For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa
229955
Power
Distribution
& Terminal
Blocks
Power Distribution & Terminal Blocks
Series PDBFS of Power Distribution Blocks
Feature/Benefits
• Enclosed, safer
installation; IP20
finger-safe under specific
conditions
• High short-circuit cur rent
ratings up to 200kA:
PDBs do not have to be
the weak link in achieving
high SCCR for an
industrial control panel
• Small footprint saves
panel space
• Listed to UL 1953 which has minimum spacing
requirements at 600V of at least 1” through air and 2” over
surface required for feeders in UL 508A Industrial Control
Panels
• For 2D CAD drawings visit www.cooperbussmann.com
Agency/Standards
• UL Listed 1953, Guide QPQS, File E256146
• CSA Certified, Class 6228-01, File 15364
• IEC 60947-7-1
• IEC 60529, IP20 (finger-safe) under specific wiring
conditions
Electrical
• 600Vac/dc (UL 1953), 690Vac/dc (IEC)
• IP20 finger-safe under specific conditions
• Short-circuit cur rent ratings up to 200kA, see table
• Ampacities up to 760 amps
• Cu wire range 14 AWG to 500 kcmil or 2.5 to 240 mm
2
Mechanical
• DIN rail or panel mount; PDBFS330 & PDBFS504 panel
mount only
• Captive termination screws; screws do not get misplaced
• Wire ready: captive termination screws shipped backed out
to save time on conductor installations
• Sliding DIN rail latch for easy mounting
• Single pole, gang mountable for multiple pole applications
with interlocking dovetail accessory (optional)
• Flammability, UL 94V0
• Tin-plated Al connectors suitable for Cu conductors
• Elongated hole for panel mounting; easier mounting with
greater flexibility in matching up with drilled panel holes
• Part 2A1279: Inter locking dovetail pin accessory
One pin interlocks two units, two pins to interlock three units
• DIN rail end anchors required to prevent damage to block
when torquing
Data Sheet: 1049
Terminal Copper Conductor Ca pability Shor t-Circuit Cur rent Rating Da ta
Line Load Configuration Conductors Max Fuse Class & Amp**
Catalog
Number Openings per Pole Line Load J T RK1 RK5
(All Single
Amps Wire Range Wire Range
AWG or AWG or LPJ JJS LPS-RK FRS-R
SCCR
Pole) Line Load kcmil kcmil JJN LPN-RK FRN-R
PDBFS204 175A
2/0 to 8 AWG 2/0 to 8 AWG
2/0 to 8 2/0 to 8 200 200 100 60 200kA
70 to 10 mm
2
70 to 10 mm
2
2/0 to 8 AWG 4 to 14 AWG
4 to 12 200 200 100 60 200kA
PDBFS220 175A
70 to 10 mm
2
25 to 2.5 mm
2
2/0 to 8
14
175 175 100 60 100kA
200 200 100 60 50kA
350kcmil to 6 AWG 350kcmil to 6 AWG
PDBFS303 310A
185 to 16 mm
2
185 to 16 mm
2
350 to 6 350 to 6 400 400 200 100 200kA
500kcmil to 6 AWG 2 to 14 AWG
2 to 6 400 400 200 100 200kA
PDBFS330 380A
240 to 16 mm
2
35 to 2.5 mm
2
500 to 6
8 to 14
200 200 100 30 50kA
175 175 100 30 100kA
300kcmil to 4 AWG 4 to 14 AWG
300 4 to 8 600 600 400 200 200kA
PDBFS377 570A
150 to 12 mm
2
25 to 2.5 mm
2
250 to 4
4 600 600 400 200 50kA
6 to 14 200 200 100 30 50kA
PDBFS500 620A
350kcmil to 4 AWG 350kcmil to 4 AWG
350 350 600 600 400 200 200kA
185 to 12 mm
2
185 to 12 mm
2
300 to 4 300 to 4 600 800* 600 200 100kA
500kcmil to 6 AWG 500kcmil to 6 AWG
500 500
600 800* 600 400 200kA
PDBFS504 760A
240 to 16 mm
2
240 to 16 mm
2
600 800* 600 600 100kA
400 to 6 400 to 6 600 600 400 200 100kA
Ampacities 75ºC per NEC®Table 310.16 and UL 508A Table 28.1
*Class L 800A (KRP-C 800_SP) or less fuses suitable for this particular SCCR case.
** Class G 60A (SC-60) or less or Class CC 30A (LP-CC-30, FNQ-R-30, KTK-R-30) or less are suitable for all SCCRs in this table.
Series PDBFS
Electrical