Bussmann BSPS1400WE, BSPS1690WER Data Sheet

Surge Protection Made Simple™ for Wind Power Applications
IEC Class I Coordinated Lightning Current Arresters with High Follow Current for 400-690 Volt, TNC, TNS & IT Systems
Description
The Cooper Bussmann®IEC Class I 400 and 690 Volt, one­pole lightning current arresters feature local, indication and optional remote contact signaling.
440V and 760V maximum continuous operating voltage arresters protect installations against surges and direct lightning strikes.
System & Application
TNC 400V/690V: 3x BSPS1400WE(R)
TNS 400/690V: 4x BSPS1400WE(R)
IT 690V: 3x BSPS1690WER
Remote Signaling Contact
The three-pole terminal remote signaling contact versions have a floating changeover contact for use as a break or make contact, according to circuit concept.
easy
ID™ visual
Visual Status Indication
BSPS1400WE(R) BSPS1690WER
Contact Available
Remote Signal
Dimensions - mm
Shown with optional remote contact signaling
Circuit Diagrams
BSPS1400WE(R)
BSPS1690WER
- Shown with optional remote contact signaling
Creepage Discharge Spark Gap
Spark Gap Trigger
0211 BU-SB11087 Page 1 of 2 Data Sheet 2091
Ordering Information
System Voltage/Poles 400V/1 690V/1
Max Continuous Operating AC Voltage (MCOV) [Uc]
440V 760V
Catalogue Numbers Without Remote Signaling BSPS1400WE - -
With Remote Signaling BSPS1400WER BSPS1690WER
Specifications
Line System Type TNC, TNS, IT TNC, TNS, IT
Lightning Impulse Current (10/350µs) [I
] 35kA 25kA
imp
Specific Energy [W/R] 306.25kJ/ohms 156.25kJ/ohms
Nominal Discharge Current (8/20µs) [In] 35kA 25kA
Voltage Protection Level [Up]
Follow Current Extinguishing Capability AC [Ifi] 50kA
Follow Current Limitation/Selectivity
fuse up to 50kA
Response Time [tA]
Max. backup fuse (L) up to IK= 25kA
Max. Backup Fuse (L) up to IK> 25kA
Max. Backup Fuse (L) up to IK= 50kA
Max. Backup Fuse (L) up to IK= 50kA
Max. Backup Fuse (L) for IK> 50kA
rms
rms
rms
(ta ≤ 5s)
_< 0.2 s) 500A gL/gG --
rms(ta
_< 5 s) 250A gL/gG --
rms(ta
≤2.5kV ≤4kV
rms
no tripping of 32A gL/gG
(prosp.)
rms
≤100ns ≤100ns
-- 250A gL/gG
-- 100A gL/gG
160A gL/gG --
25kA
rms
no tripping of 32A gL/gG
fuse up to 25kA
rms
Max. Backup Fuse (L-L´) 125A gL/gG 125A gL/gG
Short-Circuit Withstand Capability for Max. Mains-Side Overcurrent Protection
50kA
rms
25kA
rms
Temporary Overvoltage (TOV) [UT] 690V / 5sec 1000V / 5 sec
Cross-Sectional Area (L, L´, ) [min.] Cross-Sectional Area (L, L´, N/PEN) [min.]
Cross-Sectional Area (L, N/PEN) [max.]
Cross-Sectional Area (L, ) [max.]
Cross-Sectional Area (L´) [max.]
--
100mm2solid/flexible
50mm2/1AWG stranded/35mm2/
2AWG flexible
--
50mm2/1AWG stranded/35mm2/
4AWG flexible
100mm2solid/flexible
--
--
50mm2/1AWG stranded/35mm2/
2AWG flexible
50mm2/1AWG stranded/35mm2/
4AWG flexible
SPD According to EN 61643-11 Type 1
SPD According to IEC 61643-1 Class I
TOV Characteristics Withstand
Operating Temperature Range (parallel connection) [TUP]
Operating Temperature Range (series connection) [TUS]
-40oC to +80oC
-40oC to +60oC
Operating State/Fault Indication Green (good) / Red (replace)
Number of Ports 1
Mounting 35mm DIN rail per EN 60715
Enclosure Material Thermoplastic, UL94V0
Place of Installation Indoor
Degree of Protection IP20
Capacity 2 Mods., DIN 43880
Product Warranty Five Years*
Remote Contact Signaling
Remote Contact Signaling Type Changeover Contact
AC Switching Capacity (Volts/Amps) 250V/0.5A
DC Switching Capacity (Volts/Amps) 250V/0.1A; 125V/0.2A; 75V/0.5A
Conductor Ratings and Cross-Sectional Area for Remote Contact Signal Terminals
60/75oC Max. 1.5mm2/
14AWG Solid/Flexible
Ordering Information Order from Catalogue Number Above
(prosp.)
Recommended Cooper Bussmann NH DIN Size Back Up Fuse Links
Size NH Fuse Part Number
000 100NHG000B-690 (max L) up to IK> 25kA
rms
* See Cooper Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge
00 125NHG00B-690 (max L-L´)
01 160NHG01B-690 (max L) for IK> 50kA
02 250NHG02B-690 (max L) up to IK= 25kA
02 250NHG02B-690 (max L) up to IK= 50kA
3 500NHG3B-690 (max (L) up to IK= 50kA
0211 BU-SB11087 Page 2 of 2 Data Sheet 2091
rms
rms(ta
rms(ta
rms(ta
_< 5 s)
_< 5 s)
_< 0.2 s)