Bussmann Motor Circuit Protection Tables Technical Data

145
©2005 Cooper Bussmann
Columns 1 & 2
Motor horsepower ratings are listed in Column 1. Full load amps from Tables
430.247 through 430.250 are provided in Column 2.
Column 3
Various fuse types are listed in Column 3. The LPJ_SP is a 600Vac, 0 - 600 amp, time-delay, Class J, “Low-Peak fuse, with a 300,000 amp interrupting rating. The TCF is a 600Vac, 1 - 100 amp dual-element, time-delay, IP-20 finger-safe fuse with Class J performance. The LP-CC is a 600Vac, 0 - 30 amp, time-delay, Class CC, Low-Peak fuse with a 200,000 amp interrupting rating. The LPS-RK_SP and LPN­RK_SP are 600 and 250Vac, 0 - 600 amp, time-delay, Class RK1, Low-Peak fuses with interrupting ratings of 300,000 amps. FRS-R and FRN-R are 600 and 250Vac, 0 - 600 amp, time-delay, Class RK5, Fusetron Dual-Element fuses with interrupting ratings of 200,000 amps. The KRP-C_SP is a 600Vac, 601 - 6000 amp, time-delay, Class L, Low-Peak fuse, with a 300,000 amp AC interrupting rating. The DC listed ratings for these fuses are:
LPJ 1 to 600SP 300Vdc LPN-RK 0 to 60SP 125Vdc TCF 1 to 100 300Vdc LPN-RK 70 to 600SP 250Vdc LP-CC
1
2 to 2 8⁄10 300Vdc LPS-RK 0 to 600SP 300Vdc LP-CC 3 to 15 150Vdc FRN-R 0 to 600 125Vdc LP-CC 20 to 30 300Vdc FRS-R 0 to 600 300Vdc
Column 4 - Optimal Branch Circuit Protection
There are two distinct levels of protection philosophy provided in this Column. LPS­RK_SP, LPN-RK_SP, FRS-R and FRN-R fuses are sized for motor running “back-up” protection and provide superb short circuit protection at the same time. LPJ_SP, TCF, and LP-CC fuses are sized a little larger but are even more current limiting, providing an even greater degree of short circuit protection for the motor circuit.
All the fuses selected from this column provide short circuit and ground-fault pro­tection for motor branch circuits (430.52), but typically are not the maximum allowed. Fuses sized in accordance with Column 4 must be used in conjunction with properly sized motor overload protection such as overload relays or solid state motor controllers (430.32). This fuse sizing is normally large enough to allow the overload protective device to operate on overloads without opening the fuse. Yet for many cases, this fuse amp rating selection is smaller than the maximums allowed per Columns 5 or 6 (430.52). In some cases, this smaller amp rating selection may provide the benefits of a smaller size disconnect and better short cir­cuit protection. If a motor has a long starting time, high starting current profile or is cycled frequently, it may be necessary to use Column 5 or 6.
The LPS-RK_SP, LPN-RK_SP, FRS-R and FRN-R fuses sized per this column pro­vide short circuit and ground-fault protection for motor branch circuits (430.52) as discussed in the previous paragraph. In addition, these dual-element fuses exhibit longer time-delay characteristics and can therefore be sized to provide back-up motor overload protection. The fuse sizing in Column 4 for LPS-RK_SP, LPN­RK_SP, FRS-R and FRN-R fuses provides a degree of motor and circuit overload protection to back-up the normal motor overload protective device. Note: This level of protection requires a well-designed, true dual-element fuse. The Fusetron Fuses, FRS-R and FRN-R, and Low-Peak Fuses, LPS-RK_SP and LPN-RK_SP, are the industry leading dual-element fuses with excellent over-load time-delay characteristics and current-limiting short circuit ability. The Low-Peak Dual-Element Fuses have better current-limiting ability than Fusetron Dual-Element Fuses.
The amp ratings in Column 4 are determined by using Column 2 motor ampacity values and the following:
LPJ_SP & TCF: 150% or the next larger Cooper Bussmann amp rating if 150% does
not correspond to a Cooper Bussmann fuse amp rating.
LP-CC 1⁄2 to 15A: 200% (150% for DC) or the next larger Cooper Bussmann size if
200% (150% for DC) does not correspond to a Cooper Bussmann fuse amp rating.
LP-CC 20 to 30A: 300% (150% for DC) or the next larger Cooper Bussmann size if
300% (150% for DC) does not correspond to a Cooper Bussmann fuse amp rating.
LPS-RK_SP and LPN-RK_SP: 130% or the next larger Cooper Bussmann amp rat-
ing if 130% does not correspond to a Cooper Bussmann fuse amp rating.
FRS-R and FRN-R: 125% or the next larger Cooper Bussmann amp rating if 125%
does not correspond to a Cooper Bussmann fuse amp rating.
Column 5 - Branch Circuit Protection, Max. General Applications
Fuses selected from this column are intended to provide short circuit and ground­fault protection for motor branch circuits. Fuses sized in accordance with Column 5 must be used in conjunction with properly sized motor overload protection such as overload relays or solid state motor controllers (430.32). Column 5 fuse sizing provides the maximum NEC®Table 430.52 amp ratings for general purpose applications. It takes into account 430.52(C)(1) Exception No. 1, which allows the next standard amp rating fuse (per standard fuse amp ratings in 240.6) to be used if the maximum percentage in Table 430.52 does not correspond to a standard fuse amp rating. If this Column 5 fuse sizing does not allow the motor to start, then Column 6 may provide a larger amp rating.
The amp ratings in Column 5 are deter-mined by using Column 2 motor ampacity values and the following:
LPJ_SP, TCF, LPS-RK_SP, LPN-RK_SP, FRS-R, FRN-R and KRP-C_SP: 175%
(150% for DC motors) or the next larger 240.6 standard fuse amp rating if 175% (150% for DC motors) does not correspond to a standard fuse amp rating.
LP-CC: 300% (150% for DC motors) or the next larger 240.6 standard fuse amp
rating if 300% (150% for DC motors) does not correspond to a standard fuse amp rating.
Sizes shown for the LP-CC can also be used for non-time delay fuses such as JKS,
KTN-R, KTS-R, JJN, JJS, and KTK-R.
Column 6 - Branch Circuit Protection, Max. Heavy Start
When the amp rating shown in Column 5 is not sufficient to start a motor, a larger amp rating is often available by utilizing 430.52(C)(1) Exception No. 2. The amp ratings in Column 6 are the larger of the amp rating allowed by 430.52(C)(1) Exception No. 1, or 430.52(C)(1) Exception No. 2. These amp ratings will often be required when acceleration times are greater than 5 seconds, when plugging or jogging applications exist, or where there are high inrush currents (such as Design E or energy efficient Design B motors). (In a few cases, the amp rating in Column 6 may be smaller than the maximum permitted due to the limitation of the fuse type, such as LP-CC, Class CC fuses that are only available in ratings up to 30 amps. In these cases, if the amp rating shown is not sufficient to start the motor, select a dif­ferent family of fuses that meet the requirements.) The amp ratings in Column 6 are determined by using Column 2 motor ampacity values and the following:
LPJ_SP, TCF, LPS-RK_SP, LPN-RK_SP, FRS-R, and FRN-R: 225% or the next
smaller Cooper Bussmann amp rating if 225% does not correspond to a Cooper Bussmann fuse amp rating.
LP-CC: 400% or the next smaller Cooper Bussmann amp rating if 400% does not cor-
respond to a Cooper Bussmann fuse amp rating.
KRP-C_SP: 300% or the next smaller Cooper Bussmann amp rating, if 300% does
not correspond to a Cooper Bussmann amp rating.
Sizes shown for the LP-CC can also be used for non-time delay fuses such as JKS, KTN-R, KTS-R, JJN, JJS, AND KTK-R.
Column 7
Horsepower-rated switch sizes given in Column 7 are based on 115% (430.110) of Column 2. Switch sizes need to be increased when, because of starting require­ments, the fuses are sized above the rating of the switch shown in this column.
Column 8
Sizes listed are for general-purpose magnetic controllers (single speed, full­volt-age for limited plugging and jogging-duty) as shown in NEMA Standards Publication ICS-2-2000.
Motor Circuit Protection Tables
NEC®Article 430 and Tables Explanation
146
©2005 Cooper Bussmann
Column 9
Copper wire sizes are based upon 125% (430.22) of values shown in Column 2 and ampacities listed in Table 310.16 for 75°C terminals. Although the NEC
®
allows 60°C terminations for equipment rated 100 amp or less, most equipment terminations have been rated for 75°C conductors. If equipment termi­nations are rated for 60°C conductors only, the 60°C ampacities must be utilized and therefore larger conductor sizes may be required than those shown in this col­umn. See 110.14(C) (1)(a)(4).
Column 10
These rigid metallic conduit sizes are based upon copper conductors with THWN or THHN insulation, Table C8 of Annex C, and 75°C equipment terminals.
Conduit sizes are for three conductors per circuit for three phase motors and two conductors per circuit for single phase and DC motors. Conduit sizes may need to be increased if equipment grounding conductors or neutrals are also installed in the conduit.
If equipment terminations are rated for 60°C conductors only, the 60°C ampacities must be utilized and therefore larger conductor sizes and conduit sizes may be required.
Conductors operated in a high ambient temperature may need to be derated. (See correction factor table at the bottom of Table 310.16.)
Motor Circuit Protection Tables
200Vac Three-Phase Motors & Circuits
12 3 456789 10 Motor Motor Fuse Optimal NEC
®
NEC®Max Minimum Minimum Minimum Minimum
Size FLA Branch Ckt Max for for Heavy Switch NEMA Copper Wire Rigid Metallic
Protection Gen. Applic Start Size Starter THWN or THHN AWG Conduit
Table Table 430.52(C)(1) 430.52(C)(1) 430.110 NEMA ICS 2- or KCMIL Annex C
430.250 430.250 Type Class Exc. No. 1 Exc. No. 2 2000 Table 310.16 Table C8 HP AMPS AMPS
1
AMPS
1
AMPS
1
AMPS Size Size Inches
LPJ_SP J 4 6 6
TCF J
ƒ
66 6
1
2 2.5 LP-CC CC 5 10 10 30 00 14
1
2
LPN-RK_SP RK1 3 1⁄2 66
FRN-R RK5 3 2⁄10 66
LPJ_SP J 5
6
10 10 10
TCF J
ƒ
610 10
3
4 3.7 LP-CC CC 7 1⁄2 15 15 30 00 14
1
2
LPN-RK_SP RK1 5 10 10
FRN-R RK5 5 10 10
LPJ_SP J 8 10 10
TCF J
ƒ
10 10 10
1 4.8 LP-CC CC 10 15 15 30 00 14
1
2
LPN-RK_SP RK1 6 1⁄4 10 10
FRN-R RK5 6 10 10
LPJ_SP J 12 15 15
TCF J
ƒ
15 15 15
1
1
2 6.9 LP-CC CC 15 25 25 30 00 14
1
2
LPN-RK_SP RK1 9 15 15
FRN-R RK5 9 15 15
LPJ_SP J 12 15 17
1
2
TCF J
ƒ
15 15 17 1⁄2
2 7.8 LP-CC CC 25 25 30 30 0 14
1
2
LPN-RK_SP RK1 12 15 17 1⁄2
FRN-R RK5 10 15 17 1⁄2
LPJ_SP J 17 1⁄2 20 20
TCF J
ƒ
17 1⁄2 20 20
3 11 LP-CC CC 25 30 0 14
1
2
LPN-RK_SP RK1 15 20 20
FRN-R RK5 15 20 20
LPJ_SP J 30 35 35
5 17.5 TCF J
ƒ
30 35 35 30* 1 12
1
2
LPN-RK_SP RK1 25 35 35
FRN-R RK5 25 35 35
LPJ_SP J 40 45 50
7
1
2 25.3 TCF J
ƒ
40 45 50 60 1 10**
1
2**
LPN-RK_SP RK1 35 45 50
FRN-R RK5 35 45 50
LPJ_SP J 50 60 70
10 32.2 TCF J
ƒ
50 60 – 60* 2 8** 1⁄2**
LPN-RK_SP RK1 45 60 70
FRN-R RK5 45 60 70
LPJ_SP J 80 90 100
15 48.3 TCF J
ƒ
80 90 100 100 3 6**
3
4**
LPN-RK_SP RK1 70 90 100
FRN-R RK5 70 90 100
LPJ_SP J 100 110 125
20 62.1 TCF J
ƒ
100 100* 3 4** 1
LPN-RK_SP RK1 90 110 125
FRN-R RK5 80 110 125
* Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. ** If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required.
