Burn Tech OFS 39, OFS 44, OFS 49VF Instructions For Use Manual

Vent Free Universal Masonry Firebox
Models OFS/TFS 39/44/49VF
VENT FREE
Instructions
WARNING:
n
If the information in these instructions is not followed exactly, a fi re or explosion may result causing property damage, personal injury or death.
Do not store or use gasoline or other ammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
not use any phone in your building. Immediately call your gas supplier from
a neighbor’s phone and follow the gas supplier’s instructions. If you cannot reach your gas supplier,
call the fi re department.
Installation and service must be performed by a qualifi ed installer, service agency, or the gas supplier.
IMPORTANT: READ THESE INSTRUCTIONS
CAREFULLY BEFORE STARTING
INSTALLATION OF THIS FIREPLACE.
This fi rebox has been tested and approved by PFS under ANSI Z21.91 for use with any ANSI Z21.11.2 approved gas logs.
FOR USE ONLY WITH A LISTED GAS-FIRED UNVENTED DECORATIVE ROOM HEATER NOT TO EXCEED 40,000 BTU/HR
DO NOT BUILD A WOOD FIRE.
Carefully review the instructions supplied with the decorative type unvented room heater for the minimum fi replace size requirement.
DO NOT INSTALL AN APPLIANCE IN THlS FIREBOX UNLESS THlS FIREBOX MEETS THE MINIMUM DIMENSIONS REQUIRED FOR THE INSTALLATION.
Do not store gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
Installer: Leave these instructions with the consumer. Consumer: Retain for future reference.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certifi ed kit is used.
REV 18 NOV 2009
Report No. 08-154
ICC Evaluation Services Report No. 2401
CONTENTS
CONTENTS
Fireplace Parts Diagram .........................................................................................Pg. 2
Fireplace Parts List .................................................................................................Pg. 3
General Information ................................................................................................Pg. 4
Safety Information ................................................................................................... Pg. 5
Location ................................................................................................................... Pg. 6
Supporting Floor Systems ....................................................................................... Pg. 6 ~ 7
Burntech Weight Determinations .........................................................................Pg. 8
Clearances .............................................................................................................. Pg. 9,10
Air for Combustion and Ventilation .......................................................................... Pg. 10,11
Important Pre-installation Information ..................................................................... Pg. 12
Fireplace Assembly Procedures .............................................................................. Pg. 13 ~ 15
Gas Piping Installation ............................................................................................Pg. 15
Electrical Line Feed ................................................................................................. Pg. 15
Firebrick Liner Installation ....................................................................................... Pg. 16
Initial Fireplace Operation ....................................................................................... Pg. 16
Appendix I ............................................................................................................... Pg. 17
Appendix II .............................................................................................................. Pg. 18
Warranty Information ............................................................................................... Pg. 19
Below is a
sample
picture of a rating plate that is typically located inside the lower dome side of your replace.
The Rating Plate will have a Model Number, Date of Manufacture and Serial Number stamped on the plate where indicated.
FOR USE WITH LISTED ANSI Z21.91-2007 UNVENTED DECORATIVE ROOM HEATERS NOT TO EXCEED 40,000 BTU/HR (11.723W) CONSULT WITH INSTRUCTIONS FOR THIS FIREBOX FOR FURTHER INFORMATION.
MODEL No.:
THIS APPLIANCE NEEDS FRESH AIR FOR SAFE OPERATION AND MUST BE INSTALLED SO THERE ARE PROVISIONS FOR ADEQUATE COMBUSTION AND VENTILATION AIR.
Tested & Listed By
REV 18 NOV 2009
Report No. 08-154
ICC Evaluation Services Report No. 2401
0” - 10” : NO PROJECTIONS 10” - 16” : 1-1/2” MAX. PROJ.
Refer to installation instructions and check local codes prior to installing. This appliance must be installed in accordance with local codes if any, if not, in accordance with the National Fuel Gas Code ANSI Z223.1 or CAN/CGA B.149 installation codes.
DO NOT REMOVE THIS LABEL
MANTEL CLEARANCES 16” - 22” : MAX. PROJ.
22” & ABOVE : 10” MAX. PROJ.
DATE OF MFG:
SERIAL No.
CLEARANCES TO COMBUSTIBLES
BOTTOM
TOP/ BACK/ SIDES
DISTANCE FROM SIDE OPENINGS 3” MIN. : 1-3/4” MAX. PROJ.
0”
TO CEILING
0”
OPENING
RECESS
DEPTH
18
42”
1/2
ANSI Z21.91-2007 Ventless Firebox Enclosures for Gas-Fired Unvented Decorated Room Heaters.
Fireplace Parts Diagram
Figure 1
X
Exploded Diagram
Fireplace Parts Diagram
9
5
7
11
6
2
2X
2X
3X
WARNING
Failure to position the parts in
accordance with these diagrams or
failure to use only parts specifi cally
approved with this appliance may result
in property damage or personal injury.
3
7X
8
12
3A
1
2X
Customer Service & Parts Replacement
Parts and accessories may be purchased from your local dealer. Additional information is available from Burntech Fireplace Solutions. Accessory orders will be accepted by mail, or you may call your order in at: (818)564-4253.
2
MFP39/44/49VF OFS/TFS39-44-49 VF Fireplace Parts List
ITEM P/N DESCRIPTION
OFS/TFS39-1
1
OFS/TFS44-1 OFS/TFS49-1
OFS/TFS39-2
2
OFS/TFS44-2 OFS/TFS49-2
OFS/TFS39-3
3
OFS/TFS44-3 OFS/TFS49-3
OFS/TFS 39-3A
3A
OFS/TFS OFS/TFS 49-3A
OFS/TFS 39-5
5
OFS/TFS 44-5 OFS/TFS 49-5
OFS/TFS 39-6
6
OFS/TFS 44-6 OFS/TFS 49-6
OFS/TFS 39-7
7
OFS/TFS 44-7 OFS/TFS 49-7
OFS/TFS 39-9
9
OFS/TFS 44-9 OFS/TFS 49-9
OFS/TFS 170
11
12
HEARTH (Left or Right)
REAR WALL
SIDE WALL
SIDE WALL with 4” hole for Air Kit
44-3A
DOME REAR - LOWER
LINTEL
DOME SIDE - LOWER
DOME TOP
RATING PLATE
#3 REBAR (Ø3/8”) x 36”
QTY
2
4
7
1
1
1
2
1
1
8
Optional Outside Ø4”
Combustion Air Kit
Model No.: MFP4-AK
(Ø4” Ducting not included)
Only the following doors have been tested and approved for use with this fireplace:
Crown-Breckinridge
McKenzie-Pendelton
OFS/TFS (39,44,49)SHBL- Herringbone OFS/TFS (39,44,49)FRBL- Running Bond
Refractory Firebrick Liners
(Herringbone Pattern shown, also available in Running Bond - see Pg.16)
or
3
General Information
General Information
Introduction
We extend a warm welcome from all of us at Burntech Fireplace Solutions, proud manufacturers of Burntech Modular Masonry Fireplaces.
