Read this instruction carefully prior to installation and/or use. Pay attention particularly to all advises and safety instructions to prevent injuries. Bühler Technologies can not be held responsible for misusing
the product or unreliable function due to unauthorised modifications.
All rights reserved. Bühler Technologies GmbH 2019
1.1Intended use .........................................................................................................................................................................................................3
1.4Scope of delivery.................................................................................................................................................................................................. 4
1.5.1Gas cooler models with one heat exchanger ...............................................................................................................................5
1.5.2Gas cooler models with two heat exchangers ............................................................................................................................ 6
1.5.3Gas cooler model with two heat exchangers in series ..............................................................................................................7
3 Transport and storage .................................................................................................................................................................................................11
4 Installation and connection.......................................................................................................................................................................................12
4.1Installation site requirements....................................................................................................................................................................... 12
4.2.1Connecting the filter gas connections (optional) ..................................................................................................................... 12
4.2.3Connecting the moisture detector (option)................................................................................................................................12
4.2.5Connecting the heat exchanger .....................................................................................................................................................13
5 Operation and control .................................................................................................................................................................................................17
5.1Description of functions...................................................................................................................................................................................17
5.2Delta T control option .......................................................................................................................................................................................17
5.3Use of menu functions .................................................................................................................................................................................... 18
5.4Description of menu functions ..................................................................................................................................................................... 21
5.4.1Main menu ...........................................................................................................................................................................................21
5.4.4Set favourite menu ............................................................................................................................................................................25
7 Service and repair......................................................................................................................................................................................................... 27
7.1.1Error messages on the display....................................................................................................................................................... 28
7.3Cleaning and removal of the heat exchanger...........................................................................................................................................30
7.4Replacing the hoses of the peristaltic pump (option) ............................................................................................................................30
7.5Replacing the filter element (option)..........................................................................................................................................................30
7.6Drying of the moisture detector (option)....................................................................................................................................................31
7.7Calibration of the moisture detector (option)...........................................................................................................................................31
7.8Spare parts and accessories ............................................................................................................................................................................31
7.8.1Consumables and accessories ........................................................................................................................................................32
9.1Gas cooler technical data ................................................................................................................................................................................34
9.2Technical Data - Options .................................................................................................................................................................................35
This unit is intended for industrial use in gas analysis systems. It's an essential component for conditioning the sample gas to
protect the analysis instrument from residual moisture in the sample gas.
This device may be operated in a zone 2, explosion class IIC (ATEX & IECEx), explosive gas atmosphere which is rarely and only
temporarily explosive and in Class I, Division 2 (US & Canada).
Optional mounting of various add-on units may limit the area of application of this device.
Cooler with certificate Canada and IECEx
The equipment shall be mounted within a tool-secured IP54 enclosure.
Cooler with certificate USA
The equipment shall be mounted within a tool-secured IP54 enclosure which is capable of accepting one or more of the
ClassIDivision2 wiring methods per the National Electric Code (ANSI/NFPA70).
Cooler with certificate ATEX
The equipment shall be mounted within a IP54 enclosure in accordance with EN60079-15, and in a tool-secured enclosure which
meets the requirements of EN60079-0 and EN60079-15.
Please note the specifications in the data sheet on the specific intended use, existing material combinations, as well as pressure
and temperature limits.
1.2 Overview
The TC-StandardX2 series was designed specifically for high cooling capacities and high ambient temperatures.
The TC-Standard+X2 series was designed specifically for the requirements in so-called automated measuring systems(AMS) according to EN15267-3. The series connection of the heat exchangers will cool in two cycles to minimise wash out effects.
The Peltier cooler is distinguished by two types according to cooling capacity or operation temperature. This classification is reflected in the type designation. The exact item number of the model defined by you is determined by the model code in the category ordering information.
2 heat exchangers in seriesTC-Standard+ 6121 X2TC-Standard+ 6122 X23rd digit=2
4th digit=14th digit=2
Additional components which every conditioning system should feature can optionally be integrated:
– Peristaltic pump for condensate separation,
– Filter,
– Moisture detector.
This allows for various configurations of cooler and options. Here the approach is to simplify creating a complete system in a
cost-efficient way through pre-installed components with hoses connected. We further paid attention to easy access to wear
parts and consumables.
3Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
Manufacturer and address
Type designation and voltage
Serial no., Item no.
Blast protection markings
(Atex, IECex and US/Canada)
Description
Year of manufacture
TC-Standard 230 V, 50/60Hz, 130W
101001081115 449621112412510011010
FM18ATEX0012X II 3 G Ex ec nC IIC T4 Gc
IECEx FMG 18.0005X Ex ec nC IIC T4 Gc
USA/Canada: CL I DIV 2 GP ABCD
Tamb: 0°C to 50°C
Year: 2018 Manual doc.no.: BX440023
1.3 Type plate
Example:
1.4 Scope of delivery
– Cooler
– Product documentation
– Connection-/mounting accessories (optional)
4Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
1.5 Ordering instructions
1.5.1 Gas cooler models with one heat exchanger
The item number is a code for the configuration of your unit. Please use the following model code:
44962 11 X 2 X 1 X X X 0 X X X 0 X 0 Product characteristic
Gas cooler models (with 1 heat exchanger)
1TC-Standard 6111 X2: Ambient temperature 40 °C
2TC-Standard 6112 X2: Ambient temperature 50 °C
0 0without peristaltic pump
2 0CPdouble X2 with hose nipple, angled
4 0CPdouble X2 with screw connection
Moisture detector / filter
0 0without filter, without moisture detector
0 1without filter, 1 moisture detector with adapter
1 01 filter, without moisture detector
111 filter with built-in moisture detector
Status outputs
0 0status output only
1 0Analog output option, add-on
*
* 24 V DC version not available
7Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
DANGER
WARNING
CAUTION
NOTICE
2 Safety instructions
2.1 Important notices
NOTICE
The device is suitable for hazardous areas.
This unit may only be used if:
– The product is being used under the conditions described in the operating- and installation instructions, used according to
the nameplate and for applications for which it is intended. Any unauthorized modifications to the unit will void the warranty provided by Bühler Technologies GmbH,
– The specifications and markings in the type plate must be observed,
– The threshold values in the data sheet and the instructions must be observed,
– Monitoring equipment / protection devices must be connected correctly,
– Service and repair work not described in these instructions are performed by Bühler Technologies GmbH,
– Genuine replacement parts must be used.
Erecting electrical systems in explosive areas requires compliance with the following national regulations:
– IEC/EN60079-14
– National electric code (NEC)
– Canadian electric code (CEC)
Additional national regulations pertaining to initial operation, operation, maintenance, repairs and disposal must be observed.
These operating instructions are a part of the equipment. The manufacturer reserves the right to change performance-, specification- or technical data without prior notice. Please keep these instructions for future reference.
Signal words for warnings
Signal word for an imminent danger with high risk, resulting in severe injuries or death if not avoided.
Signal word for a hazardous situation with medium risk, possibly resulting in severe injuries or death if not
avoided.
Signal word for a hazardous situation with low risk, resulting in damaged to the device or the property or
minor or medium injuries if not avoided.
Signal word for important information to the product.
8Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
Warning signs
These instructions use the following warning signs:
Warns of a general hazardGeneral notice
Warns of voltageUnplug from mains
Warns not to inhale toxic gassesWear respiratory equipment
Warns of corrosive liquidsWear a safety mask
Warns of explosive areasWear gloves
Warns of hot surfaces
2.2 General hazard warnings
The equipment must be installed by a professional familiar with the safety requirements and risks.
Be sure to observe the safety regulations and generally applicable rules of technology relevant for the installation site. Prevent
malfunctions and avoid personal injuries and property damage.
The operator of the system must ensure:
– Safety notices and operating instructions are available and observed,
– The respective national accident prevention regulations are observed,
– The permissible data and operational conditions are maintained,
– Safety guards are used and mandatory maintenance is performed,
– Legal regulations are observed during disposal.
Maintenance, Repair
Please note during maintenance and repairs:
– Repairs to the unit must be performed by Bühler authorised personnel.
– Only perform conversion-, maintenance or installation work described in these operating and installation instructions.
– Always use genuine spare parts.
Always observe the applicable safety and operating regulations in the respective country of use when performing any type of
maintenance.