ƒ
Class J performance, special finger-safe dimensions.
NEC®Article 430 and Tables Explanation
147
©2005 Cooper Bussmann
Motor Circuit Protection Tables
200Vac Three-Phase Motors & Circuits continued
12 3 456789 10 Motor Motor Fuse Optimal NEC
®
NEC®Max Minimum Minimum Minimum Minimum
Size FLA Branch Ckt Max for for Heavy Switch NEMA Copper Wire Rigid Metallic
Protection Gen. Applic Start Size Starter THWN or THHN AWG Conduit
Table Table 430.52(C)(1) 430.52(C)(1) 430.110 NEMA ICS 2- or KCMIL Annex C
430.250 430.250 Type Class Exc. No. 1 Exc. No. 2 2000 Table 310.16 Table C8 HP AMPS AMPS
1
AMPS
1
AMPS
1
AMPS Size Size Inches
LPJ_SP J 125 150 175
25 78.2 LPN-RK_SP RK1 110 150 175 100* 3 3** 1**
FRN-R RK5 100 150 175
LPJ_SP J 150 175 200
30 92 LPN-RK_SP RK1 125 175 200 200 4 2** 1**
FRN-R RK5 125 175 200
LPJ_SP J 200 225 250
40 120 LPN-RK_SP RK1 175 225 250 200* 4 1/0 1
1
4
FRN-R RK5 150 225 250
LPJ_SP J 225 300 300
50 150 LPN-RK_SP RK1 200 300 300 200* 5 3/0 1
1
2
FRN-R RK5 200 300 300
LPJ_SP J 300 350 350
60 177 LPN-RK_SP RK1 250 350 350 400 5 4/0 2
FRN-R RK5 225 350 350
LPJ_SP J 350 400 450
75 221 LPN-RK_SP RK1 300 400 450 400* 5 300 2
FRN-R RK5 300 400 450
KRP-C_SP L 650
LPJ_SP J 450 500 600
100 285 LPN-RK_SP RK1 400 500 600 400* 6 500 3
FRN-R RK5 400 500 600
KRP-C_SP L 800
LPJ_SP J 600
125 359 LPN-RK_SP RK1 500 600* 6 4/0 2/PHASE (2)2
FRN-R RK5 450
KRP-C_SP L 700 1000
LPN-RK_SP RK1 600
150 414 FRN-R RK5 600 600* 6 300 2/PHASE (2)2
KRP-C_SP L 800 1200
200 552 KRP-C_SP L 1000 1600 1200 72 500 2/PHASE (2)3
* Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. ** If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. 2 These sizes are typical. They are not shown in NEMA ICS 2-2000.
208Vac Three-Phase Motors & Circuits
12 3 456789 10 Motor Motor Fuse Optimal NEC
®
NEC®Max Minimum Minimum Minimum Minimum
Size FLA Branch Ckt Max for for Heavy Switch NEMA Copper Wire Rigid Metallic
Protection Gen. Applic Start Size Starter THWN or THHN AWG Conduit
Table Table 430.52(C)(1) 430.52(C)(1) 430.110 NEMA ICS 2- or KCMIL Annex C
430.250 430.250 Type Class Exc. No. 1 Exc. No. 2 2000 Table 310.16 Table C8 HP AMPS AMPS
1
AMPS
1
AMPS
1
AMPS Size2 Size Inches
LPJ_SP J 4 6 6
TCF J
ƒ
66 6
1
2 2.4 LP-CC CC 5 10 10 30 00 14
1
2
LPN-RK_SP RK1 3 1⁄2 66
FRN-R RK5 3 6 6
LPJ_SP J 5
6
10 10 10
TCF J
ƒ
610 10
3
4 3.5 LP-CC CC 7 15 15 30 00 14
1
2
LPN-RK_SP RK1 5 10 10
FRN-R RK5 4 1⁄2 10 10
LPJ_SP J 7 10 10
TCF J
ƒ
10 10 10
1 4.6 LP-CC CC 10 15 15 30 00 14
1
2
LPN-RK_SP RK1 6 10 10
FRN-R RK5 6 10 10
LPJ_SP J 10 15 15
TCF J
ƒ
10 15 15
1
1
2 6.6 LP-CC CC 15 20 25 30 00 14
1
2
LPN-RK_SP RK1 9 15 15
FRN-R RK5 9 15 15
*Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. **If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. 2 These sizes are typical. They are not shown in NEMA ICS 2-2000.
ƒ
Class J performance, special finger-safe dimensions.
148
©2005 Cooper Bussmann
Motor Circuit Protection Tables
208Vac Three-Phase Motors & Circuits continued
12 3 456789 10 Motor Motor Fuse Optimal NEC
®
NEC®Max Minimum Minimum Minimum Minimum
Size FLA Branch Ckt Max for for Heavy Switch NEMA Copper Wire Rigid Metallic
Protection Gen. Applic Start Size Starter THWN or THHN AWG Conduit
Table Table 430.52(C)(1) 430.52(C)(1) 430.110 NEMA ICS 2- or KCMIL Annex C
430.250 430.250 Type Class Exc. No. 1 Exc. No. 2 2000 Table 310.16 Table C8 HP AMPS AMPS
1
AMPS
1
AMPS
1
AMPS Size
2
Size Inches
LPJ_SP J 12 15 15
TCF J
ƒ
15 15 15
2 7.5 LP-CC CC 15 25 30 30 0 14
1
2
LPN-RK_SP RK1 10 15 15
FRN-R RK5 10 15 15
LPJ_SP J 17
1
2 20 20
3 10.6 TCF J
ƒ
17 1⁄2 20 20 30 0 14
1
2
LPN-RK_SP RK1 15 20 20
FRN-R RK5 15 20 20
LPJ_SP J 30 30 35
5 16.7 TCF J
ƒ
30 30 35 30* 1 12
1
2
LPN-RK_SP RK1 25 30 35
FRN-R RK5 25 30 35
LPJ_SP J 40 45 50
7
1
2 24.2 TCF J
ƒ
40 45 50 60 1 10**
1
2
LPN-RK_SP RK1 35 45 50
FRN-R RK5 35 45 50
LPJ_SP J 50 60 60
10 30.8 TCF J
ƒ
50 60 60 60 2 8
1
2**
LPN-RK_SP RK1 45 60 60
FRN-R RK5 40 60 60
LPJ_SP J 70 90 100
15 46.2 TCF J
ƒ
70 90 100 60* 3 6**
3
4**
LPN-RK_SP RK1 70 90 100
FRN-R RK5 60 90 100
LPJ_SP J 90 110 125
20 59.4 TCF J
ƒ
90 100* 3 4** 1
LPN-RK_SP RK1 80 110 125
FRN-R RK5 80 110 125
LPJ_SP J 125 150 150
25 74.8 LPN-RK_SP RK1 100 150 150 100* 3 3** 1**
FRN-R RK5 100 150 150
LPJ_SP J 150 175 175
30 88 LPN-RK_SP RK1 125 175 175 200 4 2** 1**
FRN-R RK5 110 175 175
LPJ_SP J 175 200 250
40 114 LPN-RK_SP RK1 150 200 250 200* 4 1/0 1
1
4
FRN-R RK5 150 200 250
LPJ_SP J 225 300 300
50 143 LPN-RK_SP RK1 200 300 300 200* 5 3/0 1
1
2
FRN-R RK5 200 300 300
LPJ_SP J 300 300 350
60 169 LPN-RK_SP RK1 225 300 350 400 5 4/0 2
FRN-R RK5 225 300 350
LPJ_SP J 350 400 450
75 211 LPN-RK_SP RK1 300 400 450 400* 5 300 2
FRN-R RK5 300 400 450
KRP-C_SP L 601
LPJ_SP J 450 500 600
100 273 LPN-RK_SP RK1 400 500 600 400* 6 500 3
FRN-R RK5 350 500 600
KRP-C_SP L 800
LPJ_SP J 600
125 343 LPN-RK_SP RK1 450 600* 6 4/0 2/PHASE (2)2
FRN-R RK5 450
KRP-C_SP L 601 1000
LPJ_SP J 600
150 396 LPN-RK_SP RK1 600 600* 6 250 2/PHASE (2)2
FRN-R RK5 500
KRP-C_SP L 700 1100
200 528 KRP-C_SP L 1000 1500 1200* 7 400 2/PHASE (2)2-2 1⁄2
*Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. **If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. 2 These sizes are typical. They are not shown in NEMA ICS 2-2000.
ƒ
Class J performance, special finger-safe dimensions.
149
©2005 Cooper Bussmann
Motor Circuit Protection Tables
230Vac Three-Phase Motors & Circuits (220-240Vac Systems)
12 3 456789 10 Motor Motor Fuse Optimal NEC
®
NEC®Max Minimum Minimum Minimum Minimum
Size FLA Branch Ckt Max for for Heavy Switch NEMA Copper Wire Rigid Metallic
Protection Gen. Applic Start Size Starter THWN or THHN AWG Conduit
Table Table 430.52(C)(1) 430.52(C)(1) 430.110 NEMA ICS 2- or KCMIL Annex C
430.250 430.250 Type Class Exc. No. 1 Exc. No. 2 2000 Table 310.16 Table C8 HP AMPS AMPS
1
AMPS
1
AMPS
1
AMPS Size
2
Size Inches
LPJ_SP J 3
1
2 66
TCF J
ƒ
66 6
1
2 2.2 LP-CC CC 4 1⁄2 10 10 30 00 14
1
2
LPN-RK_SP RK1 3 6 6
FRN-R RK5 2 8/10 6 6
LPJ_SP J 5 6 7
TCF J
ƒ
66 6
3
4 3.2 LP-CC CC 7 10 12 30 00 14
1
2
LPN-RK_SP RK1 4 1⁄2 67
FRN-R RK5 4 6 7
LPJ_SP J 7 10 10
TCF J
ƒ
10 10 10
1 4.2 LP-CC CC 9 15 15 30 00 14
1
2
LPN-RK_SP RK1 5 6⁄10 10 10
FRN-R RK5 5 8⁄10 10 10
LPJ_SP J 9 15 15
TCF J
ƒ
10 15 15
1
1
2 6 LP-CC CC 12 20 20 30 00 14
1
2
LPN-RK_SP RK1 8 15 15
FRN-R RK5 7 1⁄2 15 15
LPJ_SP J 12 15 15
TCF J
ƒ
15 15 15
2 6.8 LP-CC CC 15 25 25 30 0 14
1
2
LPN-RK_SP RK1 9 15 15
FRN-R RK5 9 15 15
LPJ_SP J 15 20 20
TCF J
ƒ
15 20 20
3 9.6 LP-CC CC 30 30 30 30 0 14
1
2
LPN-RK_SP RK1 15 20 20
FRN-R RK5 12 20 20
LPJ_SP J 25 30 30
5 15.2 TCF J
ƒ
25 30 30 30 1 14
1
2
LPN-RK_SP RK1 20 30 30
FRN-R RK5 20 30 30
LPJ_SP J 35 40 45
7
1
2 22 TCF J
ƒ
34 40 45 30* 1 10
1
2
LPN-RK_SP RK1 30 40 45
FRN-R RK5 30 40 45
LPJ_SP J 45 50 60
10 28 TCF J
ƒ
45 50 60 60 2 10**
1
2
LPN-RK_SP RK1 40 50 60
FRN-R RK5 35 50 60
LPJ_SP J 70 80 90
15 42 TCF J
ƒ
70 80 90 60* 2 6
3
4
LPN-RK_SP RK1 60 80 90
FRN-R RK5 60 80 90
LPJ_SP J 90 100 110
20 54 TCF J
ƒ
90 100 100* 3 4 1
LPN-RK_SP RK1 80 100 110
FRN-R RK5 70 100 110
LPJ_SP J 110 125 150
25 68 LPN-RK_SP RK1 90 125 150 100* 3 4** 1
FRN-R RK5 90 125 150
LPJ_SP J 125 150 175
30 80 LPN-RK_SP RK1 110 150 175 100* 3 3** 1**
FRN-R RK5 100 150 175
LPJ_SP J 175 200 225
40 104 LPN-RK_SP RK1 150 200 225 200* 4 1** 1
1
4**
FRN-R RK5 150 200 225
LPJ_SP J 200 250 250
50 130 LPN-RK_SP RK1 175 250 250 200* 4 2/0 1
1
2
FRN-R RK5 175 250 250
LPJ_SP J 250 300 300
60 154 LPN-RK_SP RK1 225 300 300 200* 5 3/0 1
1
2
FRN-R RK5 200 300 300
*Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. **If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. 2 These sizes are typical. They are not shown in NEMA ICS 2-2000.