Please call us with any installation questions or concerns at (818)564-4253, We are here to help.
Before Beginning the Installation
Read these instructions carefully before beginning the installation of this Vent-Free fi replace. Also read the gas log appliance manufacturer’s literature regarding sizing and suitability for installation into this Enclosure prior to installation.
Statement of Intended Use:
The
Burntech Vent-Free Universal Masonry Fireplace is a modular refractory masonry unit designed for eld assembly. The rebox is constructed using pre-cast, interlocking refractory blocks. The blocks are then secured to each other using Mortar. The system includes all parts necessary for the assembly of a complete masonry vent-free decorative gas log enclosure.
Product Overview
Burntech Assembled Fireplaces to be installed on both combustible and non-combustible oor systems. They have been extensively tested to perform with excellent results in this environment. Attention: Be advised that all the illustrations in this manual are for general reference only. They are not drawn to scale. Actual design elements will vary from case to case. Pay attention to specifi ed minimum clearances as they relate to combustible materials.
replaces are designed as Factory Built - Field
In addition to the basic enclosure, a standard 1-1/8” thick, high temperature refractory brick is required to line the interior of the fi rebox.
These fi replaces are not intended to serve as a primary heat source, rather, the fi replace was expressly created as a supplemental source of heat.
The
Burntech Vent Free Fireplace is Designed for Use Only with any Vent free decorative gas log sets meeting standard ANSI Z21.11.2 Vent free decorative gas log sets meeting standard ANSI Z21.11.2, are supplied by others and are limited to any listed vent-free gas- red log sets with heat input ratings up to 40,000 Btu/hr.
WARNING: Any application other than the “Intended Use” as stated above is in violation of the manufacturer’s instructions and is hereby prohibited. Such violation may cause immediate hazard, property damage or loss of life and will void all liabilities to the manufacturer and will void all warranties explicit or implied.
Figure 2
A
W3
W2
W1
SECTION A-A
OUTSIDE AIR ACCESS
23 1/8"
32 5/8"
A
4 1/2"
38 3/4"
7 1/8"
46 3/4"
21"
28"
Model W1 W2 W3
OFS/TFS39VF 43” 39” 29-1/4” OFS/TFS44VF 48” 44” 34-1/4” OFS/TFS49VF 53” 49” 39-1/4”
4
Safety Information
Safety Information
DANGER:
n
Carbon monoxide poisoning may lead to
death!
Carbon Monoxide Poisoning: Early signs of carbon monoxide
poisoning resemble the fl u, with headaches, dizziness, or nausea. If you have these signs, the fi replace may not be working properly. Get fresh air at once! Have the fi replace serviced. Note: Some people are affected more than others by carbon monoxide. These may include pregnant women, people with heart or lung disease, are anemic, anyone under the infl uence of alcohol, and those at high altitude.
IMPORTANT: Read this owners manual carefully
and completely before trying to assemble, operate, or service this fi replace. Improper use of this replace can cause serious injury or death from burns, fi re, explosion, electrical shock, and carbon monoxide poisoning.
General Safety Concerns
1. If you smell gas
O Shut off gas supply. O Do not try to light any appliance. O Do not touch any electrical switch; do not use any
phone in your building.
O immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
O If you cannot reach your gas supplier, call the fi re
department.
2. This fi replace shall not be installed in a bedroom or
bathroom.
3. Never install the fi replace
O In a recreational vehicle. O Where curtains, furniture, clothing, or other ammable
objects are less than 36 inches from the front, top, or sides of the fi replace.
O In high traf c areas. O In windy or drafty areas.
4. Do not use this fi replace as a wood-burning fi replace.
5. Do not add extra logs or ornaments such as pine cones,
vermiculite, or rock wool. Using these added items can cause soot build-up.
6. This fi replace is designed to be smokeless. If logs appear
to smoke, turn off fi replace and call a qualifi ed service person.
7. Avoid any drafts that alter burner fl ame patterns. Do not
allow fans to blow directly into the fi replace. Do not place a blower inside burn area of the fi rebox. Ceiling fans may create drafts that alter burner fl ame patterns. Soot build-up and improper burning will occur. Soot build-up can settle on household surfaces outside the fi replace.
8. This fi replace needs fresh air ventilation to run properly.
The Vent free decorative gas log set must have an oxygen depletion sensor (ODS) pilot light safety system. The ODS shuts down the fi replace if not enough fresh air is available. See Air for Combustion and Ventilation, page 8. If the fi replace keeps shutting off, see appliance manufacturers’ troubleshooting instructions.
9. Do not run fi replace
O Where ammable liquids or vapors are used or stored. O Under dusty conditions.
10. Do not use this fi replace to cook food or burn paper or other objects.
11. Never place any objects in the fi replace or on logs.
12. Fireplace screens must be provided and are to be closed before operating the decorative room heater. If doors are installed, they must be open during operation. Fireplace front and screen become very hot when running fi replace. Keep children and adults away from hot surfaces to avoid burns or clothing ignition. The fi replace will remain hot for a time after shut down. Allow surfaces to cool before touching.
13. Carefully supervise young children when they are in the room with the fi replace.
14. Do not use fi replace if any part has been exposed to or under water. Immediately call a qualifi ed service technician to inspect the fi replace and to replace any part of the control system and gas control which has been under water.
15. Do not operate the fi replace if any log is broken. Do not operate the fi replace if a log is chipped (dime-sized or larger). Verify proper log placement prior to operating appliance.
16. Turn fi replace off and let cool before servicing. Only a qualifi ed service person should service and repair the replace.
