2Intended use ............................................................................................................................................................ 3
6Setup and function ................................................................................................................................................... 6
6.1Features of function and equipment ........................................................................................................ 6
Pos: 6 /#Neustruktur#/Online-Dokumentation (+KNX)/Überschriften (--> Für alle Dokumente <--)/1. Ebene/S - T/Sicherheit @ 18\mod_1302612791790_15.docx @ 103357 @ 1 @ 1
Safety
1 Safety
Pos: 7 /#Neustruktur#/Online-Dokumentation (+KNX)/Sicherheitshinweise und Hinweise (--> Für alle Dokumente <--)/Warnhinweise/Sicherheit - 230 V @ 18\mod_1302606816750_15.docx @ 103308 @ @ 1
Warning
Electric voltage!
Risk of death and fire due to electrical voltage of 230 V.
– Work on the 230V supply system may only be performed by authorised electricians!
– Disconnect the mains power supply prior to installation and/or disassembly!
The device is to be used exclusively with the components that are supplied and licensed as described in chapter
"Setup and function".
Pos: 10 /#Neustruktur#/Online-Dokumentation (+KNX)/Überschriften (--> Für alle Dokumente <--)/1. Ebene/U - Z/Umwelt @ 18\mod_1302614158967_15.docx @ 103383 @ 1 @ 1
3 Environment
Pos: 11 /#Neustruktur#/Online-Dokumentation ( +KNX)/Sicherheitshi nweise und Hinweise (--> Für alle Dokumente <--)/Hinweise - Umwelt/Hinweis - Umwelt - Hinweis Elektrogeräte @ 18\mod_1302763973434_15.docx @ 103500 @ @ 1
Consider the protection of the environment!
Used electric and electronic devices must not be disposed of with domestic waste.
– The device contains valuable raw materials which can be recycled. Therefore, dispose of the
device at the appropriate collecting depot.
Pos: 12 /#Neustruktur#/Online-Dokumentation ( +KNX)/Sicherheitshi nweise und Hinweise (--> Für alle Dokumente <--)/Hinweise - Umwelt/Hinweis - Umwelt - Entsorgung Elektrogeräte @ 20\mod_1325760695972_15.docx @ 136583 @ @ 1
All packaging materials and devices bear the markings and test seals for proper disposal. Always dispose of the
packaging material and electric devices and their components via the authorized collecting depots and disposal
companies.
The products meet the legal requirements, in particular the laws governing electronic and electrical devices and
the REACH ordinance.
(EU Directive 2002/96/EC WEEE and 2002/95/EC RoHS)
(EU REACH ordinance and law for the implementation of the ordinance (EC) No.1907/2006)
Pos: 13 /#Neustruktur#/Online-Dokumentation (+KNX)/Steuermodule - Online-Dokumentation (--> Für alle Dokumente <--)/++++++++++++ Seitenumbruch ++++++++++++ @ 9\mod_1268898668093_0.doc x @ 52149 @ @ 1
Operating Instructions | 1473-1-8289 — 3 —
Operating Instructions
Temperaturregler
Pos: 14 /#Neustruktur#/Online-Dokumentation (+KNX)/Überschriften (--> Für alle Dokumente <--)/1. Ebene/A - F/Bedienung @ 11\mod_1279185541649_15.docx @ 83043 @ 1 @ 1
4 Operation
Pos: 15 /#Neustruktur#/Online-Dokumentation ( +KNX)/Bedienung/ Temperaturregler/Bedi enung Zentralschei be für 1094....1097 @ 26\mod_13426997 45536_15.docx @ 224317 @ @ 1
A
B
34
2
1
5
6
C
Operation
Fig. 1: Cover
Mark / Symbol Designation / Function
A LED - temperature reduction active
B Slide switch
C Control knob for selecting the desired room temperature
1 = 5°C
2 = 10°C
3 = 15°C
4 = 20°C
5 = 25°C
6 = 30°C
Switch position for external temperature reduction
Switch position for selected temperature
Switch position for continuous temperature reduction
The temperature is continuously variable with the adjusting knob (C). The difference in
temperature between two digits is approximately 5°C. For temperature adjustment and values,
see the opposite columns.