ƒ
Class J performance, special finger-safe dimensions.
4 Limited by 600 amp being the largest amp rating for FRN-R and LPN-RK_SP.
150
©2005 Cooper Bussmann
Motor Circuit Protection Tables
230Vac Three-Phase Motors & Circuits (220-240Vac Systems) continued
460Vac Three-Phase Motors & Circuits (440-480Vac Systems)
12 3 456789 10 Motor Motor Fuse Optimal NEC
®
NEC®Max Minimum Minimum Minimum Minimum
Size FLA Branch Ckt Max for for Heavy Switch NEMA Copper Wire Rigid Metallic
Protection Gen. Applic Start Size Starter THWN or THHN AWG Conduit
Table Table 430.52(C)(1) 430.52(C)(1) 430.110 NEMA ICS 2- or KCMIL Annex C
430.250 430.250 Type Class Exc. No. 1 Exc. No. 2 2000 Table 310.16 Table C8 HP AMPS AMPS
1
AMPS
1
AMPS
1
AMPS Size
2
Size Inches
LPJ_SP J 1
8
10 33
TCF J
ƒ
33 3
1
2 1.1 LP-CC CC 2 1⁄4 6 6 30 00 14
1
2
LPS-RK_SP RK1 1 11⁄2 33
FRS-R RK5 1 4⁄10 33
LPJ_SP J 2
1
2 33
1
2
TCF J
ƒ
33 3
3
4 1.6 LP-CC CC 3 2⁄10 66
1
4 30 00 14
1
2
LPS-RK_SP RK1 2 1⁄4 33
1
2
FRS-R RK5 2 3 3 1⁄2
LPJ_SP J 3 2⁄10 66
TCF J
ƒ
66 6
1 2.1 LP-CC CC 4
1
2 10 10 30 00 14
1
2
LPS-RK_SP RK1 2 8⁄10 66
FRS-R RK5 2 8⁄10 66
LPJ_SP J 4
1
2 66
TCF J
ƒ
66 6
1
1
2 3 LP-CC CC 6 10 12 30 00 14
1
2
LPS-RK_SP RK1 4 6 6 1⁄4
FRS-R RK5 4 6 6 1⁄4
LPJ_SP J 5 6⁄10 67
TCF J
ƒ
66 6
2 3.4 LP-CC CC 7 1 5 15 30 00 14
1
2
LPS-RK_SP RK1 4 1⁄2 67
FRS-R RK5 4 1⁄2 67
1
2
LPJ_SP J 8 10 10
TCF J
ƒ
10 10 10
3 4.8 LP-CC CC 10 15 15 30 0 14
1
2
LPS-RK_SP RK1 6 1⁄4 10 10
FRS-R RK5 6 10 10
LPJ_SP J 12 15 15
TCF J
ƒ
15 15 15
5 7.6 LP-CC CC 25 25 30 30 0 14
1
2
LPS-RK_SP RK1 10 15 15
FRS-R RK5 10 15 15
* Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. ** If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required.
ƒ
Class J performance, special finger-safe dimensions.
12 3 456789 10 Motor Motor Fuse Optimal NEC
®
NEC®Max Minimum Minimum Minimum Minimum
Size FLA Branch Ckt Max for for Heavy Switch NEMA Copper Wire Rigid Metallic
Protection Gen. Applic Start Size Starter THWN or THHN AWG Conduit
Table Table 430.52(C)(1) 430.52(C)(1) 430.110 NEMA ICS 2- or KCMIL Annex C
430.250 430.250 Type Class Exc. No. 1 Exc. No. 2 2000 Table 310.16 Table C8 HP AMPS AMPS
1
AMPS
1
AMPS
1
AMPS Size
2
Size Inches
LPJ_SP J 300 350 400
75 192 LPN-RK_SP RK1 250 350 400 400 5 250 2
FRN-R RK5 250 350 400
LPJ_SP J 400 450 500
100 248 LPN-RK_SP RK1 350 450 500 400* 5 350 2
1
2
FRN-R RK5 350 450 500
KRP-C_SP L 700
LPJ_SP J 500 600
125 312 LPN-RK_SP RK1 450 600 400* 6 3/0 2/PHASE (2) 1
1
2
FRN-R RK5 400 600
KRP-C_SP L 900
LPJ_SP J 600
150 360 LPN-RK_SP RK1 500 6004 600* 6 4/0 2/PHASE (2) 2
FRN-R RK5 450 6004
KRP-C_SP L 700 1000
200 480 FRN-R RK5 600 600* 6 350 2/PHASE (2) 2-2
1
2
KRP-C_SP L 1000 1400
*Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. **If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. 2 These sizes are typical. They are not shown in NEMA ICS 2-2000. 4 Limited by 600 amp being the largest amp rating for FRN-R and LPN-RK_SP.
151
©2005 Cooper Bussmann
Motor Circuit Protection Tables
460Vac Three-Phase Motors & Circuits (440-480Vac Systems) continued
12 3 456789 10 Motor Motor Fuse Optimal NEC
®
NEC®Max Minimum Minimum Minimum Minimum
Size FLA Branch Ckt Max for for Heavy Switch NEMA Copper Wire Rigid Metallic
Protection Gen. Applic Start Size Starter THWN or THHN AWG Conduit
Table Table 430.52(C)(1) 430.52(C)(1) 430.110 NEMA ICS 2- or KCMIL Annex C
430.250 430.250 Type Class Exc. No. 1 Exc. No. 2 2000 Table 310.16 Table C8 HP AMPS AMPS
1
AMPS
1
AMPS
1
AMPS Size
2
Size Inches
LPJ_SP J 17
1
2 20 20
7
1
2 11 TCF J
ƒ
17 1⁄2 20 20 30 1 14
1
2
LPS-RK_SP RK1 15 20 20
FRS-R RK5 15 20 20
LPJ_SP J 25 25 30
10 14 TCF J
ƒ
25 25 30 30 1 14
1
2
LPS-RK_SP RK1 20 25 30
FRS-R RK5 17 1⁄2 25 30
LPJ_SP J 35 40 45
15 21 TCF J
ƒ
35 40 45 30* 2 10
1
2
LPS-RK_SP RK1 30 40 45
FRS-R RK5 30 40 45
LPJ_SP J 45 50 60
20 27 TCF J
ƒ
45 50 60 60 2 10**
1
2
LPS-RK_SP RK1 40 50 60
FRS-R RK5 35 50 60
LPJ_SP J 60 60 70
25 34 TCF J
ƒ
60 60 70 60* 2 8**
1
2**
LPS-RK_SP RK1 45 60 70
FRS-R RK5 45 60 70
LPJ_SP J 60 70 90
30 40 TCF J
ƒ
60 70 90 60* 3 8**
1
2**
LPS-RK_SP RK1 60 70 90
FRS-R RK5 50 70 90
LPJ_SP J 80 100 110
40 52 TCF J
ƒ
80 100 100* 3 6**
3
4**
LPS-RK_SP RK1 70 100 110
FRS-R RK5 70 100 110
LPJ_SP J 100 125 125
50 65 TCF J
ƒ
100 100* 3 4** 1
LPS-RK_SP RK1 90 125 125
FRS-R RK5 90 125 125
LPJ_SP J 125 150 150
60 77 LPS-RK_SP RK1 110 150 150 100* 4 3** 1**
FRS-R RK5 100 150 150
LPJ_SP J 150 175 200
75 96 LPS-RK_SP RK1 125 175 200 200 4 1** 1
1
4**
FRS-R RK5 125 175 200
LPJ_SP J 200 225 250
100 124 LPS-RK_SP RK1 175 225 250 200* 4 2/0 1
1
2
FRS-R RK5 175 225 250
LPJ_SP J 250 300 350
125 156 LPS-RK_SP RK1 225 300 350 200* 5 3/0 1
1
2
FRS-R RK5 200 300 350
LPJ_SP J 300 350 400
150 180 LPS-RK_SP RK1 250 350 400 400 5 4/0 2
FRS-R RK5 225 350 400
LPJ_SP J 400 450 500
200 240 LPS-RK_SP RK1 350 450 500 400* 5 350 2
1
2
FRS-R RK5 300 450 500
KRP-C_SP L 700
LPJ_SP J 500 600
250 302 LPS-RK_SP RK1 400 600 400* 6 3/0 2/PHASE (2) 1
1
2
FRS-R RK5 400 600
KRP-C_SP L 900
LPJ_SP J 600
300 361 LPS-RK_SP RK1 500 6004 600* 6 4/0 2/PHASE (2) 2
FRS-R RK5 500 6004
KRP-C_SP L 700 1000
LPS-RK_SP RK1 600
350 414 FRS-R RK5 600 600* 6 300 2/PHASE (2) 2
KRP-C_SP L 800 1200
400 477 KRP-C_SP L 1000 1400 600* 6 350 2/PHASE (2 )2
1
2
FRS-R RK5 600 – 450 515 KRP-C_SP L 1000 1500 1200* 7 400 2/PHASE (2) 2 1⁄2 500 590 KRP-C_SP L 1200 1600 1200* 7 500 2/PHASE (2) 3
* Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. ** If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. 4 Limited by 600 amp being the largest amp rating for FRS-R and LPS-RK_SP.
ƒ
Class J performance, special finger-safe dimensions.
152
©2005 Cooper Bussmann
Motor Circuit Protection Tables
575Vac Three-Phase Motors & Circuits (550-600Vac Systems)
12 3 456789 10 Motor Motor Fuse Optimal NEC
®
NEC®Max Minimum Minimum Minimum Minimum
Size FLA Branch Ckt Max for for Heavy Switch NEMA Copper Wire Rigid Metallic
Protection Gen. Applic Start Size Starter THWN or THHN AWG Conduit
Table Table 430.52(C)(1) 430.52(C)(1) 430.110 NEMA ICS 2- or KCMIL Annex C
430.250 430.250 Type Class Exc. No. 1 Exc. No. 2 2000 Table 310.16 Table C8 HP AMPS AMPS
1
AMPS
1
AMPS
1
AMPS Size
2
Size Inches
LPJ_SP J 1
4
10 33
TCF J
ƒ
33 3
1
2 0.9 LP-CC CC 1 8⁄10 33
1
2 30 0 14
1
2
LPS-RK_SP RK1 1 1⁄4 33
FRS-R RK5 1 1⁄8 33
LPJ_SP J 2 3 3
TCF J
ƒ
33 3
3
4 1.3 LP-CC CC 2 8⁄10 6 6 30 0 14
1
2
LPS-RK_SP RK1 1 8⁄10 33
FRS-R RK5 1 8⁄10 33
LPJ_SP J 2
8
10 33
1
2
TCF J
ƒ
33 3
1 1.7 LP-CC CC 3
1
2 66
1
4 30 0 14
1
2
LPS-RK_SP RK1 2 1⁄4 33
1
2
FRS-R RK5 2 1⁄4 33
1
2
LPJ_SP J 4 6 6
TCF J
ƒ
66 6
1
1
2 2.4 LP-CC CC 5 10 10 30 0 14
1
2
LPS-RK_SP RK1 3 2⁄10 66
FRS-R RK5 3 6 6
LPJ_SP J 4
1
2 66
TCF J
ƒ
66 6
2 2.7 LP-CC CC 5
6
10 10 10 30 0 14
1
2
LPS-RK_SP RK1 4 6 6
FRS-R RK5 3 1⁄2 66
LPJ_SP J 6 10 10
TCF J
ƒ
610 10
3 3.9 LP-CC CC 5 15 15 30 0 14
1
2
LPS-RK_SP RK1 5 6⁄10 10 10
FRS-R RK5 5 10 10
LPJ_SP J 10 15 15
TCF J
ƒ
10 15 15
5 6.1 LP-CC CC 15 20 20 30 0 14
1
2
LPS-RK_SP RK1 8 15 15
FRS-R RK5 8 15 15
LPJ_SP J 15 20 20
TCF J
ƒ
15 20 20
7
1
2 9 LP-CC CC 30 30 30 30 1 14
1
2
LPS-RK_SP RK1 12 20 20
FRS-R RK5 12 20 20
LPJ_SP J 17
1
2 20 20
10 11 TCF J
ƒ
17 1⁄2 20 20 30 1 14
1
2
LPS-RK_SP RK1 15 20 20
FRS-R RK5 15 20 20
LPJ_SP J 30 30 35
15 17 TCF J
ƒ
30 30 35 30* 2 12
1
2
LPS-RK_SP RK1 25 30 35
FRS-R RK5 25 30 35
LPJ_SP J 35 40 45
20 22 TCF J
ƒ
35 40 45 30* 2 10
1
2
LPS-RK_SP RK1 30 40 45
FRS-R RK5 30 40 45
LPJ_SP J 45 50 60
25 27 TCF J
ƒ
45 50 60 60 2 10**
1
2**
LPS-RK_SP RK1 40 50 60
FRS-R RK5 35 50 60
LPJ_SP J 50 60 70
30 32 TCF J
ƒ
50 60 70 60* 3 8
1
2
LPS-RK_SP RK1 45 60 70
FRS-R RK5 40 60 70
LPJ_SP J 70 80 90
40 41 TCF J
ƒ
70 80 90 60* 3 6
3
4
LPS-RK_SP RK1 60 80 90
FRS-R RK5 60 80 90
LPJ_SP J 80 100 110
50 52 TCF J
ƒ
80 100 100* 3 6**
3
4**
LPS-RK_SP RK1 70 100 110
FRS-R RK5 70 100 110
*Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. **If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. 2 These sizes are typical. They are not shown in NEMA ICS 2-2000.