DANGERElectrical voltage
Electrocution hazard.
a) Disconnect the device from power supply.
b) Make sure that the equipment cannot be reconnected to mains unintentionally.
c) The device must be opened by trained staff only.
d) Regard correct mains voltage.
9Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
DANGERToxic, corrosive gas/condensate
Sample gas/condensate may be hazardous to health.
a) If necessary, ensure a safe gas/condensate discharge.
b) Always disconnect the gas supply when performing maintenance or repairs.
c) Protect yourself from toxic/corrosive gasses/condensate when performing mainten-
ance. Wear appropriate protective equipment.
DANGERExplosion hazard
Life and explosion risk may result from gas leakage due to improper use.
a) Use the devices only as described in this manual.
b) Regard the process conditions.
c) Check tubes and hoses for leakage.
WARNINGRisk of breakage
a) Protect the equipment against being hit.
b) Protect the device against falling objects.
10 Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
3 Transport and storage
Only transport the product inside the original packaging or a suitable alternative.
The equipment must be protected from moisture and heat when not in use. It must be stored in a covered, dry and dust-free
room at a temperature of -20 °C to 60 °C (-4 °F to 140 °F).
11Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
4 Installation and connection
4.1 Installation site requirements
The unit is only intended for wall-mounted use in enclosed areas. Adequate protection from the weather must be provided
when used outdoors.
Install the unit leaving enough room below the cooler to discharge the condensate. Leave room above for the gas supply.
Be sure to maintain the approved ambient temperature. Do not obstruct the convection of the cooler. The vents must have
enough room to the next obstacle. The distance must especially be a minimum of 10 cm on the air outlet side.
Ensure adequate ventilation when installing in enclosed housings, e.g. analyser cabinets. If the convection is inadequate, we recommend aerating the cabinet or installing a fan to lower the inside temperature.
4.2 Installation
Run the gas supply to the cooler with a downward slope. The gas inputs are marked in red and additionally labelled "IN".
If a large amount of condensate accumulates, we recommend using a condensate trap with automatic condensate drain. Our
condensate drains, 11LDV38, AK20, AK5.5 OR AK5.2, are suitable.
Glass vessels and automatic condensate drains are available for draining condensate for external mounting below the unit.
When using automatic condensate drains, the sample gas pump must be installed upstream of the cooler (pressure operation)
to ensure proper function of the condensate drain.
If the sample gas pump is located at the cooler outlet (suction operation), we recommend using glass condensate traps or peristaltic pumps.
Connecting the condensate drain
Depending on the material, build a connecting line with fittings and tubing or hose between the heat exchanger and condensate drain. For stainless steel the condensate drain can be hung directly from the connecting tube, for hoses the condensate drain
must be secured separately using a clamp.
The condensate drain can be mounted directly to the heat exchanger.
Condensate lines must always be installed with a slope and a minimum inside diameter of 6 mm (1/4").
The MTG heat exchanger (in coolers with 2 heat exchangers) can only be operated with peristaltic pumps.
4.2.1 Connecting the filter gas connections (optional)
The connection between the heat exchanger outlet and the filter inlet already has tubing. The connection G1/4 or NPT 1/4" (filter
head marked NPT) for the gas outlet must be carefully and properly connected using a suitable screw connection.
When ordering the cooler with the
The filter head is intended for a G1/4 internal screw thread which is plugged at the factory. To use it, unscrew the plug and screw
in a suitable screw connection. Pay attention to leaks.
NOTICE
Installing
Operating pressure ≤ 2 bar
option filter without Moisture detector
filters
limits the maximum approved
, a bypass may be connected to the filter head.
operating pressure
in the system!
4.2.2 Flow adapter connection (optional)
When ordering the cooler with the
The connection between the heat exchanger outlet and the flow adapter inlet does not have tubing included. The connection
G1/4 or NPT1/4" (flow adapter marked NPT) for the gas inlet/outlet must be carefully and properly connected using a suitable
screw connection. Here the direction of flow is not relevant.
option moisture detector without filter
, it will be factory installed inside a flow adapter.
4.2.3 Connecting the moisture detector (option)
When ordering the cooler with
installed and connected in the filter head.
