Catalog Symbol: LPJ-_SP
Dual-Element, Time-Delay – 10 seconds (minimum) at 500%
rated current
Current-Limiting
Ampere Rating: 1 to 60A
Voltage Rating: 600Vac (or less)
300Vdc (or less)
Interrupting Rating: 300,000A RMS Sym. (UL)
100,000A dc
Agency Information:
UL Listed — Special Purpose*, Guide JFHR, File E56412
CSA Certified, 200,000 AIR, Class J per CSA 22.2 No. 248.8
Class 1422-02, File 53787
*Meets all performance requirements of UL Standard 248-8 for Class J fuses.
Catalog Symbol and Ampere Ratings
LPJ-1SP LPJ-3SP LPJ-7SP LPJ-25SP
LPJ-1⁄Ω¢SP LPJ-3-¤Ω¡ºSP LPJ-8SP LPJ-30SP
LPJ-1-flΩ¡ºSP LPJ-3⁄Ω™SP LPJ-9SP LPJ-35SP
LPJ-1-°Ω¡ºSP LPJ-4SP LPJ-10SP LPJ-40SP
LPJ-2SP LPJ-4⁄Ω™SP LPJ-12SP LPJ-45SP
LPJ-2⁄Ω¢SP LPJ-5SP LPJ-15SP LPJ-50SP
LPJ-2⁄Ω™SP LPJ-5flΩ¡ºSP LPJ-17⁄Ω™SP LPJ-60SP
LPJ-2°Ω¡ºSP LPJ-6SP LPJ-20SP
Carton Quantity and Weight
Ampere Carton
Weight**
Ratings Qty. Lbs. Kg.
1–30 10 1.09 0.494
35–60 10 1.78 0.808
**Weight per carton.
General Information:
• True dual-element fuses with a minimum 10 second timedelay at 500% overload.
• Long time-delay minimizes needless fuse openings due to
temporary overloads and transient surges.
• Can often be sized for back-up protection against motor
burnout from overload or single-phasing if other overload
protective devices fail.
• High interrupting rating to safely interrupt overcurrents up to
300,000A.
• High degree of current limitation due to the fast speed-ofresponse to short-circuits.
• Faster response to damaging short-circuit currents than
mechanical overcurrent protective devices.
• Reduces let-through thermal and magnetic forces in order
to protect low withstand rated components.
• Proper sizing provides “no damage” Type “2” coordinated
protection for NEMA and IEC motor control in accordance
with IEC Standard 947-4-1.
• Dual-element fuses have lower resistance than ordinary fuses
so they run cooler.
• Lower watts loss reduces power consumption.
• Unique dimensions assure that another class of fuse with
a lesser voltage rating, interrupting rating or current-Iimiting
ability cannot be substituted.
• Space-saving package for equipment down sizing.
Dimensional Data
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
Recommended fuseblocks/fuseholders for
Class J 600V fuses
See Data Sheets listed below
• Finger-safe fuseholders - 1152
• Open fuseblocks - 1114
• Open pyramid fuseblocks - 1108