SAFETY CONSIDERATIONS
Failure to follow this warning could result in personal injury or death. Before beginning any
modification or installation of this kit, ensure the main electrical disconnect is in the OFF position.
Ensure power is disconnected to the fan coil unit. On some systems both the fan coil and the
outdoor unit may be on the same disconnect. Tag the disconnect switch with a suitable warning
label. There may be more than one to disconnect.
CAUTION
INSTALLATION
Only the distributor or authorized professionals should install the unit. Installation by unskilled
persons may lead to improper installation, electric shock, or fire. Re-installation must be
performed by authorized professionals. Non-compliance may lead to electric shock or fire.
CAUTION
Read these instructions thoroughly and follow all warnings or cautions included in the
literature and attached to the wired controller. Consult local building codes and National
Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety-alert symbol . When you see this symbol
on the wired controller and in instructions or manuals, be alert to the potential for personal
injury. Understand these signal words: DANGER, WARNING, and CAUTION. These
words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in severe personal injury or
death. WARNING signifies hazards which could result in personal injury or death.
CAUTION is used to identify unsafe practices which may result in minor personal injury or
product and property damage. NOTE is used to highlight suggestions which will result in
enhanced installation, reliability, or operation.
IM-KSACN0 6(7 )01 -01 Specifications subject to change without notice. 3
NOTES: Save this manual for future reference.
• This manual provides a detailed description of the precautions that the user should be
mindful of during operation. Keep this manual, after reading it, for future reference.
• To ensure correct service of the wired controller, read this manual carefully.
NOTES:
• Do not install the wired controller in a location vulnerable to flammable gas leaks. A fire
may occur if there is a gas leak around the controller.
• Do not operate with wet hands or allow water to enter the wired controller, otherwise an
electric shock may occur.
• The wiring should be a compatible connection cable for the current wired controller.
Otherwise, electric leakage or heating may occur and result in a fire.
• Use the specified cables for wiring. Do not allow any external force to be applied to the
connection wire terminals. Use this wiring to ensure there is no mechanical damage.
Ensure the wire insulation is rated for the temperature it will sustain during operation.
Failure to use this wire could result in a fire.
4 Specifications subject to change without notice. IM-KSACN06(7)01-01
COMPATIBILITY
Table 1 — Compatibility
Indoor Unit TypeIndoor Model NumberKSACN0601AAAKSACN0701AAA
HIGH WALL
CASSETTE
DUCTED
CONSOLE
AIR HANDLER
○Optional
●Standard
40MPHA○
619PHA○
DHMPHA○
DLFPHA○
40MAQ○†
619P*B○†
DHMSHA○
DLFSHA
40MHH○
DLFEHA○
40MBQB*C○
40MBCQ○
DLFSCA○
DLFLCA○
40MBQB*D○
40MBDQ●
DLFSDA●
DLFLDA●
40MBQB*F
40MBFQ○ 9 - 12‡○ 18 - 58
DLFSFA○ 12○ 18 - 24
DLFLFA○
40MBAA●
DLFSAA●
DLFLAA●
NOTES:
•+ 7 Day programmable compatible with indoor units
starting with Serial Number 0216V10001
Not Compatible
•‡ Compatible with indoor units starting with Serial
Number 0117V10001
•Units built prior to these serial numbers require a
Control Board Replacement on the indoor unit.
IM-KSACN0 6(7 )01 -01 Specifications subject to change without notice. 5
PREPARATION BEFORE INSTALLATION
1. Confirm the following required parts have been supplied.
Table 2 — Parts
NO.NAMEQTY.REMARKS
1Wired controller1
2Installation and owner's manual1
3Screws3M4X20 (for mounting on the wall)
4Wall plugs3For mounting on the wall
5Screws2M4X25 (for mounting on the switch box)
6Plastic screw bars2For fixing on the switch box
7Battery1CR2032 3 VDC
8Connection Extension Cable119 feet (6 meters)
9Adapter Board1Required for High Wall 40MAQ/619P*B/DHMPHA
10Display Board1Required for High Wall 40MAQ/619P*B/DHMPHA
11EMC Ferrite core (magnetic ring)1
NOTES:
Extension wire available through RCD (Replacement Components)
- Part Number:17401204000769.
2. Prepare the following assemblies on site.
Table 3 — Assemblies
No.Name
1Switch box1
2
Wiring tube
(insulating sleeve and
tightening screw)
(Embedded into Wall)
wrap the wires between the indoor unit and the wired remote
controller after installation and around the Ferrite core twice.
QTY.
1
Specification
(Only for Reference)
Only
Only
Remarks
6 Specifications subject to change without notice. IM-KSACN06(7)01-01
WIRED CONTROLLER INSTALLATION PRECAUTION
0.75 (19mm)
3.3in (84mm)
1.8in (46mm)
4.7in. (120mm)
1. This manual provides the wired controller installation method. Refer to the wiring diagram (see Fig. 7
— on page 11) for guidance on wiring the wired controller to the indoor unit.
2. The wired controller works in a low voltage circuit (5-12 VDC). DO NOT connect directly to any line
voltage. Wiring clearance between the configured tubes should range 11.81-19.69 inches (30-50 cm)
or above.
3. The shielded wire of the wired controller must be properly grounded.
NOTE: Upon completion of the wired controller connection, do not use any device to test
the insulation.