GasPoint
H2S, CO, NH3, HCN, NO2, SO2, O2, Cl2
Combustibles (Catalytic 0-100% LEL) or
Combustibles (IR 0-100% LEL)
Gas Transmitter with Internal Alarm Relays
One Transmitter
with interchangeable
electrochemical, infrared
and catalytic plug-in sensors
FEATURES:
The GasPoint transmitter provides a 4-20 mA output signal that can be
connected to any control system (DCS, PLC, etc.). With advanced sensor
technology and microcontroller based operation, the GasPoint provides
continuous monitoring of hazardous gases.
The GasPoint transmitter can accept any GasPoint sensor type:
electrochemical, catalytic or IR (infrared). All plug-in sensor assemblies
are fi eld-interchangeable.
Full function sensor integrity test (auto) continuously advises gas
sensing ability and life ended
Non-intrusive, one-person calibration with auto zero and
auto span
Equipped with three 5-amp relay contacts—two gas alarm relays
(low/high) and fault alarm. Field-selectable normally energized/
de-energized and latching/non-latching alarm relay functions.
Two backlit alphanumeric LCDs advise all environmental and gas
hazard conditions as well as instrument and sensor status
Remote toxic/oxygen sensors can be installed over 3,900 ft./ 1,100 m
away; combustible sensors over 1,550 ft./475 m.
Kit can be installed at any time.
Alarm setpoints displayed on demand—simply press the
external button
Field programmable alarm levels
Backlight (auto) in low light conditions and alarm
Extensive fault diagnostics
2-way digital communication using MODBUS module
n
Fixed Gas Monitoring Systems
Ordering Information
GP-WD Gas Transmitter with Combustible Catalytic Sensor
GP-IR-WD Gas Transmitter with Combustible Infrared Sensor
GP-HD Gas Transmitter with H2S Sensor
GP-MD Gas Transmitter with CO Sensor
GP-AD Gas Transmitter with NH3 Sensor
GP-ZD Gas Transmitter with HCN Sensor
GP-DD Gas Transmitter with NO
GP-SD Gas Transmitter with SO
GP-XD Gas Transmitter with O
GP-CD Gas Transmitter with Cl
Accessories and Spares
GP-POWER1 120-240 VAC Power Supply
GP-MBUS4 2-wire/4-wire MODBUS Communication Expansion Module
GP-SEP Sensor Separation Kit
GP-1 Gas Transmitter
GP-SSPB Stainless Steel Process Baffl e
GP-SSCAL4 Stainless Steel GasPoint Splash Guard
GP-DUC-K1 Duct Mount Adaptor
Replacement Sensor Assemblies
SS-RH02.....H
SS-RZ02.....HCN SS-RD02.....NO2 SS-RC02.....Cl
SS-RS02.....SO2 SS-RX02.....O
SS-RW02....Combustible Catalytic Sensor Assembly
IR-RW03.....Combustible IR Sensor Assembly
S SS-RM02.....CO SS-RA02.....NH
2
Sensor
2
2
2
Sensor
2
Sensor
2
Sensor
3
2
www.gasmonitors.com
e-mail: info@gasmonitors.com

GasPoint
LEL, H2S, CO, NH3, HCN,
NO
, SO
2
4-20 mA Gas Transmitter
Display advises:
Gas type monitored
Continuous (%LEL, %v/v or ppm)
readout of gas concentration
Alarm level and type encountered
- LOW/HIGH or FAULT
When sensor has failed its
automatic daily self-test
“Sensor Replacement” and
“Sensor Expired” indications
When to apply gas during
calibration
Special Features
Change gases monitored in the fi eld
at any time. The GasPoint Transmitter
will recognize the sensor installed
and test and reset itself to that sensor
type.
No junction box connection required.
Daily sensor integrity test (auto)
monitors sensor operation, length
of time sensor has been in service
and advises when sensor requires
replacement.
GasPoint allows you to set or change
calibration time and gas alarm
setpoints in the fi eld.
Select or modify the measuring range
using a simple dipswitch.
The optional plug-in MODBUS
expansion module provides an
addressable communications
interface (1-247).
