BW Technologies GasAlert Extreme O2, GasAlert Extreme PH3, GasAlert Extreme CO, GasAlert Extreme H2S, GasAlert Extreme SO2 User Manual

...
Limited Warranty and Limitation Liability
BW Technologies LP (BW) warrants the product to be free from defects in material and workmanship under normal use and service for a period of two years, beginning on the date of shipment to the buyer. This warranty extends only to the sale of new and unused products to the original buyer. BW’s warranty obligation is limited, at BW’s option, to refund of the purchase price, repair or replacement of a defective product that is returned to a BW authorized service center within the warranty period. In no event shall BW’s liability hereunder exceed the purchase price actually paid by the buyer for the Product. This warranty does not include:
a) fuses, disposable batteries or the routine replacement of parts due to the normal wear and teat of the product arising from use; b) any product which in BW’s opinion, has been misused, altered, neglected or damaged, by accident or abnormal conditions of operation, handling or use; c) any damage or defects attributable to repair of the product by any person other than an authorized dealer, or the installation of unapproved parts on the product; or
The obligations set forth in this warranty are conditional on:
a) property storage, installation, calibration, use, maintenance and compliance with the product manual instructions and any other applicable recommendations of BW; b) the buyer promptly notifying BW of any defect and, if required, promptly making the product available for correction. No goods shall be returned to BW until receipt by the buyer of
shipping instructions from BW; and
c) the right of BW to require that the buyer provide proof of purchase such as the original invoice, bill of sale or packing slip to establish that the product is within the warranty period.
THE BUYER AGREES THAT THIS WARRANTY IS THE BUYERS SOLE AND EXCLUSIVE REMEDY AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BU T NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. BW SHALL NOT BE LIABLE FOR ANY SPECIAL, INDIRECT, INCIDENTAL, OR BASED ON CONTRACT, TORT OR RELIANCE OR ANY OTHER THEORY.
Since some countries or states do not allow limitation of the term of an implied warranty, or exclusion or limitation of incidental or consequential damages, the limitations and exclusions of this warranty may not apply to every buyer. If any provision of this warranty is held invalid or unenforceable by a court of competent jurisdiction, such holding will not affect the validity or enforceability of any other provision.
BW Technologies by Honeywell BW Technologies by Honeywell BW Technologies by Honeywell Corporate Headquarters America Europe 2840 - 2nd Ave. SE 3279 West Pioneer Parkway 5 Canada Close Calgary, AB Arlington, TX Banbury, Oxfordshire Canada T2A 7X9 USA 76013 United Kingdom OX16 2RT
Table of Contents
Title Page
Introduction ......................................................................................................................................................................... 1
Contacting BW Technologies by Honeywell .................................................................................................................... 2
Safety Information - Read First.......................................................................................................................................... 2
Getting Started .................................................................................................................................................................... 5
Activating the Detector....................................................................................................................................................... 9
Self-Test .......................................................................................................................................................................... 9
Self-Test Pass ............................................................................................................................................................... 12
Self-Test Fail.................................................................................................................................................................. 12
Deactivating the Detector................................................................................................................................................. 13
Confidence Beep............................................................................................................................................................... 13
User Options Menu ........................................................................................................................................................... 14
Exit ................................................................................................................................................................................ 15
Clock Option .................................................................................................................................................................. 15
Passcode Protection Option .......................................................................................................................................... 16
Enable Passcode Protection .................................................................................................................................... 16
Disable Passcode Protection.................................................................................................................................... 17
Deactivation Passcode Protection............................................................................................................................ 17
Stealth Mode Option ...................................................................................................................................................... 18
Automatic Backlight Option............................................................................................................................................ 19
Latching Alarm Option ................................................................................................................................................... 19
Automatic Oxygen (O
2
) Calibration Option.................................................................................................................... 20
Calibration Past Due Option .......................................................................................................................................... 21
Languages ..................................................................................................................................................................... 21
GasAlert Extreme
User Manual
Title Page
Portuguese Option.................................................................................................................................................... 21
Spanish Option ......................................................................................................................................................... 22
German Option ......................................................................................................................................................... 22
French Option ........................................................................................................................................................... 22
English Option .......................................................................................................................................................... 23
Datalogger Sampling Rate Option ................................................................................................................................. 23
Data Transfer Option ..................................................................................................................................................... 24
LAST and ALL Transfers .......................................................................................................................................... 25
EVNT Transfer .......................................................................................................................................................... 25
Unsuccessful Transfer .............................................................................................................................................. 25
Alarms ................................................................................................................................................................................ 26
Computed Gas Exposures ............................................................................................................................................. 28
Viewing Gas Exposures ................................................................................................................................................. 28
Toxic Gases.............................................................................................................................................................. 28
Oxygen ..................................................................................................................................................................... 28
Gas Alarm Setpoints ...................................................................................................................................................... 29
Stopping a Gas Alarm .................................................................................................................................................... 29
Clearing Gas Exposures ................................................................................................................................................ 30
Resetting Gas Alarm Setpoints ...................................................................................................................................... 30
Sensor Alarm ................................................................................................................................................................. 30
Low Battery Alarm.......................................................................................................................................................... 31
Automatic Shutdown Alarm............................................................................................................................................ 31
Calibration and Setting Alarm Setpoints ........................................................................................................................ 32
Guidelines ...................................................................................................................................................................... 32
Test Cap ........................................................................................................................................................................ 33
Calibration...................................................................................................................................................................... 34
Start Calibration ........................................................................................................................................................ 34
GasAlert Extreme
User Manual
Title Page
Auto Zero .................................................................................................................................................................. 34
Auto Zero Fail ........................................................................................................................................................... 34
Passcode Protected.................................................................................................................................................. 35
Set Span ................................................................................................................................................................... 35
Span ......................................................................................................................................................................... 36
Successful Span .................................................................................................................................................. 36
Unsuccessful Span .............................................................................................................................................. 36
Setting the Calibration Due Date ................................................................................................................................... 37
Setting the TWA Alarm Setpoint ............................................................................................................................... 37
Setting the STEL Alarm Setpoint .............................................................................................................................. 38
Setting the Low Alarm Setpoint ................................................................................................................................ 38
Setting the High Alarm Setpoint................................................................................................................................ 39
Verification ..................................................................................................................................................................... 39
Datalog and Event Log ..................................................................................................................................................... 40
Datalog........................................................................................................................................................................... 40
Event Log....................................................................................................................................................................... 40
Maintenance ...................................................................................................................................................................... 41
Replacing the Battery or Sensor .................................................................................................................................... 43
Replacing the Battery ............................................................................................................................................... 43
Replacing the Sensor ............................................................................................................................................... 43
Cleaning a Sensor Screen ............................................................................................................................................. 44
Clearing a Sensor .......................................................................................................................................................... 45
Troubleshooting................................................................................................................................................................ 46
Replacement Parts and Accessories .............................................................................................................................. 49
Specifications.................................................................................................................................................................... 50
General Specifications for Datalogger Units .................................................................................................................. 51
GasAlert Extreme
User Manual
List of Tables
Table Title Page
1. GasAlert Extreme Models .................................................................................................................................... 1
2. International Symbols ........................................................................................................................................... 4
3. GasAlert Extreme Detector .................................................................................................................................. 6
4. Display Elements.................................................................................................................................................. 7
5. Pushbuttons ......................................................................................................................................................... 8
6. Alarms ................................................................................................................................................................ 26
7. Computed Gas Exposures ................................................................................................................................. 28
8. Gas Alarm Setpoints .......................................................................................................................................... 29
9. Factory Alarm Setpoints ..................................................................................................................................... 30
10. Test Cap ............................................................................................................................................................. 33
11. Replacing the Battery or Sensor ........................................................................................................................ 41
12. Rear Shell Seal .................................................................................................................................................. 42
13. Front Shell Seal.................................................................................................................................................. 42
14. Troubleshooting Tips.......................................................................................................................................... 46
15. Replacement Parts and Accessories ................................................................................................................. 49
GasAlert Extreme
User Manual
List of Figures
Title Figure Page
1. GasAlert Extreme Detector .................................................................................................................................. 6
2. Display Elements.................................................................................................................................................. 7
3. Test Cap ............................................................................................................................................................. 33
4. Replacing the Battery or Sensor ........................................................................................................................ 41
5. Rear Shell Seal .................................................................................................................................................. 42
6. Front Shell Seal.................................................................................................................................................. 42
GasAlert Extreme
User Manual
GasAlert Extreme
Introduction
a Warning
To ensure your personal safety, read “Safety Information” before using the detector.
The GasAlert Extreme gas detector (“the detector”) warns of hazardous gas at levels above a factory set alarm setpoint. This product is a gas detector, not a measurement device.
The detector is a personal safety device. It is your responsibility to respond properly to the alarms.
Table 1 lists the GasAlert Extreme models and the gases monitored. This manual includes examples from each model.
