Form No.
Page 1 of 1
BIF Doc #720036
Bussmann
®
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann
Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to
clearly present comprehensive product data and provide technical information that will help the end user with
design applications. Bussmann reserves the right, without notice, to change design or construction of any
products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change
or update, without notice, any technical information contained in this bulletin. Once a product has been
selected, it should be tested by the user in all possible applications.
Square Body – Accessories
Fuse Bases (Blocks)
DIN 43 653 Fuse Bases
For the Typower ZILOX fuses according to DIN 43 653, the
following fuse bases are available:
Part Max. Rated Center
Number Voltage Current Distance
170H3003 1000V 630A 80mm
170H3004 1000V 1250A 80mm
170H3005 1400V 630A 110mm
170H3006 1400V 1250A 110mm
The fuse bases rated 1250A can also be used for the fuses
with higher rated current if the maximum load current is
derated according to the table below:
Fuse Rating Max. Load Current In Fuse Base
1400A 1325A
1500A 1400A
1600A 1500A
1800A 1650A
2000A 1800A
Fixed Center Max. Fuse Fuse
Base Style Max. Voltage Current Rating Size
170H1007 1000V 400A 00, 000
170H1013 660V 200A 0000,000
U.L. Recognized to U.L. 512.
Universal Fuse Bases
For the Typower ZILOX fuses according to DIN 43 653,
French style and North American style, the following fuse
bases are available:
Modular Max. Fuse BIF
Base Style Max. Voltage Current Rating Document
1BS101 600V 100A 1206
1BS102 600V 400A 1207
1BS103 600V 400A 1208
1BS104 600V 600A 1209
BH-0xxx 700V 100A 1200
BH-1xxx 2500V 400A 1201
BH-2xxx 5000V 400A 1202
BH-3xxx 1250V 700A 1203
Modular fuse bases are U.L. Recognized to U.L. 512 and
meet the spacing requirements of U.L. 347. Contact
Bussmann sales representative for more complete ordering
information.
DIN 43 620 Fuse Bases
For fuse bases used with Typower ZILOX fuses according to
DIN 43 620, please contact your local Bussmann sales
representative.
DIN 43 653
Universal
DIN 43 653
7-11-01
SB01191