17. Operating the fi replace above elevations of 4,500 feet may cause pilot outage.
DO NOT USE OR STORE GASOLINE OR OTHER FLAMMABLE LIQUIDS OR GASES IN OR NEAR THE FIREPLACE!
ATTENTION: A re or an explosion could occur causing property
damage, injury or loss of life if you do not follow the information in this manual!
NOTE: THIS MANUAL MUST BE REPRODUCED ONLY IN ITS ENTIRETY.
Carefully review the instructions supplied with the decorative type unvented room heater for the minimum fi rebox size requirement.
DO NOT INSTALL THE APPLIANCE IN THIS FIREBOX UNLESS THIS FIREBOX MEETS THE MINIMUM DIMENSIONS REQUIRED FOR THE INSTALLATION.
When choosing a location for your fi replace, avoid locations that are subject to too much draft or locations where you may encounter obstructions that may be in the way of the fi replace once installed. Always check local codes and familiarize yourself with the surrounding construction.
5
Location
Location
Note: You may need to provide combustion and ventilation air
from an outside source to adequately satisfy local codes so avoid installing a combustion air inlet where the opening could be blocked by snow, bushes or other obstacles. Note that the access for outside air inlet is located on the right hand side of the fi replace.
Figure 3
Projected installations can extend any distance into the room.
A projection may be ideal for a new addition on an existing, nished wall.
Corner installations make use of space that may not normally be used and provides a wider and more effi cient range for heat disbursement.
An internal wall installation provides a discreet option for room separation and can also be ideal as an addition to an existing wall.
Internal
Wall
Installation
Full Projection
Installation
A ush installation is recommended where living space is limited or at a premium. Check local codes for any restrictions.
Figure 4
Corner
Installation
Flush Installation
IMPORTANT: Vent-free heaters add moisture to the air. Installing a fi replace in rooms without enough ventilation air may cause mildew to form from too much moisture.
IMPORTANT: Make sure the fi replace is level. If the fi replace is not level, the log set will not work properly.
Attention: You will need a building permit to install a Burntech replace. Check with the local jurisdiction before you get started.
Supporting Floor Systems
Floor Framing
It is important to take into consideration that the load for the Burntech Fireplace is considerable, but, more important, that it is a dead load that will have to be absorbed by a relatively small amount of existing oor space.
It is the ultimate responsibility of the installer to ensure that proper concrete slab supports are used.
WARNING to the licensed design professional and/or building contractor: It is your responsibility to be certain that the Burntech can be properly supported by the combustible oor system on which the replace will rest.
H
D
W
Model W H D
*****39VF 43” 41” 28” *****44VF 48” 41” 28” *****49VF 53” 41” 28”
For fi replace support foundations installed on concrete refer to Appendix I and II (pages 17 & 18) for specifi c instructions.
Rebar locations
Lay-out the position of the fi replace and drill holes where the rebar will be located. Secure the #3 rebar 4 inches into the concrete foundation with ITW Epoxy or Simpson Epoxy. Follow manufacturer’s instructions for installation of rebar into slab.
Wood Floor
Anchorage of fi replace to wood fl oor construction is required. Refer to Figure 8 for anchorage dimensions. Four anchors are required to attach to the sub-fl ooring framing.
Crawl Space or Upper Floor:
For installation of fi rebox over combustible crawl spaces or upper fl oors, anchorage of the fi rebox is required. Illustrations of examples of possible anchorage methods are shown in Figures 5 thru 7 depending upon the type of fl oor framing. Final method of anchorage is to be determined by licensed design professional.
6
For conventional framing, where the fl oor joists are parallel with the sides of the fi rebox, the addition of fl oor joists to align with the anchor brackets allows the brackets to be directly connected to the fl oor joists.
Note that additional fl oor joists may be required to support the weight of the fi rebox and chimney. Where the fl oor joists run parallel to the front of the fi rebox, anchorage can be accomplished in like manner as shown in Figure 5 using blocking between the oor joist.
For fl oors supported by I-Joists, the method of anchorage is illustrated in Figures 6 and 7. Figure 10 illustrates the general arrangement of anchorage to fl oor framing.
Figure 6
I-Joist Anchoring Top View
Simpson Strong-Tie A-35 or equivalent
Example Only
I-Joist
It is important to take into consideration that the load for the Burntech Fireplace must be considered as additional dead load that will have to be supported by the Additional oor joists or I-joists may be required as determined by the licensed design professional.
The dead weights for the fi replace are noted in Table I. It is the task and responsibility of the general contractor/installer to see that the proper reinforcement for weight loads are made by a licensed design professional prior to the fi replace installation.
As stated above, it is desirable to place additional framing for alignment of anchor rods. Refer to Figure 10 for anchor rod locations.
Figure 5
Anchor Bracket Assembly
oor framing.
A35 Brackets (16 required)
2X FLOOR JOIST
Figure 7
I-Joist Anchoring Bottom View
Anchor Brackets
I-JOISTS
Example Only
EXAMPLE ONLY
2X FLOOR JOIST
Floor Sheathing not shown for clarity
7
Burntech Weight Determination
Table I
Fireplace Model
Fireplace Weight
Mortar, Rebar & Ready Mix Concrete
Firebrick Lining
Floor Area
Other Weight Considerations:
Fireplace fi nished facing (surround): This information needs to be obtained from the contractor.
OFS/TFS39VF OFS/TFS44VF OFS/TFS49VF
809 lbs. 896 lbs. 987 lbs.
350 lbs. 357 lbs. 364 lbs.
333 lbs. 345 lbs. 356 lbs.
43” x 28” (8.12 ft²) 48” x 28” (9.33 ft²) 53” x 28” (10.30 ft²)
Table II - Defl ection Limits
Construction L S or W D +L
1
Floor Members
1
For wood structural members having a moisture content of less than 16 per cent at time of installation and used under dry
conditions, the defl ection resulting from L + 0.5D is permitted to be substituted for the de fl ection resulting from L + D.
Note that Burntech cannot accept responsibility for structural oor support details. All drawings are presented as mere illustrations to indicate the presence of the underlying oor system. It is the responsibility of the general contractor/installer to consult with a local licensed design professional for guidance in building a proper oor support system.