Table 1. GasAlert Extreme Models
Model Gas Monitored
GasAlert Extreme O
2
Oxygen (% by volume)
GasAlert Extreme CO
Carbon monoxide (ppm)
Low H2 sensitivity
GasAlert Extreme CO Carbon monoxide (ppm)
GasAlert Extreme H
2
S
Hydrogen sulfide (ppm)
High range
Model Gas Monitored
GasAlert Extreme H2S
Hydrogen sulfide (ppm)
GasAlert Extreme PH
3
Phosphine (ppm)
GasAlert Extreme SO
2
Sulfur dioxide (ppm)
GasAlert Extreme Cl
2
Chlorine (ppm)
GasAlert Extreme NH
3
Ammonia (ppm)
GasAlert Extreme NH
3
Ammonia (ppm)
High range
GasAlert Extreme NO
2
Nitrogen dioxide (ppm)
GasAlert Extreme HCN Hydrogen cyanide (ppm)
GasAlert Extreme ETO Ethylene oxide (ppm)
GasAlert Extreme ClO
2
Chlorine dioxide (ppm)
GasAlert Extreme O
3
Ozone (ppm)
GasAlert Extreme NO Nitric oxide (ppm)
GasAlert Extreme
User Manual
Contacting BW Technologies by Honeywell
To contact BW Technologies by Honeywell, call:
USA: 1-888-749-8878 Canada: 1-800-663-4164 Europe: +44 (0) 1295 700300 Other countries: +1-403-248-9226
Address correspondence to:
BW Technologies by Honeywell 2840 – 2 Avenue S.E. Calgary, AB T2A 7X9 CANADA
Email us at:info@gasmonitors.com Visit BW Technologies by Honeywell’s website at:
www.gasmonitors.com
ISO 9001
Safety Information - Read First
Use the detector only as specified in this manual, otherwise the protec­tion provided by the detector may be impaired.
International symbols used on the detector and in this manual are explained in Table 2.
Read the Warnings and Cautions on the following pages before using the detector.
c Note
This instrument contains a lithium battery. Do not mix with the solid waste stream. Spent batteries should be dis­posed of by a qualified recycler or hazardous materials handler.
GasAlert Extreme
User Manual
a
Caution
To avoid possible personal injury, adhere to the following:
Warning: Substitution of components may impair Intrinsic Safety.
Warning: To prevent ignition of flammable or combustible atmospheres, disconnect power before servicing.
Do not use the detector if it is damaged. Before using the detector, inspect the case. Look for cracks and missing parts.
Use only a sensor specifically designed for the GasAlert Extreme model. Refer to Replacement Parts and Accesso-
ries.
Do not deactivate the detector during a work shift. Deactivating the detector resets the time-weighted average (TWA), short-term exposure limit (STEL), and maximum gas exposure values to 0. Refer to Alarms
.
Ensure the sensor screen is not blocked.
If the detector is damaged or parts are missing, contact BW Technologies by Honeywell
immediately.
If the detector has been disassembled, ensure the front and rear shells are properly aligned and fastened before acti­vating the detector. Refer to Maintenance
.
Periodically test the sensor’s response to gas by exposing the detector to a targeted gas concentration that exceeds the high alarm setpoint. Manually verify that the audible and visual alarms are activated.
Calibrate the detector before first-time use, and then at least once every 180 days. For HCN detectors, calibrate once every 90 days.
Use only the Energizer 1CR2 battery. Refer to Replacing the Battery or Sensor
.
To reduce the risk of ignition of a flammable atmosphere, batteries must only be changed in a safe area free of hazard­ous gas.
Do not place the detector near the mouth or shoulders.
GasAlert Extreme
User Manual
a
Caution
Table 2. International Symbols
To avoid possible damage to the detector, adhere to the following:
Do not expose the detector to electrical shock and/or severe continuous mechanical shock.
The oxygen GasAlert Extreme detector is classified by Underwriters Laboratories Inc. up to an atmosphere of 21% oxygen.
Do not attempt to disassemble, adjust, or service the detector unless instructions for that procedure are contained in the user manual, and/or that part is listed as a replacement part. Use only BW Technologies by Honeywell replace­ment parts. Refer to Replacement Parts and Accessories
.
The detector warranty will be voided if customer personnel or third parties damage the detector during repair attempts. Non-BW Technologies by Honeywell repair/service attempts void this warranty.
Symbol Meaning
h
Classified to both U.S. and Canadian Safety standards by Underwriter’s Laboratories, Inc.
X
Conforms to European Union Directives
g
European Explosives Protection
ATEX Conforms to European ATEX Directives
IECEx
International Electrotechnical Commission Scheme for Certification to Standards for Electrical Equipment for Explo­sive Atmospheres
GasAlert Extreme
User Manual
Getting Started
The items listed below are included with the detector. If the detector is damaged or parts are missing, contact the place of purchase immedi­ately.
3 V lithium CR2-series battery
GasAlert Extreme O
2
model: O2 sensor;
GasAlert Extreme CO model: CO sensor
(low H2 sensitivity);
GasAlert Extreme CO model: CO sensor; GasAlert Extreme H
2
S model: H2S sensor (high range);
GasAlert Extreme H
2
S model: H2S sensor;
GasAlert Extreme PH
3
model: PH3 sensor;
GasAlert Extreme SO
2
model: SO2 sensor;
GasAlert Extreme Cl
2
model: Cl2 sensor;
GasAlert Extreme NH
3
model: NH3 sensor;
GasAlert Extreme NH
3
model: NH3 sensor (high range);
GasAlert Extreme NO
2
model: NO2 sensor; GasAlert Extreme HCN model: HCN sensor; GasAlert Extreme ETO model: ETO sensor; GasAlert Extreme ClO
2
model: ClO2 sensor;
GasAlert Extreme O
3
model: O3 sensor;
GasAlert Extreme NO model: NO sensor.
Test cap and hose
The detector is shipped with the battery and sensor installed. To order replacement sensors and accessories, refer to Replacement Parts and
Accessories.
To become familiar with the features and functions of the detector, study the following figures and tables:
Figure 1 and Table 3: GasAlert Extreme Detector (describes the detector’s components).
Figure 2 and Table 4: Display Elements (describes the LCD screen and icons).
Table 5: Pushbuttons (describes the buttons on the detector.
GasAlert Extreme
User Manual
Figure 1. GasAlert Extreme Detector
Table 3. GasAlert Extreme Detector
Item Description
1 Visual alarm indicators (LEDs)
2 Liquid crystal display (LCD)
3 Pushbuttons
4 Audible alarm
5 Sensor and sensor screen
6 Infrared (IR) communication port
7 Alligator clip
GasAlert Extreme
User Manual
Figure 2. Display Elements
Note
When enabled, the backlight option automatically activates for 3 seconds whenever there is insufficient light to view the LCD. Press and hold (until the backlight activates) any button to acti­vate the backlight for 6 seconds. The detector is shipped with the backlight option enabled.
The backlight does not operate when stealth mode is enabled.
Table 4. Display Elements
Item Description
1Numeric value
2 Gas cylinder
3 Automatically span sensor
4 Passcode lock
5 Set alarm setpoints and user options
6 Maximum gas exposure
7 Alarm conditions
8 Battery
9 Data transmission
10 Alarm or alarm setpoint
11 Automatically zero sensor
12 Optional datalogger indicator
13 Parts per million (ppm)
14 Percentage by volume (% vol.)
15
Percentage by lower explosive limit (% LEL)
(future use)
GasAlert Extreme
User Manual
Table 5. Pushbuttons
Pushbutton Description
A
To activate the detector, press A.
To enable/disable the confidence beep, while the detector is deactivated press and hold
C. While
holding
C, press A to enable or disable the confidence beep during start-up.
To deactivate the detector, press
A and hold until OFF displays (5 seconds). If the detector is pass-
code protected to prevent deactivation, PASS will display. A passcode must be entered to deactivate the detector. For more information, refer to Deactivation Passcode Protection
.
E
To decrement the displayed value or to scroll down, press E.
To enter the user options menu, press
E and D simultaneously and hold until OPTN and then EXIT
displays (5 seconds).
To initiate calibration and set alarm setpoints, press and hold
E and C simultaneously until CAL.
displays.
D
To increment the displayed value, press D.
To view the TWA, STEL and maximum (MAX) gas exposures, press
D and C simultaneously.
C
To save a displayed value, press C.
To clear TWA, STEL, and maximum (MAX) gas exposures, press and hold
C for 6 seconds.
To acknowledge a latched alarm, press
C.
GasAlert Extreme
User Manual
Activating the Detector
To activate the detector, press A in a safe area, free of hazardous gas.
Self-Test
When the detector is activated, it performs several self-tests. Confirm the following tests occur.
Note
The following tests are listed in the order they are automatically performed on the detector.
1. Display Elements Test: The LCD displays all screen elements.
2. Alarm Function Test: The detector beeps, the LEDs flash, the backlight activates briefly, and the detector vibrates.
3. Battery Test: The detector tests the batteries. If the battery volt­age is too low to continue, the detector performs an automatic shutdown. Refer to Automatic Shutdown Alarm
.