A
B
34
2
1
5
6
C
Fig. 2: Cover with cutout for display of actual temperature value (only for ... UTA)
Symbol in the display Designation / Function
Heating switched on
Temperature reduction active
Calibration Calibration
Pos: 16 /#Neustruktur#/Online-Dokumentation (+KNX)/Steuermodule - Online-Dokumentation (--> Für alle Dokumente <--)/++++++++++++ Seitenumbruch ++++++++++++ @ 9\mod_1268898668093_0.doc x @ 52149 @ @ 1
1 … 6 (10 … 50°C)
Temperature reduction 4 K
Switching temperature difference ±0.5 K
Protection type IP 20, EN (60529)
Temperature sensor 1095 UF NTC 10 kΩ / 25°C
Maximum cable length 1095 UF 4 m
Operating temperature range 0 ...30 °C
Mode of operation (DIN EN 60730-1) 1B
Degree of contamination (DIN EN 60730-1) 2
Rated surge voltage (DIN EN 60730-1) 4000 V
Pos: 19 /#Neustruktur#/Online-Dokumentation (+KNX)/Steuermodule - Online-Dokumentation (--> Für alle Dokumente <--)/++++++++++++ Seitenumbruch ++++++++++++ @ 9\mod_1268898668093_0.doc x @ 52149 @ @ 1
Technical data
1094, 1095, 1095 UF, 1097 U / UTA
1096 U / UTA
1094, 1095 U / UTA
1095 UF
1096 U / UTA
1097 U / UTA
1094, 1095, 1095 UF, 1096 U / UTA, 1097 U / UTA
1095 UF
1094, 1095, 1095 UF, 1096 U / UTA, 1097 U / UTA
1095 UF
Operating Instructions | 1473-1-8289 — 5 —
Operating Instructions
Temperaturregler
Pos: 20 /#Neustruktur#/Online-Dokumentation (+KNX)/Überschriften (--> Für alle Dokumente <--)/1. Ebene/A - F/Aufbau und Funktion @ 11\mod_1279185435352_15.docx @ 83027 @ 1 @ 1
Pos: 27 /#Neustruktur#/Online-Dokumentation (+KNX)/Steuermodule - Online-Dokumentation (--> Für alle Dokumente <--)/++++++++++++ Seitenumbruch ++++++++++++ @ 9\mod_1268898668093_0.doc x @ 52149 @ @ 1
X
X
Operating Instructions | 1473-1-8289 — 7 —
Operating Instructions
Temperaturregler
Pos: 28 /#Neustruktur#/Online-Dokumentation (+KNX)/Überschriften (--> Für alle Dokumente <--)/1. Ebene/M - O/Montage und elektrischer Anschluss @ 23\mod_1336477157864_15.docx @ 209033 @ 1 @ 1
7 Installation and electrical connection
Pos: 29 /#Neustruktur#/Online-Dokumentation ( +KNX)/Sicherheitshi nweise und Hinweise (--> Für alle Dokumente <--)/Warnhinweise/Sicherheit - Niederspannungs- und 230 V-Leitungen @ 23\mod_1336558868201_15.docx @ 209 164 @ @ 1
Warning
Electric voltage!
Risk of death due to electrical voltage of 230 V during short-circuit in the low-voltage line.
– Low-voltage and 230 V lines must not be installed together in a flush-mounted socket!
Pos: 30 /#Neustruktur#/Online-Dokumentation ( +KNX)/Sicherheitshi nweise und Hinweise (--> Für alle Dokumente <--)/Warnhinweise/Sicherheit - Fachkenntnisse @ 23\mod_1336559183027_15.docx @ 209179 @ 2 @ 1
7.1 Requirements for the electrici an
Warning
Electric voltage!
Install the device only if you have the necessary electrical engineering knowledge and experience.
• Incorrect installation endangers your life and that of the user of the electrical system.
• Incorrect installation can cause serious damage to property, e.g. due to fire.
The minimum necessary expert knowledge and requirements for the installation are as follows:
• Apply the "five safety rules" (DIN VDE 0105, EN 50110):
1. Disconnect from power;
2. Secure against being re-connected;
3. Ensure there is no voltage;
4. Connect to earth and short-circuit;
5. Cover or barricade adjacent live parts.
• Use suitable personal protective clothing.
• Use only suitable tools and measuring devices.
• Check the supply network type (TN system, IT system, TT system) to secure the following
power supply conditions (classic connection to ground, protective earthing, necessary
additional measures, etc.).
Pos: 31 /#Neustruktur#/Online-Dokumentation (+KNX)/Überschriften (--> Für alle Dokumente <--)/2. Ebene/M - O/Montage @ 18\mod_1302615960458_15.docx @ 103424 @ 2 @ 1
7.2 Mounting
Pos: 32 /#Neustruktur#/Online-Dokumentation ( +KNX)/Sicherheitshi nweise und Hinweise (--> Für alle Dokumente <--)/Warnhinweise/Sicherheit - 230 V @ 18\mod_1302606816750_15.docx @ 103308 @ @ 1
Warning
Installation and electrical
connection
Electric voltage!
