounted outside or inside
and should be based on the layout of installation,
convenience and proximity to the utility supply and
load center.
Install the transfer switch as close as possible to the
electrical loads that are to be connected to it. Mount
the switch vertically to a rigid supporting structure.
To prevent switch distortion, level all mounting
points. If necessary, use washers behind mounting
holes to level the unit.
2.4 CONNECTING POWER SOURCE
AND LOAD LINES
DANGER
Make sure to turn OFF both the UTILITY
(NORMAL) and GENERATOR (STANDBY) power
supplies before trying to connect power source
and load lines to the transfer switch. Supply
voltages are extremely high and dangerous.
Contact with such high voltage power supply lines causes extremely hazardous, possibly
lethal, electrical shock.
Wiring diagrams and electrical schematics are provided in this manual.
NOTE:
All installations must comply with national, state
and local codes. It is the responsibility of the
installer to perform an installation that will pass
the final electrical inspection.
Conductor sizes must be adequate to handle the maximum current to which they will be subjected, based
on the 75°C column of tables, charts, etc. used to size
conductors. The installation must comply fully with
all applicable codes, standards and regulations.
4
Section 3 — Operation
RTSS Type Transfer Switch
Before connecting wiring cables to terminals, remove
any surface oxides from the cable ends with a wire
brush. All power cables must enter the enclosure
through the knockouts provided. This is necessary
to maintain the NEMA/UL type 3 rating. If mounted
indoors, conduits can enter the enclosure above the
knockouts. If not using the knockouts, entry must be
at or below knockouts.
If ALUMINUM conductors are used, apply corrosion inhibitor to conductors. Tighten terminal lugs
to the torque values as noted on the "Utility Service
Disconnect Circuit Breaker", and on the decal located
on the inside of the door. After tightening terminal
lugs, carefully wipe away any excess corrosion inhibitor.
Use a torque wrench to tighten the conductors,
being sure not to overtighten, or damage to
the insulating base could occur. If not tightened
enough, a loose connection would result, causing excess heat which could damage the switch
base.
Connect power source load conductors to clearly
marked transfer mechanism terminal lugs as follows
1. Connect UTILITY (NORMAL) power source cables
to the top of the UTILITY SERVICE DISCONNECT
circuit breaker.
2. Connect GENERATOR (STANDBY) source power
cables to ATS GENERATOR supply terminals,
E1-E2.
4. Connect critical customer loads to the circuit
breakers on the load center provided.
Conductors must be properly supported, of approved
insulative qualities, protected by approved conduit,
and of the correct wire gauge size in accordance with
applicable codes.
Be sure to maintain proper electrical clearance
between live metal parts and grounded metal. Allow
at least 1/2 inch for 100-400 amp circuits.
2.5 NEUTRAL CONNECTIONS
The main neutral block is provided for the connection of the neutral (ungrounded conductors) of the
Utility, Generator and non-essential load neutrals.
Tighten all wires to the specified torque. Torque values are given on the information decal located on the
inside cover.
The main neutral block is connected (bonded) to the
enclosure metal by a busbar. If bonding of the neutral
is not necessary, the jumper can be removed. When
the jumper bar is removed the control wires should
be connected as follows:
#00 wire to the neutral block.•
GRD wire to the enclosure.•
The essential load neutrals are to be connected on
the busbars mounted on the load center, next to the
branch circuit breakers.
2.6 CONNECTING CONTROL WIRES
Control system interconnections consist of N1 and
N2, and leads 0, 15B and 23. Control system interconnection leads can be run in the same conduit as
the AC power lead if the conduit length is less than
35 feet, and ALL of the wiring is rated for 600V.
If the conduit length between the generator and
PowerManager LTS is more than 35 feet, the control
and power leads must be routed in separate conduits. Recommended wire gauge sizes for this wiring
depends on the length of the wire, as recommended
in the following chart:
MAXIMUM WIRE
RUN LENGTH
35 feet (10.67m)No. 16 AWG.
60 feet (18.29m)No. 14 AWG.
90 feet (27.43m)No. 12 AWG.
RECOMMENDED WIRE
SIZE
3.1 FUNCTIONAL TESTS AND
ADJUSTMENTS
Following transfer switch installation and interconnection, inspect the entire installation carefully. A competent, qualified electrician should
inspect it. The installation should comply strictly
with all applicable codes, standards, and regulations. When absolutely certain the installation is
proper and correct, complete a functional test of
the system.
Perform functional tests in the exact order pre-
sented in this manual, or damage could be done
to the switch.
IMPORTANT: Before proceeding with functional tests,
read and make sure all instructions and information
in this section are understood. Also read the information and instructions of labels and decals affixed
to the switch. Note any options or accessories that
might be installed and review their operation.
5
Section 3 — Operation
RTSS Type Transfer Switch
3.2 MANUAL OPERATION
DANGER
Do NOT manually transfer under load.
Disconnect transfer switch from all power sources by approved means, such as the main circuit
breaker(s).
3.2.1 ATS MANUAL OPERATION
A manual HANDLE is shipped with the transfer
switch. Manual operation must be checked BEFORE
the transfer switch is operated electrically. To check
manual operation, proceed as follows (Figure 3.1):
1. Turn the generator’s AUTO/OFF/MANUAL switch
to OFF.
2. Turn OFF UTILITY SERVICE DISCONNECT circuit breaker.
3. Note position of transfer mechanism main contacts by observing the moveable contact carrier
arm. This can be viewed through the long narrow
slot in the inside cover of the ATS. The top of the
moveable contact carrier arm is yellow to be easily identified.
Manual operation handle in the UP position - •
LOAD terminals (T1, T2) are connected to UTILITY terminals (N1, N2).