4. Date and Time: The LCD displays the date and time automati­cally in the following order.
To adjust the date or time, refer to Clock Option
.
Year: The LCD displays the current year (20XX).
Month: JAN, FEB, MAR, etc.
Day of the month: (1 to 31)
Day of the week: MON, TUE, WED, etc.
Hour/Minute: 00:00 hours to 23:59 hours
GasAlert Extreme
User Manual
5. Sensor Test: The detector tests the sensor. If the sensor test fails, the detector beeps slowly, the LEDs flash slowly, and ALARM flashes.
If the sensor test passes, the self-test continues.
6. Gas Type: The LCD displays the type of gas the detector is manufactured to monitor.
Refer to Table 1 for the type of gases monitored.
If the battery is low, the LCD displays the low battery icon and the self-test continues.
7. TWA Alarm Setpoint: The LCD displays the TWA alarm set­point.
Note
The TWA alarm setpoint screen does not apply to O
2
detectors.
8. STEL Alarm Setpoint: The LCD displays the STEL alarm set­point.
Note
The STEL alarm setpoint screen does not apply to O
2
detec-
tors.
GasAlert Extreme
User Manual
9. Low Alarm Setpoint: The LCD displays the low alarm setpoint.
10. High Alarm Setpoint: The LCD displays the high alarm setpoint.
11. Calibration Due Test: The LCD displays the calibration due date.
The LCD displays the number of days remaining before the detector must be calibrated. For more information, refer to Cali-
bration.
If calibration is past due, CAL. PAST displays.
Press C to acknowledge the warning message.
If the calibration past due option is enabled or disabled, one of the following two events will occur.
Calibration Past Due Disabled: If the detector is not pass­code protected and after the CAL. PAST message is acknowl- edged, the detector continues the self-test and then enters normal operation.
Calibration Past Due Enabled: If the detector is passcode protected and when CAL. PAST displays, press
C to
acknowledge the message and to access the PASS screen. If required, refer to Passcode Protection Option
.
Press
D or E to scroll to the required passcode, and press
C within 10 seconds to confirm the selection. The detector
enters normal operation.
Note
Calibrate the detector before continuing operation.
If the passcode is not confirmed within 10 seconds or the pass­code is incorrect, the detector beeps eight times, the LEDs flash 8 times, and the LCD displays the following screen.
GasAlert Extreme
User Manual
The detector then automatically deactivates.
12. Bump Test Fail: If a previous bump test failed, the detector beeps, vibrates, and BUMP FAIL displays:.
Press
C to acknowledge the alarm.
Note
Bump test the detector before continuing operation.
For information regarding bump tests, refer to the MicroDock ll User Manual.
Self-Test Pass
If the detector passes the self-test, it enters normal operation. The LCD displays the ambient gas reading.
The detector begins recording immediately. It records the
maximum (MAX) gas exposure,
the short-term exposure levels (STEL), and
calculates the time-weighted average (TWA).
Self-Test Fail
If the detector fails the self-test, refer to Troubleshooting.
GasAlert Extreme
User Manual
Deactivating the Detector
Note
If Deactivation Passcode Protection is enabled, the detector cannot be disabled without entering a passcode first. PASS displays immediately after OFF, refer to Deactivation Passcode
Protection. This option can only be enabled at the factory and
cannot be disabled by the customer.
To deactivate the detector, complete the following:
1. Press and hold
A until OFF displays (approximately 5 seconds).
2. The detector beeps and vibrates four times, the LEDs flash four times, and then the detector deactivates.
Note
If
A is not held down until OFF displays, the detector will
remain activated.
Confidence Beep
The confidence beep provides continuous confirmation that the detector is operating properly. When the confidence beep is enabled, the detector beeps every 5 seconds.
The confidence beep can be enabled or disabled during start-up.
Note
The detector is shipped with the confidence beep disabled.
Enabling the confidence beep decreases battery life.
To enable/disable the confidence beep, complete the following:
1. Ensure the detector is deactivated.
2. Press and hold
C. While holding C, press A.
When the confidence beep option is enabled, the detector auto­matically begins beeping when activated.
When the confidence beep option is enabled in stealth mode, the detector vibrates one time every 60 seconds. For more informa­tion refer to Stealth Mode Option
and Alarms.
Note
If confidence beep is enabled and a low battery alarm occurs, the confidence beep deactivates.
GasAlert Extreme
User Manual
User Options Menu
Note
When selecting a user option, Set flashes and the LCD dis- plays the opposite of what is currently enabled.
To access the user options menu, complete the following:
1. Press and hold
D and E simultaneously until OPTN displays
and then release the buttons.
The detector beeps and vibrates four times and the LEDs flash four times while accessing the user options menu.
If the passcode protection is not enabled, the EXIT screen auto- matically displays.
If the detector is passcode protected, the following screen dis­plays.
2. Press
D or E to scroll to the required passcode. Press C to
confirm the selection and access the EXIT screen.
Note
If the passcode is not confirmed within 10 seconds, NO dis­plays and the detector returns to normal operation.
3. From the EXIT screen, press
D or E to scroll through the user
options.
4. Press
C to select a displayed option.
Note
As a safety precaution, if an option is not selected within 20 seconds the detector automatically returns to normal opera­tion.
When the required activities have been performed for a selected option, the EXIT screen automatically displays.
5. Press
D or E to select another option or press C to exit the
user options menu and return to normal operation.
GasAlert Extreme
User Manual
Exit
When entering user options, the EXIT screen displays immediately fol­lowing the options (OPTN) screen. The LCD automatically returns to the EXIT screen after a user option has been accessed.
From the EXIT screen, use
D or E to scroll to additional user options.
Or
Press
C to exit user options and return to normal operation.
Clock Option
The clock (CLCK) option sets the date (year/month/day/day of the week) and time (hour/minute) of the detector. To set the time or date, complete the following:
1. From the EXIT screen, press
D or E to scroll to the CLCK
option.
2. Press
C to select the option and access the first date/time
option, the year. Set and the last two digits of the year continually flash.
3. Press
D or E to scroll to the required year and press C to
confirm the selection.
Or
To bypass the year, press
C to retain the current value and
automatically proceed to the month screen.
4. Repeat step #3 for the remaining date/time changes.
5. Press
D or E to select another option or press C to exit the
user options menu and return to normal operation.
Note
The time and date values can only be changed in the order they are presented in this table. To bypass any
setting, press
C. The detector automatically retains
the current value and proceeds to the next date/time option.
Year: Requires only the last two numerals of the year (00-99).
Month: Scroll to select the required month (JAN, FEB, MAR, etc.).
Day: Scroll to select the required day (1-31). For months with 30 days (1-30) is available. For Feb­ruary, (1-28 & 29) is available.
Day of the week: Scroll to select the required day (MON, TUE, WED, etc.).
Time: The hour value flashes first. Scroll to select (0:00 hours. to 23:59 hours).
GasAlert Extreme
User Manual
Note
If a value is not bypassed by pressing
C within 10 seconds,
the detector automatically proceeds to the next date/time option. If the Time Minute value was not bypassed, the detec­tor automatically proceeds to the Exit screen.
If a new value is selected but not confirmed by pressing
C
within 10 seconds, NO displays and the detector proceeds to the next date/time option. If a new Time Minute value was selected but not confirmed, the detector automatically pro­ceeds to the Exit screen.
Passcode Protection Option
The passcode protection option (PASS) prevents unauthorized access to the user options and the calibration/set alarm setpoint functions.
The passcode protection option can be enabled or disabled.
Note
The detector is shipped with the passcode protection option disabled.
Enable Passcode Protection
To enable passcode protection, complete the following:
Note
The passcode is provided on a separate card inside the ship­ping container.
1. From the EXIT screen of the user options menu, press
D or E
to scroll to the PASS option.
2. Press
C to select the option.
3. Set and PAS S continually flash. Press
D or E to scroll to the
required passcode, and press
C to confirm the selection.
4. The ON screen displays and flashes continually. Press
C to
confirm. The LCD then returns to the EXIT screen.
5. Press
D or E to select another user option, or press C to exit
the user options and return to normal operation.
Note
If an incorrect passcode is selected or a correct passcode is not confirmed within 10 seconds, NO displays and the LCD returns to the EXIT screen.
GasAlert Extreme
User Manual
Disable Passcode Protection
When the detector is passcode protected, the key icon displays continu­ally. To disable the passcode protection option, complete the following:
1. Press and hold
D and E simultaneously to access the user
options menu.
The OPTN screen displays briefly before the flashing passcode screen displays.
2. Press
D or E to scroll to the required passcode and press C
to confirm. The following EXIT screen displays.
The key icon indicates that the passcode protection is currently enabled.
3. Press
D or E to scroll to the PAS S option, and press C to
select the option.
4. The LCD displays a flashing OFF screen. Press
C to confirm
the disabling option.
