Bussmann BSPS3255TNC Data Sheet

1210 BU-SB101430 Page 1 of 2 Data Sheet 1164
Description
The Cooper Bussmann®IEC Class I 230 Volt, three-pole, modular combined lightning, current and surge arresters feature local,
easy
230 Volt models are offered with a MCOV rating of 255 volts.
TNC System Arrester
The features of these three-pole devices are for use in TN-C 230/400 Volt systems (“3-0” circuit) against surges.
Remote Signaling Contact
The three-pole terminal remote signaling contact versions have a floating changeover contact for use as a break or make contact, according to circuit concept.
Surge Protection Made Simple™for IEC Applications
IEC Class I Combined Lightning, Current and Surge Arrester for 230/400 Volt, 3-Pole TNC Systems
BSPS3255TNC(R)
Shown with optional
remote contact signaling
Shown with optional
remote contact signaling
Circuit Diagrams
Dimensions - mm
Remote Signal
Contact Available
Visual Status Indication
BSPS3255TNC(R)
Creepage Discharge Spark Gap
Spark Gap Trigger
1210 BU-SB101430 Page 2 of 2 Data Sheet 1164
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information con­tained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Ordering Information
System Voltage/Poles 230/400V/3 Max. Continuous operating AC voltage (MCOV) [UC] 255V Catalog Numbers: Without Remote Signaling BSPS3255TNC
With Remote Signaling BSPS3255TNCR
Replacement Module Spark Gap Technology BPS255IEC
Specifications
SPD according to EN 61643-11/... IEC 61643-1 Type 1/Class I Energy-coordinated protection effect with regard to the terminal equipment Type 1 + Type 2 Energy-coordinated protection effect with regard to the terminal equipment (<_ 5m) Type 1 + Type 2 + Type 3 Nominal AC voltage [UN] 230/400V Lightning impulse current (10/350 µs) [L1+L2+L3-PEN] [I
total
] 75kA Specific energy [L1+L2+L3-PEN] [W/R] 1.40 MJ/ohms Lightning impulse current (10/350 µs) [L-PEN] [I
imp
] 25kA Specific energy [L-PEN] [W/R] 156.25kJ/ohms Nominal discharge current (8/20 µs) [In] 25/75kA Voltage protection level [UP] <_ 1.5kV Follow current extinguishing capability AC [Ifi] 50kA rms Follow current limitation/Selectivity no tripping of a 20A gL/gG fuse up to 50kA rms (prosp.) Response time [tA] <_ 100 ns Max. Backup fuse (L) up to IK= 50kA rms 315A gL/gG Max. Backup fuse (L) for IK> 50kA rms 200A gL/gG Max. Backup fuse (L-L´) 125A gL/gG Temporary overvoltage (TOV) [UT] 440V/5 sec. TOV characteristics withstand Operating temperature range [parallel]/[continuity] [TU] -40°C to +80°C/-40°C to +60°C Operating state/fault indication green (good)/red (replace) Number of ports 1
Cross-sectional area (L1, L1´, L2, L2´, L3, L3´, PEN, ) [min.] 10mm2solid/flexible Cross-sectional area (L1, L2, L3, PEN) [max.] 50mm2/1AWG stranded-35mm2/2AWG flexible
Cross-sectional area (L1´, L2´, L3´, ) [max.] 35mm2/2AWG stranded-25mm2/4AWG flexible Mounting 35mm DIN rail per to EN 60715 Enclosure material Thermoplastic, UL 94V0 Location category Indoor Degree of protection IP20 Capacity 6 mods., DIN 43880 Standards Information KEMA Product Warranty Five Years*
Remote Contact Signaling
Remote Contact Signaling Type Changeover Contact AC Switching Capacity (Volts/Amps) 250V/0.1A DC Switching Capacity (Volts/Amps) 250V/0.1A; 125V/0.2A; 75V/0.5A Conductor Ratings and Cross-Sectional Area for Remote Contact Signal Terminals 60/75°C Max. 1.5mm2/14AWG Solid/Flexible Ordering Information Order from Catalog Numbers Above
* See Cooper Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge.
Recommended Cooper Bussmann NH DIN Size Back Up Fuses
Size NH Fuse Part Number Size NH Fuse Part Number
00 125NHG00B (max L-L) 02 125NHG02B (max L-L)
0 125NHG0B (max L-L) 02 200NHG02B (max L Ik >50kA)
01 125NHG01B (max L-L) 2 315NHG2B (max L _<50kA)
1 200NHG1B (max L Ik >50kA) 03 315NHG03B (max L _<50kA)
Loading...