Bussmann KRP-C-SP Data Sheet

LOW-PEAK® Time-Delay Fuses KRP-C
Class L – 600 Volt 601-2000A
Form No. KRP-C-601-2000
Page 1 of 3
BIF Doc #1008
®
11-12-99
A99119
Rev. A
601Ato800A
.38"
2"
2.5"
2.53" Max.
10.75"
(± 0.09)
8.63"
(± 0.09)
6.75"
5.75"
801A
to
1200A
1350Ato1600A
1800Ato2000A
.5"
2.75"
.44"
2.38"
.38"
2"
3"
3.03" Max.
3.5"
3.53" Max.
0.63" (± 0.03)
All Slots and Holes
3.75"
2.5"
2.78" Max.
Terminal: Width (± 0.06) Thickness (± 0.03)
Catalog Symbol: KRP-C-SP Time-Delay – 4 seconds (minimum) at 500% rated current Current-Limiting
Ampere Rating: 601 to 2000 Amperes‡ Voltage Rating: 600 Volts AC (or less) 300 Volts DC (or less) Interrupting Rating: 300,000A RMS Sym. (UL) Interrupting Rating: 100,000A DC (UL) Agency Approvals:
UL Listed – Special Purpose
£,
Guide JFHR, File E56412
CSA Certified – (200,000 AIR), Class 1422-02, File 53787
Class L per CSA C22.2, No. 248.10
‡Use KRP-CL for current ratings below 601 amps. *601-3000A is rated 340 VDC and 50 KAIC. £Meets all performance requirements of UL Standard 248-10 for Class L fuses.
Ampere Ratings†
Catalog Ctn.
Weight**
Catalog Ctn.
Weight**
Number Qty. Lbs. Kg. Number Qty. Lbs. Kg.
KRP-C-601SP KRP-C-1350SP KRP-C-650SP KRP-C-1400SP KRP-C-700SP 1 3.75 1.7 KRP-C-1500SP
1 6.50 2.948
KRP-C-750SP KRP-C-1600SP KRP-C-800SP KRP-C-1800SP KRP-C-801SP KRP-C-1900SP 1 8.5 3.85 KRP-C-900SP KRP-C-2000SP KRP-C-1000SP 1 4.5 2.041 KRP-C-1100SP KRP-C-1200SP
**Weight per carton.
†Special purpose rating of 300,000 AIR.
Dimensional Data All other tolerances (± 0.02)
General Information:
• All-purpose silver-linked fuse for both overload and short­circuit protection for high capacity systems (mains and large feeders).
• Time-delay (minimum of four seconds at five times amp rating) for close sizing.
• Current-limiting action of the fuse generally affords considerable reduction in bus bracing.
• Interrupting rating of 300,000 amperes complies with NEC Sections 110-9 and 230-65 for today’s large capacity systems.
• O-ring seals maximize pressure build-up during current­limiting action and ensure filler retention.
• High grade silica-sand filler; accelerates response of fuse to short-circuits by having quenching effect upon the fuse arc.
• 99.9% pure silver fuselinks. The high conductivity of silver gives low watt loss and low operating temperature at nor­mal current levels; maximizes total clearing I
2
t fault energy
let-through.
• Selective coordination (blackout prevention).
• Glass melamine tube.
• Silver-plated end bells.
CE logo denotes compliance with European Union Low Voltage Directive (50-1000 VAC, 75-1500 VDC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information.
11-12-99 A99119
Rev. A
LOW-PEAK® Time-Delay Fuses KRP-C
Class L – 600 Volt 601-2000A
Form No. KRP-C-601-2000
Page 2 of 3
BIF Doc #1008
®
Time-Current Characteristic Curves–Average Melt
Fuseblocks: (601 - 1200 Amps)
Catalog Number Poles
51215 1 51235 3 No reducers available.
300
100
10
800A
1200A
1600A
2000A
AMPERE RATING
1
TIME IN SECONDS
.1
.01
1,000
CURRENT IN AMPERES
10,000
100,000
200,000
Loading...