1210 BU-SB101431 Page 1 of 2 Data Sheet 1165
Description
The Cooper Bussmann®IEC Class I 230 volt, four-pole, modular combined
lightning, current and surge arresters feature local,
easy
ID™ visual indication
and optional remote contact signaling. The unique module locking system
fixes the protection module to the base part. Modules can be easily replaced
without tools by simply depressing the release buttons. Integrated mechanical
coding between the base and protection module ensures against installing an
incorrect replacement module.
230 Volt models are offered with MCOV ratings of 255 volts.
TNS System Arresters
The features of these four-pole devices are for use in TNS 230/400 volt
systems (“4-0” circuit) against surges.
TT System Arrester
Provides a current arresting means between neutral conductor and protective
conductor in TT 230/400 volt systems (“3+1” circuit) against surges.
Remote Signaling Contact
The three-pole terminal remote signaling contact versions have a floating
changeover contact for use as a break or make contact, according to circuit
concept.
Surge Protection Made Simple™for IEC Applications
IEC Class I Combined Lightning, Current and Surge Arresters for
230/400 Volt, 4-Pole TNS & TT Systems
BSPS4255TNS(R)
Shown with
optional remote
contact signaling
BSPS4255TNS(R)
BSPS4255TT(R)
Shown with optional remote contact signaling
Circuit Diagrams
BSPS4255TT(R)
Shown with
optional remote
contact signaling
Dimensions - mm
Remote Signal
Contact Available
Visual Status Indication
Creepage Discharge Spark Gap
Spark Gap Trigger

1210 BU-SB101431 Page 2 of 2 Data Sheet 1165
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Ordering Information
System Voltage/Poles 230/400V/4 230/400V/4
Max. Continuous operating AC voltage (MCOV) [UC] 255V 255V
Catalog Numbers: Without Remote Signaling BSPS4255TNS BSPS4255TT
With Remote Signaling BSPS4255TNSR BSPS4255TTR
Replacement Modules (Spark Gap technology):
BPS255IEC BPS255IEC
- - BPS100NPEIEC*
Specifications
SPD according to EN 61643-11/... IEC 61643-1 Type 1/Class I
Energy-coordinated protection effect with regard to the terminal equipment Type 1 + Type 2
Energy-coordinated protection effect with regard to the terminal equipment (<_ 5m) Type 1 + Type 2 + Type 3
Nominal AC voltage [UN] 230/400V
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] [I
total
] 100kA
Specific energy [L1+L2+L3+N-PE] [W/R] 2.50MJ/ohms
Lightning impulse current (10/350 µs) [L, N-PE] [I
imp
] 25kA
TNS system specific energy [L,N-PE] [W/R] 156.25kJ/ohms
TT system specific energy [L-N]/[N-PE] [W/R] 156.25kJ/ohms/2.50kJ/ohms
Nominal discharge current (8/20 µs) [In] 25/100kA
Voltage protection level [L-PE]/[N-PE] [UP]<_ 1.5kV/<_ 1.5kV
TNS system follow current extinguishing capability AC [Ifi] 50kA rms
TT system follow current extinguishing capability AC [Ifi] 50kA rms/100A rms
Follow current limitation/Selectivity No tripping of a 20A gL/gG fuse up to 50kA rms (prosp.)
Response time [tA] <_ 100 ns
Max. Backup fuse (L) up to IK<_ 50kA rms 315A gL/gG
Max. Backup fuse (L) for IK> 50kA rms 200A gL/gG
Max. Backup fuse (L-L´) 125A gL/gG
Temporary overvoltage (TOV) [L-N] [UT] 440V/5 sec.
Temporary overvoltage (TOV) [N-PE] [UT] 1200V/200mS
TOV characteristics Withstand
Operating temperature range [parallel]/[continuity] [TU] -40°C to +80°C/-40°C to +60°C
Operating state/fault indication green (good)/red (replace)
Number of ports 1
Cross-sectional area (L1, L1´, L2, L2´, L3, L3´, N, N´, PE, ) [min.] 10mm2solid/flexible
Cross-sectional area (L1, L2, L3, N, PE) [max.] 50mm2/1AWG stranded-35mm2/2AWG flexible
Cross-sectional area (L1´, L2´, L3´, N´, ) [max.] 35mm2/2AWG stranded-25mm2/4AWG flexible
Mounting 35mm DIN Rail per EN 60715
Enclosure material Thermoplastic, UL 94V0
Location category Indoor
Degree of protection IP20
Capacity 8 mods., DIN 43880
Agency Information KEMA
Product Warranty Five Years**
Remote Contact Signaling
Remote Contact Signaling Type Changeover Contact
AC Switching Capacity (Volts/Amps) 250V/0.1A
DC Switching Capacity (Volts/Amps) 250V/0.1A; 125V/0.2A; 75V/0.5A
Conductor Ratings and Cross-Sectional Area for Remote Contact Signal Terminals 60/75°C Max. 1.5mm2/14AWG Solid/Flexible
Ordering Information Order from Catalog Numbers Above
* N-PE Surge arrester for location between neutral conductor and protective conductor in TT systems.
** See Cooper Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge.
Recommended Cooper Bussmann NH DIN Size Back Up Fuses
Size NH Fuse Part Number Size NH Fuse Part Number
00 125NHG00B (max L-L) 02 125NHG02B (max L-L)
0 125NHG0B (max L-L) 02 200NHG02B (max L Ik >50kA)
01 125NHG01B (max L-L) 2 315NHG2B (max L _<50kA)
1 200NHG1B (max L Ik >50kA) 03 315NHG03B (max L _<50kA)