Bussmann BSPM3230WE, BSPM3400WE, BSPM3690WE Data Sheet

0211 BU-SB11186 Page 1 of 2 Data Sheet 2094
Description
The Cooper Bussmann®IEC Class II 230, 400 and 690 volt three-pole, modular surge arresters feature local,
easy
TNC System Arresters
The features of these three-pole devices are for use as a single device.
Remote Signaling Contact
The three-pole terminal remote signaling contact versions have a floating changeover contact for use as a break or make contact, according to circuit concept.
Surge Protection Made Simple™ for Wind Power Applications
IEC Class II Surge Arrester for 230, 400 and 690 Volt, TNC Systems
BSPM3230WE(R) BSPM3400WE(R) BSPM3690WE(R)
Shown with optional remote contact signaling
Module Circuit Diagrams -
Shown with optional remote contact signaling
Dimensions - mm
Remote Signal
Contact Available
Visual Status Indication
BSPM3230WE(R) BSPM3400WE(R) BSPM3690WE(R)
MOV
Thermal Disconnector
0211 BU-SB11186 Page 2 of 2 Data Sheet 2094
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information con­tained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Ordering Information
System Voltage/Poles 230V/3 400V/3 690V/3 Max. Continuous operating AC voltage (MCOV) [UC] 275V 440V 600V Catalog Numbers: Without Remote Signaling BSPM3230WE BSPM3400WE BSPM3690WE (Base + Modules) With Remote Signaling BSPM3230WER BSPM3400WER BSPM3690WER Replacement Modules BPM275WE BPM440WE BPM750WE
Specifications
Line System Type TNC TNC TNC Nominal AC Voltage [UN] 230/400V 400/690V 600V Rated Varistor Voltage [U
mov
] 275V 440V 750V Nominal Discharge Current (8/20 µs) [In] 20kA 20kA 15kA Max. Discharge Current (8/20 µs) [I
max
] 40kA 40kA 25kA Voltage Protection Level [UP]_<1.25kV _< 2kV _<3kV Voltage Protection Level at 5kA [UP]_<1kV _< 1.7kV _<2.5kV Response Time [tA]_<25 ns _< 25 ns _<25 ns Max. Mains-side Overcurrent Protection 125A gL/gG 125A gL/gG 100A gL/gG Short-circuit Withstand Capability for Max. Mains-side Overcurrent Protection 50kA
rms
25kA
rms
25kA
rms
Temporary Overvoltage (TOV) [UT] 335V / 5 sec. 580V / 5 sec. 900V / 5 sec. Standards Information KEMA - - KEMA SPD According to EN 61643-11 Type 2 SPD According to IEC 61643-1 Class II TOV Characteristics Withstand Operating Temperature Range [TU] -40°C to +80°C Operating State/Fault Indication Green (good) / Red (replace) Number of Ports 1 Cross-Sectional Area (min.) 1.5mm2/14AWG solid/flexible Cross-Sectional Area (max.) 35mm2/2AWG stranded-25mm2/4AWG flexible Mounting 35mm DIN rail per EN 60715 Enclosure Material Thermoplastic, UL 94V0 Location Category Indoor Degree of Protection IP20 Capacity 3 Mods., DIN 43880 Product Warranty Five Years*
Remote Contact Signaling
Remote Contact Signaling Type Changeover Contact AC Switching Capacity (Volts/Amps) 250V/0.5A DC Switching Capacity (Volts/Amps) 250V/0.1A; 125V/0.2A; 75V/0.5A Conductor Ratings and Cross-Sectional Area for
60/75°C Max. 1.5mm2/14AWG Solid/Flexible
Remote Contact Signal Terminals Ordering Information Order from Catalog Numbers Above
* See Cooper Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge.
Recommended Cooper Bussmann Back Up Fuse
DIN Fuse Size NH Fuse Part Number
00 125NHG00B
Loading...