Bussmann BSPM175WE, BSPG1230WE, BSPM1400WE, BSPM1690WE, BSPM11000WE Data Sheet

0611 BU-SB11647 Page 1 of 2 Data Sheet 2092
Description
The Cooper Bussmann IEC Class II 75, 230, 400, 690 and 1000 volt, one­pole, modular surge arresters feature local,
easy
ID™ visual indication and optional remote contact signaling. The unique module locking system on the 75 to 690 volt arresters fixes the protection module to the base part. Modules can be easily replaced without tools by simply depressing the release buttons. Integrated mechanical coding between the base and protection module ensures against installing an incorrect replacement module.
TN System Arresters (also 1-Phase TT systems)
The features of these single-pole devices are for use as a single device or in combination with other devices.
TT System Arrester
Provides a current arresting means between neutral conductor and protective conductor in TT systems, this device helps ensure fulfilling the requirements for protection of personnel and equipment in “3+1” and “1+1” circuits.
Remote Signaling Contact
The three-pole terminal remote signaling contact versions have a floating changeover contact for use as a break or make contact, according to circuit concept.
Surge Protection Made Simple™ for Wind Power Applications
IEC Class II Surge Arresters for 75-1000 Volt, TN & TT Systems
BSPM175WE(R) BSPM1400WE(R) BSPM1690WE(R)
BSPM11000WE(R)
BSPG1230WE(R)
Module Circuit Diagrams -
Shown with optional remote contact signaling
Dimensions - mm
Remote Signal
Contact Available
Visual Status Indication
BSPM175WE(R) BSPG1230WE(R) BSPM1400WE(R) BSPM1690WE(R) BSPM11000WE(R)
Shown with
optional remote
contact signaling
75 to 690V
Arresters
1000V Arrester
MOV
Thermal Disconnector
Gas Discharge Tube (single)
0611 BU-SB11647 Page 2 of 2 Data Sheet 2092
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information con­tained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Ordering Information
System Voltage/Poles 75V/1 230V/1 400V/1 690V/1 1000V/1 Max. Continuous operating AC voltage (MCOV) [UC] 75V 255V 440V 600V 1000V Catalog Numbers: Without Remote Signaling BSPM175WE BSPG1230WE BSPM1400WE BSPM1690WE BSPM11000WE (Base + Modules) With Remote Signaling BSPM175WER BSPG1230WER BSPM1400WER BSPM1690WER BSPM11000WER Replacement Modules BPM75WE BPG255NPEWE* BPM440WE BPM750WE N/A
Specifications
Line System Type TN / TT TT TN / TT TN / TT TN / TT Max. Continuous Operating DC Voltage [UC] 100V - - 585 600V 1000V Rated Varistor Voltage AC [U
mov
] - - - - - - 750V 1000V Nominal Discharge Current (8/20 µs) [In] 10kA 20kA 20kA 15kA 15kA Max. Discharge Current (8/20 µs) [I
max
] 40kA 40kA 40kA 25kA 30kA
Follow Current Extinguishing Capability [Ifi] - - 100 A
rms
- - - - - -
Lightning Impulse Current (10/350 µs) [I
imp
] - - 12kA - - - - - ­Voltage Protection Level [UP]_< 0.4kV _< 1.5kV _< 2.0kV _< 3kV _< 4.2kV Voltage Protection Level at 5kA [UP]_< 0.35kV - - _< 1.7kV _< 2.5kV _< 3.5kV Response Time [tA]_< 25 ns _< 100 ns _< 25 ns _< 25 ns _< 25 ns Max. Mains-side Overcurrent Protection 125A gL/gG - - 125A gL/gG 100A gL/gG 100A aM** Short-Circuit Withstand Capability for
50kA
rms
- - 25kA
rms
25kA
rms
25kA
rms
Max. Mains-side Overcurrent Protection Temporary Overvoltage (TOV) [UT] 90V / 5 sec. 1200V / 200ms 580V / 5 sec. 900V / 5 sec. 1000V / 5 sec. Standards Information KEMA, CSA KEMA KEMA, CSA KEMA, CSA - ­Capacity 1 Mod., DIN 43880 1 Mod., DIN 43880 1 Mod., DIN 43880 1 Mod., DIN 43880 2 Mod., DIN 43880 SPD According to EN 61643-11 Type 2 SPD According to IEC 61643-1 Class II TOV Characteristics Withstand Operating Temperature Range [TU] -40°C to +80°C Operating State/Fault Indication Green (good) / Red (replace) Number of Ports 1 Cross-Sectional Area (min.) 1.5mm2/14AWG solid/flexible Cross-Sectional Area (max.) 35mm2/2AWG stranded-25mm2/4AWG flexible Mounting 35mm DIN rail per EN 60715 Enclosure Material Thermoplastic, UL 94V0 Location Category Indoor Degree of Protection IP20 Product Warranty Five Years***
Remote Contact Signaling
Remote Contact Signaling Type Changeover Contact AC Switching Capacity (Volts/Amps) 250V/0.5A DC Switching Capacity (Volts/Amps) 250V/0.1A; 125V/0.2A; 75V/0.5A Conductor Ratings and Cross-Sectional Area for
60/75°C Max. 1.5mm
2
/14AWG Solid/Flexible
Remote Contact Signal Terminals Ordering Information Order from Catalog Numbers Above
* N-PE Surge arrester for location between neutral conductor and protective conductor in TT systems. ** 125A gL/gG @ 690Vac. *** See Cooper Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge.
Recommended Cooper Bussmann Back Up Fuses
DIN Fuse Size NH Fuse Part Number
00 100NHG00B-690 00 125NHG00B-690