ƒ
Class J performance, special finger-safe dimensions.
153
©2005 Cooper Bussmann
Motor Circuit Protection Tables
575Vac Three-Phase Motors & Circuits (550-600Vac Systems) continued
12 3 456789 10 Motor Motor Fuse Optimal NEC
®
NEC®Max Minimum Minimum Minimum Minimum
Size FLA Branch Ckt Max for for Heavy Switch NEMA Copper Wire Rigid Metallic
Protection Gen. Applic Start Size Starter THWN or THHN AWG Conduit
Table Table 430.52(C)(1) 430.52(C)(1) 430.110 NEMA ICS 2- or KCMIL Annex C
430.250 430.250 Type Class Exc. No. 1 Exc. No. 2 2000 Table 310.16 Table C8 HP AMPS AMPS
1
AMPS
1
AMPS
1
AMPS Size
2
Size Inches
LPJ_SP J 100 110 125
60 62 LPS-RK_SP RK1 90 110 125 100* 4 4** 1
FRS-R RK5 80 110 125
LPJ_SP J 125 150 150
75 77 LPS-RK_SP RK1 110 150 150 100* 4 3** 1**
FRS-R RK5 100 150 150
LPJ_SP J 150 175 200
100 99 LPS-RK_SP RK1 150 175 200 200 4 1** 1
1
4**
FRS-R RK5 125 175 200
LPJ_SP J 200 225 250
125 125 LPS-RK_SP RK1 175 225 250 200* 5 2/0 1
1
2
FRS-R RK5 175 225 250
LPJ_SP J 225 300 300
150 144 LPS-RK_SP RK1 200 300 300 200* 5 3/0 1
1
2
FRS-R RK5 200 300 300
LPJ_SP J 300 350 400
200 192 LPS-RK_SP RK1 250 350 400 400 5 250 2
FRS-R RK5 250 350 400
LPJ_SP J 400 450 500
250 242 LPS-RK_SP RK1 350 450 500 400* 6 350 2
1
2
FRS-R RK5 350 450 500
KRP-C_SP L 700
LPJ_SP J 450 600 600
300 289 LPS-RK_SP RK1 400 600 600 400* 6 500 3
FRS-R RK5 400 600 600
KRP-C_SP L 800
LPJ_SP J 600 600
350 336 LPS-RK_SP RK1 450 600 600* 6 4/0 2/PHASE (2) 2
FRS-R RK5 450 600
KRP-C_SP L 601 1000
LPJ_SP J 600
400 382 LPS-RK_SP RK1 500 600* 6 250 2/PHASE (2) 2
FRS-R RK5 500
KRP-C_SP L 700 1100
LPS-RK_SP RK1 600
450 412 FRS-R RK5 600 600* 7 300 2/PHASE (2) 2
KRP-C_SP L 800 1200
500 472 FRS-R RK5 600 600* 7 350 2/PHASE (2) 2
1
2
KRP-C_SP L 1000 1400
* Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. ** If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. 2 These sizes are typical. They are not shown in NEMA ICS 2-2000.
154
©2005 Cooper Bussmann
Motor Circuit Protection Tables
115Vac Single-Phase Motors & Circuits (110-120Vac Systems)
12 3 456789 10 Motor Motor Fuse Optimal NEC
®
NEC®Max Minimum Minimum Minimum Minimum
Size FLA Branch Ckt Max for for Heavy Switch NEMA Copper Wire Rigid Metallic
Protection Gen. Applic Start Size Starter THWN or THHN AWG Conduit
Table Table 430.52(C)(1) 430.52(C)(1) 430.110 NEMA ICS 2- or KCMIL Annex C
430.248 430.248 Type Class Exc. No. 1 Exc. No. 2 2000 Table 310.16 Table C8 HP AMPS AMPS
1
AMPS
1
AMPS
1
AMPS Size
2
Size Inches
LPJ_SP J 8 10 10
TCF J
ƒ
10 10 10
1
6 4.4 LP-CC CC 9 15 15 30 00 14
1
2
LPN-RK_SP RK1 6 10 10
FRN-R RK5 5 6/10 10 10
LPJ_SP J 9 15 15
TCF J
ƒ
10 15 15
1
4 5.8 LP-CC CC 12 20 20 30 00 14
1
2
LPN-RK_SP RK1 8 15 15
FRN-R RK5 7 1⁄2 15 15
LPJ_SP J 12 15 15
TCF J
ƒ
15 15 15
1
3 7.2 LP-CC CC 15 25 25 30 00 14
1
2
LPN-RK_SP RK1 10 15 15
FRN-R RK5 9 15 15
LPJ_SP J 15 20 20
TCF J
ƒ
15 20 20
1
2 9.8 LP-CC CC 30 30 30 30 0 14
1
2
LPN-RK_SP RK1 15 20 20
FRN-R RK5 15 20 20
LPJ_SP J 25 25 30
3
4 13.8 TCF J
ƒ
25 25 30 30 0 14
1
2
LPN-RK_SP RK1 20 25 30
FRN-R RK5 17 1⁄2 25 30
LPJ_SP J 25 30 35
1 16 TCF J
ƒ
25 30 35 30* 0 14
1
2
LPN-RK_SP RK1 25 30 35
FRN-R RK5 20 30 35
LPJ_SP J 30 35 45
1
1
2 20 TCF J
ƒ
30 35 45 30* 1 12
1
2
LPN-RK_SP RK1 30 35 45
FRN-R RK5 25 35 45
LPJ_SP J 40 45 50
2 24 TCF J
ƒ
40 45 50 30* 1 10
1
2
LPN-RK_SP RK1 35 45 50
FRN-R RK5 30 45 50
LPJ_SP J 60 60 70
3 34 TCF J
ƒ
60 60 70 60* 2 8**
1
2**
LPN-RK_SP RK1 45 60 70
FRN-R RK5 45 60 70
LPJ_SP J 90 100 125
5 56 TCF J
ƒ
90 100 100* 3 4
3
4**
LPN-RK_SP RK1 80 100 125
FRN-R RK5 70 100 125
LPJ_SP J 125 150 175
7
1
2 80 LPN-RK_SP RK1 110 150 175 100* 3 3** 1**
FRN-R RK5 100 150 175
LPJ_SP J 150 175 225
10 100 LPN-RK_SP RK1 150 175 225 200* 42 1 1
1
4
FRN-R RK5 125 175 225
* Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. ** If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. 2 These sizes are typical. They are not shown in NEMA ICS 2-2000.
ƒ
Class J performance, special finger-safe dimensions.
155
©2005 Cooper Bussmann
Motor Circuit Protection Tables
230Vac Single-Phase Motors & Circuits (220-240Vac Systems)
12 3 456789 10 Motor Motor Fuse Optimal NEC
®
NEC®Max Minimum Minimum Minimum Minimum
Size FLA Branch Ckt Max for for Heavy Switch NEMA Copper Wire Rigid Metallic
Protection Gen. Applic Start Size Starter THWN or THHN AWG Conduit
Table Table 430.52(C)(1) 430.52(C)(1) 430.110 NEMA ICS 2- or KCMIL Annex C
430.248 430.248 Type Class Exc. No. 1 Exc. No. 2 2000 Table 310.16 Table C8 HP AMPS AMPS
1
AMPS
1
AMPS
1
AMPS Size
2
Size Inches
LPJ_SP J 3
1
2 66
TCF J
ƒ
66 6
1
6 2.2 LP-CC CC 4 1⁄2 10 10 30 00 14
1
2
LPN-RK_SP RK1 3 6 6
FRN-R RK5 2 8⁄10 66
LPJ_SP J 4
1
2 66
TCF J
ƒ
66 6
1
4 2.9 LP-CC CC 6 10 10 30 00 14
1
2
LPN-RK_SP RK1 4 6 6 1⁄4
FRN-R RK5 4 6 6 1⁄4
LPJ_SP J 5 6⁄10 10 10
TCF J
ƒ
610 10
1
3 3.6 LP-CC CC 7 15 15 30 00 14
1
2
LPN-RK_SP RK1 5 10 10
FRN-R RK5 4 1⁄2 10 10
LPJ_SP J 8 10 10
TCF J
ƒ
10 10 10
1
2 4.9 LP-CC CC 10 15 15 30 00 14
1
2
LPN-RK_SP RK1 8 10 10
FRN-R RK5 6 1⁄4 10 10
LPJ_SP J 12 15 15
TCF J
ƒ
15 15 15
3
4 6.9 LP-CC CC 15 25 25 30 00 14
1
2
LPN-RK_SP RK1 9 15 15
FRN-R RK5 9 15 15
LPJ_SP J 12 15 17
1
2
TCF J
ƒ
15 15 17 1⁄2
1 8 LP-CC CC 25 25 30 30 00 14
1
2
LPN-RK_SP RK1 12 15 17 1⁄2
FRN-R RK5 10 15 17 1⁄2
LPJ_SP J 15 20 20
TCF J
ƒ
15 20 20
1
1
2 10 LP-CC CC 30 30 30 30 0 14
1
2
LPN-RK_SP RK1 15 20 20
FRN-R RK5 15 20 20
LPJ_SP J 20 25 25
TCF J
ƒ
20 25 25
2 12 LP-CC CC 25 30 0 14
1
2
LPN-RK_SP RK1 17 1⁄2 25 25
FRN-R RK5 15 25 25
LPJ_SP J 30 30 35
3 17 TCF J
ƒ
30 30 35 30* 1 12
1
2
LPN-RK_SP RK1 25 30 35
FRN-R RK5 25 30 35
LPJ_SP J 45 50 60
5 28 TCF J
ƒ
45 50 60 60 2 10**
1
2
LPN-RK_SP RK1 40 50 60
FRN-R RK5 35 50 60
LPJ_SP J 60 70 90
7
1
2 40 TCF J
ƒ
60 70 90 60* 2 8**
1
2**
LPN-RK_SP RK1 60 70 90
FRN-R RK5 50 70 90
LPJ_SP J 80 90 110
10 50 TCF J
ƒ
80 90 100* 3 6**
1
2**
LPN-RK_SP RK1 70 90 110
FRN-R RK5 70 90 110
* Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. ** If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required.
ƒ
Class J performance, special finger-safe dimensions.
