Bussmann BSPM1A48D60LV, BSPM1A75D100LV, BSPM1A150D200LV, BSPM1A275D350LV, BSPM1A320D420LV Data Sheet

...
Surge Protection Made Simple™ for LV Power Applications
UL Type 4 BSP LV Power Series for 48Vac/60Vdc, 75Vac/100Vdc, 120Vac/200Vdc 275Vac/350Vdc, 320Vac/420Vdc, 385Vac/500Vdc, 440Vac/585Vdc and 600Vac/dc LV Systems
Description
The Bussmann UL Type 4 component assembly for use in Type 2 applications 48Vac/60Vdc, 75Vac/100Vdc, 120Vac/200Vdc, 275VAc/350Vdc, 320Vac/420Vdc, 385Vac/500Vdc, 440Vac/585Vdc and 600Vac/dc single pole, modular surge arresters feature local, easyID™ visual indication and optional remote contact signaling. The unique module locking system fixes the protection module to the base part. Modules can be easily replaced without tools by simply depressing the release buttons. Integrated mechanical coding between the base and protection module ensures against installing an incorrect replacement module.
LV Power System Arresters
The features of these single-pole devices are for use as a single device or in combination with other devices for AC and DC voltage systems.
• Surge arrester according to UL 1449 3rdEdition, Type 4 Component Assembly for use in Type 2 applications helps meet UL 508A requirements*
• Proven MOV technology for reliable surge protection
• "Thermo Dynamic Control" SPD monitoring device ensures high reliability against surge events
• Module locking system with module release button make module replacement easy without tools
• Optional remote signaling of all protection modules make status monitoring easy and accurate in any monitoring scheme
• Vibration and shock tested according to EN 60068-2 to withstand harsh environments
Optional Remote Signaling Contact
The remote signaling contact versions have a floating changeover contact for use as a break or make contact for easy adoption in any monitoring application.
* Except as noted in data sheets.
Dimensions - mm
Visual Status Indication
Non SCCR
BSP LV Power Series
Circuit Diagrams
Remote Signal
Contact Available
BSPMA48D60LV, BSPMA75D100LV, BSPMA150D200LV,
BSPM1A275D350LV, BSPM1A320D420LV, BSPM1A385D500LV,
BSPM1A440D585LV, BSPM1A600D600LV*
Shown with optional remote contact signaling
Shown with optional remote contact signaling
0115 BU-SB12332 Page 1 of 2 Data Sheet 2056
* For remote signaling contact, add “R” suffix to the part number.
E.g., BSPMA150D200LVR
Thermal Disconnector
MOV
Ordering Information - 48Vac/60Vdc to 275Vac/350Vdc
System Voltage 48Vac/60Vdc 75Vac/100Vdc 120Vac/200Vdc 275Vac/350Vdc Catalog Numbers: Without Remote Signaling BSPM1A48D60LV BSPM1A75D100LV BSPM1A150D200LV BSPM1A275D350LV (Base + Modules) With Remote Signaling BSPM1A48D60LVR BSPM1A75D100LVR BSPM1A150D200LVR BSPM1A275D350LVR Replacement Modules BPMA48D60LV BPMA75D100LV BPMA150D200LV BPMA275D350LV
Specifications
Max. continuous operating AC voltage [VC] 48Vac 75Vac 150Vac 275Vac Max. continuous operating DC voltage [VC] 60Vdc 100Vdc 200Vdc 350Vdc Nominal AC discharge current (8/20 µs) [In] 7.5kA 10kA 15kA 20kA Nominal DC discharge current (8/20 µs) [In] 7.5kA 10kA 12.5kA 12.5kA Max. AC discharge current (8/20 µs) [I Max. DC discharge current (8/20 µs) [I Voltage protection level [VPR] 0.33kV 0.4kV 0.7kV 1.25kV
] 25kA 40kA 40kA 40kA
max
] 25kA 25kA 25kA 40kA
max
Voltage protection level at 5 kA [VPR] 0.25kV 0.35kV 0.55kV 1kV Temporary overvoltage (TOV) 70V / 5 sec. 90V / 5 sec. 175V / 5 sec. 335V / 5 sec
Agency Information* - -
UL / cUL, UL / cUL, UL / cUL,
CSA, KEMA CSA, KEMA CSA, KEMA
Ordering Information - 320Vac/420Vdc to 600Vac/dc
System Voltage 320Vac/420Vdc 385Vac/500Vdc 440Vac/585Vdc 600Vac/600Vdc Catalog Numbers: Without Remote Signaling BSPM1A320D420LV BSPM1A385D500LV BSPM1A440D585LV BSPM1A600D600LV (Base + Modules) With Remote Signaling BSPM1A320D420LVR BSPM1A385D500LVR BSPM1A440D585LVR BSPM1A600D600LVR Replacement Modules BPMA320D420LV BPMA385D500LV BPMA440D585LV BPMA600D600LV
Specifications
Max. continuous operating AC voltage [VC] 320Vac 385Vac 440Vac 600Vac Max. continuous operating DC voltage [VC] 420Vdc 500Vdc 585Vdc 600Vdc Nominal AC discharge current (8/20 µs) [In] 20kA 20kA 20kA 15kA Nominal DC discharge current (8/20 µs) [In] 12.5kA 5kA 5kA 5kA Max. AC discharge current (8/20 µs) [I Max. DC discharge current (8/20 µs) [I Voltage protection level [VPR] 1.5kV 1.75kV 2kV 2.5kV Voltage protection level at 5 kA [VPR] 1.2kV 1.35kV 1.7kV 2kV Temporary overvoltage (TOV) 335V / 5 sec. 385V / 5 sec. 580V / 5 sec. 600V / 5 sec.
Agency Information*
] 40kA 40kA 40kA 30kA
max
] 40kA 40kA 40kA 30kA
max
UL / cUL, UL / cUL, UL / cUL, UL / cUL,
CSA, KEMA CSA, KEMA CSA, KEMA CSA, KEMA
Ordering Information - All Models
SPD according to EN 61643-11 Type 2 SPD according to IEC 61643-1 Class II Response time [tA] 25 ns TOV characteristics Withstand Operating temperature range [TU] -40°C to +80°C Operating state/fault indication Green (good) / Red (replace) Number of ports 1 Cross-sectional area (min.) 1.5mm2/14AWG solid/flexible Cross-sectional area (max.) 35mm2/1AWG stranded/25mm2/2AWG flexible For mounting on 35mm DIN-Rail per EN 60715 Enclosure material Thermoplastic, UL 94V0 Location category Indoor Degree of protection IP20 Capacity 1 Mod., DIN 43880 Product Warranty Five Years**
Remote Contact Signaling
Remote Contact Signaling Type Changeover Contact AC Switching Capacity (Volts/Amps) 250V/0.5A DC Switching Capacity (Volts/Amps) 250V/0.1A; 125V/0.2A; 75V/0.5A Conductor Ratings and Cross-Sectional Area for Remote Contact Signal Terminals Ordering Information Order from Catalog Numbers Above
* Standards information not applicable to DC ratings.
** See Cooper Bussmann SPD Limited Warranty Statement (3A1502)
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information con­tained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
60/75°C Max. 1.5mm2/14AWG Solid/Flexible
0115 BU-SB12332 Page 2 of 2 Data Sheet 2056