Manual operation handle in the DOWN posi-•
tion - LOAD terminals (T1, T2) are connected to
EMERGENCY terminals (E1, E2).
3.2.2 LSS MANUAL OPERATION
A manual HANDLE is shipped with the transfer
switch. Manual operation must be checked BEFORE
the LSS is operated electrically. To check manual
operation, proceed as follows (Figure 3.2):
1. Turn the generator’s AUTO/OFF/MANUAL switch
to OFF.
2. Turn OFF UTILITY SERVICE DISCONNECT circuit breaker.
3. Note position of non-essential LSS main contacts
by observing the moveable contact carrier arm.
This can be viewed through the long narrow slot
in the inside cover of the ATS. The top of the
moveable contact carrier arm is yellow to be easily identified.
Manual operation handle in the UP position - •
non-essential loads OFF.
Manual operation handle in the DOWN position - •
non-essential loads ON.
Do not use excessive force when operating the
transfer switch manually or damage could be
done to the manual handle.
Attach handle to the moveable
contact carrier arm.
NOTE: Return handle to storage position in enclosure when finished with manual transfer.
Figure 3.1 — Actuating ATS Transfer Switch
Move handle UP for the
UTILITY (NORMAL) position.
Move handle DOWN for the
GENERATOR (STANDBY) position.
6
Attach handle to the moveable
contact carrier arm.
Section 3 — Operation
RTSS Type Transfer Switch
Figure 3.2 — Actuating LSS Transfer Switch
Move handle UP for the
non-essential loads OFF.
Move handle DOWN for the
non-essential loads ON.
NOTE: Return handle to storage position in enclosure when finished with manual transfer.
3.2.3 CLOSE TO UTILITY SOURCE SIDE
Before proceeding, verify the position of the switch by
observing the position of manual operation handle in
Figure 3.1. If the handle is UP, the contacts are closed
in the UTILITY (NORMAL) position, no further action
is required. If the handle is DOWN, proceed with Step
1.
Step 1: With the handle inserted into the moveable
contact carrier arm, move handle UP. Be
sure to hold on to the handle as it will move
quickly after the center of travel.
Step 2: Remove manual operating handle from move-
able contact carrier arm. Return handle to
storage bracket.
3.2.4 CLOSE TO GENERATOR SOURCE SIDE
Before proceeding, verify the position of the switch
by observing the position of the manual operation
handle in Figure 3.1. If the handle is DOWN, the
contacts are closed in the GENERATOR (STANDBY)
position. No further action is required. If the handle
is UP, proceed with Step 1.
Step 1: With the handle inserted into the moveable
contact carrier arm, move the handle DOWN.
Be sure to hold on to the handle as it will
move quickly after the center of travel.
Step 2: Remove manual operating handle from move-
able contact carrier arm. Return handle to
storage bracket.
3.2.5 RETURN TO UTILITY SOURCE SIDE
Step 1: Manually actuate switch to return manual
operating handle to the UP position.
Step 2: Remove manual operating handle from move-
able contact carrier arm. Return handle to
storage bracket.
3.3 VOLTAGE CHECKS
1. Turn ON the UTILITY power supply to the
PowerManager LTS using the UTILITY SERVICE
DISCONNECT circuit breaker.
DANGER
PROCEED WITH CAUTION. THE TRANSFER SWITCH
IS NOW ELECTRICALLY HOT. CONTACT WITH LIVE
TERMINALS RESULTS IN EXTREMELY HAZARDOUS
AND POSSIBLY FATAL ELECTRICAL SHOCK.
2. With an accurate AC voltmeter, check for correct
voltage. Measure across ATS terminal lugs N1
and N2. Also check N1 to NEUTRAL and N2 to
NEUTRAL.
3. When certain that UTILITY supply voltage is correct
and compatible with transfer switch ratings, turn
OFF the UTILITY supply to the transfer switch.
4. On the generator panel, set the AUTO/OFF/
MANUAL switch to MANUAL position. The generator should crank and start.
5. Let the generator stabilize and warm up at noload for at least five minutes.
6. Set the generator's main circuit breaker (CB1) to
its ON or CLOSED position.
DANGER
PROCEED WITH CAUTION. GENERATOR
OUTPUT VOLTAGE IS NOW BEING DELIVERED
TO TRANSFER SWITCH TERMINALS. CONTACT
WITH LIVE TERMINALS RESULTS IN EXTREMELY
DANGEROUS AND POSSIBLY FATAL ELECTRICAL
SHOCK.
7. With an accurate AC voltmeter and frequency
meter, check the no-load, voltage and frequency.
Measure across ATS terminal lugs E1 to E2. Also
check E1 to NEUTRAL and E2 to NEUTRAL.
a. Frequency ........................................60-62 Hertz
b. Terminals E1 to E2..........................240-246 VAC
c. Terminals E1 to NEUTRAL ..............120-123 VAC
d. Terminals E2 to NEUTRAL ..............120-123 VAC
8. Set the generator’s main circuit breaker (CB1) to
its OFF or OPEN position.
9. Set the AUTO/OFF/MANUAL switch to the OFF
position to shut down the generator.
NOTE:
Do NOT proceed until generator AC output voltage and frequency are correct and within stated
limits. If the no-load voltage is correct but no-load
frequency is incorrect, the engine governed speed
may require adjustment. If no-load frequency is
correct but voltage is not, the voltage regulator
may require adjustment.
3.4 GENERATOR TESTS UNDER LOAD
3.4.1 ATS & CRITICAL LOADS
1. Set the generator's main circuit breaker to its
OFF or OPEN position.
2. Set the UTILITY SERVICE DISCONNECT circuit
breaker to the OFF position.