12 Bühler Technologies GmbHBE440023 ◦ 10/2018
moisture detector option
, it will be factory installed inside a flow adapter, or for the
filter option
TC-Standard (+) X2
gas out
gas in
gas out
gas in
condensate out
condensate out
Heat exchanger 1
Heat exchanger 2
Gas cooler
(two single heat exchangers)
gas out
gas in
gas out
gas in
condensate out
condensate out
Heat exchanger 1
Heat exchanger 2
Gas cooler +
(two heat exchangers in series)
4.2.4 Peristaltic pump connector (optional)
Coolers ordered with attached peristaltic pump already have it installed and wired. Heat exchangers ordered at the same time
are already installed and connected to the peristaltic pump.
The ø6mm (0.24inch) hose nipple for the pump’s condensate outlet must be carefully and properly connected with a suitable
hose and hose clamp.
Versions with screw connections DN4/6 or 1/6”-1/4” are supplied with ferrule and knurled nut and must be carefully sealed
with appropriate hose.
NOTICE
Installing peristaltic
ating pressure
Operating pressure ≤ 1 bar
pumps
in the system!
CPsingle / CPdouble limits the maximum permissible
oper-
4.2.5 Connecting the heat exchanger
The picture on the left shows the schematics for connecting two separate heat exchangers.
To minimise gas wash out in the cooler, the two (identical) heat exchangers must be operated in series (right picture). This
should be done as follows:
1.Gas inlet line to red gas inlet on heat exchanger 2 (pre-cooling).
2.Connection between gas outlet on heat exchanger 2 and the red gas inlet on heat exchanger 1 (after-cooling).
3.Attaching the final gas output line to the gas outlet on heat exchanger 1.
The gas inputs are marked in red.
On glass heat exchangers the correct position of the seal is important when connecting the gas lines (see image). The seal consists of a silicone ring with a PTFE sleeve. The PTFE side must face the glass thread.
13Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
Glass
PTFE
4.3 Electrical connections
The operator must install an external separator for the device which is clearly assigned to this device.
This separator
– must be located near the device,
– must be easy for the operator to reach,
– must comply with IEC 60947-1 and IEC 60947-3,
– must separate all live conductors and the status output, and
– must not be attached to the power feed.
The mains supply of the device must be fused according to the specifications under technical data.
Potential equalization/static charge
Static charges can result in incendive sparking. Avoid static charges. Any conductive parts of the cooler must be grounded!
The housing has a connection for an earth/equipotential bonding conductor. Ensure the housing is adequately earthed (minimum conductor cross-section 4 mm2).
Particularly observe the requirements of EN 60079-14!
WARNINGHazardous electrical voltage
The device must be installed by trained staff only.
CAUTIONWrong mains voltage
Wrong mains voltage may damage the device.
Regard the correct mains voltage as given on the type plate.
14 Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
Plug numbering
Electric supply S1
115/230 V (24 V DC)
Alarm contact S2 *
Analogue output S3
1 - N/C
2 - N/C
3 - GND
4 - 4-20 mA out
5 - shield
(+24 V)
(-24 V)
*
Connection via plug
The device is equipped with connectors according to EN 175301-803 for mains and status output. If the cables are mounted properly, they cannot be interchanged. Please make sure that the connectors are remounted correctly after connecting the cable. The
following figures show the pin assignment with respect to the numbers printed on the connector.
The supply line cross-sections must be suitable for the rated current. Use a maximum line cross-section of 1.5mm² (AWG16) and
a cable diameter of 8-10mm (0.31-0.39 inch).
* When using an alarm contact connect to ≥33VAC or ≥70VDC PE voltage.
The clamping area has a diameter of 8-10mm (0.31–0.39 inch).
4.4 Signal outputs
The device provides different status signals. The maximum switching load of the alarm outputs is limited to 250VAC/150VDC,
2A, 50VA each.
An alarm is triggered by the alarm contact/status output (S2) if the temperature of the cooler is outside the specified limits. It
does not indicate if the alarm was triggered due to excess temperature or insufficient temperature.
The LEDs OP and S2 indicate the device status similar to S2.
If the option “temperature signal” is built in, the unit has a signal output via the analogue output to indicate the actual cooler
temperature.