Figure 8
Model A
OFS/TFS39VF 38-3/4”
OFS/TFS44VF 43-3/4”
OFS/TFS49VF 48-3/4”
I/360 --- I/240
A
F
4"
10"
Figure 9
Figure 10
Typical Anchorage Layout
Fireplace outline
EXAMPLE ONLY
10”
SECTION VIEW ROTATED 90CW
8
Clearances
Clearances
The Importance of Clearances
Warning to the structural engineer and/or building contractor: It is your responsibility to be certain that the Burntech can be properly supported by the combustible
oor system on which the replace will rest. Be advised that this engineering equation will be in addition to any live or dead weights that the oor has to carry.
Clearances to Combustibles
Nothing is more important than paying strict attention to giving clearance between fi replace surfaces and surrounding “combustibles” the most common of which are:
ODrywall
OWood ooring
OPlywood sub- ooring
OFraming materials
OParticle board
OMill board
OPlywood paneling
Required Clearances are:
Unit front, sides, rear: .......................................... 0"
Combustible Floor: .............................................0"
Combustible Sheathing above opening top: ....... 8" (200 mm)
Sheathing or trim to opening sides: ....................8" (200 mm)
Mantle above opening: ....................................... 12" (300 mm)
Opening to sidewall: ........................................... 24" (500 mm)
Insulation from fi rebox: ....................................... 0"
Figure 11
1-1/2”
8” MIN
NON­COMBUSTIBLE FACIA
Figure 12
12” MIN
NON-COMBUSTIBLE
FACIA
1-1/2”
Clearance to combustible trim are those distances required to ensure that combustible mantle and facing material will not be exposed to excessive heat while the unit is operating.
These clearances should be adequate to prevent discoloration or warping of trim facings due to heat. However, circumstances unique to each installation create variables that may be beyond the scope of this manual. Therefore be sure to follow gas log appliance manufacturer’s explicit installation instructions regarding all minimum trim facing, mantle height and side wall clearance requirements.
Figure 13
The Burntech Vent-Free replace may be installed at “zero
clearance” to plywood sheathing and to uninsulated wood framing members at the unit bottom, sides, rear and top when used for enclosing any listed vent-free gas- red log set with maximum heat input ratings up to 40,000 Btu/hr. However, when a Vent-Free replace is to be installed on carpeting, wood ooring, or any combustible material other than tile or concrete, the Vent-Free replace shall then be installed on a
metal or wood platform extending the full width and depth of the Vent-Free replace.
Clearance to Combustible Trim:
Burntech Vent-Free Fireplaces are designed to be custom nished with facing trim and mantle to be an owner option. However, all such trim material must meet standard replace code requirements.
Non-combustible facing material must be applied to a minimum of eight inches (8”) beyond the sides of the fi nished opening of the Vent-Free fi replace and non-combustible facing material must cover a minimum of twelve inches (12”) above the fi nished opening of the installed unit.
Parts of the combustible mantle assembly located above and projecting more than one and one-half inches (1-1/2”) inches from the fi rebox opening shall be kept at least twelve inches (12”) from the top of the opening.
Mantle shelves with horizontal projection of ten inches (10”) from the face of the fi replace must be held to a minimum vertical
distance of twenty inches (20”) from the top of the fi nished replace opening.
Note: Mantle height clearances may vary among gas log appliance manufacturers or with the use of fi rebox canopies.
Be sure to follow the gas log appliance manufacturer’s explicit installation instructions for mantle height clearance requirements.
9
Interior Wall Materials:
Air for Combustion and Ventilation
Wall materials, such as drywall, should be set fl ush with the rough front face of the Vent-Free fi replace. This will allow for placement of required non-combustible surround material in such a way that the surround material can lay fl at against the
nished wall surface and also align with the leading edge of the re brick interior of the Vent-Free fi replace (see Figure 15).
Trim Facings:
Parts of the combustible mantle assembly located along the sides of the fi rebox opening, which project more than one and one-half inches (1-1/2”) from the face of the fi replace, shall be kept at least eight inches (8”) from the fi rebox opening.
Adjoining Room Walls:
Interior wall surfaces of adjoining room walls must be at a minimum horizontal measure of twenty four inches (24”) away from the fi nished opening of the Vent-Free fi replace.
Air for Combustion and Ventilation
Energy effi cient homes require homes to be airtight but at the same time provide suffi cient fresh air to breathe. Fresh air enters the home through air conditioning duct vents, around doors and windows but also must provide enough fresh air for proper combustion on all fuel-burning appliances in the home. Exhaust fans, fi replaces, clothes dryers, and fuel-burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
Figure 16
Non-combustible
Flex Hose
Exterior
Figure 14
FRAMING
8” MIN. NON-COMBUSTIBLE MATERIAL
W
1-1/2”
Model W D1
OFS/TFS39VF
OFS/TFS44VF
OFS/TFS49VF
43” 73-1/2”
48” 77”
53” 80-1/2”
Figure 15
FRAMING
1-1/2”
8” MIN. NON-COMBUSTIBLE MATERIAL
8” MIN
D1
20”
MIN
Providing Adequate Ventilation
In accordance with the National Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation, all spaces in homes fall into one of the three following ventilation classifi cations:
1. Unusually Tight Construction
2. Unconfi ned Space
3. Confi ned Space
The following information will help you classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in homes of unusually tight construction, you must provide additional fresh air. Unusually tight construction is defi ned as construction where:
a. Walls and ceilings exposed to the outside atmosphere have
a continuous water vapor retarder with a rating of one perm* or less with openings gasketed or sealed and...
b. Weather stripping has been added on openable windows and
doors and...
c. Caulking or sealants are applied to areas such as joints
around window and door frames, between sole plates and oors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and other openings.
* A perm is a unit of permeance or water vapor transmission, the US perm-inch is defi ned as the passage of 1 grain of vapor through 1 square foot of 1 inch thick material in 1 hour under a pressure difference of 1 inch of mercury.
If your home meets all the three criteria above, you must provide additional fresh air.
10
Unconfi ned Space
An unconfi ned space has a minimum total air volume of 50 cu.ft. (cubic feet) for each 1,000 Btu/Hr input rating of all appliances in the total space (cu.ft. = length x width x height of space). Include adjoining rooms only if there are doorless passageways or ventilation grills between the rooms. If the Btu per 50 cu.ft. is less than 1,000 Btu/Hr, then fresh air will be provided by the natural air fl ow into the house.
