Bussmann OPM-1038 Data Sheet

Materials: Grey Thermoplastic UL Flammability: UL 94VO Agency Information:
UL - see table below CSA Certified: C22.2 No. 39, Class 6225-01, File 47235 IEC - see table below
Shipping Weight: Approx. 213g (.47 lb.) Carton Quantity: 1
OPM-1038
Overcurrent Protection Module - Fuseholder Non-Switch Series for ⁄‹Ω£™∑ ≈ 1⁄Ω™∑ (10mm 38mm) Fuses
Form No. OPM-1038
Non-Switch Series
Page 1 of 3
Data Sheet: 1102
Bussmann
®
1-23-04
SB04028
Physical Characteristics:
• Small size matches 45mm IEC starter width.
• Fits #8-18 AWG stranded wire, #10-18 AWG solid wire.
• 3-pole version.
Product Features:
• “Open” fuse indication lights. (Min. 100V required)
• Cam action handle for easy removal.
• Finger safe terminals. (Qualified as IP2O per IEC529)
• Removable module for convenient fuse loading.
• 35mm DIN-rail or screw panel mounting (#8 screw, 1⁄Ω¢∑ long).
• Dead front construction.
Additional Features:
• Option for remote “open fuse” status indication feature available (less down-time).
• Offered with Class CC rejection clips or European 10mm 38mm clips to meet global needs.
• Wire ready: Saves time as terminals are ready to accept wires.
Catalog SC Remote Open UL Information Number Electrical Rating Rating Clips Fuse Indication Std. File Guide IEC
OPM-1038 30A, 600V UL/CSA** * Non-rejection, No Recognized
(Max. 3 Watts per fuse) 10x 38mm or
32A, 660V IEC 13/32” x 1-1/2” UL 512 E14853 IZLT2 IEC 269-2-1
OPM-1038R 30A, 600V UL/CSA** 200kA Rejection, No Listed
Class CC UL 512 E14853 IZLT
OPM-1038C 30A, 600V UL/CSA** * Non-rejection, Yes Recognized
(Max. 3 Watts per fuse) 10x 38mm or
32A, 660V IEC 13/32” x 1-1/2” UL 512 E14853 IZLT2 IEC 269-2-1
OPM-1038RC 30A, 600V UL/CSA** 200kA Rejection, Yes Listed
Class CC UL 512 E14853 IZLT
*Rating varies depending on fuse used in module. **DC Voltage Rating: 600V UL/CSA
Recommended Fuse Types:
Class CC Midget (non-rejection)
LP-CC KTK KTK-R FNM FNQ-R FNQ
CE logo denotes compliance with European Union Low Voltage Directive (50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. Applies to OPM-1038 and OPM-1038R.
O P M - 1 0 3 8
Series Fuse Type Communication
C - Communication
Feature
Blank - 10 x 38mm
or 13/32” x 1-1/2”
R - Class CC
Catalog Symbol:
Bussmann
®
OPM-1038
Overcurrent Protection Module - Fuseholder Non-Switch Series for ⁄‹Ω£™∑ ≈ 1⁄Ω™∑ (10mm ≈ 38mm) Fuses
Form No. OPM-1038
Non-Switch Series
Page 3 of 3
Data Sheet: 1102
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Status Output Specifications:
*Minimum operating voltage: 460Vac, 3-phase *Maximum operating voltage: 620Vac, 3-phase
Status output maximum conducting current: 40mA Status output maximum on resistance: 35 ohms
@ 40mA Status output typical off resistance: >10 Mohm Status output maximum turn-on and
turn-off delay: 850 milli-second
Status Output Interface Specifications:
Rated Voltage: Recommended 5-35Vdc, 300Vac max. Rated Current: 40mA max. Wire Size: #28-14 AWG Torque: 2.25 lb. in.
Open Fuse Indicator Status Output Description:
The open fuse indicator status output acts very much like an on/off switch. With all three fuses in place and operating properly, this status output has a high resistance value of greater than ten mega-ohms. When one or more of the fuses are open, the status output becomes turned-on with a resistance value less than 35 ohms. This status output withstands voltage (AC or DC) up to 35 volts at off-state and conducts current up to 40 milli-amps at on-state. Applying voltage and current exceeding these limits will result in damage to the components inside this status output device permanently. There is some time-delay when the status output changes on/off state. The open fuse communications or status output device includes optical isolators within the unit.
Communications output states: Fuse Good NO - High Resistance, >10 mega-ohms Opened Fuse NC - Low Resistance, < 35 ohms
OPEN FUSE INDICATION
Note: Operating this device beyond the above limits will
cause permanent damage to the components on the board.
For applications requiring status output below a system voltage of 460V, contact Bussmann.
The examples shown below illustrate typical interface to Programmable Logic Controllers.
STATUS OUTPUT
TTL Digital Input
PC / PLC
Vcc (5V to 35V) Pull up Resistor (> 1K)
EXAMPLE 1: DIRECT INTERFACE TO PC/PLC
PC / PLC
EXAMPLE 2: INTERFACE TO PC / PLC WITH OPTICAL ISOLATION
Current­Limiting Resistor
Optical Isolator
TTL Digital Input
Vcc (5V to 35V)
ISOLATED AC OR DC
POWER SOURCE
STATUS OUTPUT
Pull up Resistor (> 1K)
Note: When energized, a low load terminal voltage will be present when fuses are
open or when pullout module is removed. The leakage current is limited to .5mA maximum.
Example of Output Voltage with three open fuses or pullout module removed.
Catalog Number OPM-1038, OPM-1038R OPM-1038C, OPM-1038RC
Type of Indication Standard Communication
System Voltage Load Terminal Voltage
(1L1-3L2-5L3) (2T1-4T2-6T3)
125Vdc * 12Vdc * 31Vdc * 480Vac, 3-phase 26Vac 56Vac 600Vac, 3-phase 33Vac 88Vac
*The communication device requires a minimum circuit voltage (1L1-3L2-5L3) of 460 volts for the status indicating device to operate. Below 460 volts, but above 120 volts the indicator lights will luminate, but there will not be any communication status output.