Bürkert Type 6013 Operating Instructions

Bedienungsanleitung Manuel d‘utilisation
Operating Instructions
Type 6013
Magnetventil
2/2-Way Solenoid Valve 2/2-Wege Magnetventil Électrovanne à 2/2 voies
Address / Adresse
Germany / Deutschland / Allemagne
Bürkert Fluid Control Systems Sales Center Christian-Bürkert-Str. 13-17 D-74653 Ingelfingen Tel. + 49 (0) 7940 - 10 91 111 Fax + 49 (0) 7940 - 10 91 448 E-mail: info@de.buerkert.com
International
www.burkert.com Bürkert Company Locations
Manuals and data sheets on the Internet: www.burkert.com Bedienungsanleitungen und Datenblätter im Internet: www.buerkert.de Manuel d'utilisation et fiches techniques sur Internet : www.buerkert.fr
2
2 INTENDED USE
Incorrect use of the solenoid valve Type 6013 can be dangerous to people, nearby equipment and the environment.
▶ The device is designed for blocking, dosing, filling and venting neutral
gaseous and liquid media.
▶ In the potentially explosion-risk area the device may be used only
according to the specification on the separate Ex type label. For use observe the additional information enclosed with the device together with safety instructions for the explosion-risk area.
▶ Devices without a separate Ex type label may not be used in a poten-
tially explosive area.
▶ Use according to the permitted data, operating conditions and
conditions of use specified in the contract documents and operat­ing instructions.
▶ The device may be used only in conjunction with third-party devices
and components recommended and authorised by Bürkert.
▶ Correct transportation, correct storage and installation and careful
use and maintenance are essential for reliable and problem-free operation.
▶ Use the device only as intended.
1 OPERATING INSTRUCTIONS
The operating instructions contain important information.
▶ Read the instructions carefully and follow the safety instructions in
particular, and also observe the operating conditions. ▶ Instructions must be available to each user. ▶ The liability and warranty for Type 6013 are void if the operating
instructions are not followed.
1.1 Symbols
▶ Designates an instruction to prevent risks.
→ designates a procedure which you must carry out.
Warning of injuries:
DANGER!
Imminent danger! Serious or fatal injuries.
WARNING!
Potential danger! Serious or fatal injuries.
CAUTION!
Danger! Minor or moderately severe injuries.
Warns of damage to property:
NOTE!
english
3
2.1 Restrictions
If exporting the system/device, observe any existing restrictions.
2.2 Definition of term
In these operating instructions, the term “device” always refers to the solenoid valve Type 6013.
3 BASIC SAFETY INSTRUCTIONS
These safety instructions do not make allowance for any contin­gencies and events which may arise during installation, operation and maintenance.
Danger – high pressure!
▶ Before loosening the lines and valves, turn off the pressure and
vent the lines.
Risk of electric shock!
▶ Before reaching into the system, switch off the power supply and
secure to prevent reactivation!
▶ Observe applicable accident prevention and safety regulations for
electrical equipment!
Risk of burns/risk of fire!
During continuous operation the surface of the device may become hot.
▶ Keep the device away from highly flammable substances and media
and do not touch the device with bare hands.
▶ Do not obstruct the heat release required for operation.
english
© Bürker t Werke GmbH & Co. KG, 201 - 2017 Operating Instructions 1706/_(8(1_008 / Original DE
4
Destruction of the coil by overheating!
▶ Connect the coil electrically only when the housing has been installed.
In the case of AC voltage pay attention to movable core.
To prevent injury, ensure that:
▶ Do not supply the medium connectors of the system with aggressive
or flammable mediums.
▶ Do not make any external modifications to the device bodies. Ensure
that the system cannot be activated unintentionally.
▶ Installation and repair work may be carried out by authorized techni-
cians only and with the appropriate tools.
▶ After an interruption in the power supply or pneumatic supply, ensure
that the process is restarted in a defined or controlled manner.
▶ Do not put any loads on the body. ▶ Observe the general regulations of technology.
4 TECHNICAL DATA
4.1 Conformity
In accordance with the EC Declaration of conformity, the solenoid valve Type 6013 is compliant with the EC Directives (if applicable).
4.2 Standards
The applied standards, which verify conformity with the EC Directives, can be found on the EC-Type Examination Certificate and / or the EC Declaration of Conformity (if applicable).
4.3 Operating conditions
WARNING!
Heat sources and temperature fluctuations may cause malfunc­tions or leaks!
▶ If the device is used outdoors, do not expose it unprotected to the
weather conditions.
▶ Avoid heat sources which may cause the allowable temperature
range to be exceeded.
english
5
Medium temperature:
Operating principles
Sealing material Medium temperature
CFA FKM -10 ... +100 °C (PA Coil)
-10 ... +120 °C (Epoxide Coil)
PTFE/Graphite -10 ... +180 °C
CFB FKM -10 ... +100 °C (AC)
-10 ... +120 °C (DC)
Ambient temperature: -10 ... +55 °C Viscosity: 21 mm/s Protection class: IP65 in accordance with EN 60529 with
cable plug
Media: neutral gaseous and liquid media, which do not attack
body and sealing materials (see table of resistance under
www.burkert.com)
Check resistance in individual cases
4.4 Fluidic data
Operating principle
A
(NC)
1 (P)
2 (A)
2/2-way valve, normally closed
B
(NO)
1 (P)
2 (B)
2/2-way valve, normally open
Pressure range: see type label Line connectors: Type 6013: G1/8, G1/4, G3/8, Flange
Type 6013A: G1/8, G1/4
Note the information specified on the type label for voltage, type of current, and pressure.
english
6
4.5 Type label (example)
Ident. no.
Voltage, Frequency, Output
if applicable
Nominal connection pressure
Type
Circuit function
Orifice
Sealing material
Body material
6013 A 2,0 FKM MS
Made in Germany
00450000
WXXXX
24V 50Hz 7W
G1/8 PN 0
-
10 bar
4.6 Electrical data
Connections: DIN EN 175301-803 Form A
for cable plug Type 2508
Supply voltage: Type 6013: 24 V DC ± 10 %
max. residual ripple 10 % 24 V / 50 Hz 230 V / 50 Hz
Type 6013A: 24 V DC ± 10 %
max. residual ripple 10 %
230 V / 50 Hz Voltage tolerance: ± 10 % Nominal output: CFA: 8 W (5 W, 10 W)
CFB AC: 7 W (9 W)
DC: 8 W
Impulse version DC: 7 W Nominal operating mode: 100 % continuous operation
for block installation: 5 W continuous operation on request a. A. 8 W intermittent operation 60 % (30 min)
english
Type 6013