Bussmann SC Data Sheet

Time-Delay Fuses SC
Class G – 600 Volt, ⁄Ω™ - 20 Amps
480 Volt, 25 - 60 Amps
Form No. SC
Page 1 of 3
Data Sheet: 1024
Bussmann
®
Catalog Numbers
SC-⁄Ω™ SC-6 SC-25 SC-1 SC-7 SC-30 SC-1⁄Ω™ SC-8 SC-35 SC-2 SC-9 SC-40 SC-2⁄Ω™ SC-10 SC-45 SC-3 SC-12 SC-50 SC-4 SC-15 SC-60 SC-5 SC-20
Dimensional Data
Catalog Symbol: SC
Current-Limiting Ampere Rating:
⁄Ω™ to 60A (fast-acting),
7 to 60A (time-delay)
Voltage Ratings:
SC ⁄Ω™ to 20 600Vac, 170Vdc SC 25 to 60 480Vac, 300Vdc
Interrupting Rating: 100,000A RMS Sym. AC, 10,000A dc Agency Information:
UL Listed, Std. 248-5, Class G, Guide JDDZ, File E4273 CSA Certified, C22.2 No. 248.5, Class 1422-01, File 53787
Carton Quantity and Weight
Catalog Carton
Weight†
Number Qty. Lbs. Kg.
⁄Ω™–15 4 0.060 0.0272 20 4 0.064 0.029 25–30 2 0.040 0.018 35–60 2 0.075 0.0340 †Weight per carton.
Fuse (Amps) A
SC-⁄Ω™ to 15 1.31∑ SC-20 1.41∑ SC-25 to 30 1.62∑ SC-35 to 60 2.25∑
General Information:
• Compact branch-circuit units with high interrupting rating and current-limitation.
• With 600V rating, they can be used in 120/208, 120/240 and 277/480V circuits.
• Length variations relative to case size make the “rejection” type fuses.
• In general, SC fuses are about
⁄Ω£ the size of the 600V NEC
fuse type.
• SC fuses with ampere ratings above 6A have a degree of overload time-delay which permits them to pass temporary overloads. At 200% load, they have a minimum opening time of 12 seconds.
CE logo denotes compliance with European Union Low Voltage Directive (50-1000Vac, 75-1500Vdc). Refer to
Data Sheet:
8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
4-01-04
SB04105
Recommended fuseblocks/fuseholders for Class G fuses
See Data Sheets listed below
• Open fuseblocks - 1106
• In-line fuseholders - 1123, 1124
(Length)
.41"
(10.3mm)
Time-Delay Fuses SC
Class G – 600 Volt, ⁄Ω™ - 20 Amps
480 Volt, 25 - 60 Amps
Form No. SC
Page 2 of 3
Data Sheet: 1024
Bussmann
®
Peak Let-Through Curves
B
60
30 20
15
AMPERE
RATING
A
10,000
1,000
100
100
1,000
10,000
100,000
INSTANTANEOUS PEAK LET-THROUGH
CURRENT IN AMPS
RMS SYMMETRICAL CURRENTS IN AMPERES
A–B=ASYMMETRICAL AVAILABLE PEAK (2.3 X SYMM RMS AMPS)
4-01-04
SB04105
CURRENT IN
AMPERES
TIME IN SECONDS
100
10
1
.1
.01
10
100
1,0 0 0
1
.7
2,000
1/2A
1-1/2A
2-1/2A
1A
2A
3A
5A6A8A
10A
12A
15A
20A
30A
60A
4A
300
Time-Delay Fuses SC
Class G – 600 Volt, ⁄Ω™ - 20 Amps
480 Volt, 25 - 60 Amps
Time-Current Characteristic Curves– Total Clearing
Bussmann
®
Form No. SC
Page 3 of 3
Data Sheet: 1024
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information con­tained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
4-01-04
SB04105
Loading...