156
©2005 Cooper Bussmann
Motor Circuit Protection Tables
90Vdc3Motors & Circuits
12 3 456789 10 Motor Motor Fuse Optimal NEC
®
NEC®Max Minimum Minimum Minimum Minimum
Size FLA Branch Ckt Max for for Heavy Switch NEMA Copper Wire Rigid Metallic
Protection Gen. Applic Start Size Starter THWN or THHN AWG Conduit
Table Table 430.52(C)(1) 430.52(C)(1) 430.110 NEMA ICS 2- or KCMIL Annex C
430.257 430.257 Type Class Exc. No. 1 Exc. No. 2 2000 Table 310.16 Table C8 HP AMPS AMPS
1
AMPS
1
AMPS
1
AMPS Size
2
Size Inches
LPJ_SP J 6 6 6
TCF J
ƒ
66 6
1
4 4.0 LPC_CC CC 6 6 15 30 1 14
1
2
LPN-RK_SP RK1 6 6 9
FRN-R RK5 5 6 9
LPJ_SP J 8 10 10
TCF J
ƒ
10 10 10
1
3 5.2 LP-CC CC 10 10 20 30 1 14
1
2
LPN-RK_SP RK1 8 10 10
FRN-R RK5 7 10 10
LPJ_SP J 12 15 15
TCF J
ƒ
15 15 15
1
2 6.8 LP-CC CC 15 15 25 30 1 14
1
2
LPN-RK_SP RK1 9 15 15
FRN-R RK5 9 15 15
LPJ_SP J 15 15 20
TCF J
ƒ
15 15 20
3
4 9.6 LP-CC CC 15 15 30 30 1 14
1
2
LPN-RK_SP RK1 15 15 20
FRN-R RK5 12 15 20
1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. ** If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. 2 These sizes are typical. They are not shown in NEMA ICS 2-2000. 3 All equipment manufacturers should be consulted about DC voltage ratings of their equipment.
ƒ
Class J performance, special finger-safe dimensions.
157
©2005 Cooper Bussmann
Motor Circuit Protection Tables
120Vdc3Motors & Circuits
12 3 456789 10 Motor Motor Fuse Optimal NEC
®
NEC®Max Minimum Minimum Minimum Minimum
Size FLA Branch Ckt Max for for Heavy Switch NEMA Copper Wire Rigid Metallic
Protection Gen. Applic Start Size Starter THWN or THHN AWG Conduit
Table Table 430.52(C)(1) 430.52(C)(1) 430.110 NEMA ICS 2- or KCMIL Annex C
430.257 430.257 Type Class Exc. No. 1 Exc. No. 2 2000 Table 310.16 Table C8 HP AMPS AMPS
1
AMPS
1
AMPS
1
AMPS Size
2
Size Inches
LPJ_SP J 5 6 6
TCF J
ƒ
66 6
1
4 3.1 LP-CC CC 6 6 12 30 1 14
1
2
LPN-RK_SP RK1 4 1⁄2 66
1
4
FRN-R RK5 4 6 6 1⁄4
LPJ_SP J 7 10 10
TCF J
ƒ
10 10 10
1
3 4.1 LP-CC CC 9 10 15 30 1 14
1
2
LPN-RK_SP RK1 5 6⁄10 10 10
FRN-R RK5 5 6⁄10 10 10
LPJ_SP J 9 10 12
TCF J
ƒ
10 10 10
1
2 5.4 LP-CC CC 10 10 20 30 1 14
1
2
LPN-RK_SP RK1 7 1⁄2 10 12
FRN-R RK5 7 10 12
LPJ_SP J 12 15 15
TCF J
ƒ
15 15 15
3
4 7.6 LP-CC CC 15 15 30 30 1 14
1
2
LPN-RK_SP RK1 10 15 15
FRN-R RK5 10 15 15
LPJ_SP J 15 15 20
TCF J
ƒ
15 15 20
1 9.5 LP-CC CC 15 15 30
5
30 1 14
1
2
LPN-RK_SP RK1 15 15 20
FRN-R RK5 12 15 20
LPJ_SP J 20 20 25
TCF J
ƒ
20 20 25
1
1
2 13.2 LP-CC CC 20 20 30
5
30 1 14
1
2
LPN-RK_SP RK1 17 1⁄2 20 25
FRN-R RK5 17 1⁄2 20 25
LPJ_SP J 30 30 35
TCF J
ƒ
30 30 35
2 17 LP-CC CC 30 30 30
5
30* 1 12
1
2
LPN-RK_SP RK1 25 30 35
FRN-R RK5 25 30 35
LPJ_SP J 40 40 50
3 25 TCF J
ƒ
40 40 50 60 1 10**
1
2
LPN-RK_SP RK1 35 40 50
FRN-R RK5 35 40 35
LPJ_SP J 60 60 90
5 40 TCF J
ƒ
60 60 60 60* 2 8**
1
2**
LPN-RK_SP RK1 60 60 90
FRN-R RK5 50 60 90
LPJ_SP J 90 90 125
7
1
2 58 TCF J
ƒ
90 90 100* 3 4**
3
4**
LPN-RK_SP RK1 80 90 125
FRN-R RK5 80 90 125
LPJ_SP J 125 125 150
10 76 LPN-RK_SP RK1 100 125 150 100* 3 3** 1
FRN-R RK5 100 125 150
* Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. ** If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. 2 Reduced voltage magnetic controller ratings 3 All equipment manufacturers should be consulted about DC voltage ratings of their equipment. 5 Largest LP-CC Fuse 30 amp. With other type fuse, could use larger amp rating in this application.
ƒ
Class J performance, special finger-safe dimensions.
158
©2005 Cooper Bussmann
Motor Circuit Protection Tables
180Vdc3Motors & Circuits
240Vdc3Motors & Circuits
12 3 456789 10 Motor Motor Fuse Optimal NEC
®
NEC®Max Minimum Minimum Minimum Minimum
Size FLA Branch Ckt Max for for Heavy Switch NEMA Copper Wire Rigid Metallic
Protection Gen. Applic Start Size Starter THWN or THHN AWG Conduit
Table Table 430.52(C)(1) 430.52(C)(1) 430.110 NEMA ICS 2- or KCMIL Annex C
430.257 430.257 Type Class Exc. No. 1 Exc. No. 2 2000 Table 310.16 Table C8 HP AMPS AMPS
1
AMPS
1
AMPS
1
AMPS Size
2
Size Inches
LPJ_SP J 3 3 4
1
2
1
4 2.0 TCF J
ƒ
33 3 30 1 141⁄2
LPS-RK_SP RK1 2 8⁄10 34
1
2
FRS-R RK5 2 1⁄2 34
1
2
LPJ_SP J 4 6 6
1
3 2.6 TCF J
ƒ
66 6 30 1 141⁄2
LPS-RK_SP RK1 3 1⁄2 66
FRS-R RK5 3 1⁄2 66
LPJ_SP J 5
6
10 66
1
2 3.4 TCF J
ƒ
66 6 30 1 141⁄2
LPS-RK_SP RK1 4 1⁄2 66
1
4
FRS-R RK5 4 1⁄2 67
1
2
LPJ_SP J 8 10 10
3
4 4.8 TCF J
ƒ
10 10 10 30 1 14
1
2
LPS-RK_SP RK1 6 1⁄4 10 10
FRS-R RK5 6 10 10
LPJ_SP J 10 10 12
1 6.1 TCF J
ƒ
10 10 10 30 1 14
1
2
LPS-RK_SP RK1 8 10 12
FRS-R RK5 8 10 12
LPJ_SP J 15 15 17
1
2
TCF J
ƒ
15 15 15
1
1
2 8.3 LP-CC CC 30 30 1 14
1
2
LPS-RK_SP RK1 12 15 17 1⁄2
FRS-R RK5 12 15 17 1⁄2
LPJ_SP J 15 20 20
TCF J
ƒ
15 20 20
2 10.8 LP-CC CC 20 20 30 30 1 14
1
2
LPS-RK_SP RK1 15 20 20
FRS-R RK5 15 20 20
LPJ_SP J 25 25 35
TCF J
ƒ
25 25 35
3 16 LP-CC CC 25 25 30 30* 1 14
1
2
LPS-RK_SP RK1 20 25 35
FRS-R RK5 20 25 35
LPJ_SP J 40 45 60
5 27 TCF J
ƒ
40 45 60 60 2 10**
1
2
LPS-RK_SP RK1 40 45 60
FRS-R RK5 35 45 60
* Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. ** If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. 2 These sizes are typical. They are not shown in NEMA ICS 2-2000. 3 All equipment manufacturers should be consulted about DC voltage ratings of their equipment.
ƒ
Class J performance, special finger-safe dimensions.
12 3 456789 10 Motor Motor Fuse Optimal NEC
®
NEC®Max Minimum Minimum Minimum Minimum
Size FLA Branch Ckt Max for for Heavy Switch NEMA Copper Wire Rigid Metallic
Protection Gen. Applic Start Size Starter THWN or THHN AWG Conduit
Table Table 430.52(C)(1) 430.52(C)(1) 430.110 NEMA ICS 2- or KCMIL Annex C
430.257 430.257 Type Class Exc. No. 1 Exc. No. 2 2000 Table 310.16 Table C8 HP AMPS AMPS
1
AMPS
1
AMPS
1
AMPS Size
2
Size Inches
LPJ_SP J 2
1
2 33
1
2
1
4 1.6 TCF J
ƒ
33 3 30 1 141⁄2
LPN-RK_SP RK1 2 1⁄4 33
1
2
FRS-R RK5 2 3 3 1⁄2
LPJ_SP J 3 3 4 1⁄2
1
3 2.0 TCF J
ƒ
33 3 30 1 141⁄2
LPS-RK_SP RK1 2 8⁄10 34
1
2
FRS-R RK5 2 1⁄2 34
1
2
* Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. ** If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. 2 Reduced voltage magnetic DC controller ratings. 3 All equipment manufacturers should be consulted about DC voltage ratings of their equipment.
ƒ
Class J performance, special finger-safe dimensions.
159
©2005 Cooper Bussmann
Motor Circuit Protection Tables
240Vdc3Motors & Circuits continued
12 3 456789 10 Motor Motor Fuse Optimal NEC
®
NEC®Max Minimum Minimum Minimum Minimum
Size FLA Branch Ckt Max for for Heavy Switch NEMA Copper Wire Rigid Metallic
Protection Gen. Applic Start Size Starter THWN or THHN AWG Conduit
Table Table 430.52(C)(1) 430.52(C)(1) 430.110 NEMA ICS 2- or KCMIL Annex C
430.257 430.257 Type Class Exc. No. 1 Exc. No. 2 2000 Table 310.16 Table C8 HP AMPS AMPS
1
AMPS
1
AMPS
1
AMPS Size
2
Size Inches
LPJ_SP J 4
1
2 66
1
2 2.7 TCF J
ƒ
66 6 30 1 141⁄2
LPS-RK_SP RK1 4 6 6
FRS-R RK5 3 1⁄2 66
LPJ_SP J 6 6 8
TCF J
ƒ
66 6
3
4 3.8 LP-CC CC 15 30 1 14
1
2
LPS-RK_SP RK1 5 6 8
FRS-R RK5 5 6 8
LPJ_SP J 8 10 10
1 4.7 TCF J
ƒ
10 10 10 30 1 14
1
2
LPS-RK_SP RK1 6 1⁄4 10 10
FRS-R RK5 6 10 10
LPJ_SP J 10 10 12
1
1
2 6.6 TCF J
ƒ
10 10 10 30 1 14
1
2
LPS-RK_SP RK1 9 10 12
FRS-R RK5 9 10 12
LPJ_SP J 15 15 17
1
2
2 8.5 TCF J
ƒ
15 15 15 30 1 14
1
2
LPS-RK_SP RK1 12 15 17 1⁄2
FRS-R RK5 12 15 17 1⁄2
LPJ_SP J 20 20 25
TCF J
ƒ
20 20 25
3 12.2 LP-CC CC 20 20 30 30 1 14
1
2
LPS-RK_SP RK1 17 1⁄2 20 25
FRS-R RK5 17 1⁄2 20 25
LPJ_SP J 30 30 45
TCF J
ƒ
30 30 45
5 20 LP-CC CC 30 30 30 30* 1 12
1
2
LPS-RK_SP RK1 30 30 45
FRS-R RK5 25 30 45
LPJ_SP J 45 45 60
7
1
2 29 TCF J
ƒ
45 45 60 60 2 8
1
2
LPS-RK_SP RK1 40 45 60
FRS-R RK5 40 45 60
LPJ_SP J 60 60 80
10 38 TCF J
ƒ
60 60 60 60* 2 8**
1
2**
LPS-RK_SP RK1 50 60 80
FRS-R RK5 50 60 80
LPJ_SP J 90 90 110
15 55 TCF J
ƒ
90 90 100* 3 4 3/4**
LPN-RK_SP RK1 80 90 110
FRS-R RK5 70 90 110
LPJ_SP J 110 110 150
20 72 LPN-RK_SP RK1 100 110 150 100* 3 3** 1
FRS-R RK5 90 110 150
LPJ_SP J 150 150 200
25 89 LPN-RK_SP RK1 125 150 200 200 3 2** 1**
FRS-R RK5 125 150 200
LPJ_SP J 175 175 225
30 106 LPN-RK_SP RK1 150 175 225 200* 4 1/0** 1
1
4
FRS-R RK5 150 175 225
LPJ_SP J 225 225 300
40 140 LPN-RK_SP RK1 200 225 300 200* 4 2/0** 1
1
4**
FRS-R RK5 175 225 300
LPJ_SP J 300 300 350
50 173 LPN-RK_SP RK1 225 300 350 400 5 4/0** 1
1
2**
FRS-R RK5 225 300 350
LPJ_SP J 350 350 450
60 206 LPN-RK_SP RK1 300 350 450 400* 5 300** 2**
FRS-R RK5 300 350 450
LPJ_SP J 400 400 500
75 255 LPN-RK_SP RK1 350 400 500 400* 5 400** 2**
FRS-R RK5 350 400 500
LPJ_SP J 600 600
100 341 LPN-RK_SP RK1 450 600 600 6 4/0 2/PHASE (2) 1
1
2**
FRS-R RK5 450 600
* Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. ** If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. 2 Reduced voltage magnetic DC controller ratings. 3 All equipment manufacturers should be consulted about DC voltage ratings of their equipment.