When the moisture detector (optional) is installed, an alarm is activated by the alarm contact/status output (S2) if the moisture
is still present in the prepared sample gas. Thereby, no distinction is made between the alarm/cable break triggered by moisture
detector 1 or 2. This information is displayed by an error message instead.
The temperature signal can be read via the panel plug (S3) using the M12x1 connector. This plug is located next to the moisture
detector connectors at the top of the cooler.
15Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
Description of signal outputs
Function / contact
type
Regarding S2) internal changeover
contact: max.
250VAC / 150VDC,
2A, 50VA
Regarding S3) 4-20mA analogue
output
(R
<500Ω)
Load
Description
the following device statuses can
be indicated via two switching
outputs:
Signalling of actual temperature
(please use shielded cables)
Contact between 3 and 2 closed (alarm)
– No mains voltage and/or actual temperature out-
side the alarm thresholds
Contact between 3 and 1 closed (ok)
– Mains voltage attached + actual temperature
within the alarm thresholds
With moisture detector option
Contact between 3 and 2 closed (alarm)
– The moisture detector registers residual humidity
in the sample gas or cable break: Error message
Contact between 1 and 3 closed (ok)
– no residual moisture in measuring gas / no cable
break
With temperature signal option
T
= -20°C ≙ (-4°F) -> 4mA/ 2 V
Cooler
T
= 5°C ≙ (41°F) -> 9mA/ 4,5 V
Cooler
T
= 60°C ≙ (140°F) -> 20mA/ 10 V
Cooler
16 Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
5 Operation and control
NOTICE
The device must not be operated beyond its specifications.
After switching on the cooler the block temperature will be displayed. The display will flash until the block temperature has
reached the preset target value (± adjustable alarm range). The status contact is in the Alarm position.
Once the target temperature range has been reached, the temperature will continuously be displayed and the status contact
switches over.
If the display flashes during operation or an error message appears, please refer to bullet “Troubleshooting”.
Please refer to the data sheet for performance data and maximum ratings.
5.1 Description of functions
The cooler is controlled by a microprocessor. With the factory preset the control already incorporates the various characteristics
of the built-in heat exchangers.
The programmable display shows the block temperature in the selected display unit (°C/°F) (factory preset °C). Application-specific settings can easily be configured guided by the menu, using the 5 buttons. For one, this applies to the target outlet dew
point, which can be set from 2 to 20°C (36°F to 68°F) (factory preset 5°C/41°F).
And then the warning thresholds can be adjusted for low and excess temperature. These are set relative to the outlet dew point
τa setting.
For the low temperature the range is τa -1 to - 3K (at a minimum 1°C/ 34°F cooling block temperature), for the excess temperature the range is τa +1 to +7K. The factory presets for both values are 3K.
The flashing display and the status relays indicate the conditions are below or above the configured warning range (e.g. after
switching on).
The status output can e.g. be used to control the sample gas pump to allow for the gas flow to only be switched on once the permissible cooling range has been reached or shut off the pump in the event of a moisture detector alarm.
The separated condensate can be drained via connected peristaltic pumps or add-on automatic condensate drains.
Fine mesh filters can also be used, which in turn can be installed in optional moisture detectors.
The glass dome allows the dirt level of the filter element to easily be determined.
The moisture detector is easy to remove. This may be required if a condensate enters the cooler due to a malfunction and the
peristaltic pump or the automatic condensate drain is unable to remove it.
5.2 Delta T control option
Not all applications require an outlet dew point of 5°C (41°F). In some applications a higher dew point is sufficient. In other applications a stable outlet dew point doesn’t matter, it’s enough for the gas to be dry, so if the outlet dew point has an adequate
difference in temperature below the ambient temperature.
Here the electronics measure the ambient temperature and regulate the outlet dew point to an adjustable value below it. This
extends the potential cooling capacity to the limits of the heat exchanger. Here it’s important to note the outlet dew point fluctuates along with the ambient temperature and a stable dew point cannot be a prerequisite for the measurement.
The target temperature range is defined by the ambient temperature, the adjustable temperature difference and the alarm limits. If the block temperature is not within the target range with active Delta T-control, the status message "dt" will flash in the
display.
Example:
to an ambient temperature of approx. 35°C (95°F), and the safe drop is only preferred over the ambient temperature with ambient temperature peaks over 35°C (95°F). The cooling capacity specified in the cooling capacity graphs at 35°C (95°F) is then
available at above 35°C (95°F).
