0211 BU-SB11187 Page 2 of 2 Data Sheet 2095
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
O
RDERINGINFORMATION
System Voltage/Poles 230/400V/4 230/400V/4
Max. continuous operating AC voltage (MCOV) [UC] 275V - Max. continuous operating AC voltage (MCOV) [L-N] [UC] - - 275V
Max. continuous operating AC voltage [N-PE] [UC] - - 255V
Catalog Numbers: Without Remote Signaling BSPM4230WE BSPH4230WE
With Remote Signaling BSPM4230WER BSPH4230WER
Replacement Modules: MOV technology BPM275WE BPM275WE
Spark Gap technology - - BPSNPEWE*
S
PECIFICATIONS
Line System Type TNS TT / TNS
Nominal AC voltage [UN] 230/400V 230/400V
Lightning impulse current (10/350 µs) [N-PE] [I
imp
] - - 12kA
Voltage protection level [UP]<_ 1.25kV - Voltage protection level at 5kA [UP]<_ 1kV - Voltage protection level [L-N] [UP]- -<_ 1.25kV
Voltage protection level [L-N] at 5kA [UP]- -<_ 1kV
Voltage protection level [N-PE] [UP]- -<_ 1.5kV
Follow current extinguishing capability [N-PE] [Ifi] - - 100A
rms
Response time [tA]<_ 25 ns - Response time [L-N] [tA]- -<_ 25 ns
Response time [N-PE] [tA]- -<_ 100 ns
Temporary overvoltage (TOV) [UT] 335V / 5 sec. - Temporary overvoltage (TOV) [L-N] [UT] - - 335V / 5 sec.
Temporary overvoltage (TOV) [N-PE] [UT] - - 1200V / 200 ms
SPD according to EN 61643-11 Type 2
SPD according to IEC 61643-1 Class II
Nominal discharge current (8/20 µs) [In] 20kA
Max. discharge current (8/20 µs) [I
max
] 40kA
Max. mains-side overcurrent protection 125A gL/gG
Short-circuit withstand capability for max. mains-side overcurrent protection 50kA rms
TOV characteristics withstand
Operating temperature range [TU] -40°C to +80°C
Operating state/fault indication green (good)/red (replace)
Number of ports 1
Cross-sectional area (min.) 1.5mm2/14AWG solid/flexible
Cross-sectional area (max.) 35mm2/2AWG stranded-25mm2/4AWG flexible
Mounting 35mm DIN rail per EN 60715
Enclosure material Thermoplastic, UL 94V0
Location category Indoor
Degree of protection IP20
Capacity 4 Mods., DIN 43880
Standards Information KEMA
Product Warranty Five Years**
REMOTE CONTACT SIGNALING
Remote Contact Signaling Type Changeover Contact
AC Switching Capacity (Volts/Amps) 250V/0.1A
DC Switching Capacity (Volts/Amps) 250V/0.1A; 125V/0.2A; 75V/0.5A
Conductor Ratings and Cross-Sectional Area for Remote Contact Signal Terminals 60/75°C Max. 1.5mm2/14AWG Solid/Flexible
Ordering Information Order from Catalog Numbers Above
* N-PE Surge arrester module for location between neutral conductor and protective conductor in TT systems.
** See Cooper Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge.
Recommended Cooper Bussmann Back Up Fuse
DIN Fuse Size NH Fuse Part Number
00 125NHG00B