Description
The Cooper Bussmann®IEC Class II 120/240 volt and 230/400 volt, three­pole, modular surge arresters feature local,
easy
120 Volt models are offered with a MCOV rating of 150 volts.
230 Volt models are offered with a MCOV rating of 275 or 385 volts.
TNC System Arresters
The features of these three-pole devices are for use in TN-C 120/240 volt or 230/400 volt systems (“3-0” circuit) against surges.
Remote Signaling Contact
The three-pole terminal remote signaling contact versions have a floating changeover contact for use as a break or make contact, according to circuit concept.
Surge Protection Made Simple™for IEC Applications
IEC Class II Surge Arrester for 120/240 and 230/400 Volt, 3-Pole TNC Systems
BSPM3150TNC(R), BSPM3275TNC(R), BSPM3385TNC(R)
Shown with optional remote contact signaling
BSPM3150TNC(R)
BSPM3275TNC(R)
BSPM3385TNC(R)
Shown with optional remote contact signaling
Circuit Diagrams
Dimensions - mm
Remote Signal
Contact Available
Visual Status Indication
MOV
Thermal Disconnector
0611 BU-SB11583 Page 2 of 2 Data Sheet 1168
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information con­tained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
O
RDERINGINFORMATION
System Voltage/Poles 120V/3 230V/3 230V/3 Max. Continuous operating AC voltage (MCOV) [UC] 150V 275V 385V Catalog Numbers: Without Remote Signaling BSPM3150TNC BSPM3275TNC BSPM3385TNC
With Remote Signaling BSPM3150TNCR BSPM3275TNCR BSPM3385TNCR
Replacement Module MOV technology BPM150IEC BPM275IEC BPM385IEC
S
PECIFICATIONS
Nominal AC voltage [UN] 120/240V 230/400V 230/400V Voltage protection level [UP]_< 0.7kV <_ 1.25kV _< 1.75kV Voltage protection level at 5kA [UP]_< 0.55kV <_ 1kV _< 1.35kV Short-circuit withstand capability for max. mains-side overcurrent protection 50kA
rms
50kA
rms
25kA
rms
Temporary overvoltage (TOV) [UT] 175V/5 sec 335V/5 sec. 385V/5 sec Standards Information - - KEMA - ­Nominal discharge current (8/20 µs) [In] 15kA 20kA 20kA Max. Discharge current (8/20 µs) [I
max
] 40kA SPD according to EN 61643-11 Type 2 SPD according to IEC 61643-1 Class II Response time [tA] <_ 25 ns Max. mains-side overcurrent protection 125A gL/gG TOV characteristics withstand Operating temperature range [TU] -40°C to +80°C Operating state/fault indication Green (good)/Red (replace) Number of ports 1 Cross-sectional area (min.) 1.5mm2/14AWG solid/flexible Cross-sectional area (max.) 35mm2/2AWG stranded-25mm2/4AWG flexible Mounting 35mm DIN rail per EN 60715 Enclosure material Thermoplastic, UL 94V0 Location category Indoor Degree of protection IP20 Capacity 3 mods., DIN 43880 Product Warranty Five Years*
R
EMOTECONTACTSIGNALING
Remote Contact Signaling Type Changeover Contact AC Switching Capacity (Volts/Amps) 250V/0.1A DC Switching Capacity (Volts/Amps) 250V/0.1A; 125V/0.2A; 75V/0.5A Conductor Ratings and Cross-Sectional Area for Remote Contact Signal Terminals 60/75°C Max. 1.5mm2/14AWG Solid/Flexible Ordering Information Order from Catalog Numbers Above
* See Cooper Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge.
Recommended Cooper Bussmann Back Up Fuses
DIN Fuse Size NH Fuse Part Number
00 125NHG00B
0 125NHG0B 01 125NHG01B 02 125NHG02B