3. Manually actuate the transfer switch main contacts to their GENERATOR (STANDBY) position.
Refer to "Manual Operation".
4. Manually actuate the LSS main contacts to the UP
position. Non-essential loads OFF.
5. To start the generator, set the AUTO/OFF/ MANUAL
switch to MANUAL. When engine starts, let it stabilize for a few minutes.
6. Turn the generator's main circuit breaker to its
ON or CLOSED position. The generator now powers all LOAD circuits. Check generator operation
under load as follows:
Turn ON electrical loads to the full rated watt-•
age/amperage capacity of the generator. DO NOT
OVERLOAD.
With maximum rated load applied, check volt-•
age and frequency across transfer switch terminals E1 and E2. Voltage should be greater than
230VAC and frequency should be greater than 59
Hertz.
Let the generator run under rated load for at •
least 30 minutes. With unit running, listen for
unusual noises, vibration, overheating, etc., that
might indicate a problem.
7. When checkout under load is complete, set main
circuit breaker of the generator to its OFF or
OPEN position.
8. Let the generator run at no-load for several minutes. Then, shut down by setting the AUTO/OFF/
MANUAL switch to its OFF position.
9. Move the switch's main contacts back to their
UTILITY position. For example, LOAD connected
to UTILITY power supply. Refer to "Manual
Operation". Handle and operating lever of transfer switch should be in UP position.
10. Turn on the UTILITY power supply to transfer
switch, using the UTILITY SERVICE DISCONNECT
circuit breaker. The utility power source now
powers the loads.
11. Set the generator's AUTO/OFF/MANUAL switch to
its AUTO position.
8
Section 3 — Operation
RTSS Type Transfer Switch
3.4.2 LOAD SHED FUNCTIONAL TEST
1. Set the generator’s main circuit breaker to its
OFF or OPEN position.
2. Set the UTILITY SERVICE DISCONNECT circuit
breaker to the OFF position.
3. Manually actuate the transfer switch main contacts to the GENERATOR position. Refer to
“Manual Operation” section of this manual.
4. Manually actuate the LSS main contacts to the
DOWN position. Non-essential loads ON.
5. To start the generator, set the AUTO/OFF/MANUAL
switch to MANUAL. When engine starts, let it stabilize for a few minutes.
6. Turn the generator’s main circuit breaker its ON
position. The generator now powers all LOAD
circuits. Check generator operation under load as
follows:
Turn ON electrical loads to the full rated wattage/•
amperage capacity of the generator.
Increase the load to slightly overload the genera-•
tor (load to draw frequency down 55-56 hz). This
will require turning loads on that are connected
to the LSS. Do not severely overload the generator.
The LSS should actuate after three (3) seconds •
to disconnect the non-essential loads. The door
mounted LOAD SHED LED should be ON.
Decrease the electrical load on the generator to •
allow the generator frequency to increase to 60
Hz.
7. The next step will depend on how the LSC is set
up (see the "Load Shed Controller" section). If set
up for:
Manual Operation• — Press the door mounted
LOAD SHED RESET button. The LSS will reconnect non-essential loads.
Automatic Operation• — The LSS will reconnect
non-essential loads after the delay time setup on
the DIP switches of the LSC.
8. Turn ON the UTILITY power supply to the
transfer switch using the UTILITY SERVICE
DISCONNECT circuit breaker. After the return
to utility time delay, the utility power source will
power the loads.
9. Set the generator's AUTO/OFF/MANUAL switch to
the AUTO position.
9
Section 4 — Installation Diagrams
RTSS Type Transfer Switch
Load Shed Interconnection - Drawing No. 0G8774-B
KEYPD
69 0C6748 2 NUT HEX LOCK M4-0.7 SS NYL INS
70 0F4460 2 SPACER M4/#8 X 5/16 X 1/4 NYL
71 0G8412 1 CABLE, KEYPAD INTERFACE
72 0G8534 1 NEUTRAL WIRE
73 0G7925 1 ASSY PCB 2008HSB LOAD
SHEDCTRL
74 027911 2 RELAY SOC 12VDC DPDT
10A@240VA
75 0D6511 4 SPACER .20 X .375 X .375 PL
76 0E6423 4 NUT HEX FL WHIZ M5-0.8
77 0G8293 1 16 CIR L/CENTR 200A/240V SIEMS
78 0E7888 1 CB 0020A 2P PLUG IN
79 0E7888B 5 CB 0015A 1P PLUG IN
80 0E7888C 5 CB 0020A 1P PLUG IN
81 0E7888D 1 CB 0040A 2P PLUG IN
82 0E7888E 1 CB 0050A 2P PLUG IN
83 0E6034 1 STRAIGHT SPADE CONNECTOR
84 0F6685 3 TIE-WRAP MOUNT(FIR TREE
SYTLE)
19
Section 7 — Notes
20
Section 7 — Notes
21
Part No. 0G8637 Revision D (08/27/08) Catalog No. KGALT-1SI Printed in U.S.A.
INSTALLATION GUIDE
For 100 Amp Automatic Transfer Switch/Load Center Models:
8, 10, 12, 14 and 16 Circuit.
Installed with 8, 10, 12, 14, 16, 17 and 20kW Generators.
This Automatic Transfer Switch with built-in
Load Center includes an Express Install Kit.
C
US
• Saves on installation time and cost, in many
cases up to 50% compared to traditional
transfer switch installations.
• Automatically supplies electricity to
selected critical circuits.
LISTED
• Can be installed prior to, or along with
generator installation.
This manual should remain with the unit.
