not UL Listed with any tool on 900 Compact Al.
◆ For applications greater than 2000 Volts consult cable
manufacturer for voltage stress relief instructions.
Note: All dimensions shown are for reference only.
• Contact BURNDY®or conductor, stud sizes and hole
drillings not shown.
▲ See tooling section of this catalog for complete tool and
die listings.
‡ Use Y60 BHU HYPRESS™ with L46ART and L48ART die
sets.
90° C Rated.
TYPE YA-A
HYLUG™
UNINSULATED ALUMINUM
COMPRESSION TERMINAL
FOR ALUMINUM AND
COPPER CONDUCTORS
2-HOLE AND 4-HOLE
DESIGNS
UL Listed 90° C,
600 V
olts to 35 kV◆
Type YA-A 2- and 4-hole pads inhibit connector rotation
and increase area contact. These aluminum terminals have
the same design features and benefits as the 1-hole YA-A
DIE AND CRIMP
INFORMATION
COLOR CODED
END CAP
(2) HOLE
DRILLING
CLOSED
BARREL
ELECTRO-TIN
PLATED
BEVELED
ENTRY
CRIMPS
CABLE
ACCOMIDATION
* Use PUADP-1 adaptor with U dies in Y46 HYPRESS™.
** P39ART and P44ART die sets for use with Y46
HYPRESS™ only. PUADP-1 adapter not required.
+ Tested with Y644HS and PAT644 dieless tools only and
Y644HS DIELESS HYPRESS™
RANGE-TAKING
CAPABILITIES
The following size HYDENT™ lugs and two
way splices, when crimped with the Y644HS
DIELESS HYPRESS™ tool, produce the
following range taking capabilities:
Aluminum Connectors
Standard Expanded Standard Expanded Standard Expanded
Wire Size Wire Range Wire Size Wire Range Wire Size Wire Range
#6 AWG #6 AWG 1/0 AWG 1/0 - #1 AWG 250 kcmil 250 kcmil - 1/0 AWG
#4 AWG #4 - #6 AWG 2/0 AWG 2/0 - #1 AWG 300 kcmil 300 kcmil - 2.0 AWG
#2 AWG #2 - #6 AWG 3/0 AWG 3/0 - #1 AWG 350 kcmil 350 kcmil - 3/0 AWG
#1 AWG #1 - #2 AWG 4/0 AWG 4/0 - #1 AWG 400 kcmil 400 kcmil - 4/0 AWG
500 kcmil 500 kcmil - 4/0 AWG
600 kcmil 600 - 250 kcmil
750 kcmil 750 - 500 kcmil
●
Dimensions Installation Tooling ▲
●
No. of E Dieless (# of crimps) Y35, Y39, Y750, Y46* ▲ Wire
Catalog Code Stud Holes & T Z Mechanical Hydraulic Die Number Color Die Strip
Number Conductor Size in Pad C D F L N REF. Min. Tooling HYPRESS (# of crimps) Code Index Length
Y644HS (1)
Y81KFT (1)
YA2 CA9 2 str. 1/2 2-NEMA .88 3.11 1.75 4.73 .63 .16 .73
MY29-3 (1)
Y81KFTMBH (1)
U2CABT (1) Pink 348 1-1/8
PAT81KFT-18V (1
)
Y644HS (1)
YA25A5 3/8 2 .82 2.24 1.06 3.73 .63 .21 .55
Y81KFT (2)
1/0 str
.
MY29-3 (1)
Y81KFTMBH (2)
U25ART (1) Tan 296 1-1/16
YA25A7 1/2 2-NEMA 1.03 3.10 1.75 4.59 .63 .17 .72
PAT81KFT-18V (2
)
YA26A3 1/2 2-NEMA 1.03 3.11 1.75 4.78 .63 .20 .73
YA26A5
2/0 str.