ƒ
Class J performance, special finger-safe dimensions.
Recommendations for Electrician and Maintenance Crews
Often, for various reasons, motors are oversized for applications. For instance, a 5Hp motor is installed when the load demand is only 3Hp. In these cases a much higher degree of protection can be obtained by sizing the overload relay elements and/or Fusetron and Low-Peak dual-element, time-delay fuses based on the actual full-load current draw.
160
©2005 Cooper Bussmann
Motor Protection
Tips For Electricians & Maintenance Crews
Selection of Fusetron or Low-Peak Dual-Element Fuses based upon Motor FLA for Optimum Motor Circuit Protection*
Fusetron or Low-Peak Motor Current Dual- FRN-R LPN-RK_SP Element FRS-R LPS-RK_SP LPJ_SP LP-CC Fuse Size Class RK5 Class RK1 Class J Class CC
1
10 0-0.08 0.0000-0.0769
1
8 0.09-0.10 0.0770-0.0961
15
100 0.11-0.12 0.0962-0.1153
2
10 0.13-0.16 0.1154-0.1538
1
4 0.17-0.20 0.1539-0.1923
3
10 0.21-0.24 0.1924-0.2307
4
10 0.25-0.32 0.2308-0.3076
1
2 0.33-0.40 0.3077-0.3846 0.0000-0.2500
6
10 0.41-0.48 0.3847-0.4615 0.2501-0.3000
8
10 0.49-0.64 0.4616-0.6153 0.3001-0.4000 1 0.65-0.80 0.6154-0.7692 0.0-0.6666 0.4001-0.5000 1 1⁄8 0.81-0.90 0.7693-0.8653 0.6667-0.7500 0.5001-0.5625 1 1⁄4 0.91-1.00 0.8654-0.9615 0.7501-0.8333 0.5626-0.6250 1 4⁄10 1.01-1.12 0.9616-1.076 0.8334-0.9333 0.6251-0.7000 1 1⁄2 1.13-1.20 1.077-1.153 0.9334-1.000 0.7001-0.7500 1 6⁄10 1.21-1.28 1.154-1.230 1.001-1.066 0.7501-0.8000 1 8⁄10 1.29-1.44 1.231-1.384 1.067-1.200 0.8001-0.9000 2 1.45-1.60 1.385-1.538 1.201-1.333 0.9001-1.000 2 1⁄4 1.61-1.80 1.539-1.730 1.334-1.500 1.001-1.125 2 1⁄2 1.81-2.00 1.731-1.923 1.501-1.666 1.126-1.250 2 8⁄10 2.01-2.24 1.924-2.153 1.667-1.866 1.251-1.400 3 2.25-2.40 2.154-2.307 1.867-2.000 1.401-1.500 3 2⁄10 2.41-2.56 2.308-2.461 2.001-2.133 1.501-1.600 3 1⁄2 2.57-2.80 2.462-2.692 2.134-2.333 1.601-1.750 4 3.81-3.20 2.693-3.076 2.334-2.666 1.751-2.000 4 1⁄2 3.21-3.60 3.077-3.461 2.667-3.000 2.001-2.250 5 3.61-4.00 3.462-3.846 3.001-3.333 2.251-2.500 5 6⁄10 4.01-4.48 3.847-4.307 3.334-3.733 2.501-2.800 6 4.49-4.80 4.308-4.615 3.734-4.000 2.801-3.000 6 1⁄4 4.81-5.00 4.616-4.807 3.001-3.125 7 5.01-5.60 4.808-5.384 4.001-4.666 3.126-3.500 7 1⁄2 5.61-6.00 3.501-3.750 8 6.01-6.40 5.385-6.153 4.667-5.333 3.751-4.000 9 6.41-7.20 6.154-6.923 5.334-6.000 4.001-4.500 10 7.21-8.00 6.924-7.692 6.001-6.666 4.501-5.000 12 8.01-9.60 7.693-9.230 6.667-8.000 5.001-6.000 15 9.61-12.00 9.231-11.53 8.001-10.00 6.001-7.500 17 1⁄2 12.01-14.00 11.54-13.46 10.01-11.66 7.501-8.750 20 14.01-16.00 13.47-15.38 11.67-13.33 8.751-10.00 25 16.01-20.00 15.39-19.23 13.34-16.66 10.01-12.50 30 20.01-24.00 19.24-23.07 16.67-20.00 12.51-15.00 35 24.01-28.00 23.08-26.92 20.01-23.33 — 40 28.01-32.00 26.93-30.76 23.34-26.66 — 45 32.01-36.00 30.77-34.61 26.67-30.00 — 50 36.01-40.00 34.62-38.46 30.01-33.33 — 60 40.01-48.00 38.47-46.15 33.34-40.00 — 70 48.01-56.00 46.16-53.84 40.01-46.66 — 75 56.01-60.00 — 80 60.01-64.00 53.85-61.53 46.67-53.33 — 90 64.01-72.00 61.54-69.23 53.34-60.00 — 100 72.01-80.00 69.24-76.92 60.01-66.66 — 110 80.01-88.00 76.93-84.61 66.67-73.33 — 125 88.01-100.00 84.62-96.15 73.34-83.33 — 150 100.01-120.00 96.16-115.3 83.34-100.0 — 175 120.01-140.00 115.4-134.6 100.1-116.6 — 200 140.01-160.00 134.7-153.8 116.7-133.3 — 225 160.01-180.00 153.9-173.0 133.4-150.0 — 250 180.01-200.00 173.1-192.3 150.1-166.6 — 300 200.01-240.00 192.4-230.7 166.7-200.0 — 350 240.01-280.00 230.8-269.2 200.1-233.3 — 400 280.01-320.00 269.3-307.6 233.4-266.6 — 450 320.01-360.00 307.7-346.1 266.7-300.0 — 500 360.01-400.00 346.2-384.6 300.1-333.3 — 600 400.01-480.00 384.7-461.5 333.4-400.0
1. Preferable – With a clamp-on meter, determine running RMS current when the motor is at normal full-load. (Be sure this current does not exceed nameplate current rating.) The advantage of this method is realized when a lightly loaded motor (especially those over 50 HP) experiences a single-phase condition. Even though the relays and fuses may be sized correctly based on motor nameplate, circulating currents within the motor may cause damage.
Alternate – if unable to meter the motor current, then take the current rating off the nameplate.
2. Then size the overload relay elements and Fusetron FRS-R and FRN-R or Low­Peak LPS-RK_SP and LPN-RK_SP dual-element fuses based on this current. For optimum motor circuit protection offering a high degree of “back-up overload” protection, use the table that follows to assist in sizing dual-element fuses. The other fuses in the table LPJ_SP, TCF and LP-CC can provide excellent short circuit protection when sized for Optimum Motor Circuit Protection. However, they typically can not be sized close enough to provide motor back-up overload protection.
3. Use a labeling system to mark the type and amp rating of the fuse that should be in the fuse clips, such as FRS-R 6 1/4. This simple step makes it easy to run spot checks for proper fuse replacement. When installing the proper fuses in the switch to give the desired level of protection, it often is advisable to leave spare fuses on top of the disconnect, the starter enclosure or in a cabinet adjacent to the motor control center. In this way, should the fuses open, the problem can be corrected and proper size fuses easily reinstalled.
* Abnormal installations may require Fusetron or Low-Peak dual-element fuses of a larger size than shown provid-
ing only short circuit protection. These applications include:
(a) Fusetron or Low-Peak dual-element fuses in high ambient temperature environments. (b) A motor started frequently or rapidly reversed. (c) Motor is directly connected to a machine that cannot be brought up to full speed
quickly (large fans, centrifugal machines such as extractors and pulverizers, machines having large fly wheels such as large punch presses.)
(d) Motor has a high Code Letter (or possibly no Code Letter) with full voltage start. (e) WYE delta open transition start. (f) Motor has a large inrush current, such as a Design B.
5 Amperes
READ NAMEPLATE
1
/
FRS-R 6
4
460V.
5 Amperes
460V.
460V.
61
©2005 Cooper Bussmann
Transformers — 600V or Less
Equipment Protection
The requirements of 450.3 cover only transformer protection. In practice, other components must be considered in applying circuit overcurrent protection. For circuits with transformers, requirements for conductor protection per Articles 240 and 310 and for panelboards per Article 408, must be observed. Refer to
240.4(F), 240.21(B)(3), 240.21(C), 408.36(A) & (B). Primary Fuse Protection Only [450.3(B)] (See Figure below) If secondary fuse
protection is not provided (as discussed in the next Section) then the primary fuses must not be sized larger than as shown below.
Individual transformer primary fuses are not necessary where the primary circuit fuse provides this protection.
Note: Section 450.3 requirements pertain only to transformer protection. Additional circuit overcurrent protection for conductors or panelboards may be required per Articles 240, 310, 408, 430.72.
* Primary Fuse (600V or less) and Secondary Fuse (600V or less). If secondary (600V or less) fuses are sized not greater than 125% of trans­former secondary current, individual transformer fuses are not required in the primary (600V or less) provided the primary feeder fuses are not larger than 250% of the transformer rated primary current. [See Note 3 of Table 450.3(B) for overcurrent protection requirements of thermally protected transformers].
Note: Transformer overload protection will be sacrificed by using overcurrent protective devices sized much greater than the transformer F.L.A. The limits of 150%, 167%, 250% and 300% may not adequately protect transformers. It is suggested that for the highest degree of transformer overload protection the fuse size should be within 125% of the transformer full-load amps.
Normal magnetizing inrush currents for power transformers can range from 10 times to 12 times the transformer full load current, for up to 6 cycles, and as high as 25 times transformer full load current at 0.01 seconds. Some
transformers may have inrush magnitudes substantially greater. Severe inrush should be compared with melting times to assure that unnecessary opening of the device does not occur.
There is a wide fuse amp rating range available to properly protect transformers. Fusetron Class RK5 and Low-Peak Class RK1 dual-element fuses can be sized on the transformer primary and/or secondary rated at 125% of the transformer F.L.A. These dual-element fuses have sufficient time­delay to withstand the high magnetizing inrush currents of transformers. There is a wide amp rating selection in the 0 to 15A range for these dual-element fuses to provide protection for even small control transformers.
