Bussmann R600 Series Data Sheet

Class R Fuseblocks (600V) Catalog Data (for LRS-RK, FRS-R, DLS-R and KTS-R Fuses)
Terminal Type (Suffix No.) Dimensions (Inches)
Basic
Screw w/ Box Lug w/
0.259 J Dia. Catalog Pres. Clip Quick- Fig. x Wire Number Plate — Cu Only Connect No. A B C D E F G H C’ Bore K Range
⁄Ω¡º 1 R60030-1 SR PR CR COR 1 1.54 COR #6-14 CU ONLY to 2 R60030-2 SR PR CR COR 2 6.25 1.73 2.90 1.56 0.25 0.62 3.13 1.56 0.28 x 0.5 .26 CR #2-14 CU, #2-12 AL 30 3 R60030-3 SR PR CR COR 3 4.25 PR, SR #10-18 CU ONLY 31 1 R60060-1 — CR COR 4
COR #2-14 CU ONLY
to 2 R60060-2 — CR COR 5 (See Figures)
CR #2-14 CU, #2-8 AL
60 3 R60060-3 — CR COR 6 61 1 R60100-1 — CR COR 7 2.22 to 2 R60100-2 — CR COR 8 9.5 2.38 4.03 2.63 0.67 0.88 4.25 1.81 0.28 x 0.5 0.34
COR 1/0 -8 CU ONLY
100 3 R60100-3 — CR COR CRQ† 9 5.84
CR, CRQ 1/0-8 CU/AL
101
1 R60200-1 — CR CRQ† 10 9.63 3.09 3.0 3.31 0.5 2.0 3.0 0.75 — 0.31
CR, CRQ
to 200
3 R60200-3 — CR 11 (See Figures) 250kcmil-6 CU/AL
201
1 R60400-1 — CR‡ COR‡ 10 12.0 4.0 3.0 4.5 0.63 1.75 3.0 1.0 — 0.56
COR to 500kcmil-4/0 CU ONLY 400
3 R60400-3 — CR† 12 (See Figures)
CR 500kcmil-4 CU/AL
401
1 R60600-1 — CR 10 14.0 4.97 3.0 5.5 1.125 1.75 4.0 1.0 0.56
CR (2) 500kcmil-4/0 CU/AL
to 600
3 R60600-3 — CR† 13 (See Figures)
†No UL, No CSA Certification. ‡UL Recognized, CSA Certification
Dimensional Data: See pages 2 and 3.
Class R Fuseblocks R600 Series
600 Volts
Form No. R600 Series
Page 1 of 3
Data Sheet: 1111
Bussmann
®
Catalog Symbol: R600 Series Ampere Rating: ⁄Ω¡º to 600A Voltage Rating: 600V Agency Information:
UL Listed, UL 512, Guide IZLT, File E14853 CSA Certified, C22.2 No. 39, Class 6225-01, File 47235 Withstand Rating: 200,000A RMS Sym.
For use with Class R fuses (LPS-RK and FRS-R)
UL Flammability: 94VO Materials: Thermoplastic
Amps
Poles
CE logo denotes compliance with European Union Low Voltage Directive (50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact Bussmann Application Engineering at 314-527-1270 for more information.
10-4-02
SB02295
Class R Fuseblocks R600 Series
600 Volts
Bussmann
®
Dimensional Data
600V, ⁄Ω¡º to 30A
600V, 31 to 60A
FIGURE 1. FIGURE 2. FIGURE 3.
FIGURE 4. FIGURE 5. FIGURE 6.
600V, 61 to 100A
FIGURE 7. FIGURE 8. FIGURE 9.
Form No. R600 Series
Page 2 of 3
Data Sheet: 1111
10-4-02
SB02295
B K
C
F
E
C H
F
F
C
HE
H
A
2.06"
0.25"
7.36"
J
3.38"
1.56"
0.62"
0.62"
1.81"
0.59"
J
0.59"
0.62"
4.94"
J
G
D
1.56"1.56"
0.28" DIA. x
0.5" C'BORE
3.125"
2.38"
B K
A
C
F
E
J
C
H
F
J
E
F
C
H
H
2.125"
J
G
D