Bussmann BSPH2A24D24LV, BSPH2A48D48LV, BSPH2A60D60LV, BSPH2A150D150LV, BSPH2A230D230LV Data Sheet

Surge Protection Made Simple™ for LV Control Applications
UL Type 4 BSP LV Control Series for 24Vac/dc to 230Vac/dc LV Systems
Description
The Bussmann UL Type 4 component assembly for use in Type 3 applications 24Vac/dc, 48Vac/dc, 60Vac/dc, 120Vac/dc and 230Vac/dc, two-pole, modular surge arresters feature local, easy ID™ visual indication and optional remote contact signaling. The unique module locking system fixes the protection mod­ule to the base part. Modules can be easily replaced without tools by simply depressing the release buttons. Integrated mechanical coding between the base and protection module ensures against installing an incorrect replace­ment module.
LV Control System Arresters
The features of these two-pole devices are for use in coordination with other upstream SPDs in UL 508A Applications*.
• Surge arrester according to UL 1449 3rdEdition, Type 4 Component Assembly for use in Type 3 applications helps meet UL 508A requirements
• Proven MOV and GDT hybrid technology for reliable surge protection
• "Thermo Dynamic Control" SPD monitoring device ensures high reliability against surge events
• Module locking system with module release button make module replacement easy without tools
• Optional remote signaling of all protection modules make status monitoring easy and accurate in any monitoring scheme
• Vibration and shock tested according to EN 60068-2 to withstand harsh environments
Optional Remote Signaling Contact
The remote signaling contact versions have a floating changeover contact for use as a break or make contact for easy adoption in any monitoring application.
* UL 1449 3rdEdition not applicable to DC voltages.
Dimensions - mm
Visual Status Indication
Circuit Diagrams
BSPH2A24D24LV BSPH2A48D48LV BSPH2A60D60LV BSPH2A150D150LV BSPH2A230D230LV
Remote Signal
Contact Available
Non SCCR
BSP LV Control Series
MOV
BSPHA24D24LV, BSPHA48D48LV, BSPHA60D60LV
BSPHA150D150LV, BSPHA230D230LV*
Shown with optional remote contact signaling
* For remote signaling contact, add “R” suffix to the part number.
0115 BU-SB11750 Page 1 of 2 Data Sheet 2057
E.g., BSPHA230D230LVR
Gas Discharge Tube (single)
Ordering Information
System Voltage 24Vac/dc 48Vac/dc 60Vac/dc 120Vac/dc 230Vac/dc Max. Continuous operating AC voltage (MCOV) [VC] 30Vac/dc 60Vac/dc 75Vac/dc 150Vac/dc 255Vac/dc Catalog Numbers: Without Remote Signaling BSPH2A24D24LV BSPH2A48D48LV BSPH2A60D60LV BSPH2A150D150LV BSPH2A230D230LV (Base + Modules) With Remote Signaling BSPH2A24D24LVR BSPH2A48D48LVR BSPH2A60D60LVR BSPH2A150D150LVR BSPH2A230D230LVR Replacement Modules BPHA24D24LV BPHA48D48LV BPHA60D60LV BPHA150D150LV BPHA230D230LV
Specifications
Nominal AC voltage [Vo] 24V 48V 60V 120V 230V Max. continuous operating AC voltage [VC] 30V 60V 75V 150V 255V Max. continuous operating DC voltage [VC] 30V 60V 75V 150V 255V Nominal load current AC [IL] 25A 25A 25A 25A 25A Nominal discharge current (8/20 µs) [In] 1kA 1kA 2kA 2kA 3kA Total discharge current (8/20 µs) [L+N-Gnd] [I
] 2kA 2kA 4kA 4kA 5kA
total
Combined impulse [UOC] 2kV 2kV 4kV 4kV 6kV Combined impulse [L+N-Gnd] [UOCtotal] 4kV 4kV 8kV 8kV 10kV Voltage protection level [L-N] [VPR]_< 180V _< 350V _< 400V _< 640V _< 1250V Voltage protection level [L/N-Gnd] [VPR]_< 630V _< 730V _< 730V _< 800V _< 1500V Temporary overvoltage (TOV) [L-N] -- -- -- -- 335V / 5 sec. Temporary overvoltage (TOV) [L/N-Gnd] -- -- -- -- 400V / 5 sec. Temporary overvoltage (TOV) [L+N-Gnd] -- -- -- -- 1200V + V0/ 20 TOV characteristics [L-N] -- -- -- -- Withstand TOV characteristics [L/N-Gnd] -- -- -- -- Withstand TOV characteristics [L+N-Gnd] -- -- -- -- Failure SPD according to EN 61643-11 Type 3 SPD according to IEC 61643-1 Class III Response time [L-N] [tA]_< 25 ns Response time [L/N-Gnd] [tA]_< 100 ns Operating temperature range [TU] -40°C to +80°C Operating state/fault indication Green (good) / Red (replace) Number of ports 1 Cross-sectional area (min.) 0.5mm2/18AWG solid/flexible Cross-sectional area (max.) 4mm2/10AWG solid/2.5mm2/12AWG flexible For mounting on 35mm DIN rail per EN 60715 Enclosure material Thermoplastic, UL 94V0 Location category Indoor Degree of protection IP20 Capacity 1 Mod., DIN 43880 Agency Information* UL / cUL, CSA, KEMA Product Warranty Five Years**
Remote Contact Signaling
Remote Contact Signaling Type Changeover Contact AC Switching Capacity (Volts/Amps) 250V/0.5A DC Switching Capacity (Volts/Amps) 250V/0.1A; 125V/0.2A; 75V/0.5A Conductor Ratings and Cross-Sectional Area for Remote Contact Signal Terminals Ordering Information Order from Catalog Numbers Above
60/75°C Max. 1.5mm2/14AWG Solid/Flexible
* Standards information not applicable to DC ratings.
** See Cooper Bussmann SPD Limited Warranty Statement (3A1502)
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information con­tained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
0115 BU-SB11750 Page 2 of 2 Data Sheet 2057
Loading...