Residential Transfer Switch Installation Guide
PLEASE NOTE:
This installation guide should be used in conjunction with the “Installation and Owner’s Manual”
that is furnished with the Air-cooled Standby Generator. Please review both manuals prior to installation of the
generator and transfer switch. This Automatic Transfer Switch/Load Center is not intended for use with the
Liquid-cooled Generator product line. This unit is not compatible with other generator manufacturer’s products.
INTRODUCTION
Thank you for purchasing this 100 Amp Automatic Transfer
Switch/Load Center with Express Install Kit. The Express Install
Kit includes:
• 30 foot, five foot, and two foot pre-wired conduits for making
all required wiring runs.
• An outdoor junction box for making connections between
outdoor and indoor pre-wired conduits.
• UL listed wire nuts for reconnecting emergency circuits
within the main distribution panel.
The 100 Amp Automatic Transfer Switch/Load Center with
Express Install Kit can be installed along with a 8, 10, 12, 14, 16
or 17kW Air-cooled Standby Generator, or can be used to prewire a home or small business in advance of generator installation. In either case, the Express Install Kit saves installation
time and cost, since the majority of labor involved in installing
a standby power system is in wiring the generator, automatic
transfer switch and emergency circuit subpanel.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each
indicates follows:
This symbol points out important safety information
that, if not followed, could endanger personal safety
and/or property.
This symbol points out potential explosion hazard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock
hazard.
SAVE THESE INSTRUCTIONS – The manufacturer
suggests that these rules for safe operation be copied and posted near the unit’s installation site. Safety
should be stressed to all operators and potential
operators of this equipment.
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warnings in this
manual, and on tags and decals affixed to the unit are therefore,
not all-inclusive. If using a procedure, work method or operating
technique the manufacturer does not specifically recommend,
ensure that it is safe for all personnel. Also make sure the procedure, work method or operating technique chosen does not
render the equipment unsafe.
DANGER
After this heading, read instructions that, if not strictly
complied with, will result in serious personal injury,
including death, and/or severe property damage.
After this heading, read instructions that, if not strictly
complied with, may result in serious personal injury
and/or property damage.
After this heading, read instructions that, if not strictly
complied with, could result in damage to equipment
and/or property.
NOTE:
After this heading, read explanatory statements that
require special emphasis.
ELECTRICAL HAZARDS
• Utility power delivers extremely high and dangerous voltages
to the transfer switch as does the standby generator when it
is in operation.
• Do not handle any kind of electrical device while standing
in water, while barefoot, or while hands or feet are wet.
DANGEROUS ELECTRICAL SHOCK MAY RESULT.
• In case of accident caused by electric shock, immediately
shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor.
AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting implement, such as a rope or board, to free the
victim from the live conductor. If the victim is unconscious,
apply first aid and get immediate medical help.
• Never wear jewelry when working on this equipment. Jewelry
can conduct electricity resulting in electric shock, or may get
caught in moving components causing injury.
1
Residential Transfer Switch Installation Guide
100 Amp Automatic Transfer
Switch/Load Center with
Express Install Kit
KIT INCLUDES:
THE OUTDOOR CONNECTION BOX WITH FIVE FOOT
A
PRE-WIRED LIQUID TIGHT CONDUIT
B
Mounted outside the home or business nearest the
planned generator location. This is for connection to generator controls and main line circuit breaker.
30 FOOT FLEXIBLE CONDUIT
C
Pre-wired from the automatic transfer switch with built-in
emergency load center for connection to the outdoor connection box.
PRE-WIRED AUTOMATIC TRANSFER SWITCH AND
D
EMERGENCY LOAD CENTER
E
Installed within one (1) foot of the building’s main distribu-
tion panel. This transfer switch provides smooth and safe
transition between utility and generator power.
Designed with installation
cost savings in mind!
A
C
B
D
F
ITEMS TO BE PURCHASED OR SUPPLIED FOR
COMPLETE INSTALLATION:
E
TWO FOOT PRE-WIRED CONDUIT FOR EASY
F
CONNECTION TO THE BUILDING’S MAIN
DISTRIBUTION PANEL
UL LISTED WIRE NUTS (not shown)
G
TOOLS REQUIRED:
Drill, drill bits, hole saw (type and length will be determined by the materials to be drilled and cut), open-end
wrenches or adjustable wrenches, socket wrenches or nut
drivers, standard and Phillips screwdrivers, sledge hammer, level, pencil, channel-lock pliers, spade shovel, rake
and safety goggles.
; 70 amp or 40 amp (7kW) double pole circuit breaker (must
be the same type as in the main electrical distribution
panel)
; Ground rod with grounding strap (for generator
installation)
; Padlock to lock outdoor connection box
; Crushed stone or pea gravel (approximately 10-12 cubic
feet) (for generator installation)
; Black poly-film or other vegetation blocking fabric (for
generator installation)
; Silicone caulk
; Fasteners (to mount outdoor connection box and
automatic transfer switch)
; Battery - 12V automotive type, group 26R, negative
ground, 350 CCA (8kW), 525 CCA (10, 12, 14, 16, 17 and
20kW) minimum capacity (required as part of generator
installation).
2
Site Preparation and Standby Generator Placement
1
2
3
Residential Transfer Switch Installation Guide
5
Crushed Stone or Pea Gravel
4
1. PLAN THE LOCATION OF THE GENERATOR.
NOTE:
Do not place the generator directly under a window.
Select an area outside of the home or business nearest
the incoming gas service. Determine where the generator will be placed outside of the building. Arrange for fuel
piping with shut-off valve to be run to this location. Keep
in mind that the manufacturer recommends placement no
closer than 18 inches to any structure. Local codes may dictate placement farther from a structure. If facing the
unit from the front, the generator's fuel inlet is located at
the rear lower right of the unit.
