TYPES YA-A
AND YA-A-TN
(Continued)
HYLUG™
UNINSULATED ALUMINUM
COMPRESSION TERMINAL
FOR ALUMINUM AND
COPPER CONDUCTORS
1-HOLE DESIGN
AL9CU
• Contact BURNDY®for conductor, stud sizes and hole
drillings not shown.
▲ See tooling section of this catalog for complete tool and
die listings.
Y644HS DIELESS HYPRESS™
RANGE-TAKING
CAPABILITIES
The following size HYDENT™ lugs and two
way splices, when crimped with the Y644HS
DIELESS HYPRESS™ tool, produce the
following range taking capabilities:
DIE AND CRIMP
INFORMATION
ELECTRO-TIN
PLATED
CLOSED
BARREL
COLOR CODED
END CAP
CRIMP
CRIMP
CABLE
ACCOMMODATION
Aluminum Connectors
Standard Expanded Standard Expanded Standard Expanded
Wire Size Wire Range Wire Size Wire Range Wire Size Wire Range
#6 AWG #6 AWG 1/0 AWG 1/0 - #1 AWG 250 kcmil 250 kcmil - 1/0 AWG
#4 AWG #4 - #6 AWG 2/0 AWG 2/0 - #1 AWG 300 kcmil 300 kcmil - 2.0 AWG
#2 AWG #2 - #6 AWG 3/0 AWG 3/0 - #1 AWG 350 kcmil 350 kcmil - 3/0 AWG
#1 AWG #1 - #2 AWG 4/0 AWG 4/0 - #1 AWG 400 kcmil 400 kcmil - 4/0 AWG
500 kcmil 500 kcmil - 4/0 AWG
600 kcmil 600 - 250 kcmil
750 kcmil 750 - 500 kcmil
* Use PUADP-1 adaptor with U dies in Y46 Hypress™.
** P44ART for use with Y46 HYPRESS™ only. PUADP-1
adapter not required.
+ Tested with Y644HS and PAT644 dieless tools only and
Dimensions Installation Tooling ▲
Dieless (# of crimps) Y35, Y39, Y750, Y46* ▲ Wire
Catalog Code Stud No. of T Z Mechanical Hydraulic Die Number Color Die Strip
Number Conductor Size Holes in Pad C D L N REF. Min. Tooling HYPRESS™ (# of crimps) Code Index Length
YA4 CA1 1/4 .47 .75 2.13 .33 .18 .42 Y81KFT (1)
YA4 CA3 5/16 .80 .87 2.25 .41 .12 .46 MY29-3 (1)
Y81KFTMBH (1)
4 str. 1
MRC840AL (1)
PAT81KFT-18V (1)
U4CABT (1) Green 375 7/8
YA4 CA6 3/8 .80 .94 2.32 .44 .12 .50
Y644HS (1)
YA2 CA5 1/4 .50 .91 2.25 .32 .22 .43
YA2 CA1 2 str. 5/16 1 .88 1.03 2.50 .41 .16 .47 U2CABT (1) Pink 348 1-1/8
YA2 CA3 3/8 .88 1.03 2.56 .44 .16 .50
YA1 CA1 1 str. 3/8 1 .76 1.19 2.59 .44 .19 .75
MY29-3 (1)
U1CART (1) Gold 471 15/16
YA25A1 5/16 .60 .87 2.31 .41 .21 .46
MRC840AL (1)
YA25A3 1/0 str. 3/8 1 .82 1.18 2.67 .63 .21 .55 U25ART (1) Tan 296 1-1/16
YA25A9 1/2 1.03 1.34 2.67 .63 .17 .71 Y81KFT (2)
YA26A6 3/8 .67 1.18 2.79 .44 .24 .74
Y81KFTMBH (2)
YA26A1
2/0 str.
1/2
1
1.03 1.36 3.03 .63 .20 .73 Y644HS (1)
U26ART (2) Olive 297 1-3/8
YA27A1 3/8 .73 1.18 2.88 .44 .26 .74 MY29-3 (2)
PAT81KFT-18V (2)
YA27A3
3/0 str.
1/2
1
1.04 1.37 3.27 .63 .26 .74
MRC840AL (2)
U27ART (2) Ruby 467 1-1/2
YA28A1 3/8 1.17 1.18 3.26 .44 .30 .74
YA28A3
4/0 str.
1/2
1
1.17
1.36 3.44 .63 .30 .73
U28ART (2) White 298 1-5/8
YA29A1 250 kcmil 1/2 1 1.26 1.36 3.53 .63 .33 .73 U29ART (2) Red 324 1-5/8
YA30A6 3/8 1.38 1.37 3.90 .63 .36 .74 —
YA30A1
300 kcmil
1/2
1
1.38 1.37 3.90 .63 .36 .74
U30ART (2) Blue 470 1-3/4
Y644HS (1)
Y81KFT (3)
YA31A1 350 kcmil 1/2 1 1.52 1.37 4.33 .63 .39 .74 —
Y81KFTMBH (3)
U31ART (2) Brown 299 2-1/8
PAT81KFT-18V (3)
YA32A1 400 kcmil 5/8 1 1.62 1.88 4.92 .88 .43 1.00 U32ART (4) Green 472 2-1/2
YA34A1 500 kcmil 5/8 1 1.80 1.91 5.56 .88 .46 1.03
Y644HS (1)
U34ART (4) Pink 300 2-5/8
YA36A1 600 kcmil 5/8 1 1.97 1.88 5.82 .88 .52 1.00 —
Y81KFT (4)
U36ART (4) Black 473 2-7/8
YA39A1 700/750 kcmil 1/2 2.05 1.34 5.26 .63 .43 .71
Y81KFTMBH (4)
YA39A3
900 Compact AL +
5/8
1
2.05 1.88 5.80 .88 .43 1.00
PAT81KFT-18V (4)
U39ART-2 (4) Yellow 936 2-7/8
YA44A1 1000 kcmil 5/8 1 2.50 1.89 6.50 .88 .43 1.01 — P44ART** (4) Brown 302 3
not UL Listed with any tool on 900 Compact Al.
◆ For applications greater than 2000 Volts consult cable
manufacturer for voltage stress relief instructions.
Note: All dimensions shown are for reference only.
UL Listed 90° C,
600 Volts to 35 kV◆
C-115
BURNDY
®
Compression Connections
Aluminum Compression — Tin Plated — For Aluminum & Copper Conductors