Note
To ensure if the passcode protection option is enabled/dis­abled, use
D and E to toggle between the ON and OFF
options. Display the desired option and press
C to confirm the
selection.
The LCD returns to the EXIT screen.
5. Press
D or E to select another user option, or press C to exit
the user options and return to normal operation.
Note
If a passcode value is not selected or confirmed by pressing
C within 10 seconds, NO displays and the LCD returns to the
EXIT screen.
Deactivation Passcode Protection
As a backup safety precaution, the deactivation passcode protection option can be enabled prevent unauthorized deactivation. A separate security passcode is required for this option and will be available to lim­ited personnel only.
Note
The detector can be shipped with this option enabled perma­nently. This option can only be enabled at the factory and can­not be disabled by a customer.
The passcode must be entered every time the detector is deactivated.
GasAlert Extreme
User Manual
To deactivate the detector, complete the following:
1. From normal operation, press and hold
A to deactivate the
detector.
If the detector is passcode protected to prevent deactivation, OFF displays briefly and then PASS immediately displays.
2. Press
D or E to scroll to the required security passcode.
Press
C to confirm the selection.
The detector then deactivates.
Stealth Mode Option
The stealth (STLH) mode option ensures that the detector is undetected in situations that require concealment. This option disables the
audible alarms,
visual alarms, and
backlight.
Only the vibrator alarm remains enabled.
Note
The detector is shipped with stealth mode disabled.
To enable/disable the stealth mode, complete the following:
1. From the EXIT screen, press
D or E to scroll to the STLH
option.
2. Press
C to select the option. The LCD flashes either ON or
OFF.
3. Press
D or E to toggle between the ON/OFF options. Ensure
the desired option is displayed and press
C to confirm the
selection.
The LCD returns to the EXIT screen.
If stealth mode has been enabled, the screen displays STLH continually unless
functions are being performed,
readings are not 0 ppm for toxics, or
reading is not 20.9% vol for oxygen.
Note
The vibrator alarm is disabled at -20°C.
4. Press
D or E to scroll to a new user option or press C to exit
and return to normal operation.
Enabled Disabled
GasAlert Extreme
User Manual
Note
If the option is not confirmed by pressing
C within 10 seconds,
the detector returns to normal operation.
Automatic Backlight Option
The automatic backlight (BKLT) option enables or disables the backlight of the detector. When enabled, the backlight automatically activates for 3 seconds whenever there is insufficient light to view the LCD.
Press any button to activate the backlight for 6 seconds.
Note
The detector is shipped with the automatic backlight option enabled. The backlight option is not available in the user options menu when stealth mode is enabled.
To enable/disable the automatic backlight, complete the following:
1. From the EXIT screen, press
D or E to scroll to the BKLT
option.
2. Press
C to select the option. The LCD flashes either ON or
OFF.
3. Press
D or E to toggle between the ON/OFF options. Ensure
the desired option is displayed and press
C to confirm the
selection.
The LCD returns to the EXIT screen.
4. Press
D or E to scroll to a new user option or press C to exit
and return to normal operation.
Note
If the option is not confirmed by pressing
C within 10 seconds,
the detector returns to normal operation.
Latching Alarm Option
The latch alarm (LTC H) option ensures that an alarm persists until it is acknowledged by the user.
If enabled, during an alarm condition the latched alarms (LTCH) option causes the low and high gas alarms (audible, visual, and vibrator) to per­sist until the gas concentration is below the alarm setpoint and the alarms have been acknowledged by pressing
C.
The audible alarm can be temporarily deactivated (press
C) for 30 sec-
onds, but the LCD continues to display the peak concentration until the alarm condition no longer exists.
In stealth mode, the detector continues to vibrate until the alarm is acknowledged.
Note
The detector is shipped with the latching alarm option disabled.
GasAlert Extreme
User Manual
To enable/disable the latching alarm option, complete the following:
1. From the EXIT screen, press
D or E to scroll to the LT C H
option.
2. Press
C to select the option. The LCD flashes either ON or
OFF.
3. Press
D or E to toggle between the ON/OFF options. Ensure
the desired option is displayed and press
C to confirm the
selection.
The LCD returns to the EXIT screen.
4. Press
D or E to scroll to a new user option or press C to exit
and return to normal operation.
Note
If the option is not confirmed by pressing
C within 10 seconds,
the detector returns to normal operation.
Automatic Oxygen (O2) Calibration Option
Note
For oxygen detectors only.
If the automatic oxygen (O
2
) calibration option is enabled, ensure the detector is activated in safe area in normal (20.9%) oxygen atmosphere.
This option enables/disables the automatic oxygen (O
2
) calibration. The
O
2
calibration begins automatically during start-up after the calibration
due screen displays.
Note
The detector is shipped with the automatic O
2
calibration option
disabled.
To enable/disable the automatic O
2
calibration option, complete the fol-
lowing:
1. From the EXIT screen of the user options menu, press
D or E
to scroll to the ACAL option.
2. Press
C to select this option. The LCD flashes either ON or
OFF.
3. Press
D or E to toggle between the ON/OFF options. Ensure
the desired option is displayed and press
C to confirm the
selection.
The LCD returns to the EXIT screen.
4. Press
D or E to scroll to a new user option or press C to exit
and return to normal operation.
Note
If the option is not confirmed by pressing
C within 10 seconds,
the detector returns to normal operation.
GasAlert Extreme
User Manual
Calibration Past Due Option
The calibration past due (PAST) option enables an automatic shutdown during start-up if the detector is past due for calibration.
Note
The detector is shipped with the calibration past due shutdown option disabled.
To calibrate a past due calibration detector, refer to Calibration Past Due
Enabled in Self-Test.
To enable/disable the calibration past due automatic shutdown option, complete the following:
1. From the EXIT screen of the user options menu, press
D or E
to scroll to the PAS T option.
2. Press
C to select the option. The LCD flashes either ON or
OFF.
3. Press
D or E to toggle between the ON/OFF options. Ensure
the desired option is displayed and press
C to confirm the
selection.
The LCD returns to the EXIT screen.
4. Press
D or E to scroll to a new user option or press C to exit
and return to normal operation.
Note
If the option is not confirmed by pressing
C within 10 seconds,
the detector returns to normal operation.
Languages
The LCD can display text in five different languages. Refer to the follow­ing language options.
Portuguese Option
The Portuguese (PORT) option enables the LCD to display text in Portu­guese.
Note
If the multi-language option is included, the detector is shipped with English selected as the default language.
1. From the EXIT screen of the user options menu, press
D or E
to scroll to the PORT option.
2. Press
C to select the option. The LCD then displays the Portu-
guese exit screen.
3. Press
D or E to scroll to another user option or press C to
exit and return to normal operation.
GasAlert Extreme
User Manual
Spanish Option
The Spanish (ESPA) option enables the LCD to display text in Spanish.
Note
If the multi-language option is included, the detector is shipped with English selected as the default language.
1. From the EXIT screen of the user options menu, press
D or E
to scroll to the ESPA option.
2. Press
C to select the option. The LCD then displays the Span-
ish exit screen.
3. Press
D or E to scroll to another user option or press C to
exit and return to normal operation.
German Option
The German (DEUT) option enables the LCD to display text in German.
Note
If the multi-language option is included, the detector is shipped with English selected as the default language.
1. From the EXIT screen of the user options menu, press
D or E
to scroll to the DEUT option.
2. Press
C to select the option. The LCD then displays the Ger-
man exit screen.
3. Press
D or E to scroll to a new user option or press C to exit
and return to normal operation.
French Option
The French (FRAN) option enables the LCD to display text in French.
Note
If the multi-language option is included, the detector is shipped with English selected as the default language.
1. From the EXIT screen of the user options menu, press
D or E
to scroll to the FRAN option.
GasAlert Extreme
User Manual
2. Press C to select the option. The LCD then displays the French
exit screen.
3. Press
D or E to scroll to another user option or press C to
exit and return to normal operation.
English Option
The English (ENGL) option enables the LCD screens to display text in English.
Note
If the multi-language option is included, the detector is shipped with English selected as the default language.
1. From the EXIT screen of the user options menu, press
D or E
to scroll to the ENGL option.
2. Press
C to select the option. The LCD then displays the English
exit screen.
3. Press
D or E to scroll to another user option or press C to
exit and return to normal operation.
Datalogger Sampling Rate Option
The datalogger sampling rate (RATE) option defines how often the detector records a datalog. The datalogger sampling rate ranges from 1 to 60 seconds.
Note
The detector is shipped with a datalogging sampling rate of 5 seconds.
To adjust the datalogger sampling rate, complete the following:
1. From the EXIT screen of the user options menu, press
D and
E to scroll to the RATE option.
2. Press
C to select the option and display the sample rate screen.
3. The sample rate screen displays the current selected rate. Press
D or E to scroll to a new rate and press C to save the new
value.
GasAlert Extreme
User Manual
4. Press D or E to scroll to another user option or press C to
exit and return to normal operation.