2. Clear an area 62 inches by 50 inches of grass and vegeta-
tion to a depth of five inches. This includes the distance the
generator should be set away from a structure (18 inches)
and six inches beyond the width and length of the generator
mounting pad (49" L x 25" W).
3. Lay black poly-film to cover the area.
Drill Hole Through House
6
1-3/4”
Diameter Hole
7. While adhering to all local electrical codes, route the 30
foot conduit along ceiling/floor joists and wall studs to the
location where the conduit will pass through the wall to the
exterior of the building.
Drill Pass Through Hole
7
4. Fill the area to ground level with pea gravel or crushed
stone.
5. Drive an eight foot grounding rod into the ground to grade.
Make sure grounding rod and strap are not exposed above
ground level. (NEC code applies to grounding method.)
6. Determine where the flexible conduit will pass through
the building from inside to outside. When certain there is
clearance on each side of the wall, drill a small pilot hole
through the wall to mark the location. Drill a 1-3/4” diameter
hole through the sheathing and siding with hole saw.
1-3/4”
Diameter Hole
3
Residential Transfer Switch Installation Guide
8. From inside the building, feed the end of the 30-foot
conduit (INCLUDED and pre-wired from transfer switch)
through the wall to the outside.
Feed Conduit and Wires
8
Silicone
Caulk
The outer diameter of the conduit
connector is 1-11/16”
9. Remove the threaded lock nut from the conduit coupling.
The outer diameter of the threaded
end is 15/16 inches.
The outdoor connection box must be locked to
ensure safety and to discourage tampering.
11. Locate automatic transfer switch with built-in emergency
load center in close proximity to the main distribution
panel. The transfer switch can be located to the left or
right of the main distribution panel. Two (2) feet is the
suggested distance (see Figure 11). The transfer switch
may be located a different distance from the main panel
depending on available mounting area. Using the two
(2) foot conduit connected straight across to the main
panel is another option. Always adhere to local electrical
codes during installation. Hold transfer switch against
the mounting surface. Level the transfer switch and mark
the mounting holes. Drill the appropriate size pilot holes.
Mount transfer switch with built-in load center to mounting
surface with appropriate fasteners.
9
Threaded Lock Nut
10. Lift cover. Remove internal
cover plate screw and internal
cover. Remove the knock out
in the lower right corner of the
external connection box. From
the rear of the connection box,
feed wires, 4-pin and 2-pin plugs
into box. Slip the lock nut over
wires and plugs and tighten
securely onto conduit coupling.
10
Using appropriate fasteners,
mount external connection box
over pre-drilled hole to fully conceal the hole. Seal around the hole and conduit with silicone
caulk from both the inside and outside of the building. Also,
caulk around the sides and top of the box to seal the edges
to the siding or wall. Connect wires to lugs; black to black,
white to white, and red to red. Torque nuts to 20 in/lbs. Snap
together the 4-pin and 2-pin plug connector. Loosen nut from
grounding lug and attach ground wire (green) from conduit.
Reinstall nut and tighten to 45 in/lbs. Reinstall internal cover
plate and screw. Close cover and install lock. This wiring is
complete.
4
Mounting Automatic Transfer Switch
11
Two (2)
Feet
Suggested
Distance
The manufacturer recommends that a licensed elec-
trician or an individual with complete knowledge of
electricity perform the procedures in Sections 12 and
13.
Switch service main circuit breaker to the
OFF (OPEN) position prior to removal of
cover or removal of any wiring of the main
electrical distribution panel. The wires connected to the service main circuit breaker
remain LIVE or HOT. Avoid contact with these wires and
the service main circuit breaker connection lugs.
OFF
Residential Transfer Switch Installation Guide
NOTE:
Balance must be maintained when moving circuit locations from main electrical distribution panel to emergency
load center. Circuit breaker positions alternate buss bars
vertically. Circuits sharing a neutral wire should either be
moved together to adjacent positions in emergency load
center or not moved. If unsure of the proper procedure or
if the installation differs from that described in this guide,
consult a licensed professional at this time.
12a. Remove the main electrical distribution panel cover.
Remove appropriate size knockout from the bottom or
side of the main panel. (A two foot flexible conduit is prewired from the transfer switch with built-in load center).
Remove threaded lock nut from conduit coupling. Feed all
wires through knockout into main panel. Slip lock nut over
wires and tighten securely onto conduit coupling.
Connection of Emergency Circuits
12a
Models
Circuits 50A, 240V---11
40A, 240V--111
30A, 240V111--
20A, 240V-1-11
20A, 120V13345
15A, 120V53545
Connection of Emergency Circuits
12b
UL approved wire nuts are included with installation kit.
8
Circuit
10
Circuit
12
Circuit
14
Circuit
Circuit
16
NOTE:
Circuits to be moved must be protected by same size
breaker. For example, a 15 amp 120 volt circuit in emergency load center will replace a 15 amp 120 volt circuit in
main electrical distribution panel.
12b. In the main panel, remove the black (hot) wire from the
circuit breaker that protects a circuit to be powered in
the event of a power failure. Wire nut the black wire to
the matching circuit lead wire from the emergency circuit
breaker in the load center in the transfer switch. (All circuit
wires are color coded and labeled for easy identification).
UL listed wire locknuts are included in installation kit.
Trace each black (hot) wire connected and wire nut the
white (neutral) wire from the same Romex cable (circuit)
to the matching circuit number on the white (neutral) wire
from the emergency load center. Repeat for each circuit.
Repeat this process with the remaining circuits to be
powered by the generator.
NOTE:
Both grounded and ungrounded conductors must be
moved to the emergency panel and connected to the new
wiring from the emergency panel using supplied wire
nuts.