Confi ned Space
A confi ned space has an air volume of less than 50 cu.ft. for each 1,000 Btu/Hr input rating of all appliances in the space (cu. ft. = length x width x height of space). Include adjoining rooms only if there are door less passageways or ventilation grills between the rooms.
Determining Total Air Volume
Use this work sheet to determine if you have a confi ned or unconfi ned space. The space to be considered includes not only the room in which you will install the fi replace but also any adjoining rooms with ventilation grills between them or door less passageways.
1. Determine the total volume of your space
L x W x H = _______ cu.ft. Example: Space size = 20 ft. long x 20 ft. wide x 8 ft. high (ceiling height) = 3,200 cu.ft. If adjoining ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.
2. Divide the space volume by 50 cu.ft. to determine the
maximum Btu/Hr the space can support. _______ cu.ft. (volume of space) 50 cu ft. = (Maximum Btu/Hr the space can support) Example: 3200 cu ft. (Volume of space) / 50 cu. Ft. = 64.0 or 64,000 (maximum Btu/Hr the space can support.)
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free fi replace _______ Btu/hr Gas water heater* _______ Btu/hr Gas furnace _______ Btu/hr Vented gas heater _______ Btu/hr Gas fi replace logs _______ Btu/hr Other gas appliances* _______ Btu/hr
Total = _______ Btu/hr
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
_________ Btu/Hr (maximum the space can support) _________ Btu/Hr (actual amount of Btu/Hr used)
Example: 64,000 Btu/Hr (maximum the space can support) 76,000 Btu/Hr (actual amount of Btu/Hr used)
The space in the previous example was a confi ned space because the actual Btu/Hr used was more than the maximum Btu/Hr the space could support. If you fi nd you have a Confi ned Space, you must provide additional fresh air. Your options are as follows:
a) Re-work worksheet, adding the space of an adjoining room
that may not have qualifi ed for the extra volume. If the extra space provides enough volume to convert the area to an unconfi ned space, remove door to adjoining room or add ventilation grills between rooms.
b) Vent room directly to the outdoors.
c) Install a lower Btu/Hr gas log (if lower Btu/Hr size makes
room unconfi ned).
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfi ned space. You will need no additional fresh air ventilation.
WARNING: If the area in which the heater may be operated is smaller than that defi ned as an unconfi ned space, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1 Section
5.3 or applicable local codes.
Local codes may have stricter defi nitions for confi ned space and/or for unusually tight construction. Installing our optional outside air kit may allow the space to be classifi ed as not being unusually tight or being an unconfi ned space. Check you local codes.
IMPORTANT: Do not provide openings for inlet or outlet air into an attic if the attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.
Example: Gas water heater 40,000 Btu/hr
Vent-free fi replace +36,000 Btu/hr
Total = 76,000 Btu/hr
* Do not include direct-vented gas appliances. Direct vent draws combustion air from the outdoors and vents to the outdoors.
11
Important Pre-installation Information
Important Pre-installation Information
Overview
You will nd that the Burntech Fireplace is designed for complete assembly at your construction site with all necessary items delivered consisting of interlocking precast parts, 50 lbs. of Burntech mortar and rebar.
The parts of the fi replace are made of Burntech’s incredibly strong blend of specialty cement and a lightweight aggregate.
The design of the fi replace calls for the installation of a refractory re brick liner. This should be a minimum of 1-1/8” thick. The liner will be applied within the walls of the rebox. Modular rebrick panels are also available from Burntech.
Additional Materials Required:
1) Ready-Mix concrete - 2 cu.ft.
SURFACE CRACKS - The Burntech FIREPLACES are manufactured using high quality materials. During the drying
process, surface cracking may occur. These small cracks (under 1/16” will not affect the replace safety or performance). During the assembly process, ll surface cracks with thin-set mortar and brush when drying for a smooth surface nish.
Leveling and Aligning Components:
It is important to assemble all Vent-Free replace components ush, level and square. Since it is not intended that mortar
be used to lay a mortar joint of any measurable thickness as is typical when laying brick or concrete block, adjustments in component height and level alignments are accomplished with the use of small shims. These shims can be tapped into place to level and align components. Once the Burntech Mortar is set, the shims must be removed completely. Be sure to re-grout any and all gaps where shims have been inserted and then removed or where contact surfaces have been separated by shim leveling.
Field Assembly Procedures
1) Mixing the BURNTECH mortar – You will require a 50 lb. bucket of BURNTECH mortar which will be more than enough to adequately af x all the replace components, one to the next. The mortar is premixed and dry and is to be used to adhere all the replace components. Be sure to use clean water and work it up into a mixture that is pasty but not lumpy. If it is too thin, the components will not adhere. Some trial and error may be necessary. You will want to apply the mixture with a standard grout bag.
2) Moisten all surfaces which will have grout applied prior to assembly. This will minimize shrinkage and cracks developing in the joint areas. Best way to accomplish this is with a bucket of water and a large sponge. Dip sponge into water and apply a liberal amount of water to the grout joint surface several minutes before the part is to be assembled. The water will absorb into the surface allowing the grout to properly cure.
3) Assembly of the Components – Once you have found the proper consistency of the mixture, load it into the grout bag
and then place the components together applying the mixture directly to the components where they come together. As a rule, you can fi gure that you should lay down about ½” (one- half inch) of a thread of mortar. The line of mortar should be approximately ½” (one-half inch) away from all the edges of each separate component.
The mortar has a considerable amount of holding power so do not overload the components with too much mortar.
4) You will notice that some mortar will “ooze out” when you place the next component on top of or next to the component you previously place. This is to be expected – it means the two pieces have properly bonded -- and you will want to swipe the excess away with a trowel. It is never intended that the surfaces of the Burntech components are to be completely covered with mortar.
5) Do not apply the mortar in thick bands even if the component you are working with is larger than the rest. You will want to apply “stripes” of mortar in these situations.
6) Making Sure Components Are Level – It is extremely important that you pay careful attention to how you are assembling the Burntech. Since every component builds on the next, it is critical, that from the beginning, you are checking that the components are tting together to be level and ush. If you have to make any kind of an adjustment, do not try to do it “by loading an opening” with mortar. That is completely unacceptable, resulting in a replace that will not be plumb or level. What you are advised to do is make use of shims. You will nd these supplied with the Burntech and you can nudge them in between openings to achieve the precision you need in making component adjustments.