Note
If a datalogging sample rate value is not selected or confirmed by pressing
C within 10 seconds, NO displays and the LCD
displays the EXIT screen.
Data Transfer Option
The data transfer (SEND) option transfers the datalog/event log informa­tion from the detector to a PC.
Note
An IR DataLink (or other BW accessory) is required to transfer the data from the detector to a PC.
To transfer data, complete the following:
1. Connect the IR DataLink (or other BW accessory) to the detector and the PC.
Refer to the IR DataLink Instruction Sheet.
2. From the EXIT screen of the user options menu, press
D or E
to scroll to the SEND option.
3. Press
C to select the option and to access the data transfer
option screens.
4. Select one of the following options to transfer data.
5. When the data transfer is complete, the detector beeps and vibrates, and the LEDs flash. The LCD displays the EXIT screen.
Press D or E to scroll to the event (EVNT) option. Press
C to
automatically transfer all events.
Press
D or E to scroll to the
last (LAST) option. Press
C to
automatically send all of the data­logs since the last datalog down­load.
Press
D or E to scroll to the all
(ALL) option. Press
C to auto-
matically send all of the datalogs that are saved on the detector.
GasAlert Extreme
User Manual
LAST and ALL Transfers
If the LAST or ALL option is selected, the LCD displays a countdown and the data transmission icon to indicate that the detector is transferring data.
Note
The number at the beginning of the countdown depends upon the amount of data to transfer.
EVNT Transfer
If the EVNT option is selected, the event logs transfer immediately and the LCD displays the EXIT screen.
Unsuccessful Transfer
If the connection between the detector and the IR DataLink is discon­nected during a transfer, FAIL displays.
The LCD then displays the EXIT screen.
1. From the PC, save the previously transferred data to ensure that it will not be deleted.
2. Repeat steps #3-5 of the Data Transfer Option
.
3. From the detector, select LAST to automatically resume the transfer from where it stopped sending.
Or
Select ALL to transfer all of the data again.
GasAlert Extreme
Alarms
Alarms
Table 6 describes detector alarms and corresponding screen. During an alarm condition, the detector activates the backlight and the LCD displays the current ambient gas reading.
To change the factory-set alarm setpoints, refer to Calibration and Setting Alarm Setpoints
.
Table 6. Alarms
Alarm Display Alarm Display
Low Alarm:
Slow beep
•Slow flash
ALARM flashes
Slow vibrations
TWA Alarm:
Slow beep
•Slow flash
ALARM flashes
Slow vibrations
High Alarm:
Fast beep
Fast flash
ALARM flashes
Fast vibrations
STEL Alarm:
Fast beep
Fast flash
ALARM flashes
Fast vibrations
Sensor Alarm:
Slow beep
•Slow flash
ALARM flashes
Slow vibrations
Low Battery Alarm:
One beep and one flash every 5 seconds, and one quick vibration every minute (when confidence beep is disabled).
If confidence beep is enabled no beeps, flashes, or vibrations
LOW displays
GasAlert Extreme
User Manual
Table 6. Alarms
Note
The high alarm and STEL alarm have the same priority. A high alarm and/or STEL alarm overrides a low alarm and/or TWA alarm. To check STEL and TWA alarms specifically, press and hold
C and D simultaneously.
The vibrator alarm is disabled at -20°C.
The high and low alarms deactivate when the gas concentration is lower than the low alarm setpoint. If the alarms are set to latch, alarms persist until the gas concentration is below the alarm setpoint and the alarms have been acknowledged by pressing
C. The TWA and STEL
alarms deactivate by clearing the TWA and STEL peak exposure. Refer to Clearing Gas Exposures
.
Alarm Display Alarm Display
Automatic Shutdown Alarm:
(Low battery)
Eight beeps, flashes, and vibrations
LOW displays
Automatic Shutdown Alarm:
(Calibration past)
Eight beeps, flashes, and vibrations
Automatic Shutdown Alarm:
(After Automatic Shutdown Alarm)
No beep
No flash or vibrations
displays for a short time
Confidence Beep:
One beep every 5 seconds
One quick vibration per minute
Note
If the detector enters low battery alarm, the confidence beep deacti­vates.
GasAlert Extreme
User Manual
Computed Gas Exposures
a Warning
To avoid possible personal injury, do not deactivate the detector during a work shift. The detector automatically resets the TWA, STEL, and MAX gas exposures during start-up. If the detector is reactivated during a work shift, the new values will not reflect the entire work shift.
Table 7. Computed Gas Exposures
Viewing Gas Exposures
Toxic Gases
1. Press C and D simultaneously. The LCD displays the TWA
gas exposure first.
2. Then the LCD displays the STEL gas exposure.
3. Then the LCD displays the MAX gas exposure.
Oxygen
For oxygen detectors, press C and D simultaneously to view both the maximum low and maximum high levels of oxygen exposure.
Gas Exposure Description
TWA Time-weighted average based on an
8-hour workday.
Accumulated value.
STEL Short-term exposure limit (STEL) to
gas based on a 15-minute period.
Accumulated value.
MAX* Maximum (MAX) concentration
encountered during a work shift.
*For oxygen, it is the highest or the lowest value from
20.9% encountered.
GasAlert Extreme
User Manual
Gas Alarm Setpoints
Table 8 describes the gas setpoints that trigger the gas alarms.
Table 8. Gas Alarm Setpoints
Stopping a Gas Alarm
The low and high alarms deactivate when the ambient gas level returns to below the low alarm setpoint.
Note
If alarms are set to latch, the alarms deactivate after the gas concentration is lower than the low alarm setpoint and the alarms have been acknowledged by pressing
C.
The TWA and STEL alarms can be stopped either by
• Clearing the MAX, TWA, and STEL peak exposures. Refer to
Clearing Gas Exposures
.
or
• deactivating the detector and reactivating it again.
If the detector is passcode protected to prevent deactivation, refer to Deactivation Passcode Protection
.
a Caution
Follow all safety procedures as defined by your employer. Confirm with your supervisor before clearing TWA and STEL alarms.
Alarm Condition
Low alarm Toxic gases: Ambient gas level
above low alarm setpoint.
O
2
: ambient gas level may be set
to above or below 20.9%.
High alarm Toxic gases: ambient gas level
above high alarm setpoint.
O
2
: ambient gas level may be set
to above or below 20.9%.
TWA alarm TWA above TWA alarm setpoint.
(O
2
: not applicable)
STEL alarm STEL above STEL alarm setpoint.
(O
2
: not applicable)
GasAlert Extreme
User Manual
Clearing Gas Exposures
The peak gas exposures automatically clear after deactivating the detec­tor.
To clear the MAX, TWA, and STEL peak exposure readings immediately, press and hold
C for 6 seconds. The detector beeps and vibrates two
times to confirm that the exposures have been cleared.
a Caution
Follow all safety procedures as defined by your employer. Confirm with your supervisor before clearing TWA and STEL alarms.
Resetting Gas Alarm Setpoints
Note
Standard factory alarm setpoints vary by region.
Table 9 lists the factory alarm setpoints.
To change the factory alarm setpoints, refer to Calibration and Setting
Alarm Setpoints.
Note
To disable an alarm, set the alarm setpoint to 0.
The ETO sensor is extremely cross sensitive and it responds strongly to CO.
Table 9. Factory Alarm Setpoints
Sensor Alarm
The detector tests for a missing or defective sensor during the activation self-test. Refer to Troubleshooting
.
Gas TWA STEL Low High
O
2
N/A N/A 19.5% vol. 22.5% vol.
CO
(low H2)
35 ppm 200 ppm 35 ppm 200 ppm
CO 35 ppm 200 ppm 35 ppm 200 ppm
H2S
(high range)
10 ppm 15 ppm 10 ppm 15 ppm
H
2
S 10 ppm 15 ppm 10 ppm 15 ppm
PH
3
0.3 ppm 1.0 ppm 0.3 ppm 1.0 ppm
SO
2
2.0 ppm 5.0 ppm 2.0 ppm 5.0 ppm
Cl
2
0.5 ppm 1.0 ppm 0.5 ppm 1.0 ppm
NH
3
25 ppm 35 ppm 25 ppm 50 ppm
NH
3
(high range)
25 ppm 35 ppm 25 ppm 50 ppm
NO
2
2.0 ppm 5.0 ppm 2.0 ppm 5.0 ppm
HCN 4.7 ppm 10.0 ppm 4.7 ppm 10.0 ppm
ETO 1.0 ppm 5.0 ppm 1.0 ppm 5.0 ppm
ClO
2
0.1 ppm 0.3 ppm 0.1 ppm 0.3 ppm
O
3
0.10 ppm
0.10 ppm 0.10 ppm 0.20 ppm
NO 25 ppm 25 ppm 25 ppm 25 ppm
GasAlert Extreme
User Manual
Low Battery Alarm
If a low battery alarm occurs, follow your company’s safety procedures.
