Bussmann BSPM2 Data Sheet

Technical Data 2150
Effective February 2016 Supersedes August 2014
Two-pole high SCCR UL Type 2 surge protective devices for split-phase Delta and Wye systems
Standard local visual indication
The green and red visual indicator flags show the module protective status (green = good, red = replace).
Optional remote contact signaling
Remote contact signaling available
easy
ID™ local visual status indication
Catalog symbols:
•
BSPM2___S3G
•
Description:
Eaton Bussmann® series two-pole UL modular surge arresters feature easyID™ local visual indication and optional remote contact signaling for system monitoring.
The unique module locking system fixes the protection modules to the base and they can be easily replaced without tools by simply depressing the release buttons.
Integrated mechanical coding between the base and protection module ensures against installing an incorrect replacement.
The three-pole terminal remote contact signaling option has a floating changeover contact for use as a break or make contact, according to circuit concept.
Specifications:
System volts
•
120/240Vac
•
240/480Vac
•
120/208Vac
•
277/480Vac
•
240Vac
•
480Vac
Short-Circuit Current Rating (SCCR)
•
Up to 200kA
Systems types
•
Single-phase center tap
•
3 wire Wye
•
2 wire Delta, corner ground and ungrounded
Agency information
•
UL® Recognized 1449 4th Edition, Type 2 Component Assembly
•
Vibration and shock tested per EN 60068-2
•
CE
•
RoHS compliant
Mounting
•
35mm DIN-Rail
Warranty
•
Five years
Technical Data 2150
L2L1
L
L1
L1
L1
Effective February 2016
Two-pole high SCCR UL Type 2 surge protective devices
for split-phase Delta and Wye systems
Dimensions - mm:
Module circuit diagrams:
Shown with optional remote contact signaling
12 11 14
Gnd/N
Gnd/N
BSPM2240S3G
BSPM2480S3G
12 11 14
MOV
Optional remote contact signal
Thermal disconnector
Shown with optional remote contact signaling.
Typical installation/system application:
N
L
120/240V, 240/480Vac
Single-phase (split) center tap
BSPM2240S3G, BSPM2480S3G
120/208V, 277/480Vac
3 wire Wye
BSPM2240S3G, BSPM2480S3G
L2
N
L3
L2
2 wire corner grounded delta
240, 480Vac
BSPM2440S3G, BSPM2480S3G
L2
2 wire ungrounded delta
240, 480Vac
BSPM2440S3G, BSPM2480S3G
2
Eaton.com/bussmannseries
Two-pole high SCCR UL Type 2 surge protective devices for split-phase Delta and Wye systems
Technical Data 2150
Effective February 2016
Ordering information:
Nominal system voltage 120/240, 240Vac 240/480Vac
Max. Continuous Operating Voltage MCOV (V
Catalog numbers (base + modules)
Replacement module MOV technology BPM275UL BPM385UL
Specifications
Rated voltage
Voltage Protection Rating VPR [L-G/L-L] 1kV/1.8kV 1.5kV/2.5kV
Discharge current
Response time t
A
SCCR 200kA Frequency 50/60Hz Number of poles 2 Number of wires/connection points 2 wires or 3 wires / 3 connection points Operating state/fault indication Green (good) / Red (replace)
Cross-sectional area
Terminal torque 45 lb-in (5.1N•m) Mounting 35mm DIN-rail per EN 60715 Enclosure material Thermoplastic, UL 94V0 Protection IP20 (finger-safe) Location Indoor Capacity 2 mods, DIN 43880 Application/standard UL Type 2 Component Assembly, UL 1449, 4 Agency information cURus, RoHS Compliant Warranty Five years*
Remote contact signaling
Signaling type Changeover contact
Switching capacity (volts/amps)
Conductor and cross-sectional area 60/75°C Max. 1.5mm Ordering information Order from catalog numbers above
* See Eaton Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge.
) [L-G/L-L] 275/550Vac 385/770Vac
C
W/O remote signaling BSPM2240S3G BSPM2480S3G
W/ remote signaling BSPM2240S3GR BSPM2480S3GR
120-127Vac 240-480Vac
240-254Vac 480Vac
240Vac
Nom. I
Max. I
max
n
20kA 40kA 25 ns
Min. 14AWG - Cu stranded, solid or fine
Max. 2AWG - Cu solid or stranded, 4AWG - Cu fine
th
Edition
AC 250V/0.5A
DC 250V/0.1A; 125V/0.2A; 75V/0.5A
2
/14AWG solid/flexible
Eaton.com/bussmannseries
3