Once you have removed the shims, you will want to cover
7) any gaps that may have resulted with the grout.
Warning: All surfaces where grout is applied must have water sponged on several minutes prior to assembly. This will minimize cracking of grout joint and provide maximum strength.
12
Fireplace Assembly Procedures
Fireplace Assembly Procedures
Note - Wipe excess water from surface prior to applying grout.
This will help grout to adhere to surface during assembly.
Warning: All surfaces where grout is applied must have water sponged on several minutes prior to assembly. This will minimize cracking of grout joint and provide maximum strength.
Place the Burntech Fireplace hearth base on top of your non­combustible fl oor. For concrete slabs, supporting fl oor needs to be rated at ASTM 90.
Draw an outline of the hearth area based on the dimensions
1)
shown in Figure 17. Position Hearth slabs and mark rebar center locations. Drill 4 inches into concrete slab and secure the 8 pieces of 12 inch rebar with epoxy.
Figure 17
Left Side Hearth 2nd
Right Side Hearth 1st
Apply mortar
between joints
28”
Figure 19
Before installing side walls, confi rm placement of outside
5)
Hearth shown prepared for Left Side position
combustion air access (if required), this can be installed either side depending on which side is accessible to outside combustion air (all diagrams in this manual show the combustion air inlet hole on the right side). Prepare side wall and rear wall mating surfaces with the prepared mortar and begin assembly.
Side Wall shown prepared for Right Side Air Access. For Left Side bead opposite side.
1/2” AWAY FROM EDGES
Model W
MFP-39 43”
W
12 inch rebar
Mix a batch of mortar and prepare Right Side Hearth bottom
2)
MFP-44 48”
MFP-49 53”
surface to be bonded as shown in Figure 18.
Figure 18
APPLY MORTAR BEAD TO ALL MATING SURFACES
Align Right Side Hearth to the outline created. The overall
3)
Hearth section shown prepared for Right Side position
1/2” MORTAR BEAD TYPICAL
1/2” AWAY FROM EDGES
width should allow for an approximate gap of 1/8” between slabs for the additional mortar to unite the remaining slab. Check for surface fl atness, level if necessary.
Apply mortar to the remaining Hearth except this time apply
4)
beading on surface to be facing fl oor as shown in Figure
19.
Figure 20
Keep the assembly of the next sections of the fi rebox side
6) walls moving up, keeping components moist, mixing mortar as you need it and threading the mortar appropriately as you stack each section, one onto the next. Constantly check for squareness and levelness while building each course of block. As you complete each section, make certain that you adhere the mortar at each and every joint.
Figure 21
Side Wall
Apply mortar
Combustion Air Access Right or Left (Right shown).
When you have arranged all the components into place
7)
Apply mortar
Rear Wall
Side Wall
and you are working on the top rear fi rebox, check that your work is level. If you need to, you can make some adjustments in the top surface of the box assembly simply by using shims. Once you are satisfi ed with the degree of levelness, you can address any gap that may have occurred with an appropriate amount of mortar.
13
Although you are cautioned to use Burntech mortar sparingly because it does have such holding power, you should look over the
rebox assembly at the end and ll any gaps with mortar especially at joint connections. Adjustments must be made to ensure the replace is level and square while the mortar is still wet.
Place Lower Side Domes between Lintel and Lower Rear
11) Dome to verify fi t. The face with the rating plate faces the inside of the fi rebox as shown in Figure 24. Remove and prepare mating surfaces with mortar. Assemble Lower Dome Sides and check that all four top surfaces are level with each other. Shim if necessary.
8)
After fourth row of walls are in place, add 36” rebar to all cells as shown in Figure 22. The rebar should enter the holes in the Hearth and lie adjacent to the 12” rebar secured in subfl oor. Then fi ll cells with approx. 2 cu.ft. Ready-Mix Concrete.
Figure 22
9)
Temporarily place Lintel between side walls, making sure
Add rebar after fourth row
12 inch
rebar
it is fl ush to the front and snug at the inside. Check for alignment. Remove Lintel and apply mortar on surfaces to be mated. Install Lintel.
Figure 24
Lower Dome Sides (Rating Plate faces inside)
13) Now install the Smoke Dome Tops. Align outer edges with
Lower Dome Sides. Check for fl atness and squareness.
Figure 25
10)
Install Lower Rear Dome fl ush to the rear walls as shown in
Figure 23.
Figure 23
Lintel
Lower Rear Dome
14
Raised and Flush Hearth Application:
Gas Piping Installation
Electrical Line Feed
If you would prefer to have a raised hearth, the Vent-Free box can be raised to the desired height using wood studs or concrete blocks.
Gas Piping Installation
The provision for installation of a gas pipe is only for connection to a Vent free decorative gas log sets meeting standard ANSI Z21.11.2
Figure 26
Concrete Block Raised Platform
When determining raised hearth height, be sure to allow for the 3” thick fi rebox hearth and 1-1/2” thick fi rebrick fl oor, in addition to the height of base platform.
Figure 27
Raised Wood Platform
Familiarize yourself with requirements for installation as outlined by the National Fuel Gas Code, ANSI Z223.1. This gas pipe provision must only be connected to an approved vent-free gas log heater certifi ed to ANSI Z21.11.2 heater standard. Check local building codes for specifi c pipe and material requirements.
1) Gas piping can be routed from the fl oor, rear or side walls. With a masonry drill, follow the instructions from the gas appliance manufacturer. Any wires must be routed through separate conduit. Make sure provisions are made for access to manual shut-off valve.
Figure 28
Approved Flexible Gas Line
Minimum
Pipe
Nipple
Cap
CSA Certifi ed Manual Shut-off Valve
Tee-joint
Sediment Trap
3”
From External Regulator (11-14” W.C. pressure)
For a “fl ush hearth” (fi replace fl oor fl ush with the room’s
oor) the base plate can be omitted from the assembly and the rebox walls built directly on the concrete support slab. The re brick fl oor of the fi rebox is then set directly to the concrete
support slab. This makes the fi replace fi nished fi re brick fl oor approximately one and one-half inches (1-1/2”) above the top of the concrete support slab.
2) After routing piping, ll hole around pipe with BURNTECH mortar.
Electrical Line Feed
Electrical line feed can be routed through the Standard rebox back wall, side walls or fl oor by drilling an appropriately sized hole using a masonry drill bit. Be sure to follow the Vent free decorative gas log Manufacturer’s explicit electrical line connection instructions for vented masonry fi replace installations.