The detector tests the battery upon activation and continuously thereaf­ter. If the battery voltage is low, the detector activates the low battery alarm.
The low battery alarm continues until the battery is replaced or the bat­tery power is almost depleted. If the battery voltage drops too low, the detector automatically deactivates.
Note
If the detector enters low battery alarm, the confidence beep deactivates.
a Caution
Replace the battery in only a safe area, free of hazardous gas.
Automatic Shutdown Alarm
There are two situations when an automatic shutdown alarm occurs.
1. If the battery voltage is in immediate danger of falling below the minimum operating voltage, the detector beeps and vibrates eight times, and the LEDs flashes eight times. After 3 seconds, the LCD deactivates and the detector deactivates.
The LCD periodically displays until the battery power is depleted.
To replace the battery, refer to Replacing the Battery or Sensor
.
Note
The low battery alarm continues for approximately 30 minutes before an automatic shutdown occurs.
2. If the calibration past due user option is enabled and the detector is past the calibration due date, the detector automatically deacti­vates.
GasAlert Extreme
User Manual
Calibration and Setting Alarm Setpoints
Guidelines
When calibrating the detector, adhere to the following guidelines.
Recommended gas mixture: O
2
: clean air, 20.9% vol.
CO (low H
2
sensitivity): 50 to 500 ppm balance N
2
CO: 50 to 500 ppm balance N2 H
2
S (high range): 10 to 100 ppm balance N
2
H2S: 10 to 100 ppm balance N
2
PH3: 1 to 5 ppm balance N
2
SO2: 10 to 50 ppm balance N
2
Cl2: 3 to 25 ppm balance N
2
NH3: 20 to 100 ppm balance N
2
NH3: (high range) 20 to 100 ppm balance N
2
NO2: 5 to 50 ppm balance N
2
HCN: 5 to 20 ppm balance N
2
ETO: 5 to 50 ppm balance N
2
ClO2: 0.1 to 1.0 ppm balance N
2
O3: 0.1 to 1.0 ppm balance N
2
NO: 10 to 250 ppm balance N
2
Before operating an ETO detector, allow the detector to stabilize at the temperature it will be operating in. After the detector has stabilized, zero the detector.
It is necessary to periodically re-zero the ETO detector.
To ensure accurate calibration, BW recommends using a pre­mium-grade calibration gas approved by the National Institute of Standards and Technology (NIST).
Do not use a gas cylinder beyond its expiration date.
Before calibrating a new NO or ETO sensor, allow the sensor to stabilize for 2 hours in a safe area that is free of hazardous gas.
Calibrate a new sensor before use. Allow the sensor to stabilize before starting calibration (used: 60 seconds; new: 5 minutes).
Calibrate the detector at least once every 180 days (for HCN detectors calibrate at least once every 90 days), depending upon use and sensor exposure to poisons and contaminants.
Calibrate the detector if the ambient gas display varies at start-up.
It is best to calibrate the sensor before changing the alarm set­points.
Calibrate only in a safe area that is free of hazardous gas.
To disable an alarm, set the alarm setpoint to zero.
If a certified calibration is required, contact
BW Technologies by Honeywell
.
Note
A generator must be used to calibrate O
3
and ClO2 GasAlert
Extreme sensors.
GasAlert Extreme
User Manual
Test Cap
The calibration cap and hose are shipped with the detector for calibra­tion.
Refer to Table 10 and Figure 3 for installation information.
Note
Only use the calibration cap during calibration.
Table 10. Test Cap
Figure 3. Test Cap
Item Description
1Test cap
2Hose
3 Regulator
4 Gas cylinder
GasAlert Extreme
User Manual
Calibration
Calibration requires several steps, some of which can be bypassed. A note is added to each option that can be bypassed.
Start Calibration
Note
To quit calibration at any point, press
A. The detector retains
any saved values and the detector beeps and vibrates four times before returning to normal operation.
Calibrate O
2
in clean air only.
1. To enter calibration, in a safe area free of hazardous gas, press and hold
C and E simultaneously as the detector beeps and
vibrates four times, and the LEDs flash four times.
After the CAL. screen displays, the detector beeps one time and the auto zero screen displays.
Auto Zero
The auto zero function automatically zeroes the detector.
2. The LCD flashes while the detector automatically zeroes the sensor. When the auto zero is complete the detector beeps twice.
Note
Do not apply the calibration gas until the LCD displays the flashing gas cylinder icon; otherwise, the detector auto zero will fail.
Auto Zero Fail
If the sensor fails auto zero, the following screen displays.
The detector then bypasses the sensor span and automatically proceeds to the alarm setpoints.
1. Press A to exit the alarm setpoint screens and to return to nor­mal operation.
2. Restart the calibration procedures in a safe area that is free of hazardous gas. If auto zero fails a second time, deactivate and then reactivate the detector to test the sensors.
3. If the auto zero is successful and the passcode protection is dis­abled, the detector automatically proceeds to the auto span func­tion.
GasAlert Extreme
User Manual
Passcode Protected
After a successful auto zero, and if the passcode protected option is enabled, PAS S displays. The passcode is required to access the auto span and alarm setpoint functions.
3. Press
D or E to scroll to the required passcode and press C
to confirm. For additional information, refer to Passcode Protec-
tion Option.
If the correct code is confirmed by pressing
C within 10 sec-
onds, the detector beeps twice and automatically proceeds to the set span screen.
If the passcode is not confirmed within 10 seconds or the pass­code is incorrect, NO displays.
The detector then beeps four times and automatically returns to normal operation.
Set Span
Note
To bypass the set span function, press
C to automatically pro-
ceed to the span screen.
The set span function inputs a new calibration gas concentration value.
4. Set SPAN flashes.
Press
D or E to scroll to the required gas concentration. The
detector value must match the concentration value on the gas cylinder.
Note
If a new value is selected but not confirmed within 10 seconds by pressing
C, the detector rejects the new value and NO dis-
plays. The detector beeps six times and retains the original value. The detector automatically proceeds to the span screen.
5. Press
C to save the new value and proceed to the span screen.
GasAlert Extreme
User Manual
Span
Note
To bypass the span function, press
C to automatically pro-
ceed to the alarm setpoint screens. If the span is bypassed, the calibration due date cannot be changed.
Verify that the calibration gas being used matches the span concentration values that are defined for the detector. For more information, refer to Calibration Guidelines
.
6. The set span screen displays a flashing .
Note
The flashing does not display for oxygen (O
2
) detectors.
7. Apply the calibration gas.
8. Apply gas to the sensor at a flow rate of 500 ml/min. (for NH
3
, Cl2, and ETO: 1000 ml/min.)
The gas readings change as gas is applied to the sensor. When the detector senses a sufficient concentration of gas (approxi­mately 30 seconds), the detector beeps once.
9. The detector then begins spanning the sensor as follows:
•NH
3
, Cl2, ClO2, O3, and ETO: 5 minutes to span
•O
2
: 30 seconds to span
other gases: 2 minutes (approximately) to span.
The detector beeps three times when the span is complete.
Successful Span
If the span is successful, the LCD automatically displays the calibration due date screen.
Unsuccessful Span
If the detector fails to span a sensor successfully,
FAIL displays.
The detector vibrates and beeps, and the LEDs flash. Then the detector automatically proceeds to the alarm setpoint screens.
If the span fails confirm that
gas is being applied to the sensor,
the sensor is detecting a sufficient gas concentration within 30 seconds, and
the gas concentration has not dropped significantly during the 2-minute span.
If the span is still unsuccessful, use a new gas cylinder.
If the span continues to be unsuccessful, replace the sensor. Refer to
Replacing the Battery or Sensor
.
GasAlert Extreme
User Manual
Setting the Calibration Due Date
After a successful calibration, the LCD displays the CAL. DUE screens and the number of days remaining before the next calibration.
Note
To bypass the calibration due notification, press
C. The
detector automatically proceeds to the TWA alarm setpoint.
BW Technologies by Honeywell recommends that the detector be calibrated every 180 days (6 months). The detector is shipped with the factory default setting of 180 days.
10. Press
D or E to scroll to the required value
(1 to 365).
11. Press
C to save the new value and automatically proceed to the
TWA alarm setpoint screen.
Note
If a new value is selected but not confirmed within 10 seconds by pressing
C, the detector automatically retains the original
value and NO displays. The detector proceeds to the TWA alarm setpoint.
Setting the TWA Alarm Setpoint
Note
To bypass and retain the current TWA alarm setpoint value, press
C. The detector automatically proceeds to the STEL
alarm setpoint.
When the CAL. DUE function has been completed, the Set TWA alarm setpoint screen automatically displays.
12. Press
D or E to scroll to the required value.
13. Press
C to save the new value and proceed to the STEL alarm
setpoint.
Note
If a new value is selected but not confirmed within 10 seconds by pressing
C, the detector automatically retains the original
value and NO displays. The detector proceeds to the STEL alarm setpoint.