At a difference of 30°C (30 K/54 °F), at a set outlet dew point of 5°C (41°F) this means the dew point remains stable up
17Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
OK
ESC
F
Func
5.3 Use of menu functions
Brief description of the operating principle:
The unit is operated using 5 keys. Their functions are:
ButtonSectionFunctions
Display– Switches from the measurement display to the main menu
or
or
Menu– Selects the menu item displayed
Enter– Applies an edited value or a selection
Display– temporarily switches to the alternative measurement display (if option installed)
Menu– Back
Enter– Increase value or browse selection
– Note:
– Press button 1 x = changes parameter / value by one;
– Hold button = fast mode (numerical values only)
– Display flashes: modified parameter/value
– Steady display: original display/value
Display– temporarily switches to the alternative measurement display (if option installed)
Menu– Next
Enter– Reduce value or browse selection
Menu– Move one level up
Enter– Return to menu
Changes will not be saved!
– Sets a menu to favourite.
(Note: The favourite menu will also be activated with the menu locked!)
5.3.1 Lock Menu
Some menus can be locked to prevent inadvertently changing the settings of the unit. This requires setting a code. For information on setting up or disabling the menu lock please refer to "Global Settings" (toP) under menu item toP>Loc.
The menu lock is
With the menu locked, only the following menu items will be visible without entering the correct code:
Menu itemExplanation
toP > unitTemperature unit selection (°C or °F).
F or Func.Accessing the Favourites menu
not
enabled at the time of delivery, all menu items can be accessed.
NOTICE!This menu may be one that is normally locked.
18 Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
Top Settings
top
Globale Einstellungen
3
21
Eingabe
5'C
-20 . . . 60 'C
6
54
Auswahl
oP
op haLf Lo hi
9
87
10
5.3.2 Menu navigation overview
When pressing the OK button in normal mode, the display will show the prompt code if the menu is locked. Use the ▲ and ▼
buttons to enter the correct code and press OK.
If an incorrect code or no code is entered, the menu will not be unlocked and you will not be able to access all menu items.
If you forgot the password you can always enter master code 287 to access the menu; the menu will be unlocked.
The following image shows an overview of the menu structure.
Items with a dashed frame will only appear with the respective settings or with the respective status messages.
The factory defaults and settings ranges are specified in the overview as well as under the respective menu item. The factory defaults apply unless otherwise agreed.
You can cancel entries and menu selections without saving by pressing the
ESC
key.
Menu:
Parameter:
Optional menu
navigation:
1.
Menu designation
2.
Display
3.
Brief description
4.
Value input
5.
Factory preset
6.
Parameter range
7.
Selecting from the list of values
8.
Factory preset
9.
Parameter range/selection
10. dashed box = Optional
19Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
Login
Loc
Enable menu lock
Selection
noP
nop- haLf - Lo - hi
OK
OK
OK
OK
OK
OK
OK
Input
0
0. . . . 9999
OK
OK
Selection
unit
°C - °F
Reset
rSt
Factory settings
Exit
E
Close submenu
TC Standard
tcSt
Device designation
Display
ch1
Temperature CH1
Display
ch2
Ambient temperature CH2
Top Settings
top
Global settings
Analogue Out1
An1
Settings menu Analog 1
Settings menu
unit
Temperature unit
Temperature
tEmP
Target temp. Cooling block
Exit
E
Close submenu
Drop-down menu
cout
Functional test
Exit
E
Close submenu
OK
DisplayMain menuSubmenu 1Submenu 2Parameter
Input
5°C
2 . . . 20 °C
OK
OK
Input
3°C
1 . . . 7 °C
Settings menu
A hi
Alarm hysteresis
Settings menu
A Lo
Alarm hysteresis
Drop-down menu
dt
DeltaT Temp. Mode
OK
OK
Drop-down menu
h2o
Drop-down menu
sen
Moisture detector 1 sensitivity
Drop-down menu
h2o.2
Drop-down menu
sen.2
OK
Input
-3°C
-1 . . . -3 °C
OK
