Operating Instructions Type 0211/0212
Voltage 12V or 24V
UL / UR valid with
class 2 power supply only
Design:
2-way solenoid valve, direct acting, normally closed (Circuit
function A) or normally open (Circuit function B).
Seal Materials and Fluids handled:
See Table.
Fluid and Ambient Temperature:
For Hazardous Locations Div. 1 (T4 rated)
Max. Ambient Temperature 104 °F (40 °C)
Max. Fluid Temperature 194 °F (90 °C)
The UL-listed valve for Hazardous Locations is suitable for
the fluids air, inert gas, water and gasoline.
For Hazardous Locations Div. 1 (T6 rated)
Max. Ambient Temperature 104 °F (40 °C)
Max. Fluid Temperature 140 °F (60 °C)
For Hazardous Locations Div. 2 and Ordinary Locations:
See Table.
Pressure Range:
Maximum inlet pressure see label on valve.
Installation:
Before installing valve ensure that piping etc. is free of foreign
matter (metal fillings, seal materials, welding scale etc.). Installation as required but preferably with coil uppermost. Installation in this position tends to prevent foreign matter remaining
in core tube (increased life). Do not put any loads on coil unit.
Type 0211: PTFE tape is recommended for sealing ports. Arrow
on val ve body indicates fl ow direction. Mounting is accompl ished
by means of four M4 x 8 mm tapped holes located on the valve
underside.
Type 0212: Outlet port is coded on side of body. For common
pressure, align "A" marking on valve and manifold. To remove
valve from manifold loosen only the two unsealed screws.
Manifolds can be connected togehter with nipples.
Approvals
The valve is either approved as
General Purpose valve for Hazardous Locations
Class I, Division 1, Group A, B, C, D
Class II, Division 1, Group E, F, G
Class III, Division 1 and 2
Operating Temperature T 4
or
General Purpose valve for Hazardous Locations
Class I, Division 1, Group A, B, C, D
Class II, Division 1, Group E, F, G
Class III, Division 1 and 2
Operating Temperature T 6
or
FM approved as
Nonincendive for Hazardous Locations
Class I, Division 2, Group A, B, C, D
Class II, Division 2, Group F, G
Class III, Division 1 and 2
Operating Temperature T 4
UL listed for Ordinary locations
CSA approved for Ordinary locations
See label on the valve.
Marking (example):
Circuit function
A = Nor mally Closed
B = Normally Open
Seal Material
EPDM = EPDM
NBR = NBR
FKM = FKM
EA = PTFE seat and EPDM O-r ing
EF = PTFE seat and FKM O-ring
NN = Neoprene
Seal Materials Seat / O-ring
Fluid
Air
Water
Neutral Gas
Light oil
LP-gas
Operating Instructions 0605/08_EU-EN_00893132
Refrigerants
Temperatures [°F]
Fluid T.
Ambient
Fluid T.
Ambient
Fluid T.
Ambient
Fluid T.
Ambient
Fluid T.
Ambient
Fluid T.
Ambient
Buna „N‰ Ethylene
+14 to +194
+14 to +130
+32 to +194
+32 to +130
+14 to +194
+14 to +130
+14 to +194
+14 to +130
+14 to +140
+14 to +130
Propylene
-40 to +266
+14 to +130
+32 to +212
+32 to +130
-40 to +266
+14 to +130
FKM
+14 to +266
+14 to +130
+32 to +212
+32 to +130
+14 to +266
+14 to +130
+14 to +266
+14 to +130
+14 to +140
+14 to +130
Body Material
BR = Brass
SS = Stainless Steel
NI = Nickel Plated Brass
PL = Polyamide Plastic
Maximum Pressure
Voltage / Frequency / Power Consumption
Recorder No.
PTFE/
Ethylene
Propyl.
+14 to +266
+14 to +130
+32 to +212
+32 to +130
+14 to +266
+14 to +130
PTFE/
FKM
+14 to +266
+14 to +130
+32 to +212
+32 to +130
+14 to +266
+14 to +130
+14 to +266
+14 to +130
+14 to +140
+14 to +130
Neoprene
+14 to +194
+14 to +130
Operating Instructions
Bürkert Company Locations
Wiring Diagram
Electrical Connection Type 2509
Power*
Ground (green dot)
Power*
* Orientation is not important
Electrical Connection:
Ensure supply voltage/frequency corresponds with that on label.
Voltage tolerance is ± 10 %.
Available Electrical Connections see “Marking”.
Wiring diagram see above.
For this product to be considered UL-listed and CSA approved
for General Purpose and FM approved for Hazardous Locations
Division 2, it must be in conjunction with the type 2509 cable plug
connector (Electrically Operated Valves Parts, YSYI2).
The connector and gasket must be assembled to the valve with the
screw provided after the connection of the wire leads. This valve
and connector assembly is delivered together and is to be used as
one unit.
For valves to be used in Intrinsically Safe Applications the positive
pole is identified by a “+” on the pin or wire No. 1 has to be connected to the “+”.
See Control Drawing for the Rules of Interconnection.
Warning:
All valves to be used in Intrinsically Safe Applications must be
clearly marked as Intrinsically Safe Apparatus.
Trouble-Shooting:
Check port connections, minimum operating pressure differential
if required and supply voltage. Ensure pilot hole in piston is clear
and pilot bore in the valve outlet is not abstracted. If core does not
pull in, check for short circuit, coil burn-out or foreign matter impeding core movement. A jammed or missing core causes the coil
to overheat in the case of AC supply.
Warning:
These products are designed to operate in a wide variety of applications, it is the user’s responsibility to select a model that is
appropriate for the application. This product is designed to be
installed only by suitably qualified and trained personnel.
Specifications should not be exceeded under any circumstances.
The torque for the terminal screw on type 2509 is 0,5 Nm
(4,4 lbf-in.).
Germany
Contact address:
Bürkert Fluid Control Systems
Sales Center
Chr.-Bürkert-Str. 13-17
D-74653 Ingelfingen
Tel. + 49 (0) 7940 - 10 91 111
Fax + 49 (0) 7940 - 10 91 448
E-mail: info@de.buerkert.com
International
Contact addresses can be found on the Internet at:
Changes made to this product will render any applicable warranty
null and avoid.
Specifications subject to change without notice.
Any questions? Please call Bürkert Contromatic Technical Service
at (949) 223 31 00.
www.burkert.com