NOTE: Gas line and electric line must be routed through separate access holes.
Figure 29
Firebrick SideGas or
Electric Line
IMPORTANT: All access holes must be grouted with mortar to seal any gaps or cracks.
15
Firebrick Liner Installation
Firebrick Liner Installation
Initial Fireplace Operation
Initial Fireplace Operation
It is required that the interior sides, rear and bottom be lined with minimum 1-1/8” thick rebrick. rebrick liner walls can make the installation easier.
All required through-wall accesses (gas and electrical line feeds and combustion air supply access holes) should be drilled before the required fi re brick lining is installed.
Modular Firebrick Lining
If using our Burntech Firebrick Liners, simply use an extra bucket of mortar. Install Hearth Liner rst, rear next and sides last. Consider if brackets for grates will be required, also if pre­drilling is required for gas lines, electrical or if the outside combustion air kit is to be installed.
The following Firebrick Patterns are available from Burntech:
OFS/TFS(XX)SHBL- Herring Bone
Figure 30
Burntech Pre-fabricated
Follow the gas appliance manufacturers’ requirements for lighting and operating your vent free log. When fi rst operating the fi replace, open a window in the room to allow smells created from the heater and fi replace curing.
We suggest operating the heater for several 30 minute intervals allowing the fi replace to cool for an hour in between. This will allow any moisture in the brick and fi replace to escape.
Keep in mind that it may require several operations to completely remove any smell from the operation of a vent­free heater and fi replace. If this condition continues, contact your gas appliance dealer to inspect the gas heater for proper operation.
Figure 31
OFS/TFS(XX)FRBL- Running Bond
16
)
c
(f’
a
c
c
d
d,e,f
3,000
used to
3,500
b
,shallbeas
c
f’
d
d,e,f
Weathering Potential
2,500 3,000
Negligible Moderate Severe
MINIMUM SPECIFIED COMPRESSIVE STRENGTH
Appendix I
TABLE R402.2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE
For installations regulated by the International Residential Code, the support foundation for the fireplace installed on concrete shall
consist of a minimum of 6 inches thick reinforced concrete slab. The minimum specified compressive strength of
required in Table R402.2 of the International Residential Code (IRC). Concrete subject to moderate or severe weathering as indicated
in Figure R301.2(3) of the International Residential Code (IRC) shall be air entrained as specified in Table R402.2 of the International
Residential Code (IRC). The maximum weight of fly ash, other pozzolans, silica fume, slag or blended cements that is included in
produce concrete and testing thereof shall comply with the applicable standards listed in Chapter 3 of ACI 318.
concrete mixtures for garage floor slabs and for exterior porches, carport slabs and steps that will be exposed to deicing chemicals
shall not exceed the percentages of the total weight of cementitious materials specified in Section 4.2.3 of ACI 318. Materials
accordance with Footnote d.
a. Strength at 28 days psi.
b. See Figure R301.2(3) for weathering potential.
c. Concrete in these locations that may be subject to freezing and thawing during construction shall be air-entrained concrete in
d. Concrete shall be air-entrained. Total air content (percent by volume of concrete) shall be not less than 5 percent or more than
TYPE OR LOCATION OF CONCRETE CONSTRUCTION
For installations regulated by the International Building Code (IBC), the support foundation for the fireplace installed on concrete
shall consist of a minimum of 6 inches thick reinforced concrete slab. The concrete strength and durability shall comply with Sections
1903, 1904 and 1905 of the International Building Code (IBC).
Basement walls, foundations and other concrete not exposed to the weather 2,500 2,500 2,500
Basement walls, foundation walls, exterior walls and other vertical concrete
work exposed to the weather
Basement slabs and interior slabs on grade, except garage floor slabs 2,500 2,500 2,500
Porches, carport slabs and steps exposed to the weather, and garage floor slabs 2,500 3,000
17
7 percent.
3 percent is permitted if the specified compressive strength of the concrete is increased to not less than 4,000 psi.
e. See Section R402.2 for maximum cementitious materials content.
f. For garage floors with a steel troweled finish, reduction of the total air content (percent by volume of concrete) to not less than
Appendix II
FIGURE R301.2(3) WEATHERING PROBABILITY MAP FOR CONCRETE
18
a. Alaska and Hawaii are classified as severe and negligible, respectively.
severe classification is where weather conditions result in significant snowfall combined with extended periods during which there is
b. Lines defining areas are approximate only. Local conditions may be more or less severe than indicated by region classification. A
little or no natural thawing causing deicing salts to be used extensively.
Lifetime Limited Warranty
Burntech® Fireplace Solutions
Burntech® Fireplace Solutions, Inc. warrants all Burntech® Fireplaces to be free from defects in materials that adversely affect replace
performance for the lifetime of the product from the date of purchase, subject to the terms and conditions of this limited warranty. Burntech® Fireplace Solutions does not warrant accessory chimney, outside air ducts and devices not manufactured by Burntech® Fireplace Solutions.
This warranty covers only products manufactured by Burntech® Fireplace Solutions, specically the modular masonry replace, and
NO WARRANTY, EXPRESS OR IMPLIED, EXTENDS TO ANY OF THE HARDWARE, FOUNDATION, VENTING, DUCTS, OR ACCESSORIES. THIS WARRANTY DOES NOT COVER DRAFTING, SMOKING, OR SOOTING OF THE FIREPLACE SYSTEM. Factors beyond the manufacturer’s control affect drafting, smoking, and sooting and Burntech® Fireplace Solutions cannot
guarantee these aspects of performance.
Coverage under this warranty is subject to the following conditions and exclusions:
This warranty is null and void when the replaces are not installed pursuant to the installation instructions provided by Burntech®
• Fireplace Solutions or local building codes have not been followed completely.
Glass is warranted against thermal breakage only and only on models that are manufactured by Burntech® Fireplace Solutions with a glass
front. On Direct Vent models the safety glass or safety screen must be kept in front of this glass when replace is in use. Safety screen must be used on all models when in use.
This warranty does not apply to any component or part that shows evidence of misuse, abuse, improper installation, accident or lack of
• regular maintenance. Burntech® Fireplace Solutions is not responsible for misuse or mishandling of component parts.