Calibrate moisture detector 1
Calibrate moisture detector 2
Moisture detector 2 sensitivity
Drop-down menu
Modes
Deactivate DeltaT mode
OK
Selection
Abso
Abso - dt
Drop-down menu
out
Output signal
Selection
i
i- u
rst
OK
Input
non
non - hi - Lo
OK
rst
OK
Input
non
non - hi - Lo
OK
Confirm
rst
yes - no
OK
Exit
E
Close submenu
Drop-down menu
PuMP
Stop pumps
Input
-15°C
-30°C .. . .0°C K
Drop-down menu
noP
NoP - off
OK
Moisture detector 1
Moisture detector 2
Confirm
Confirm
Error
Err
Status message
Drop-down menu
hLtc
Humidity auto reset
Input
no
yes - no
OK
Drop-down menu
bLtc
Cable break auto reset
Input
YES
yes - no
OK
Restart
rESt
Restart device
Confirm
no
yes - no
OK
Drop-down menu
h.chn
Heat exchanger material selection
Drop-down menu
tS
tS
OK
t6
tU
(Steel)
(Glass)
(PVDF)
Fig.1: Menu Overview TC Standard
20 Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
5.4 Description of menu functions
5.4.1 Main menu
Peltier Cooler TC-Standard (tc.St)
Display → tc.st
This will take you to the cooler target temperature and the tolerance range setting (alarm
threshold).
Global setting (ToP Settings)
Display → toP
This menu is used to configure the global cooler settings.
Peristaltic Pump
Display → PuMP
Switching the peristaltic pump on and off.
Parameter range:NoP , oFF
Factory setting:NoP
Note:Status switches, "PuMP" flashes.
Heat exchanger material selection
Display → h.chn
Heat exchanger material selection
Parameter range:tS (Steel), t6 (Glass), tU (PVDF)
Factory setting:tS (cooler without heat exchanger), or respective material per configuration
Exit main menu
Display → E
Selecting this will return you to display mode.
5.4.2 Submenu 1
Target temperature (Temperature)
Display → Cooler → temp
This setting determines the nominal temperature for the cooler temperature.
Parameter range:2 °C to 20 °C (35.6 °F to 68 °F)
Factory setting:5 °C (41 °F)
Note:If the temperature is changed the indicator may blink, until the new operating range has been
reached.
This menu item is hidden if the keylock is enabled.
21Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
upper alarm limit (alarm high)
Display → Cooler → A hi
Here you can set the upper threshold for the visual signal and the alarm relay. The alarm limit is set
based on the cooler temperature setting.
Parameter range:1 °C to 7 °C (1.8 °F to 12.6 °F)
Factory setting:3 °C (5.4 °F)
Note:This menu item is hidden if the keylock is enabled.
lower alarm limit (alarm low)
Display → Cooler → A Lo
Here you can set the lower threshold for the visual signal and the alarm relay. The alarm limit is set
based on the cooler temperature setting.
Parameter range:-1 °C to -3 °C (-1.8 °F to -5.4 °F)
Factory setting:-3 °C (-5.4 °F)
Note:This menu item is hidden if the keylock is enabled.
DeltaT (dt)
Display → Cooler → dt
Here you can set the nominal difference with respect to ambient temperature.
Parameter range:-30 K…0 K
Factory setting:-15 K
Note:This menu will be hidden if the menu is locked.
DeltaT mode (Modu)
Display → Cooler → Modu
Here you can activate or deactivate DeltaT-mode.
Parameter range:AbSo , dt
Factory setting:AbSo (normal operation mode)
Note:This menu will be hidden if the menu is locked.
Exit submenu 1
Display → Submenu → E
Selecting this will return you to the main menu.
5.4.3 Submenu 1 (global settings)
Temperature unit
Display → toP → unit
Used to select the temperature display unit.
Parameter range:°C, °F
Factory setting:°C
22 Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
Analog output
Display → toP → An1
This submenu is used to specify the settings for analog output 1, see chapter Submenu 2 (Analog
Output 1)
Note:This menu will be hidden if the menu is locked.
Calibrate moisture detector
Display → toP → h2o (h2o)
If a moisture detector is installed, calibration can now be performed. To do so, the unit must be
flushed with dry gas.
Note:Calibration was performed at the factory using ambient air. After replacing the moisture detector a
calibration is again required.
