Bussmann LPJ Data Sheet

Page 1
LOW-PEAK
®
LPJ
Dual-Element Time-Delay Fuses 1-60 Amps Class J – 600 Volt
Form No. LPJ 1-60
Page 1 of 3
Data Sheet: 1006
®
10-2-02
SB02295
Catalog Symbol: LPJ-_SP Dual-Element, Time-Delay – 10 seconds (minimum) at 500%
rated current
Current-Limiting
Ampere Rating: 1 to 60A Voltage Rating: 600Vac (or less)
300Vdc (or less)
Interrupting Rating: 300,000A RMS Sym. (UL)
100,000A dc
Agency Information:
UL Listed — Special Purpose*, Guide JFHR, File E56412 CSA Certified, 200,000 AIR, Class J per CSA 22.2 No. 248.8
Class 1422-02, File 53787
*Meets all performance requirements of UL Standard 248-8 for Class J fuses.
Catalog Symbol and Ampere Ratings
LPJ-1SP LPJ-3SP LPJ-7SP LPJ-25SP
LPJ-1⁄Ω¢SP LPJ-3-¤Ω¡ºSP LPJ-8SP LPJ-30SP
LPJ-1-flΩ¡ºSP LPJ-3⁄Ω™SP LPJ-9SP LPJ-35SP
LPJ-1-°Ω¡ºSP LPJ-4SP LPJ-10SP LPJ-40SP
LPJ-2SP LPJ-4⁄Ω™SP LPJ-12SP LPJ-45SP
LPJ-2⁄Ω¢SP LPJ-5SP LPJ-15SP LPJ-50SP
LPJ-2⁄Ω™SP LPJ-5flΩ¡ºSP LPJ-17⁄Ω™SP LPJ-60SP
LPJ-2°Ω¡ºSP LPJ-6SP LPJ-20SP
Carton Quantity and Weight
Ampere Carton
Weight**
Ratings Qty. Lbs. Kg.
1–30 10 1.09 0.494 35–60 10 1.78 0.808 **Weight per carton.
General Information:
• True dual-element fuses with a minimum 10 second time­delay at 500% overload.
• Long time-delay minimizes needless fuse openings due to temporary overloads and transient surges.
• Can often be sized for back-up protection against motor burnout from overload or single-phasing if other overload protective devices fail.
• High interrupting rating to safely interrupt overcurrents up to 300,000A.
• High degree of current limitation due to the fast speed-of­response to short-circuits.
• Faster response to damaging short-circuit currents than mechanical overcurrent protective devices.
• Reduces let-through thermal and magnetic forces in order to protect low withstand rated components.
• Proper sizing provides “no damage” Type “2” coordinated protection for NEMA and IEC motor control in accordance with IEC Standard 947-4-1.
• Dual-element fuses have lower resistance than ordinary fuses so they run cooler.
• Lower watts loss reduces power consumption.
• Unique dimensions assure that another class of fuse with a lesser voltage rating, interrupting rating or current-Iimiting ability cannot be substituted.
• Space-saving package for equipment down sizing.
Dimensional Data
CE logo denotes compliance with European Union Low Voltage Directive (50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact Bussmann Application Engineering at 636-527-1270 for more information.
Recommended fuseblocks/fuseholders for Class J 600V fuses
See Data Sheets listed below
• Finger-safe fuseholders - 1152
• Open fuseblocks - 1114
• Open pyramid fuseblocks - 1108
2.25"
(± 0.03)
.81"
.5"
(± 0.03)
1A to 30A
2.38"
(± 0.03)
.63"
35A to 60A
1.06"
(± 0.03)
Page 2
LOW-PEAK
®
LPJ
Dual-Element Time-Delay Fuses 1-60 Amps Class J – 600 Volt
Form No. LPJ 1-60
Page 2 of 3
Data Sheet: 1006
®
AMPERE RATING
1A
3A
6A
300
100
10
1
.1
.01
TIME IN SECONDS
10A
15A
30A
60A
1,000
10
1
CURRENT IN AMPERES
200
100
Time-Current Characteristic Curves–Average Melt
10-2-02
SB02295
Page 3
®
Form No. LPJ 1-60
Page 3 of 3
Data Sheet: 1006
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
LOW-PEAK
®
LPJ
Dual-Element Time-Delay Fuses 1-60 Amps Class J – 600 Volt
Current Limitation Curves
10-2-02
SB02295
Loading...