Bussmann FRS-R Data Sheet

Fusetron
®
FRS-R
Dual-Element, Time-Delay Fuses
⁄Ω¡º-60A
Class RK5 – 600 Volt
Form No. FRS-R 1/10-60
Page 1 of 2
Bussmann
®
7-25-03
A03014
Catalog Numbers
FRS-R-⁄Ω¡º FRS-R-1°Ω¡º FRS-R-8 FRS-R-⁄Ω• FRS-R-2 FRS-R-9 FRS-R-⁄fiΩ¡ºº FRS-R-2⁄Ω¢ FRS-R-10 FRS-R-¤Ω¡º FRS-R-2⁄Ω™ FRS-R-12 FRS-R-⁄Ω¢ FRS-R-2°Ω¡º FRS-R-15 FRS-R-‹Ω¡º FRS-R-3 FRS-R-17⁄Ω™ FRS-R-›Ω¡º FRS-R-3¤Ω¡º FRS-R-20 FRS-R-⁄Ω™ FRS-R-3⁄Ω™ FRS-R-25 FRS-R-flΩ¡º FRS-R-4 FRS-R-30 FRS-R-°Ω¡º FRS-R-4⁄Ω™ FRS-R-35 FRS-R-1 FRS-R-5 FRS-R-40 FRS-R-1⁄Ω• FRS-R-5flΩ¡º FRS-R-45 FRS-R-1⁄Ω¢ FRS-R-6 FRS-R-50 FRS-R-1›Ω¡º FRS-R-6⁄Ω¢ FRS-R-60 FRS-R-1⁄Ω™ FRS-R-7 — FRS-R-1flΩ¡º FRS-R-7⁄Ω™
Fuse Reducers For Class R Fuses
Desired Catalog Number Equipment Fuse (Case) (Pairs) Fuse Clips Size 600V
60A 30A No. 663-R 100A
30A No. 216-R 60A No. 616-R
200A 60A No. 626-R
Dimensional Data
Carton Quantity and Weight
Ampere Carton
Weight*
Ratings Qty. Lbs. Kg.
⁄Ω¡º–15 10 0.40 0.181
17.5–30 10 0.50 0.277 35-60 10 3.10 1.406 *Weight per carton.
General Information:
• Provides motor overload, ground fault and short-circuit pro-
tection. When used in circuits subject to surge currents such as those caused by motors, transformers and other inductive components, these fuses can be sized close to full-load amperes to give maximum overcurrent protection.
• Permits the use of smaller and less costly switches. The time-
delay feature makes it possible to use fuse ampere ratings which are much smaller than those of non-time-delay fuses. Considerable cost saving occurs by permitting the use of smaller size switches, panels and fuses themselves.
• Provides a higher degree of short-circuit protection (greater
current-limitation) in circuits in which surge currents or tempo­rary overloads occur.
• Helps protect motors against burnout from overloads.
• Gives motor running back-up protection to motors without
extra costs.
• Helps protect motors against burnout from single phasing on
three phase systems.
• Simplifies and improves blackout prevention (selective
coordination).
• Dual-element fuses can be applied in circuits subject to tem-
porary motor overloads and surge currents to provide both high-performance, short-circuit and overload protection.
• The overload element provides protection against low level
overcurrent of overloads and will hold an overload which is five times greater than the ampere rating of the fuse for a minimum of ten seconds.
Catalog Symbol: FRS-R Dual-Element, Time-Delay – 10 second (minimum) at 500%
rated current
Current-Limiting
Ampere Rating: ⁄Ω¡º to 60A Voltage Rating: 600Vac (or less) Interrupting Rating: 200,000A RMS Sym.
dc Ratings (20,000AIC @ 250Vdc)
Agency Information:
UL Listed, Std. 248-12, Class RK5, Guide JDDZ, File E4273 CSA Certified, C22.2 No. 248.12, Class 1422-02, File 53787
CE logo denotes compliance with European Union Low Voltage Directive (50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact Bussmann Application Engineering at 314-527-1270 for more information.
Recommended fuseblocks for Class R 600V fuses See Data Sheet: 1111
5" (± 0.31)
.81" (± 0.008)
⁄Ω¡ºA to 30A
5.5" (± 0.31)
1.06" (± 0.008)
35A to 60A
Fusetron
®
FRS-R
Dual-Element, Time-Delay Fuses
⁄Ω¡º-60A
Class RK5 – 600 Volt
Form No. FRS-R 1/10-60
Page 2 of 2
Bussmann
®
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Current-Limitation Curves
Time-Current Characteristic Curves–Average Melt
7-25-03
A03014
.5
.811.25
2.5
.1.2.15.3.4
300
100
10
1
TIME IN SECONDS
.1
.6
1.6
2
456.25
3.2
AMPERE RATING
8
10
12
300
100
10
AMPERE
60A
30A
15A
1
RATING
.01
.1
1
CURRENT IN AMPERES
400,000
100,000
10,000
CURRENT IN AMPERES
INSTANTANEOUS PEAK LET- THROUGH
A
1,000
10
100
1,000
B
AMPERE
60 30
15
TIME IN SECONDS
.1
RATING
.01
20
100
CURRENT IN AMPERES
1,000
10,000
30,000
1,000
PROSPECTIVE SHORT-CIRCUIT CURRENT
SYMMETRICAL RMS AMPERES
10,000
100,000
200,000
Loading...