Bussmann NON, NOS Data Sheet

Carton Quantity and Weight—NOS ONE-TIME (600Vac)
Catalog Carton
Weight**
Number Qty. Lbs. Kg.
NOS 1–30 10 1.45 0.657 NOS 35–60 10 2.6 1.179 NOS 70–100 5 2.80 1.270 NOS 110–200 1 1.24 0.562 NOS 225–400 1 3.03 1.374 NOS 450–600 1 4.63 2.100
**
Weight per carton.
One-Time General Purpose Fuses NON and NOS
Form No. NON/ NOS
Page 1 of 2
Data Sheet: 1030
Bussmann
®
Catalog Numbers—NON ONE-TIME (250Vac)
NON-⁄Ω• NON-5 NON-40 NON-175 NON-⁄Ω™ NON-6 NON-45 NON-200 NON-‹Ω¢ NON-6⁄Ω¢ NON-50 NON-225 NON-°Ω¡º NON-7 NON-60 NON-250 NON-1 NON-8 NON-65 NON-300 NON-1⁄Ω¢ NON-9 NON-70 NON-350 NON-1⁄Ω™ NON-10 NON-75 NON-400 NON-1flΩ¡º NON-12 NON-80 NON-450 NON-2 NON-15 NON-90 NON-500 NON-2⁄Ω™ NON-20 NON-100 NON-600 NON-3 NON-25 NON-110 — NON-3¤Ω¡º NON-30 NON-125 — NON-4 NON-35 NON-150
Catalog Symbol: NON (250V); NOS (600V)
For general purpose application
Ampere Rating: ⁄Ω• to 600A Voltage Rating: NON: 250Vac, 125Vdc (0-100A);
NOS: 600Vac
Non-Current-Limiting Interrupting Rating: 50,000A RMS Sym. (0-60A),
10,000A RMS Sym. (65-600A), 50,000A @ 125Vdc (NON 0-60), 10,000A @ 125Vdc (NON 65-100A)
Agency Information:
UL Listed - 250V: Class K5 (0-60A), Std. 248-9
Class H (65-600A), Std. 248-6 (125Vdc: NON 0-100)
600V: Class K5 (0-60A), Std. 248-9
Class H (70-600A), Std. 248-6 UL Guide JDDZ, File E4274 CSA Certified, Class 1421-01, File 53787 (0-12 & 65-600A)† 250V
(0-600A) 600V
General Information:
• Protect lighting, heating and other circuits not subject to tem­porary surges and where available short-circuit currents are relatively low.
• ONE-TIME fuses do not have any appreciable degree of time­delay and thus should not be specified in circuits where large transients or motor overloads occur. Use Buss FUSETRON
®
or LOW-PEAK®dual-element, time-delay fuses.
• For general purpose circuits, size at ampere rating of circuit.
• For motor circuits, size at 300% to 400%.
.56" (± 0.008)
2" (250V) (± 0.031)
.81" (± 0.008)
3" (250V) (± 0.031)
1.06" (250V)
1.34" (600V)
2.06" (250V)
2.59" (600V)
2.59" (250V)
3.13" (600V)
1.56" (250V)
1.84" (600V)
0.81" (± 0.008)
5" (600V) (± 0.031)
1.06" (± 0.008)
5.5" (600V) (± 0.031)
5.88" (250V) (± 0.062)
7.9" (600V) (± 0.062)
7.13" (250V) (± 0.062)
9.63" (600V) (± 0.062)
8.63" (250V) (± 0.094)
11.63" (600V) (± 0.094)
10.38" (250V) (± 0.094)
13.38" (600V) (± 0.094)
⁄Ω¡º to 30A ⁄Ω¡º to 30A
35A to 60A
70A to 100A
225A to 400A
35A to 60A
110A to 200A
450A to 600A
Carton Quantity and Weight—NON ONE-TIME (250Vac)
Catalog Carton
Weight**
Number Qty. Lbs. Kg.
NON ⁄Ω•–30 10 0.38 0.172 NON 35–60 10 1.00 0.453 NON 65–100 5 0.79 0.358 NON 110–200 1 0.79 0.358 NON 225–400 1 1.65 0.748 NON 450–600 1 2.76 1.251 NON -(1/8-60) is rated at 125Vdc with 50,000 AIC Rating.
NON -(65-100) is rated at 125Vdc with 10,000 AIC Rating.
**Weight per carton.
Catalog Numbers—NOS ONE-TIME (600Vac)
NOS-1 NOS-12 NOS-70 NOS-225 NOS-2 NOS-15 NOS-75 NOS-250 NOS-3 NOS-20 NOS-80 NON-300 NOS-4 NOS-25 NOS-90 NOS-350 NOS-5 NOS-30 NOS-100 NOS-400 NOS-6 NOS-35 NOS-110 NOS-450 NOS-7 NOS-40 NOS-125 NOS-500 NOS-8 NOS-45 NOS-150 NOS-600 NOS-9 NOS-50 NOS-175 — NOS-10 NOS-60
CE logo denotes compliance with European Union Low Voltage Directive (50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. Applies to OPM-1038 and OPM-1038R.
Dimensions All diameters (± 0.008)
For CSA Certified 15-60A Ratings, see PON Data Sheet: 4126
10-2-02
SB02295
Recommended fuseblocks for Class H & K5, 250V & 600V fuses
See Data Sheets: 1112 (250V) and
1113 (600V)
One-Time General Purpose Fuses NON and NOS
250 and 600 Volts, ⁄Ω• to 600 Amps
Form No. NON/NOS
Page 2 of 2
Data Sheet: 1030
Bussmann
®
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information con­tained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Time-Current Characteristic Curves–Average Melt
NON ONE-TIME (250Vac) NOS ONE-TIME (600Vac)
10-2-02
SB02295
300
15A
20A
30A
35A
60A
100A
200A
400A
600A
AMPERE RATING
300
15A
20A
30A
35A
60A
100A
200A
400A
600A
AMPERE RATING
100
10
1
TIME IN SECONDS
.1
100
10
1
TIME IN SECONDS
.1
.08 .06
.04 .03
.02
.01
20
100
CURRENT IN AMPERES
1,000
10,000
.01
20
100
CURRENT IN AMPERES
1,000
10,000
Loading...