GasAlert Extreme
User Manual
Setting the STEL Alarm Setpoint
Note
To bypass and retain the current STEL alarm setpoint value, press
C. The detector automatically proceeds to the low
alarm setpoint.
When the TWA alarm setpoint value has been changed or bypassed, the Set STEL alarm setpoint screen displays.
14. Press
D or E to scroll to the required value.
15. Press
C to save the new value and proceed to the low alarm
setpoint.
Note
If a new value is selected but not confirmed within 10 seconds by pressing
C, the detector automatically retains the original
value and NO displays. The detector proceeds to the low alarm setpoint.
Setting the Low Alarm Setpoint
Note
To bypass and retain the current low alarm setpoint value, press
C. The detector automatically proceeds to the high
alarm setpoint.
When the STEL alarm setpoint value has been changed or bypassed, the Set LOW alarm setpoint screen displays.
\
16. Press D or E to scroll to the required value.
17. Press
C to save the new value and proceed to the high alarm
setpoint.
Note
If a new value is selected but not confirmed within 10 seconds by pressing
C, the detector automatically retains the original
value and NO displays. The detector proceeds to the high alarm setpoint.
GasAlert Extreme
User Manual
Setting the High Alarm Setpoint
Note
To bypass and retain the current high alarm setpoint value, press
C. The detector then returns to the normal operation.
When the low alarm setpoint value has been changed or bypassed, the Set HIGH alarm setpoint screen displays.
18. Press
D or E to scroll to the required value.
19. Press
C to save the new value and return to normal operation.
Note
If a new value is selected but not confirmed within 10 seconds by pressing
C, the detector automatically retains the original
value and NO displays. The detector proceeds to normal oper­ation.
When calibration is complete, the detector beeps and vibrates four times, and the LEDs flash four times before returning to normal opera­tion.
Verification
1. After calibration is complete and the detector is in normal opera­tion, verify calibration by using a gas cylinder other than the one used for calibration.
2. The gas concentration should not exceed the sensor’s detection range. Confirm that the LCD displays the expected concentration values.
3. To ensure that the reading is accurate, apply the verification gas for the same period of time as was applied to the sensor when it was calibrated.
Example: SO
2
span time was 2 minutes therefore, apply verifica-
tion gas for 2 minutes.
GasAlert Extreme
User Manual
Datalog and Event Log
The GasAlert Extreme datalogger version allows the detector to record various information so a report can be compiled.
Datalog
Datalog sampling rate is defined in the detector user options. To set the sample rate, refer to Datalogger Sampling Rate Option
.
The following information is recorded in a datalog:
Date and time
Detector serial number
Type of gas the detector monitors
Current gas reading
Sensor status
Detector status
Passcode protect enabled/disabled
STEL period setting (fixed to a 15 minute period)
Confidence beep enabled/disabled
Automatic backlight enabled/disabled
Stealth mode enabled/disabled
Latching alarm enabled/disabled
Calibration past due user option enabled/disabled
Language the detector is set to display
Event Log
Event log information is recorded when an event (i.e., an alarm) occurs. The following information is recorded in an event log:
Detector serial number
Type of exposure the detector that occurred
Time the alarm started and ended
Peak exposure of the alarm
GasAlert Extreme
User Manual
Maintenance
To maintain the detector in good operating condition, perform the follow­ing basic maintenance as required:
Calibrate, bump test, and inspect the detector at regular inter­vals.
Maintain an operations log of all maintenance, calibrations, bump tests, and alarm events.
Clean the exterior with a soft damp cloth. Do not use solvents, soaps, or polishes.
Do not immerse the detector in liquids.
Table 11. Replacing the Battery or Sensor
Figure 4. Replacing the Battery or Sensor
Item Description
1 Rear shell machine screws (4)
2 Rear shell
3Battery
4 PCB machine screws (2)
5PCB
6 Sensor
7 Sensor screen
8 Front shell
GasAlert Extreme
User Manual
Figure 5. Rear Shell Seal
Table 12. Rear Shell Seal
Figure 6. Front Shell Seal
Table 13. Front Shell Seal
Item Description
1 Seal
Item Description
1 Seal
GasAlert Extreme
User Manual
Replacing the Battery or Sensor
a Warning
To avoid possible personal injury, adhere to the following:
• Replace the battery in a safe area, free of hazardous gas immediately when the detector enters low battery alarm.
• Use only the Energizer 1CR2 battery.
• Use only the sensor specifically designed for the GasAlert Extreme model. Otherwise, the detector will not monitor the target gas. Refer to Replacement Parts and Accessories
.
• After replacing a sensor, allow the new sensor 5 minutes to stabilize before use. For an ETO or NO sensor, allow the new sensor 2 hours to stabilize before use.
• Do not expose a sensor to vapors of organic solvents such as paint fumes or organic solvents.
Note
When the battery is removed from the detector, the clock reverts back to the default value. Refer to Clock Option
.
To preserve the life of the battery, deactivate the detector when not in use.
For additional information regarding problems caused by a sensor requiring calibration or replacement, refer to Troubleshooting
.
Replacing the Battery
To replace a battery, complete the following. Refer to Figures 4, 5, and 6 and Tables 11, 12, and 13. Replace the battery in a safe area, free of hazardous gas.
1. Deactivate the detector.
2. Remove the four machine screws on the rear shell and remove the rear shell.
3. Remove the battery.
c Warning
This instrument contains a lithium battery. Do not mix with the solid waste stream. Spent batteries should be disposed of by a qualified recycler or hazardous materials handler.
4. Insert the new battery.
5. Re-assemble the detector. When assembling the detector be aware of the following:
• Clean the seal on the front and rear shells with a soft damp
clean cloth. Do not use solvents, soaps, or polishes. Refer to Figures 5 and 6.
• Ensure the front and rear shells are properly aligned to ensure
a proper environmental seal.
• Torque the screws to 3-4 in-lbs in a crisscross pattern to
ensure a proper environmental seal. Do not overtighten.
Replacing the Sensor
To replace a sensor, complete the following. Refer to Figures 4, 5, and 6 and Tables 11, 12, and 13.
1. Deactivate the detector.
2. Remove the four machine screws on the rear shell and remove the rear shell.
3. Remove the two machine screws from the PCB.
GasAlert Extreme
User Manual
4. Remove the PCB.
5. Replace the sensor.
Gently rock the sensor back and forth to remove a tightly held sensor.
Note
Allow the new sensor 5 minutes to stabilize before use. For a new ETO or NO sensor, allow the new sensor 2 hours to stabi­lize before use.
6. Re-assemble the detector. When assembling the detector be aware of the following:
• Clean the seal on the front and rear shells with a soft damp
clean cloth. Do not use solvents, soaps, or polishes. Refer to Figures 5 and 6.
• Ensure the front and rear shells are properly aligned to ensure
a proper environmental seal.
• Torque the screws to 3-4 in-lbs in a crisscross pattern to
ensure a proper environmental seal. Do not overtighten.
Cleaning a Sensor Screen
Clean or replace the sensor screen as required. If replacement sensor screens are required, refer to Replacement Parts and Accessories
.
To clean a removed sensor screen, complete the following. Refer to Fig­ures 4, 5, and 6 and Tables 11, 12, and 13.
1. Deactivate the detector.
2. Remove the four machine screws on the rear shell and remove the rear shell.
3. Remove the two machine screws from the PCB.
4. Remove the PCB. Place the PCB on a clean surface.
5. Remove the screen.
6. Using a soft, clean brush, wash the screen with clean, warm water.
7. Insert the sensor screen with the shiny side facing the sensor grill.
Note
Ensure the screen is dry before inserting back into the detec­tor.
8. Re-assemble the detector. When assembling the detector be aware of the following:
• When inserting the sensor screen back into the detector,
ensure the sensor screen is inserted with the shiny side facing the sensor grill.
• Clean the seal around the edge of the front and rear shells with
a soft damp clean cloth. Do not use solvents, soaps, or pol­ishes. Refer to Figures 5 and 6.
• Ensure the front and rear shells are properly aligned to guaran-
tee a proper environmental seal.
• Torque the screws to 3-4 in-lbs in a crisscross pattern to
ensure a proper environmental seal. Do not overtighten.
GasAlert Extreme
Maintenance
Clearing a Sensor
Each sensor has a high degree of resistance to common vapors and gases. To clear a sensor, move the detector to a clean environment and wait 10 to 30 minutes.
Note
Do not expose a sensor to the vapors of inorganic solvents, such as paint fumes or organic solvents.
GasAlert Extreme
User Manual
Troubleshooting
If a problem occurs, refer to the solutions provided in Table 14. If the problem persists, contact BW Technologies by Honeywell.
Table 14. Troubleshooting Tips
Problem Possible Cause Solution
The detector does not activate. No battery Install a battery. Refer to Replacing the Bat-
tery or Sensor.
Depleted battery Replace the battery. Refer to Replacing the
Battery or Sensor.
Damaged or defective detector Contact BW Technologies by Honeywell
.