The required secondary protection may be satisfied with multiple overcurrent devices that protect feeders fed from the transformer secondary. The total amp rating of these multiple devices may not exceed the allowed value of a single secondary overcurrent device. If this method is chosen, dual-element, time­delay fuse protection offers much greater flexibility. Note the following examples:
Design 1 utilizes a single secondary overcurrent device. It provides the
greatest degree of selective coordination, transformer protection, secondary cable protection, and switchboard/ panelboard/load center protection. The transformer cannot be overloaded to a significant degree if future loads are added (improperly). With this arrangement the transformer’s full capacity is utilized.
Primary Fuse Only
Primary Current Primary Fuse Rating
9 amps or more 125% or next higher standard rating if
2 amps to 9 amps 167% maximum Less than 2 amps 300% maximum
TRANSFORMER No Secondary
Primary
600V
or Less
Fuse must not be larger than 125% of transformer primary F.L.A. When no transformer secondary protection is provided (exceptions as noted above).
125% does not correspond to a standard fuse size.
Protection
Secondary
600V
or Less
Primary and Secondary Fuses
Secondary Current Primary Fuse Rating Secondary Fuse Rating
9 amps or more 250% max. 125% or next higher standard
Less than 9 amps 250% max. 167% max.
TRANSFORMER
Primary
600V
Or Less
Individual primary transformer fuse or primary feeder fuse must not be larger than 250% of primary full-load current when secondary fuses are provided at 125%, except as noted above.
Secondary
600V
Or Less
rating if 125% does not corre­spond to a standard fuse size
Secondary Fuses at 125% of secondary F.L.A. except as noted above.
62
©2005 Cooper Bussmann
Transformers — 600V or Less
Equipment Protection
Design 2 In this case the single secondary overcurrent device is
eliminated, much of the protection described in Design 1 will be reduced. If dual-element fuses are utilized as branch circuit protection, the transformer can continue to be loaded with the five 83A motors because 5 x 110 = 550A, (less than the maximum 600A). If additional loads are improperly added in the future, overload protection will be lost because the primary device can be sized at 250%.
Design 3 If the single secondary overcurrent device is eliminated and
MCPs are utilized as branch circuit protection, the transformer will be seriously under-utilized because only one motor can be connected. For one motor, 1 x 700% of 83 = 581 amps. For two motors, 2 x 700% of 83 = 1162 amps. Since the sum of the devices cannot exceed 600 amps, only one motor can be connected when the motor circuit is protected by an MCP.
Design 4 Using the same procedure, if the single secondary main is
eliminated and thermal magnetic circuit breakers are utilized as branch circuit protection per 430.52, only three of the motors can be connected because the thermal magnetic breakers will have been sized at approximately 250% of the motor F.L.A. (83 x 250% = 207.5A.)
Note: If sized less than permitted by 430.52, nuisance tripping may result since the new energy efficient motors have higher inrush currents.
Using a 200A circuit breaker would allow only three (600 ÷ 200) motors to be connected. To add two additional motors of the same type as shown in Design 1 and Design 2 requires a larger transformer - one that would have a 1000A or more secondary capability. A 300kVA 208V transformer has a 830A secondary rating which is not sufficient. Therefore, the next standard size 3Ø transformer is a 400kVA with a 1110A capacity to meet the new rule.
63
©2005 Cooper Bussmann
Transformers — Over 600V
Equipment Protection
Primary and Secondary Protection
In unsupervised locations, with primary over 600V, the primary fuse can be sized at a maximum of 300%. If the secondary is also over600V, the secondary fuses can be sized at a maximum of 250% for transformers with impedances not greater than 6% or 225% for transformers with impedances greater than 6% and not more than 10%. If the secondary is 600V or below, the secondary fuses can be sized at a maximum of 125%. Where these ratings do not correspond to a standard fuse size, the next higher standard size is permitted.
In supervised locations, the maximum ratings are as shown in the next diagram. These are the same maximum settings as the unsupervised locations except for secondary voltages of 600V or less, where the secondary fuses can be sized at maximum of 250%.
Primary Protection Only
In supervised locations, the primary fuses can be sized at a maximum of 250%, or the next larger standard size if 250% does not correspond to a standard fuse size.
Note: The use of “Primary Protection Only” does not remove the requirements for compliance with Articles 240 & 408. See (FPN) in Section 450.3, which references 240.4, 240.21, 240.100 and 240.101 for proper protection for secondary conductors.
E-Rated Fuses for Medium Voltage Potential & Small Power Transformers
Low amperage, E-Rated medium voltage fuses are general purpose current­limiting fuses. A general purpose current-limiting fuse is capable of interrupting all current from the rated interrupting current down to the current that causes melting of the fusible element in 1 hour (ANSI C37.40). The E rating defines the melting-time-current characteristic of the fuse and permits electrical interchangeability of fuses with the same E Rating. For a general purpose fuse to have an E Rating the following condition must be met:
The current responsive element shall melt in 300 seconds at an RMS current within the range of 200% to 240% of the continuous current rating of the fuse, fuse refill, or link (ANSI C37.46).
Cooper Bussmann low amperage, E-Rated fuses are designed to provide primary protection for potential, small service, and control transformers. These fuses offer a high level of fault current interruption in a self-contained non­venting package which can be mounted indoors or in an enclosure.
Application
As for all current-limiting fuses, the basic application rules found in the fuseology section of this brochure should be adhered to. In addition, potential transformer fuses must have sufficient inrush capacity to successfully pass through the magnetizing inrush current of the transformer. If the fuse is not sized properly, it will open before the load is energized. The maximum magnetizing inrush currents to the transformer at system voltage, and the duration of this inrush current varies with the transformer design. Magnetizing inrush currents are usually denoted as a percentage of the transformer full-load current, i.e., 10x, 12x, 15x, etc. The inrush current duration is usually given in seconds. Where this information is available, an easy check can be made on the appropriate Cooper Bussmann minimum melting curve to verify proper fuse selection. In lieu of transformer inrush data, the rule of thumb is to select a fuse size rated at 300% of the primary full-load current and round up to the next larger standard size.
Example:
The transformer manufacturer states that an 800VA 2400V, single phase potential transformer has a magnetizing inrush current of 12x lasting for 0.1 second.
A. IFL= 800VA/2400V = 0.333A
Inrush Current = 12 x 0.333 = 4A
Since the voltage is 2400 volts we can use either a JCW-1E or JCD-1 E.
B. Using the rule of thumb–300% of 0.333A is 0.999A.
Therefore we would choose a JCW-1E or JCD-1E.
PRIMARY
Over 600V
Max Fuse
=
300%
Over 600V
Max Fuse
=
300%
Over 600V
Max Fuse
=
300%
% Z ≤ 6%
6% < Z ≤ 10%
PRIMARY SECONDARY
Over 600V
% Z ≤ 6%
Max Fuse
= 300%
Over
600V
6% < Z ≤ 10%
Max Fuse
= 300%
Over
600V
SECONDARY
Over 600V
Max Fuse
=
250%
Over 600V
Max Fuse
225%
=
600V or
Below
Max Fuse
125%
=
Over 600V
Max Fuse
= 250%
Over 600V
Max Fuse
= 225%
600V or
Below
Unsupervised
Locations
Supervised
Locations
Max Fuse
= 300%
Max Fuse
= 250%
64
©2005 Cooper Bussmann
Transformers — Over 600V
Equipment Protection
Typical Potential Transformer Connections
The typical potential transformer connections encountered in industry can be grouped into two categories:
E-Rated Fuses for Medium Voltage Transformers & Feeders
Cooper Bussmann E-Rated medium voltage fuses are general purpose current-limiting fuses. A general purpose current-limiting fuse is capable of interrupting all currents from the rated interrupted current down to the current that causes melting of the fusible element in 1 hour (ANSI C37.40). The fuses carry either an ‘E’ or an ‘X’ rating which defines the melting-time-current characteristic of the fuse. The ratings are used to allow electrical interchangeability among different manufacturers’ fuses.
For a general purpose fuse to have an E rating, the following conditions must be met:
1. 100E and below - the fuse element must melt in 300 seconds at 200% to 240% of its rating (ANSI C37.46).
2. Above 100E - the fuse element must melt in 600 seconds at 220% to 264% of its rating (ANSI C37.46).
A fuse with an ‘X’ rating does not meet the electrical inter-changeability for an ‘E’ rated fuse but offers the user other ratings that may provide better protection for a particular application.
Application
Transformer protection is the most popular application of E-Rated fuses. The fuse is applied to the primary of the transformer and is used solely to prevent rupture of the transformer due to short circuits. It is important, therefore, to size the fuse so that it does not clear on system inrush or permissible overload currents. See section on transformers over 600V for applicable sizing recom­mendations. Magnetizing inrush must also be considered when sizing a fuse. In general, power transformers have a magnetizing inrush current of 12x the full-load rating for a duration of
1
10 second.
Cooper Bussmann E-Rated Medium Voltage Fuse.
2. Those connections which must pass the magnetizing inrush of more than one potential transformer
1. Those connections which require the fuse to pass only the magnetizing inrush of one potential transformer
186
©2005 Cooper Bussmann
430.72(C)
Secondary conductors of a single-phase transformer having only a 2-wire secondary are protected by the primary fuse (600V or less) if the primary fuse rating is:
1. Not larger than that determined in Table 430.72(B), multiplied by secondary-to­primary voltage ratio and,
2. not more than the following percent of transformer rated primary current:
Control conductors are permitted to be protected by the motor branch circuit overcurrent device where the opening of the control circuit would create a hazard.
Motor Control Circuit Protection
Transformer Primary Fuse Primary Ampacity Must Current Not Exceed†
Less than 2 amps 500% 2 to 9 amps 167% 9 amps or more 125%*
* If 125% of rated primary current does not corre­spond to a standard fuse rating, then the next higher standard fuse rating is permitted. † Refer to Section 8.12 of NFPA79 for the allowable sizing for control transformers in Industrial Machinery.
Class 1 POWER LIMITED, Class 2 and Class 3 Remote Motor Control Circuits
1. Control circuit conductors shall be protected from overcurrent in accordance with Article 725.
2. Control circuit conductors 18 AWG and 16 AWG, shall be protected by a control circuit fuse not to exceed 7 and 10 amps respectively.
Exception No. 2 Relative to Transformer Protection
Refer to Exception 3, [430.72(B)], covered in preceding paragraphs.
Motor Control Circuit Transformers [430.72(C)]
Control circuit transformers (600V or less) shall be protected as shown
previously in Exception No. 3 under 430.72(B).
430.72(C)(3): Control circuit transformers rated less than 50VA can be
protected by a primary fuse, impedance limiting means, or other inherent means. The transformer must be an integral part of the motor controller, and be located within the controller.
430.72(C)(4): Allows transformers with primary currents less than 2 amps
to be protected with primary fuses at 500% or less of primary full-load amps.
430.72(C)(1): Allows the control transformer to be protected by the motor
branch circuit overcurrent device when the transformer supplies a Class 1 power-limited, circuit [see 725.11(A)] Class 2, or Class 3 remote control circuit conforming with the requirements of Article 725.
430.72(C)(5): Allows the control transformer to be protected by the motor
branch circuit overcurrent device where protection is provided by other approved means.
430.72(C) Exception: States that overcurrent protection shall be
omitted where the opening of the control circuit would create a hazard, as for example, the control circuit of a fire pump motor and the like.
Table 430.72(B). Maximum Rating of Overcurrent Protective Device­Amperes
Column A Column B Column C Basic Rule Exception No. 1 Exception No. 2
Control Alum. or Alum. or Alum. or Circuit Copper- Copper- Copper­Conductor Clad Clad Clad Size, AWG Copper Alum. Copper Alum. Copper Alum.
18 7 – 25 – 7 – 16 10 – 40 – 10 – 14 Note 1 – 100 – 45 – 12 Note 1 Note 1 120 100 60 45 10 Note 1 Note 1 160 140 90 75 larger than Note 1 Note 1 Note 2 Note 2 Note 3 Note 3 10
Note 1: Value specified in Section 310-15, as applicable. Note 2: 400 percent of value specified in Table 310-17 for 60°C conductors. Note 3: 300 percent of value specified in Table 310-16 for 60°C conductors.