13. Install the 70 amp double pole circuit breaker; 10, 12,
14, 16, 17 and 20kW units or the 40 amp double pole
breaker; 8kW units (purchased or supplied separately),
into main electrical distribution panel. This circuit breaker
must be compatible with the main electrical distribution panel. It may be necessary to reposition remaining
circuit breakers or remove circuit breakers that have been
disconnected to accommodate the insertion of the 70
amp or 40 amp double pole circuit breaker. Connect white
wire to the main distribution panel neutral bar. Connect
solid green wire to main electrical panel ground bar.
Connect the black and red wires to the 70 amp or 40 amp
double pole circuit breaker. Reinstall the main distribution
panel cover.
Install 70 Amp Circuit Breaker
13
70
70
5
Residential Transfer Switch Installation Guide
THE AUTOMATIC TRANSFER SWITCH/LOAD CENTER IS NOW INSTALLED!
If a generator is being installed at this time, proceed
to step 19. If a generator will not be installed at this
time, perform steps 14 through 17 to complete the
pre-wiring project.
14. Open the outdoor connection box and unplug the 4-pin
and 2-pin connector. Remove the black, white, red, and
green wires that lead from the five foot pre-wired conduit.
Make sure the mating wires from the 30 foot conduit are
on the connection box terminal lugs (or ground screw),
re-install all washers and nuts and secure them in place.
15. Remove the lock nut holding the five foot pre-wired conduit coupling to the outdoor connection box. Slip the lock
nut over the wires and plug, then remove the conduit from
the connection box. Use a knockout plug to close off the
opening where the conduit was removed.
The external connection box must be locked to
ensure safety and to discourage tampering.
16. For pre-existing buildings, switch the service main circuit
breaker back on to provide utility power to the building.
17. Save the five foot pre-wired conduit for re-installation at
time of generator installation. At that time, re-install the
conduit by reversing steps 14 and 15. The grounding
strap will also be installed with the generator. Save this
guide for reference at time of generator installation.
DANGER
Be sure the service main circuit breaker is switched
OFF at time of generator installation.
18. Place the generator and mounting pad in the location
prepared in steps one through five.
18
19. Attach one end of the grounding strap (No. 12 AWG
stranded copper wire) to grounding rod, and the other
end to the grounding lug (located at rear corner of unit).
Make sure the grounding rod and strap are not exposed
above ground level (NEC code applies to grounding
method).
NOTE:
The generator mode switch should be placed in the OFF
position. Generator main line circuit breaker should be
switched to the OFF or OPEN position.
20. Access wiring connections for installation of five foot har-
ness at the generator. To gain access to wiring connections and the circuit breaker you must remove the cover
plate (black) over the control module. Remove the two
screws retaining the cover plate. Lift the cover plate up
and towards the front of the generator to remove.
Connect Five Foot Conduit to Generator
20
19
This completes the pre-wiring portion of the 100 Amp
Automatic Transfer Switch/Load Center Installation.
Proceed with step 18 for generator installation.
6
Residential Transfer Switch Installation Guide
Remove the small black cap (covering 1-1/16” diameter
hole) from back of enclosure. Remove threaded lock
nut from conduit coupling (with 90° elbow) and wires.
Feed wires into 1-1/16” diameter hole. Place threaded
lock nut over wires and onto conduit coupling. Tighten
securely with screwdriver and hammer to ensure lock nut
is tight. Connect power leads (red & black) to the circuit
breaker lugs. Connect the neutral wire (white) to terminal
connection (NEUTRAL). Connect ground wire (green) to
grounding bolt with star washer below all ground wire
lugs. Tighten securely ensuring the star washer makes
good contact with metal base plate. Connect sensing
wires to terminal strip as follows: Blue - N1, Yellow - N2,
Brown - 23 and Orange - 194.
FUEL HOOKUP AND CHECK FOR LEAKS
21a.Make the connection between the rigid fuel piping and the
generator using the supplied threaded flexible fuel line.
Use a pipe sealant suitable for gaseous fuel connections.
Check connections for leaks by opening manual fuel shutoff valve and swab, or spray, connections with soapy water.
If a leak exists, the area will bubble with the presence of the
soapy water.
21b. If a leak is located, shut off fuel and disconnect flexible
piping. Dry the threaded ends and reapply an adequate
amount of pipe sealant. Reconnect flexible fuel line,
open fuel supply and recheck for leaks. If leak still
exists, repeat step 21b.
22. Follow all generator installation and setup instructions
in the Installation and Owner’s Manual provided with the
generator. During testing performed in Section 2 of the
generator Installation and Owner’s Manual, utility power
supply to the Automatic Transfer Switch/Load Center
can be controlled using the 40 or 70 amp feeder circuit
breaker located in the main distribution panel.
Part No. 0G8571 Revision D (07/31/08) Catalog No. KGATX100-1SI Printed in U.S.A.
P/N 0G6419
Installation Instructions
GenReady Load Center EZ Transfer™ Operator
Model #005447-0
DANGER
Hazardous voltage that will cause
This instruction sheet outlines the general installation procedure. It is not intended to cover all details or variations in
equipment nor does it provide for every
possible contingency to be met in connection with installation. If unsure of the
correct procedure, have any questions,
or need assistance, contact a qualified
electrical contractor.
This device should be installed in accordance with all local electrical codes
and/or the latest edition of the National
Electrical Code®.
death, serious injury or substantial property damage. Turn off
power supplying this equipment
before working inside.
STEP 1:
Remove the six (6) screws that hold the
trim (front cover) on. Remove the trim
from the front of the panel board.
NOTE: The GenReady Panel is designed to be directly compatible with any
Generac manufactured product. Use of
another manufacturer’s generator may
require the purchase and installation of
additional sensing and control components.
