Bussmann FWC Data Sheet

Form No.
Page 1 of 1
BIF Doc #720011
Bussmann
®
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Ferrule
FWC 600V 6-32A
®
Dimensions
500 600400250100
1.5
1.0
0.5
0.3
0.2
0.15
E
g
K
U
L
2.0
1.6
1.2
10
3
800 600
500 400 300
400300200 500 600
E
g
Kp
1.0
0.8
0.4
0.5
0.6
0.3
0.2
0.1 30 40 50 60
70
80 90 100%
I
b
38.1
(1.500")
9.5
(0.375")
10.3
(0.406")
Electrical Characteristics Ordering Information Dimensions Curves
Rated
I
2
t (A2S)
Carton
Current Clearing Watts Part Carton Weight Figure
Size RMS-Amps Pre-arc at 600V Loss Number Qty. (kg) Number BIF #
6 4 30 1.5 FWC-6A10F 8 6 50 2.0 FWC-8A10F
10 9 70 2.5 FWC-10A10F
10 ≈ 38mm 12 15 120 3.0 FWC-12A10F
10 0.100 Fig. 1 35785306
(⁄‹Ω£™∑) 16 25 150 3.5 FWC-16A10F
20 34 260 4.8 FWC-20A10F 25 60 390 6.0 FWC-25A10F 32 95 600 7.5 FWC-32A10F
n Interrupting rating 200kA RMS Symmetrical. 1 kg = 2.2 lbs. 1 lb = 0.45 kg n Watts loss provided at rated current. n (400 Vdc/Interrupting rating 50kA) U.L. Recognition: 32A n (700 Vdc/Interrupting rating 50kA) U.L. Recognition: 6 - 25A
Fig. 1: 6-32 Amp Range
Dimension in mm. 1mm = 0.0394∑ 1∑ = 25.4mm
Total Clearing I2t
The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other volt­ages, the clearing I
2
t is found by multi­plying by correction factor, K, given as a function of applied working voltage, E
g
, (RMS).
Arc Voltage
This curve gives the peak arc voltage, U
L
, which may appear across the fuse during its operation as a function of the applied working voltage, E
g
, (RMS) at a
power factor of 15%.
Power Losses
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K
p
, is given as a function of the RMS load current, I
b
, in % of the rated current .
Electrical Characteristics
7-18-01
SB01191