0611 BU-SB11647 Page 1 of 2 Data Sheet 2092
Description
The Cooper Bussmann IEC Class II 75, 230, 400, 690 and 1000 volt, onepole, modular surge arresters feature local,
easy
ID™ visual indication and
optional remote contact signaling. The unique module locking system on the
75 to 690 volt arresters fixes the protection module to the base part. Modules
can be easily replaced without tools by simply depressing the release buttons.
Integrated mechanical coding between the base and protection module
ensures against installing an incorrect replacement module.
TN System Arresters (also 1-Phase TT systems)
The features of these single-pole devices are for use as a single device or in
combination with other devices.
TT System Arrester
Provides a current arresting means between neutral conductor and protective
conductor in TT systems, this device helps ensure fulfilling the requirements
for protection of personnel and equipment in “3+1” and “1+1” circuits.
Remote Signaling Contact
The three-pole terminal remote signaling contact versions have a floating
changeover contact for use as a break or make contact, according to circuit
concept.
Surge Protection Made Simple™ for Wind Power Applications
IEC Class II Surge Arresters for 75-1000 Volt, TN & TT Systems
BSPM175WE(R)
BSPM1400WE(R)
BSPM1690WE(R)
BSPM11000WE(R)
BSPG1230WE(R)
Module Circuit Diagrams -
Shown with optional remote contact signaling
Dimensions - mm
Remote Signal
Contact Available
Visual Status Indication
BSPM175WE(R)
BSPG1230WE(R)
BSPM1400WE(R)
BSPM1690WE(R)
BSPM11000WE(R)
Shown with
optional remote
contact signaling
75 to 690V
Arresters
1000V Arrester
MOV
Thermal Disconnector
Gas Discharge Tube (single)

0611 BU-SB11647 Page 2 of 2 Data Sheet 2092
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Ordering Information
System Voltage/Poles 75V/1 230V/1 400V/1 690V/1 1000V/1
Max. Continuous operating AC voltage (MCOV) [UC] 75V 255V 440V 600V 1000V
Catalog Numbers: Without Remote Signaling BSPM175WE BSPG1230WE BSPM1400WE BSPM1690WE BSPM11000WE
(Base + Modules) With Remote Signaling BSPM175WER BSPG1230WER BSPM1400WER BSPM1690WER BSPM11000WER
Replacement Modules BPM75WE BPG255NPEWE* BPM440WE BPM750WE N/A
Specifications
Line System Type TN / TT TT TN / TT TN / TT TN / TT
Max. Continuous Operating DC Voltage [UC] 100V - - 585 600V 1000V
Rated Varistor Voltage AC [U
mov
] - - - - - - 750V 1000V
Nominal Discharge Current (8/20 µs) [In] 10kA 20kA 20kA 15kA 15kA
Max. Discharge Current (8/20 µs) [I
max
] 40kA 40kA 40kA 25kA 30kA
Follow Current Extinguishing Capability [Ifi] - - 100 A
rms
- - - - - -
Lightning Impulse Current (10/350 µs) [I
imp
] - - 12kA - - - - - Voltage Protection Level [UP]_< 0.4kV _< 1.5kV _< 2.0kV _< 3kV _< 4.2kV
Voltage Protection Level at 5kA [UP]_< 0.35kV - - _< 1.7kV _< 2.5kV _< 3.5kV
Response Time [tA]_< 25 ns _< 100 ns _< 25 ns _< 25 ns _< 25 ns
Max. Mains-side Overcurrent Protection 125A gL/gG - - 125A gL/gG 100A gL/gG 100A aM**
Short-Circuit Withstand Capability for
50kA
rms
- - 25kA
rms
25kA
rms
25kA
rms
Max. Mains-side Overcurrent Protection
Temporary Overvoltage (TOV) [UT] 90V / 5 sec. 1200V / 200ms 580V / 5 sec. 900V / 5 sec. 1000V / 5 sec.
Standards Information KEMA, CSA KEMA KEMA, CSA KEMA, CSA - Capacity 1 Mod., DIN 43880 1 Mod., DIN 43880 1 Mod., DIN 43880 1 Mod., DIN 43880 2 Mod., DIN 43880
SPD According to EN 61643-11 Type 2
SPD According to IEC 61643-1 Class II
TOV Characteristics Withstand
Operating Temperature Range [TU] -40°C to +80°C
Operating State/Fault Indication Green (good) / Red (replace)
Number of Ports 1
Cross-Sectional Area (min.) 1.5mm2/14AWG solid/flexible
Cross-Sectional Area (max.) 35mm2/2AWG stranded-25mm2/4AWG flexible
Mounting 35mm DIN rail per EN 60715
Enclosure Material Thermoplastic, UL 94V0
Location Category Indoor
Degree of Protection IP20
Product Warranty Five Years***
Remote Contact Signaling
Remote Contact Signaling Type Changeover Contact
AC Switching Capacity (Volts/Amps) 250V/0.5A
DC Switching Capacity (Volts/Amps) 250V/0.1A; 125V/0.2A; 75V/0.5A
Conductor Ratings and Cross-Sectional Area for
60/75°C Max. 1.5mm
2
/14AWG Solid/Flexible
Remote Contact Signal Terminals
Ordering Information Order from Catalog Numbers Above
* N-PE Surge arrester for location between neutral conductor and protective conductor in TT systems.
** 125A gL/gG @ 690Vac.
*** See Cooper Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge.
Recommended Cooper Bussmann Back Up Fuses
DIN Fuse Size NH Fuse Part Number
00 100NHG00B-690
00 125NHG00B-690