Revision D (04/17/08) Printed in U.S.A
STEP 2:
a. Open outer trim door exposing the
upper pan (dead front).
b. Remove all twist-outs covered by
existing labels.
c. Apply one of the ATS Danger decals
to the load center as shown in the
following figure.
2a.
2c.
STEP 4:
a. Add additional 125 Amp, 2-pole
switch on right. Place in OFF position. Before lowering switch on stabs
install interlock bar under the existing switch handle and the new switch
handle as shown.
2b.
STEP 3:
Remove the RED retaining clip by
unscrewing the fastener in the center of
clip and discard.
b. Push both switches into the bus
stabs.
STEP 5:
a. Position operator under the hold
down bracket. Locate operator and
switch tie bracket around the two 125
Amp switches.
b. Install the two (2) screws (M3 x 6mm
PPHMS) to mount the switch tie
bracket to the operator mechanism.
2
5a.
5b.
STEP 7:
Install the 15 Amp 2-pole circuit breaker
in the position shown.
STEP 8:
Install generator control wiring (must be
installed in conduit). Install 5A fuse (if
required) to the terminal strip in generator and connect the control wire from the
generator.
STEP 6:
Install the four (4) screws (10-32 x 5/16
HHTT) to mount operating mechanism
to the back of the panel board.
Refer to the wiring diagram (P/N
0G4744) for further details. 2007 and
earlier generator models – refer to
0G4744 page 1, for generator models
introduced in 2008 and later- refer to
0G4744 page 2.
3
STEP 9:
Apply one of the ATS Danger decals to
the load center as shown.
Danger
Decal
STEP 10:
Place the front cover on the panel board.
Install the six (6) screws to hold the front
cover on.
STEP 11:
Apply decal 0G4742A on the left side,
and decal 0G4732B on right side of the
EZ Transfer™ operator box as shown.
4
REFERENCE: Items supplied in the EZ Transfer™ operator kit.
5
6
7
Part Number 0G6419 Revision D (04/17/08) Printed in U.S.A
® The National Electrical Code is a registered trademark of the National Fire Protection Association.
Air-cooled Generator
Battery Charger
Installation Guidelines
Table of Contents
Table of Contents ................................Inside Front Cover
Section 1 — General Information ............................... IFC
This battery charger supplies a trickle charging current and voltage to maintain the charge on the generator starting battery inside the generator enclosure.
The charger will not replenish a fully discharged battery. It is intended to be connected to a 120VAC generator backed-up circuit only. If it is not connected
to a generator backed-up circuit the battery could go
“dead” while the generator is running for extended
periods of time.
Figure 1.1 — Charger as Supplied Indicating
Input and Output Wiring
DC OutputAC Input
This battery charger must be properly installed
and wired for correct operation of all 2008
model line Air-cooled Standby Generators.
Failure to do so will result in a dead battery
condition at the generator.
For authorized service, reference
the dealer locator number found
in the generator owner’s manual
or on the generator.
NOTE:
This installation guide should be used in conjunction with the “Installation and Owner’s Manual”
that is furnished with the Air-cooled Standby
Generator and the Installation and appropriate
transfer switch manual. Please review all manuals
prior to installation of the generator and transfer
switch. This battery charger is not required with
the Liquid-cooled Generator product line. This
battery charger is not required for Air-cooled
Standby Generators prior to the 2008 model line.
This unit is not compatible with other generator
manufacturer’s products.
Section 1 — General Information
Battery Charger Installation Guidelines
These Installation Guidelines are designed to familiarize personnel with the installation process for the
battery charger required for the air-cooled generator
only. It does not replace or supersede any information
contained in any of the written documents shipped
with the unit. This booklet should only be used in
conjunction with the Owner’s Manual, Installation
Guide and other technical documents shipped with
the unit.
Future product updates and/or modifications will be
reflected in the written documentation included with
the equipment. Always read all accompanying documentation carefully before attempting to install any
generator, transfer switch or related equipment.
NOTE:
It is essential to comply with all regulations established by the Occupational Safety and Health
Administration (OSHA) and strict adherence to all
local, state and national codes is mandatory.
This device should be installed with all local
electrical codes and/or the latest edition of the
National Electrical Code. All wiring must be the
correct size and type, and must conform to local
codes, standards, and regulations.
1.2 BATTERY CHARGER
COMPATIBILITY
This battery charger is compatible, and required with
all 2008 model line Air-cooled Standby Generators.
For all generators that were supplied with a transfer
switch/load center, the charger is already installed in
the transfer switch enclosure and this charger is not
needed. For all generators that were NOT supplied
with a transfer switch/load center, the charger is NOT
already installed and MUST be installed according to
these guidelines.
1.2.1 DETERMINATION OF GENERATOR/
TRANSFER SWITCH MODEL TYPE
The Battery charger included with this manual only
needs to be used with certain transfer switch configurations. Some transfer switch configurations already
have the battery charger installed in the transfer
switch. Before proceeding it is necessary to select the
transfer switch used from the following table.
Switch TypeSwitch DescriptionNotesProceed to Section
RTSD
RTSF
ST100R10C
RTSH
RTSP
ST100R14C
RTSW
ST100R16C
KGATX0216100
RTSS
KGALT0101200
SR200RDPM
RTSN
SRXXXR
KGATX
RTSE
SRXXXRD
KGATD
005448-0
005449-0
KGATD0101RSP
NOTE: Switch Type is the first four (4) digits of the model number and can be found on the data label inside the switch.