MOTOR BRANCH CIRCUIT FUSE
CONTROL
TRANSFORMER
Secondary Conductors Protected by Primary Circuit
M
2-Wire Secondary Control Circuit
POWER SOURCE
CONTROL CIRCUIT FUSE
For conductors 14 AWG and larger, refer to Tables 310.16 thru
310.19, without derating factors.
Control
Circuit
POWER SOURCE
CONTROL CIRCUIT FUSE 7 OR 10 AMP; MAX. RESPECTIVELY
18 AWG, 16 AWG
Control
Circuit
187
©2005 Cooper Bussmann
The following Selection Guide Tables simplify and permit easy application of fuses for the protection of the motor control circuits in accordance within the National Electrical Code
®
. Apply fuses per Table 1 for control circuit without a control transformer (see Circuit Diagrams 1 and 2). Apply fuses per Table 2 for a control circuit with a control transformer (see Circuit Diagrams 3 and 4).
Motor Control Circuit Protection
Control Circuit Without Control Transformer (See Table 1)
Circuit 1 Circuit 2
Control Circuit With Control Transformer (See Table 2)
Circuit 3 Circuit 4
BCPD (Branch Circuit Protective Device)
Cop per Con trol Conductor Remaining Within Enclosure
A
BCPD (Branch Circuit Protective Device)
C
D
C
Copper Control Conductor Remaining Within Enclosure
BCPD (Branch Circuit Protective Device)
B
BCPD (Branch Circuit Protective Device)
C
E
C
Copper Control Conductor Extending Beyond Enclosure
Copper Control Conductor Extending Beyond Enclosure
Table 2. Fuse Selection Guide–Control Circuit With Control Transformer (See Circuit Diagrams 3 and 4)
Control V Xfmr Rating BCPD Exceeds Amps Provided) Exceed These Amp Values
pri/Vsec
(Volts) (Amps) (Amps)
Ipri I
sec
480/120 0.05 0.21
25VA
480/24 0.05 1.00 240/120 0.10 0.21 240/24 0.10 1.00 0.50 0.50 0.50 0.50 0.50 1.25 3.0
1
Fuse C Fuse D or E
2
Req’d. If
These Amps 18 AWG 16 AWG 14 AWG 12 AWG Time Non-Time Values Wire Wire Wire Wire Delay
6
See 430-72(C) Except. 1
4,5
Maximum Required if BCPD and Fuse C (When Recommended Amps
1
0.25 0.25 0.25 0.25 0.25 0.25 0.60
0.25 0.25 0.25 0.25 0.25 1.25 3.0
0.50 0.50 0.50 0.50 0.50 0.25 0.60
Delay
480/120 0.10 0.42 0.5 0.50 0.50 0.50 0.50 0.50 0.50 1.0
50VA
480/24 0.10 2.10 0.5 0.50 0.50 0.50 0.50 0.50 2.5 6.0 240/120 0.21 0.42 1.0 1.0 1.0 1.0 1.0 1.0 0.50 1.0 240/24 0.21 2.10 1.0 1.0 1.0 1.0 1.0 1.0 2.5 6.0 480/120 0.21 0.83 1.0 1.0 1.0 1.0 1.0 1.0 1.0 2.0
100VA
480/24 0.21 4.20 1.0 1.0 1.0/.3591.0/.5091.0 1.0 5.0 12.0 240/120 0.42 0.83 2.0 2.0 2.0 2.0 2.0 2.0 1.0 2.0 240/24 0.42 4.20 2.0 2.0 2.0/.7092.0/1.092.0 2.0 5.0 12.0 480/120 0.31 1.25 1.5 1.5 1.5 1.5 1.5 1.5 1.50 3.50
150VA
480/24 0.31 6.25 1.5 1.5 1.5/0.591.5 1.5 7.50 15.0 240/120 0.62 1.25 3.0 3.0 3.0 3.0 3.0 3.0 1.50 3.50 240/24 0.62 6.25 3.0 3.0 3.0/1.093.0 3.0 7.50 15.0 480/120 0.42 1.67 2.0 2.0 2.0/1.7592.0 2.0 2.0 2.0 5.0
200VA
480/24 0.42 8.33 2.0 2.0 2.0 2.0 10.0 20.0 240/120 0.84 1.67 4.0 4.0 4.0/3.592.0 4.0 4.0 2.0 5.0 240/24 0.84 8.33 4.0 4.0 4.0 4.0 10.0 20.0
1
Time-Delay Fuses: FNQ, FNW, FNM, FNA–Supplementary Type; FNQ-R, FRN-R, FRS-R, LPN-RK_SP, LPS-RK_SP, LPJ_SP, LP-CC, SC6 & above–Branch Circuit Fuses (Rejection Type).
2
For exceptions, see 430.72(C).
3
Non-Time-Delay Fuses: KTK, BAN, BAF, MIN, MIC–Supplementary Fuses; KTK-R, JJN, JJS, SC⁄Ω™-5–Branch Circuit Fuses (Rejection Types).
4
These are maximum values as allowed by 430.72(C). Closer sizing at 125%-300% may be possible for better overload protection using time-delay branch circuit fuses.
5
Fuse shall be a rejection type branch circuit fuse when withstand rating of controller is greater than 10,000 amps RMS symmetrical
6
These transformers less than 50VA still need protection–either primary overcurrent protection, inherent protection, or the equivalent. Note that the primary conductors may be protected as shown in Circuit 1 Table 1. AWG.
9
Smaller value applied to Fuse "E".
7
Minimum copper secondary control conductor for this application is 14 AWG. 8Minimum copper secondary control conductor for this application is 12
3
7
7
7
7
8
8
188
©2005 Cooper Bussmann
Motor Control Circuit Protection
Supplementary Fuses (13/32” x 11/2”) (All Voltage and Interrupting Ratings are AC) Dual-Element,
Time-Delay Non-Time-Delay
Time-Delay
FNA FNM FNQ FNW BAF BAN KTK MIC MIN
1
/10-8/10A
1
/10-10A
1
/10-30A 12-30A
1
/2-15A
2
/10-30A
1
/10-30A 1-15A 1-15A
250V
250V
500V 250V* 250V
250V
††
600V 250V
250V† 1-15A 12-15A 10K AIR 20-30A 100K AIR 20-30A 20-30A 125V* 125V* (FNQ
1
10 - 3
2
10 125V* 32V** 32V** 20-30A 20-30A Dual-Element) 32V** 32V**
Branch Circuit Fuses
(All Voltage and Interrupting Ratings are AC)
Class R
Class G
Class CC
Dual-Element, Time-Delay Fast-Acting, Time-Delay
LPN-RK_SP FRN-R FRS-R LPS-RK_SP SC KTK-R FNQ-R LP-CC TCF
1
/10-30A
1
/10-30A
1
/10-30A
1
/10-30A
1
/2-20A 600V
§
1
/10-30A
1
/4-30A
1
/2-30A 1-30A
250V 250V 600V 600V 25-30A 480V
§
600V 600V 600V 600V
300K AIR 200K AIR 200K AIR 300K AIR 100K AIR 200K AIR 200K AIR 200K AIR 300K AIR
0 to 1 amp–35 AIR; 1.1 to 3.5 amp–100 AIR; 3.6 to 10 amp–200 AIR; 10.1 to 15 amp–750 AIR; 15.1 to 30 amps–1500AIR *10K AIR. **1K AIR.
§
1
/2thru 6 amp fuses are Non-Time-Delay Type; 7 thru 60 amp fuses are Time-Delay Type.
††
0 to 3.5 amp-35 AIR; 3.6 to 10 amp-100 AIR; 10.1 to 15 amp-200 AIR; 15.1-30 amp-750 AIR
205
©2005 Cooper Bussmann
Fuse Diagnostic Sizing Charts
Transformers 600V Nominal or Less (NEC®450.3)
Primary
Protection
Only
*When 125% of FLA corresponds to a standard rating, the next larger size is not permitted.
Primary And Secondary Protection
Optimum Protection
125% or next size larger
125% or next size larger
125% or next size larger Max. of 125% or next larger*
NEC®Maximums
Max. 300% or next size smaller (See NEC®430.72(C) for control circuit trans­former maximum of 500%
Max. 167% or next size smaller
Rated secondary current 9 amps or greater
Rated secondary current less than 9 amps
Transformer Impedance of 6% or Less
Rated secondary current 9 amps or greater
Rated secondary current less than 9 amps
Transformer Impedance of More Than 6% But Less Than 10%
Rated secondary current less than 9 amps
Rated secondary current 9 amps or greater
Without Thermal Overload Protection
With Thermal Overload Protection
Note: Components on the secondary still need overcurrent protection
Rated primary current less than 2 amps
Rated primary current greater than or equal to 9 amps
Rated primary current greater than or equal to 2 amps but less than 9 amps
Fuse Recommendations
Volts Fuse(s)
250V LPN-RK_SP, FRN-R 600V KRP-C_SP, LPJ_SP, LPS-RK_SP, FNQ-R, FRS-R, TCF
AA
B
C
D
E
F
B
C
D
E
F
Primary and secondary fuses at 125% of primary and secondary FLA or next size larger
% of Primary FLA
(or next FLA size smaller)
A = 250% B = 250% C = 600% D = 600% E = 400% F = 400%
% of Secondary FLA
A = 167% or next size smaller B = 125% or next size larger* C = 167% or next size smaller D = 125% or next size larger* E = 167% or next size smaller F = 125% or next size larger*
206
©2005 Cooper Bussmann
Fuse Diagnostic Sizing Charts
Transformers Over 600V Nominal (NEC®450.3)
Solid State Devices (Diodes, SCRs, Triacs, Transistors)
Supervised
Installations
Unsupervised
Installations
Fuse Recommendations
Volts Fuse(s)
250V LPN-RK_SP, FRN-R 600V LPS-RK_SP, LPJ-_SP,
KRP-C_SP, FRS-R, FNQ-R,
TCF 2475V JCD 2750V JCX 2750/5500V JCW 5500V JCE, JCQ, JCY, JCU,
5.5 ABWNA, 5.5 AMWNA,
5.5 FFN
7200V 7.2 ABWNA, 7.2 SDLSJ,
7.2 SFLSJ 8300V JCZ, JDZ, 8.25 FFN 15500V JCN, JDN, JDM, 15.5 CAVH 17500V 17.5 CAV, 17.5 SDM 24000V 24 SDM, 24 SFM, 24 FFM 36000V 36 CAV, 36 SDQ, 36 SFQ 38000V 38 CAV
Note: Components on the secondary still need overcurrent protection
Primary at code max. of 250% or next standard size if 250% does not corre­spond to a standard rating
Primary Protection Only
Transformer Impedance Less Than or Equal to 6%
Primary at code max. of 300%
Secondary Over 600V
Secondary at code max. of 250%
Secondary at code max. of 250%
Secondary at code max. of 225%
Secondary Over 600V
Primary at code max. of 300%
Secondary at code max. of 250%
Secondary Over 600V
Primary at code max. of 300% or next standard size if 300% does not correspond to a standard rating
Transformer Impedance Less Than or Equal to 6%
Primary at code max. of 300% or next standard size if 300% does not correspond to a standard rating
Secondary Over 600V
Secondary at code max. of 125% or next standard size if 125% does not correspond to a standard rating
Secondary at code max. of 225% or next standard size if 225% does not correspond to a standard rating
Secondary at code max. of 125% or next standard size if 125% does not correspond to a standard rating
Secondary at code max. of 250% or next standard size if 250% does not correspond to a standard rating
Transformer Impedance Greater Than 6% But Less Than 10%
Secondary 600V or Below
Secondary 600V or Below
Primary and Secondary Protection
Transformer Impedance Greater Than 6% But Less Than 10%
Secondary 600V or Below
Secondary 600V or Below
Short-Circuit
Protection Only
“F,” “S,” “K,” & 170M Series fuses sized up to several sizes larger than full load RMS or dc rating of device.
Fuse Recommendations
Volts Fuse(s)
0-130 FWA 0-250 FWX 0-500 FWH 0-600 FWC, KAC, KBC 0-700 FWP, 170M Series,
SPP
0-1000 FWJ, 170M Series,
SPJ
Loading...