This warranty does not apply to any damage sustained to the appliance while in transit.
Neither Burntech® Fireplace Solutions, nor any afliate thereof, is responsible for any labor costs or indirect costs incurred for the
• replacement of defective components. Any covered component that, in our judgment, is defective shall be repaired, replaced or refunded at Burntech® Fireplace Solutions’s option.
Nothing in this warranty makes Burntech® Fireplace Solutions, or any afliate thereof, liable in any respect for any injury or damage to
the building or structure in which the replace has been installed or to the persons or property therein arising out of the use, misuse, or
installation of properly manufactured Burntech® Fireplace Solutions products.
The replace must be used in accordance with operating instructions. The grate or andirons must be installed when using the replace.
NEITHER Burntech® Fireplace Solutions, NOR ANY AFFILIATE THEREOF, SHALL BE HELD LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES OR EXPENSES ARISING OUT OF THE USE OF THE FIREPLACE. ALL SUCH DAMAGES AND EXPENSES ARE HEREBY EXCLUDED. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.
If a component is found to be defective under the terms of this warranty the party this warranty is extended shall, notify Burntech® Fireplace Solutions, 6520 Platt Ave #577, West Hills, CA 91307 in writing, by registered mail, within thirty (30) days following the discovery of the defect within the lifetime warranty period. The letter shall include proof of purchase and state the (1) date of purchase, model number and serial number ; (2) place of purchase; (3) address of installation; (4) name, address and phone number of the homeowner; and (5) a brief description of the defect.
This warranty applies only to those replaces installed in the continental United States, Alaska and Canada. If any part of this warranty is
found to be unenforceable, the remaining parts shall remain in force and effect.
THE FOREGOING WARRANTY IS EXCLUSIVE AND IS IN LIEU OF ALL OTHER WARRANTIES, TERMS OR CONDITIONS, EXPRESS OR IMPLIED EITHER IN FACT OR BY OPERATION OF LAW. Burntech® Fireplace Solutions HEREBY DISCLAIMS ALL GUARANTEES AND WARRANTIES, EXPRESS OR IMPLIED, BEYOND THE WARRANTIES SET FORTH HEREIN, INCLUDING BUT NOT LIMITED TO WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
Burntech® Fireplace Solutions
6520 Platt Ave #577, West Hills, CA 91307
Main: (818)564-4253, Fax: (818) 564-4232
Revised 12/05/2012 WWW.BURNTECH.COM
ATTENTION BURNTECH FIREPLACE
INSTALLER:
UPON COMPLETION OF A BURNTECH FIREPLACE INSTALLATION, LEAVE THE FOLLOWING NOTICES ON THE INTERIOR HEARTH OF EACH BURNTECH FIREPLACE INSTALLED. FAILURE TO DO SO WILL VOID THE BURNTECH FIREPLACE WARRANTY AND CREATE A POTENTIALLY DANGEROUS CONDITION.
1. ATTENTION OWNER SHEET
2. BURNTECH MODULAR FIREPLACE START UP CURING
INSTRUCTIONS
3. A COPY OF THE INSTALLATION MANUAL
ATTENTION OWNER:
PRIOR TO LIGHTING YOUR BURNTECH FIREPLACE, REFER TO YOUR INSTALLATION MANUAL FOR IMPORTANT WARNING NOTICES AND SPECIFIC INSTRUCTIONS FOR PROPER CURING AND SAFE OPERATION OF YOUR FIREPLACE . IF YOU DID NOT RECEIVE A BURNTECH INSTALLATION MANUAL UPON INSTALLATION OF YOUR BURNTECH FIREPLACE, PLEASE CONTACT YOUR INSTALLER IMMEDIATELY.
INSTALLER:_____________________ PHONE:________________________ INSTALLATION DATE:_____________ FIREPLACE MODEL:_______________
YOU
MAY ALSO DOWNLOAD A COPY OF THE INSTALLATION MANUAL AND CURING INSTRUCTIONS AT : http://burntech.com/downloads-manuals.htm
ATTENTION BURNTECH FIREPLACE INSTALLER:
THIS NOTICE MUST BE PLACED
HOMEOWNER! FAILURE TO DO SO WILL VOID THE BURNTECH WARRANTYAND
COULD CREATE A POTENTIALLY DANGEROUS CONDITION
IN THE HEARTH OF THE FIREPLACE FOR THE
ATTENTION OWNER: THIS VENT FREE FIREPLACE IS DESIGNED FOR USE WITH VENT-FREE GAS LOGS ONLY. NEVER BURN WOOD IN THIS FIREPLACE AS IT DOES NOT HAVE A CHIMNEY FOR VENTILATION. DOING SO CAN RESULT IN SERIOUS INJURY OR DEATH. PLEASE REFER TO YOUR INSTALLATION MANUAL FOR IMPORTANT SAFETY WARNINGS AND INFORMATION REGARDING SAFE AND EFFICIENT OPERATION. IF YOU DID NOT RECIEVE A COPY OF YOUR INSTALLATION MANUAL, ONE MAY BE OBTAINED FOR FREE FROM OUR WEBSITE http://burntech.com/downloads-manuals.htm OR BY CALLING US AT (818)564-4253.
BURNTECH MODULAR FIREPLACE START UP CURING INSTRUCTIONS:
Burntech Fireplace’s r equire a specific curing process prior to normal useage. Doing so will help to minimize shrinkage cracks in the mortar and in the fireplace components. Please follow the curing process as described below prior to normal use of your Burntech Fireplace. Please refer to your installation manual for important information regarding
First Lighting - After construction is completed, all elements of the fireplace must be completely d
of 28 days. Light your Vent Free gas logs with a flame approximately 3-4" high and keep lit continuous for one hour. Wait a minimum of 24 hours until second lighting.
Second Lighting - Light your Vent Free gas logs with a flame approximately 4-6" high and
keep lit continuous for 2 hours. Wait a minimum of 24 hours until the third lighting.
Third Lighting
lit continuous for 2 hours. Wait a minimum of 24 hours until regular usage.Y
You may now enjoy your Burntech fireplace!
ry. This means that the unit must stand without any firing for a minimum
Light your Vent Free gas logs with a flame approximately 6-8" high and keep
FOR ADDITIONAL COPIES OF THIS SHEET PLEASE VIST OUR WEBSITE AT WWW.BURNTECH.COM
Loading...