Description
The Cooper Bussmann three-module photovoltaic Surge Protective Device (SPD) (with three-step DC switching device) features
ID™ visual indication and optional remote contact signaling (floating changeover contact) for use in PV systems.
These complete surge protective devices are suitable for all PV systems in accordance with UL 1449 3rdEdition and IEC 60364-7-712. Includes a five year limited warranty.
These prewired solutions consist of a base and locking modules that feature a combined disconnection and short-circuiting (shunting) device with safe electrical isolation to prevent fire damage due to DC arcs. An integrated DC fuse allows safe module replacement without arc formation.
In case of insulation faults in the generator circuit, a reliable and tested fault-resistant Y circuit prevents damage to the surge protective devices.
The green and red visual indicator flags show the module protective status (green = good, red = replace). Apart from this visual indica­tion, the remote signaling option features a three terminal floating changeover contact that can be used as a make or break contact depending on the particular monitoring system design employed.
Dimensions - mm
Module Circuit Diagrams
BSPH_____YPV(R)
Shown with optional remote contact signaling
Remote Signal
Contact Available
Visual Status Indication
Short-Circuit Interrupting (SCI) Technology
1. Original State 2. Disconnection Device Response
3. Arc Extinguishes 4. Safe Electrical Isolation
1234
DC+/– DC–/+
12 11 14
Fuse Closed
Fuse Open
MOV
Thermal Disconnector
Arc
0911 BU-SB111084 Page 2 of 2 Data Sheet 2055
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled.This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Ordering Information
Nominal PV System Voltage 600Vdc 1000Vdc 1200Vdc Catalog Numbers: Without Remote Signaling BSPH3600YPV BSPH31000YPV BSPH31200YPV (Base + Modules) With Remote Signaling BSPH3600YPVR BSPH31000YPVR BSPH31200YPVR Replacement Modules: Outer (2) BPH300YPV BPH500YPV BPH600YPV
Center (1) BPM300YPV BPM500YPV BPM600YPV
Specifications
Nominal PV System Voltage 600V 1000V 1200V MCOV [U
CPV
]
700Vdc 1170Vdc 1200Vdc
Max System Discharge Current (8/20 µs) [I
max
] 40kA 40kA 30kA Voltage Protection Level [UP]<_2.5kV <_4.0kV <_4.5kV Voltage Protection Level at 5kA [UP]<_2.0kV <_3.5kV <_4.0kV Integrated Fuse Breaking Capacity/Interrupting Rating 30kA/1000Vdc 30kA/1000Vdc 30kA/1200Vdc Technology Short-Circuit Interruption (SCI) Overcurrent Protection Operating Temperature Range [TU] -40°C to +80°C Nominal Discharge Current (8/20 µs) [(DC+/DC-) --> PE] [In] 12.5kA Response Time [tA] <_25ns Operating State/Fault Indication Green (good)/Red (replace) Conductor Ratings and Cross-Sectional Area: Minimum 60/75°C 1.5mm2/14AWG Solid/Flexible
Maximum 60/75°C 35mm2/2AWG Stranded/25mm2/4AWG Flexible Mounting 35mm DIN Rail per EN 60715 Enclosure Material UL 94V0 Thermoplastic Degree of Protection IP20 Capacity 3 Modules, DIN 43880 Standards Information: UL UL 1449 3rdEdition (Type 2)*
IEC IEC 61643-11 Type 2, IEC 61643-1 Class II Product Warranty Five Years**
Remote Contact Signaling
Remote Contact Signaling Type Changeover Contact AC Switching Capacity (Volts/Amps) 250V/0.1A DC Switching Capacity (Volts/Amps) 250V/0.1A; 125V/0.2A; 75V/0.5A Conductor Ratings and Cross-Sectional Area for Remote Contact Signal Terminals 60/75°C Max. 1.5mm2/14AWG Solid/Flexible Ordering Information Order from Catalog Numbers Above
* Does not apply to 1200Vdc.
** See Cooper Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge.
*** BSPH31000YPV(R) 1000Vdc one energized pole/mode requires the following:
1. Use a suitable electrical insulator to keep a 10mm min. safety distance from the PV-SPD and other grounded parts in the housing.
2. No metal covers are in the area of the module release buttons as shown.
Typical Application Schematics
Application A
Two energized poles/modes
600, 1000 & 1200Vdc systems
Application B
One energized pole/mode
600Vdc & 1000Vdc*** systems only
Application C
One energized pole/mode
600Vdc & 1000Vdc*** systems only
(
Max. system discharge current
(8/20 µs) [I
max
] 25kA)
Common
Common
Equipment
Grounding Conductor
Equipment
Grounding Conductor
Common
Equipment
Grounding Conductor