3/8 2 .92 1.89 1.00 3.56 .44 .24 .45
U26ART (2) Olive 297 1-3/8
YA27A5 1/2 2-NEMA 1.04 3.12 1.75 5.02 .63 .26 .74
YA27A7
3/0 str.
3/8 2 1.04 1.89 1.00 3.79 .44 .26 .45
MY29-3 (2)
Y644HS (1)
U27ART (2) Ruby 467 1-1/2
YA28A5 1/2 2-NEMA 1.17 3.11 1.75 5.19 .63 .30 .73 Y81KFT (2)
YA28A7
4/0 str.
3/8 2 1.17 1.89 1.00 3.97 .44 .30 .45
Y81KFTMBH (2)
U28ART (2) White 298 1-5/8
YA29A3 1/2 2-NEMA 1.26 3.11 1.75 5.28 .63 .33 .73
PAT81KFT-18V (2
)
YA29A5
250 kcmil
3/8
2 1.26 1.89 1.00 4.06 .44 .33 .45
U29ART (2) Red 324 1-5/8
YA30A3 1/2 2-NEMA 1.38 3.11 1.75 5.69 .63 .36 .73
MY29-3 (2)
Y
A30A5
300 kcmil
3/8 2 1.38 1.89 1.00 5.64 .44 .36 .45
U30ART (2) Blue 470 1-3/4
YA31A5 3/8 2 1.52 1.89 1.00 4.85 .44 .39 .45 Y644HS (1)
YA31A3 350 kcmil 1/2 2-NEMA 1.52 3.11 1.75 6.07 .63 .39 .73 Y81KFT (3)
U31AR
T (2) Brown 299 2-1/8
Y81KFTMBH (3)
YA32A5 400 kcmil 3/8 2 1.62 1.89 1.00 4.93 .44 .43 .94
PAT81KFT-18V (3
)
U32ART (4) Green 472 2
YA34A3 1/2 2-NEMA 1.62 3.15 1.75 6.80 .63 .46 .77
Y
A34A5
500 kcmil
3/8 2 1.80 1.89 1.00 5.54 .44 .46 .45
U34ART (4) Pink 300 2-5/8
YA36A3 1/2 2-NEMA 1.62 3.15 1.75 7.09 .63 .52 .77
Y644HS (1)
YA36A5
600 kcmil
3/8 2 1.97 1.89 1.00 5.83 .44 .52 .45
Y81KFT (4) U36ART (4) Black 473 2-7/8
YA39A7 3/8 2 2.05 1.89 1.00 5.81 .44 .43 .45
Y81KFTMBH (4)
YA39A5
700/750 kcmil
1/2
2-NEMA 1.62 3.15 1.75 7.07 .63 .43 .77
PAT81KFT-18V (4)U39ART-2 (4) Yellow 936 2-7/8
YA39AM2
900 Compact AL +
1/2 2-NEMA 1.69 3.12 1.75 7.31 .63 .57 .74 P39ART** (4) Red 301 2-7/8
YA44A3 1000 kcmil 1/2 2-NEMA 1.65 3.15 1.75 7.76 .63 .66 .77 P44ART** (4) Brown 302 3
YA45A5 1250 kcmil 1/2 2-NEMA 1.65 3.15 1.75 7.76 .63 .66 .77 P44ART** (4) Brown 302 3
YA46A3 1500 kcmil 1/2 2-NEMA 3.09 3.16 1.75 8.75 .63 .81 .78 — —
YA46A5 1500 kcmil 1/2 4-NEMA 3.09 3.16 1.75 8.75 .63 .81 .78
L46ART (2) Red 478 2-3/4
YA48A3 2000 kcmil 1/2 2-NEMA 3.57 3.11 1.75 8.49 .63 .90 .73 L48ART (2) Red 479 4-1/8
with an added stud hole for a more secure termination to
various types of equipment pads. They are dual-rated for
use on both aluminum and copper conductors.
C-116
Compression Connections BURNDY
®
Aluminum Compression — Tin Plated — For Aluminum & Copper Conductors