2, Cl2
or O
SPECIFICATIONS
MONITOR: 3-wire, 4-20 mA gas transmitter with advanced microcontroller-based circuitry
Power Input: 12 to 32 volts DC
Output Current: Normal Operation: Isolated linear 4-20 mA output
2
Calibration Mode: Steady 3 mA (auto reset to normal operation)
Fault Mode: 2 mA signal (and less)
Power Consumption: Toxic Versions: 40 mA at 24 VDC
Combustible Version: 100 mA at 24 VDC
Relays: 50 mA per relay at 24 VDC
S
Detection Type: Combustible gases: catalytic or IR; Toxic gases and Oxygen: electrochemical
Self-Test:: Automatic daily self-test of sensor integrity and sensor life
Relative Humidity: 5 to 95% RH non-condensing
Drift: Zero: <5% per year; Span: <10% per year
Gas Monitoring
Specifi cations
Combustibles - Catalytic 1% 1 -40 to +90°C / -40 to +194°F %LEL 0-100*
Combustibles - Infrared 1% 1 -40 to +70°C / -40 to +150°F %LEL 0-100*
*Factory default setting
**Note: Cl
CALIBRATION: Non-intrusive, via pushbutton
Auto zero and auto span
D
LCD 1 3-digit continuous readout of the gas present (ppm, % LEL or %v/v)
LCD 2 Alphanumeric diagnostic status display
Alarm Setpoints: Two setpoints: user-selectable
R
LOW/HIGH: Field selectable for normally energized/de-energized and latching/
non-latching
FAULT: Normally energized and non-latching
T
CONTROLS: Calibration: Non-intrusive via external pushbuttonM
Alarm Setpoints: Simple up/down pushbuttons with LCD readout of setpoints
P
Weight: 4.85 lb. / 2.2 kg (approx.)
Transmitter: Nema 4, explosion-proof, anodized aluminum enclosure with mounting fl anges
Sensor: Stainless steel enclosure
W
RATINGS AND CERTIFICATIONS:
not rated for Class I, Div. 1
2
RANSMISSION RANGES: Relay contacts not considered. (For ranges with relays see manual.)
DUE TO ONGOING RESEARCH AND PRODUCT IMPROVEMENT, SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
ENSORS: Plug-in, smart sensors
Detectable
Accuracy
H
S 0.25 ppm 1 -40 to +50°C / -40 to +122°F ppm 0-20, 0-50, 0-100*, 0-500
2
CO 1 ppm 1 -20 to +50°C / -4 to +122°F ppm 0-50, 0-100, 0-500*, 0-1,000
NH
1 ppm 1 -10 to +50°C / +14 to +122°F ppm 0-50*, 0-100, 0-500, 0-1,000
3
HCN 0.1 ppm 0.1 -20 to +50°C / -4 to +122°F ppm 0-20.0*, 0-50.0, 0-100
NO20.1 ppm 0.1 -20 to +50°C / -4 to +122°F ppm 0-50.0*, 0-10.0, 0-20.0, 0-99.9
1 ppm 1 -20 to +50°C / -4 to +122°F ppm 0-100*, 0-50, 0-20, 0-10
SO
2
O
0.1% 0.1 -20 to +50°C / -4 to +122°F %v/v 0-30.0%*
2
Cl2** 0.1 ppm 0.1 -20 to +50°C / -4 to +122°F ppm 0-5.0*, 0-10.0, 0-100.0
ISPLAYS: Two backlit liquid crystal displays
ELAY CONTACTS: Three SPDT relays; 5 amps at 250 VAC
HYSICAL: Size: 6.8 x 7 x 4.3 inches / 17 x 17.8 x 10.8 cm (approx.)
ARRANTY: Instrument: 2 years non-prorated; Sensor: 2 years full replacement warranty
LCD
Increment
Conductor Size Toxic / Oxygen Sensors Combustible Sensors
22 AWG 0.64 mm 6,712 ft. 2,045 m 3,356 ft 1,022 m
20 AWG 0.75 mm 10,953 ft. 3,253 m 5,336 ft. 1,626 m
18 AWG 1.0 mm 16,953 ft. 5,167 m 8,476 ft. 2,583 m
Temperature Range Units Programmed Measuring Ranges
n Class I, Div. 1, Groups B, C, D (LEL and IR models)
Class I, Div. 1, Groups B, C, D; Class II, Div. 1, Groups E, F, G (toxic models only)
Explosion-proof: ANSI/ISA: UL 1203; CSA: C22.2 No 30
Combustible Performance Standards: ANSI/ISA: ISA-S12.13; CSA: C22.2 No 152
For further information:
1-888-749-8878 USA
1-800-663-4164 Canada
+44 (0)1295 700 300 Europe
+33 (0) 442 98 17 70 France
+971-4-8871766 Middle East
+61-3-9464-2770 Australia
+86 10 6786 7305 China
+65 6748 4915 South East Asia
+1-403-248-9226 Other Countries
Corporate Headquarters
2840 - 2 Avenue S.E.
Calgary, AB, Canada T2A 7X9
Phone: 1-403-248-9226
Fax: 1-403-273-3708
e-mail: info@gasmonitors.com
www.gasmonitors.com
BW1021-01-01-00-8.25x11-20070612-5124-7
© 2007 Honeywell International Ltd. All Rights Reserved.
3
Locally distributed by:
1 Large, backlit LCD readout
of gas concentration
2 Alphanumeric LCD
1
showing transmitter
STATUS and diagnostics
3 Non-intrusive calibration
via simple pushbutton
2
4 Interchangeable sensor
types: LEL (catalytic
or IR), toxic gas or
oxygen with common
transmitter assembly
5 Three relays: two
4
gas alarm relays,
one fault relay