0611 BU-SB11646 Page 2 of 2 Data Sheet 1166
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
* N-PE Surge arrester for location between neutral conductor and protective conductor in TT systems.
** See Cooper Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge.
Recommended Cooper Bussmann Back Up Fuses
DIN TT / TN System NH Fuse Part Numbers
Fuse Size 275, 320, 385, 440V 600V
00 125NHG00B 100NHG00B-690
0 125NHG0B 100NHG0B-690
01 125NHG01B - -
1 - - 100NHG1B-690
02 125NHG02B - -
2 - - 100NHG2B-690
Ordering Information
System Voltage/Poles 230V/1 230V/1 230V/1 400V/1 600V/1 230V/1*
Max. Continuous operating AC voltage (MCOV) [UC] 275V 320V 385V 440V 600V 255V
Catalog Numbers: Without Remote Signaling BSPM1275TN BSPM1320TN BSPM1385TN BSPM1440TN BSPM1600TN BSPG1255NPE
(Base + Modules) With Remote Signaling BSPM1275TNR BSPM1320TNR BSPM1385TNR BSPM1440TNR BSPM1600TNR BSPG1255NPER
Replacement Modules BPM275IEC BPM320IEC BPM385IEC BPM440IEC BPM600IEC BPG255NPE
Specifications
Line system type TN / TT TN / TT TN / TT TN TN TT
Max. Continuous operating DC voltage [UC] 350V 420V 500V 585V 600V - Voltage protection level [UP]<_ 1.25kV <_ 1.5kV <_ 1.75kV <_ 2kV <_ 2.5kV <_ 1.5kV
Voltage protection level at 5kA [UP]<_ 1kV <_ 1.2kV <_ 1.35kV <_ 1.7kV <_ 2kV - Max. mains-side overcurrent protection 125A gL/gG 125A gL/gG 125A gL/gG 125A gL/gG 100A gL-gG - Short-circuit withstand capability for max.
50kA
rms
25kA
rms
25kA
rms
25kA
rms
25kA rms - -
mains-side overcurrent protection
Temporary overvoltage (TOV) [UT] 335V/5 sec. 335V/5 sec. 385V/5 sec. 580V/5 sec. 600V/5 sec. 1200V/200 ms
Response time [tA]<_ 25 ns <_ 25 ns <_ 25 ns <_ 25 ns <_ 25 ns <_ 100 ns
Follow current extinguishing capability [Ifi] - - - - - - - - - - 100A
rms
Lightning impulse current (10/350 µs) [I
imp
] - - - - - - - - - - 12kA
Nominal discharge current (8/20 µs) [In] 20kA 20kA 20kA 20kA 15kA 20kA
Max. Discharge current (8/20 µs) [I
max
] 40kA 40kA 40kA 40kA 30kA 40kA
Standards Information KEMA KEMA, CSA KEMA, CSA KEMA, CSA KEMA KEMA
Capacity 1 mod., DIN 43880
SPD according to EN 61643-11 Type 2
SPD according to IEC 61643-1 Class II
TOV characteristics Withstand
Operating temperature range [TU] -40°C to +80°C
Operating state/fault indication Green (good) / Red (replace)
Number of ports 1
Cross-sectional area (min.) 1.5mm2/14AWG solid/flexible
Cross-sectional area (max.) 35mm2/2AWG stranded-25mm2/4AWG flexible
Mounting 35mm DIN Rail per EN 60715
Enclosure material Thermoplastic, UL 94V0
Location category Indoor
Degree of protection IP20
Product Warranty Five Years**
Remote Contact Signaling
Remote Contact Signaling Type Changeover Contact
AC Switching Capacity (Volts/Amps) 250V/0.1A
DC Switching Capacity (Volts/Amps) 250V/0.1A; 125V/0.2A; 75V/0.5A
Conductor Ratings and Cross-Sectional Area for
60/75°C Max. 1.5mm
2
/14AWG Solid/Flexible
Remote Contact Signal Terminals
Ordering Information Order from Catalog Numbers Above