Reversed battery Reinstall the battery correctly.
The detector enters alarm mode immedi­ately when it is activated.
Sensor needs to stabilize Used sensor: wait 60 seconds.
New sensor: wait 5 minutes.
Low battery alarm Replace the battery. Refer to Replacing the
Battery or Sensor.
Sensor alarm Replace the sensor. Refer to Replacing the
Battery or Sensor.
The start up self-test fails during one of the checks.
General fault Contact BW Technologies by Honeywell
.
Alarm setpoints are incorrect Reset the alarm setpoints. Refer to Reset-
ting Gas Alarm Setpoints.
GasAlert Extreme
Troubleshooting
Table 14. Troubleshooting Tips
Problem Possible Cause Solution
The detector does not display a normal ambient gas reading after the activation self-test.
Target gas is present Detector is operating properly. Use caution
in suspect areas.
Detector requires calibration Calibrate the detector. Refer to Calibration
and Setting Alarm Setpoints.
Sensor not stabilized Used sensor: wait 60 seconds.
New sensor: wait 5 minutes.
The detector does not respond to the push­buttons.
Battery is depleted Replace the battery. Refer to Replacing the
Battery or Sensor.
Detector is performing operations that does not require user input
Pushbutton operation restores automatically when the operation ends.
The detector does not accurately measure the gas.
Detector requires calibration Calibrate the sensor. Refer to Calibration
and Setting Alarm Setpoints.
Detector is colder/hotter than ambient gas Allow the detector to acquire ambient tem-
perature before use.
Sensor screen is blocked Clean the sensor screen. Refer to Cleaning
a Sensor Screen.
The detector does not enter alarm mode. Alarm setpoint(s) are set incorrectly Reset the alarm setpoints. Refer to Reset-
ting Gas Alarm Setpoints.
Alarm setpoint(s) set to zero Reset the alarm setpoints. Refer to Reset-
ting Gas Alarm Setpoints.
Detector is in calibration mode Complete calibration. Refer to Calibration
and Setting Alarm Setpoints.
GasAlert Extreme
User Manual
Table 14. Troubleshooting Tips
Problem Possible Cause Solution
The detector intermittently enters alarm mode without apparent reason.
Ambient gas levels are near alarm setpoint or the sensor is exposed to a puff of the tar­get gas
Detector is operating normally. Use caution in suspect areas. Check MAX gas exposure reading.
Alarms set incorrectly. Reset the alarm setpoints. Refer to Calibra-
tion and Setting Alarm Setpoints.
Missing or faulty sensor Replace the sensor. Refer to Replacing the
Battery or Sensor.
The detector automatically deactivates. Automatic shutdown feature activated due
to depleted battery
Replace the battery. Refer to <Replacing
the Battery or Sensor.
Detector does not auto zero or calibrate. Sensor may be expired Change the sensor.
O
2
sensor reading is erratic. Sensor may be expired Change the sensor.
GasAlert Extreme
User Manual
Replacement Parts and Accessories
a Warning
To avoid personal injury or damage to the detector, use only specified replacement parts.
To order any parts or accessories, contact BW Technologies by Honey-
well.
Table 15. Replacement Parts and Accessories
Model No. Description Qty
SR-X10
Replacement O
2
sensor
1
PS-RM04H Replacement CO sensor
(low H2 sensitivity) 1
PS-RM04 Replacement CO sensor 1
PS-RH04S
Replacement H
2
S sensor
1
SR-P04
Replacement PH
3
sensor
1
PS-RS04
Replacement SO
2
sensor
1
PS-RC10
Replacement Cl
2
sensor
1
SR-A04
Replacement NH
3
sensor
1
SR-A204
Replacement NH
3
sensor (high range)
1
PS-RD04
Replacement NO
2
sensor
1
PS-RZ10 Replacement HCN sensor 1
SR-E04 Replacement ETO sensor 1
SR-V04
Replacement ClO
2
sensor
1
SR-G04
Replacement O
3
sensor
1
SR-N04 Replacement NO sensor 1
GAXT-SS Sensor screens 10
GA-TC-1 Test cap and hose 1
GA-BALERT Concussion-proof boot 1
GA-BSPLASH-K Splash guard filters 5
GA-HC-1 Hard hat clip 1
GA-AG-1 Alligator clip (non-conductive) 1
GA-AG-2 Alligator clip (stainless-steel) 1
GA-CL-1 Belt clip with screw 1
GA-NS-1 Neckstrap with safety release 1
GA-LY-1 Short strap (6 in./15.2 cm) 1
GA-USB2 IR DataLink 1
Model No. Description Qty
GasAlert Extreme
User Manual
Specifications
Instrument dimensions: 2.8 x 5.0 x 9.5 cm (1.1 x 2.0 x 3.75 in.)
Weight: 82 g (2.9 oz.)
Operating temperature:
H
2
S, SO2, HCN: -40°C to +50°C (-40°F to +122°F) CO: -30°C to +50°C (-22°F to +122°F) NH
3,
NH3 (high range): -20°C to +40°C (-4°F to +104°F)
Other gases: -20°C to +50°C (-4°F to +122°F)
Operating humidity:
CO, H
2
S, SO2, Cl2, HCN, NO2, NH3, PH3, ETO, NO, O3: 15% to 90% relative humidity (non-condensing) Cl2: 10% to 95% relative humidity (non-condensing) ClO2: 15% to 95% relative humidity (non-condensing) O2: 0% to 99% relative humidity (non-condensing)
Detection range:
GasAlert Extreme O
2
: 0 – 30.0% vol. (0.1% vol. increments) GasAlert Extreme CO: 0 – 1000 ppm (1 ppm increments) GasAlert Extreme CO (low H
2
sensitivity): 0 – 1000 ppm (1 ppm increments) GasAlert Extreme H
2
S: 0 – 100 ppm (1 ppm increments)
GasAlert Extreme H
2
S (high range): 0 – 500 ppm (1 ppm increments)
GasAlert Extreme PH
3
: 0 – 5.0 ppm (0.1 ppm increments)
GasAlert Extreme SO
2
: 0 – 150.0 ppm (0.1 ppm increments)
GasAlert Extreme Cl
2
: 0 – 50.0 ppm (0.1 ppm increments)
GasAlert Extreme NH
3
: 0 – 100 ppm (1 ppm increments)
GasAlert Extreme NH
3
: (high range) 0 – 400 ppm (1 ppm increments)
GasAlert Extreme NO
2
: 0 – 100.0 ppm (0.1 ppm increments)
GasAlert Extreme HCN: 0 – 30.0 ppm (0.1 ppm increments)
GasAlert Extreme ETO: 0 – 100.0 ppm (0.1 ppm increments) GasAlert Extreme ClO
2
: 0 – 1.00 ppm (0.01 ppm increments)
GasAlert Extreme O
3
: 0 – 1.00 ppm (0.01 ppm increments)
GasAlert Extreme NO: 0 – 250 ppm (1 ppm increments)
Sensor type: Plug-in electrochemical cells
Calibration: Auto zero, set span, and span sensor
Alarm conditions: TWA alarm, STEL alarm, low alarm, high alarm, sen-
sor alarm, low battery alarm, confidence beep, automatic shutdown alarm.
Audible alarm: 95 dB at 0.3 m (1 ft.) typical
Visual alarm: Red light-emitting diode (LED)
Display: Alpha-numeric liquid crystal display (LCD)
Backlight: Automatically activates for 3 seconds whenever there is
insufficient light to view the display and during alarm conditions. Any pushbutton reactivates the backlight for 6 seconds.
Self-test: Initiated upon activation
Battery test: Every 0.5 seconds
Battery: 3 V lithium Energizer 1CR2-series battery
Warranty: 2 years including sensors.
Approvals:
Classified by UL to both U.S. and Canadian Standards as Intrinsically Safe for Class I, Division 1, Group A, B, C, D European Explosives Protection EEx ia IIC
CE 0539
g II 1 G DEMKO 04 ATEX 03 36363
IECEx
ABS Type Approved: VA-348-169-X
GasAlert Extreme
User Manual
General Specifications for Datalogger Units
Storage: Maximum of 8 months of data at 5 second intervals (based on a normal workweek).
Memory Type: Wrap-around memory ensures most recent data is always saved.
Sample Rate: One reading every 5 seconds (standard)
Data Recorded: All sensor readings, all alarm conditions, calibrations,
event flags, battery status, sensor status, confidence beep activation, and detector status along with the time and date and the detector serial number.
Indicators: Icon advising datalogger is operating normally
Transfer Accessory: IR DataLink or other BW accessory
Support:
BW Excel Datalog Manager (EDM): This software organizes GasAlert Extreme datalog and event log files into a readable report
Fleet Manager CD Support: This software organizes GasAlert Extreme datalog and event log files into a readable report
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules and ICES­003 Canadian EMI requirements. These limits are designed to provide reasonable protection against harmful interference in a residential instal­lation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that radio interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
GasAlert Extreme
User Manual