Risk of death and fire due to electrical voltage of 230 V.
– Work on the 230V supply system may only be performed by authorised electricians!
– Disconnect the mains power supply prior to installation and/or disassembly!
Pos: 33 /#Neustruktur#/Online-Dokumentation (+KNX)/Steuermodule - Online-Dokumentation (--> Für alle Dokumente <--)/++++++++++++ Seitenumbruch ++++++++++++ @ 9\mod_1268898668093_0.doc x @ 52149 @ @ 1
Operating Instructions | 1473-1-8289 — 8 —
Operating Instructions
Temperaturregler
Installation and electrical
connection
Pos: 34 /#Neustruktur#/Online-Dokumentation ( +KNX)/Montage/alle G eräte/Montage - UP-Dosen - DIN 49073-1 oder geeignet es Aufputzgehaeuse - Ohn e Docvariable @ 25\mod_1340 354979636_15.doc x @ 219890 @ @ 1
The flush-mounted insert must only be installed in flush-mounted wall boxes according to DIN 49073-1, Part 1, or
suitable surface-mounted housings.
The temperature controller is suitable for use in dry rooms only.
ca. 30 cm
ca. 150 cm
ABCD
Fig. 3: Installation site
Position Description
A Mounting height: approx. 150 cm
Minimum distance to doors or windows: approx. 30 cm
B Avoid mounting on cold walls (thermal bridges)
C Avoid draught and heat radiation, such as direct sunlight
D Avoid heat radiation from adjacent devices (dimmers)
1. Connect the device according to the circuit diagram.
Note
In connection with hot-water heating, servo valves of "closed when de-energized“ design are
required for the controller.
2. Fix the device in the flush-mounted box according to its design.
Connections 24 V AC
Input for activating the temperature reduction (see nighttime reduction)
Output for controlling the heating load
Output for controlling the cooling load
* The sensor cable must be routed in a protective tube.
Pos: 39 /#Neustruktur#/Online-Dokumentation (+KNX)/Steuermodule - Online-Dokumentation (--> Für alle Dokumente <--)/++++++++++++ Seitenumbruch ++++++++++++ @ 9\mod_1268898668093_0.doc x @ 52149 @ @ 1
N
N
LL1
Installation and electrical
N
230 V230 V230 V24 V
N
LL12
2
1
connection
1
2
1
Operating Instructions | 1473-1-8289 — 10 —
Operating Instructions
Temperaturregler
Pos: 40 /#Neustruktur#/Online-Dokumentation (+KNX)/Überschriften (--> Für alle Dokumente <--)/1. Ebene/G - L/Inbetriebnahme @ 11\mod_1279185496977_15.docx @ 83035 @ 1 @ 1
After the installation the accuracy of the switching point is established only after an operating
period of 1 to 2 hours.
For faster heating and alignment of the room temperature to the setpoint temperature, it is
recommended to initially set the temperature higher than required.
8.1 Calibrating the display of the actual temperature value (applies only to UT A devices)
To properly control loads larger than 2 A, the heating system must be connected for calibrating the display. After
the connection, the heating system is switched on automatically for about 20 minutes. During this time, the “CA”
symbol will be displayed. After this, the display adjusts itself to the room temperature within a few minutes.
Before repeating the calibration procedure, the unit must be disconnected from the power supply for at least 8
minutes.
8.2 Offset function (scale correction)
Reaching the selected room temperature depends on the ambient conditions such as heating system capacity (at
least 5°K/h min.), room size, ambient temperature, insulation, etc. That is why the values in the scale are merely
guide values. To obtain a setting that is as accurate as possible, the adjusting knob can be offset in 4 stages by a
total of ±6°C as follows. Compare illustration 4:
1. Pull off the adjusting knob (3).
2. Cut the position lug (1) on the bottom side of the adjusting knob off with a suitable tool.
3. Re-attach the adjusting knob, which has been offset to the basic position with the desired correcting value.
=== Ende der Liste für Textmarke Content ===
Operating Instructions | 1473-1-8289 — 11 —
A
A
Operating Instructions
Temperaturregler
Pos: 43 /#Neustruktur#/Online-Dokumentation (+KNX)/Rückseiten (--> Für alle Dokumente <--)/Rückseite - BJE-Variante @ 32\mod_1357201421897_15.docx @ 262132 @ @ 1