Pre-wire with 8 circuit load
center
Pre-wire with 10 circuit
load center
Pre-wire with 12 circuit
load center
Pre-wire with 14 circuit
load center
Pre-wire with 16 circuit
load center
Power Manager LTS - Load
Shed with 16 circuit load
center
Standard
Service Entrance Rated
GenReady
Battery charger is included and pre-wired with
the transfer switch. Discard this charger. No
further installation is required
Battery charger is included and pre-wired with
the transfer switch. Discard this charger. No
further installation is required
Battery charger is included and pre-wired with
the transfer switch. Discard this charger. No
further installation is required
Battery charger is included and pre-wired with
the transfer switch. Discard this charger. No
further installation is required
Battery charger is included and pre-wired with
the transfer switch. Discard this charger. No
further installation is required
Battery charger is included with the transfer
switch. Proceed with connections.
The included battery charger must be installed
and connected
The included battery charger must be installed
and connected
The included battery charger must be installed
and connected
Stop Here
Stop Here
Stop Here
Stop Here
Stop Here
2
3
3
4
1
Section 2 — Load Shed Transfer Switch Installation
Battery Charger Installation Guidelines
2.1 LOAD SHED TRANSFER SWITCH
(RTSS) INSTALLATION
2.1.1 WIRING AND CONNECTIONS AT THE
TRANSFER SWITCH
Connect the 15B, 0, and 23 low voltage control wires
to the load shed controller connector J5 per the wiring diagram. Wires should be sized according to the
following table.
The charger is already mounted in the transfer
switch (Figure 2.1).
NOTE:
See RTSS Installation/Wiring Diagram in the
"Interconnection Diagrams" section for connections.
Figure 2.1 — Wiring Connections at the Transfer
Switch
Recommended Wire
Size (stranded copper)
Connections
2.1.2 WIRING AND CONNECTIONS AT THE
GENERATOR
1. Crimp spade lugs onto all three low voltage wires,
15B, 0, and 23 (Purchased or supplied separately).
2. Connect the low voltage wires, 15B, 0, and 23 to
the terminal strip on the controller (Figure 2.2).
Figure 2.2 — Connection of Charger DC Output
Wires in Generator Control Panel
2.1.3 OPERATIONAL TESTING
1. If already connected, disconnect the battery in
the generator. Remove the negative cable first followed by the positive cable. Take care not to short
the cables together.
2. Ensure power is applied to the battery charger
input.
3. Connect a volt meter across the battery leads.
The voltage reading should be between 12.8 VDC
and 13.8 VDC (Figure 2.3).
Charger
2
Figure 2.3 — Measurement of Charger Output
with Battery Disconnected
Section 3 — Standard or Service Entrance Transfer Switch Installation
Battery Charger Installation Guidelines
4. If the voltage is within range installation of the
battery charger is complete. If the voltage is not
within range verify all wiring and sizing and
retest.
5. Re-connect the battery cables. Positive cable first
followed by the negative cable.
3.1 STANDARD TRANSFER SWITCH
(RTSN) OR (RTSE) SERVICE
ENTRANCE RATED TRANSFER
SWITCH INSTALLATION
3.1.1 WIRING AND CONNECTIONS AT THE
TRANSFER SWITCH
Choose the appropriate option.
NOTE:
See the appropriate RTSN or RTSE Installation/
Wiring Diagram in the "Interconnection Diagrams"
section for connections.
Option 1 — Protected Load Provided in Load
Center
1. Install a 15A breaker in the load center (Purchased
or supplied separately). The breaker must be on
a generator backed-up circuit or the battery in
the generator will not maintain its charge during
extended run periods.
2. Run the 120VAC hot wire and neutral wires to the
generator.
NOTE:
See the appropriate RTSN or RTSE Installation/
Wiring Diagram in the "Interconnection Diagrams"
section for connections.
3. Run the other side of the fuse holder (120VAC
Hot) along with the neutral from the neutral lug
to the generator (see Figures 3.1 and 3.5).
NOTE:
See the appropriate RTSN or RTSE Installation/
Wiring Diagram for connections.
Figure 3.1 — RTSN Fuse Block Installation and
Neutral Connection
Figure 3.2 — RTSN Fuse Block Installation T1
Connection
Option 2 — Protected Load Provided in the RTS,
Fuse Block Installation
NOTE:
This section is only appropriate for 2008 RTSN or
RTSE transfer switches.
1. Mount the optional 5amp 600V fuse and holder
in the transfer switch. (Purchased or supplied
separately). Pre-2008 transfer switches will not
have holes pre-drilled for the fuse holder. In this
case, it is necessary to drill holes in the enclosure
to mount the fuse holder (see Figures 3.1 and
3.4).
2. Connect one side of the fuse to terminal (T1) of
the transfer switch using a spade lug. Pre-2008
transfer switches will not have the spade lug
attached to terminal T1. The spade terminal is
available separately if required (see Figures 3.2
and 3.4).
3
Section 3 — Standard or Service Entrance Transfer Switch Installation
Battery Charger Installation Guidelines
Figure 3.3 — RTSN Fuse Block Installation When
Completed
Figure 3.4 — RTSE Fuse Block Installation T1
Connection
Figure 3.6 — RTSE Fuse Block Installation When
Completed
Figure 3.5 — RTSE Neutral Connection
4
3.1.2 CHARGER MOUNTING
1. Remove the cover over the controller in the generator
2. The battery charger can be located anywhere
within the controls area on the generator. It is
convenient to mount the charger on the vertical surface on right-hand side of the controller
(Figure 3.7).
3. Clean the surface where the charger is to be
mounted prior to mounting with a damp cloth
and wait for the area to dry.
4. Remove the adhesive covering on the backside
of the charger and firmly press the charger into
place as shown. Once mounted the charger may
be removed for inspection by separating the hook
& loop mounting (Figure 3.8).
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.