Calibrating the moisture detector will set the menu sEn to hi.
This menu will be hidden if the menu is locked.
If the unit has multiple moisture detectors built in, they will be numbered in the menu. In this case, h2o indicates the first, h2o2
the second moisture detector. The same applies to setting the sensor sensitivity in menu SEn.
Moisture detector sensitivity
Display → toP → SEn
If moisture detectors are installed, the sensitivity can be reduced here.
Parameter range:hi: high sensitivity
Lo: low sensitivity
non: no moisture detector
Factory setting:hi
Note:This menu will be hidden if the menu is locked.
Moisture detector: automatic reset following moisture ingress
Display → toP → hLtc
(hLtc = humidity latch). The setting applies to all connected moisture detectors.
Specifies whether the moisture ingress message must be reset manually or will automatically be re-
set after the sensor dries.
Parameter range:YES: The status will be indicated until the user restarts the device and the pumps will be disabled.
no: The status message will automatically be cleared/the pumps will be released again once mois-
ture is no longer detected.
Factory setting:no
Note:This menu will be hidden if the menu is locked.
23Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
Moisture detector: error cleared automatically after cable break
Display → toP → bLtc
(bLtc = broken wire latch). The setting applies to all connected moisture detectors.
Determines whether the cable break alarm must be reset manually or will automatically clear on
valid measuring signal.
Parameter range:YES: The status will be indicated until the user restarts the device/clears the error, and the pumps
will be disabled.
no: The error message will extinguish/the pumps will be released again once the moisture detector
is recognised again.
Factory setting:YES
Note:This menu will be hidden if the menu is locked.
Lock Menu
To protect the menu from unauthorised use, enter a value for the lock code. Menu items can then only be accessed after entering the correct code.
Display → toP → Loc
This setting will cancel/enable the menu lock.
Parameter range:0 to 9999
Factory setting:0 (keylock cancelled)
Note:This menu will be hidden if the menu is locked.
Restart
Display → toP → rESt
(rESt = restart)
The device will restart, all settings are saved. All error messages will be reset.
The moisture detector will be reset, irrespective of the settings in menus h.Itc and h.Moi.
Parameter range:YES: Restart. The display will show the software version for the device and returns to measurement
display.
no: Exit menu without restarting.
Note:The user settings will be saved.
Factory settings
Display → toP → rst
This setting restores the factory settings.
Parameter range:Yes: factory settings restored.
No: Exit menu without making changes.
Factory setting:No
Note:This menu will be hidden if the menu is locked.
Exit submenu 1
Display → Submenu → E
Selecting this will return you to the main menu.
24 Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
5.4.3.1 Submenu 2 (Analog Output 1)
The analog output will display the actual cooler temperature.
Signal behaviour
In normal mode (noP) the measuring point will output the actual temperature. For testing purposes you can generate constant
values hi, Lo or hALF. The analogue output will output a constant signal with a value as specified in the table.
ConstantCurrent output
4 – 20 mA
hi 20 mA10 V
Mi 12 mA6 V
Lo 4 mA2 V
noP4 – 20 mA2 – 10 V
After testing, the signal behaviour must be changed back to normal mode (noP).
Display → toP → An1 → cout
This setting determines how the analogue output will behave.
Note:This menu will be hidden if the menu is locked.
Voltage output
2 – 10 V
Selection -> Output Signal
Display → toP → An1 → out
Select the type of output signal.
Parameter range:i Status output 4… 20mA
u Status output 2…10V
Factory setting:i
Note:Disconnect meter before switching!
This menu item is hidden if the keylock is enabled.
Exit Submenu 2
Display → toP → An1 → E
Selecting this will return you to submenu 1.
5.4.4 Set favourite menu
Use the F or
– Open the menu you wish to set as the favourite. This menu can also be a lockable menu.
– Press the function key for more than 3 sec.
The current menu has been set as the favourite. The display will briefly show the message Func.
– Press
To now access the favourite menu, press the F or
NOTICE!The favourite menu can also be accessed if the menu is locked.
Func
(function) key to set a favourite menu to later open it with just the push of a button.
ESC
or E (Exit) to return to the display.
Func
key.
25Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
6 Maintenance
If the cooler is delivered in basic configuration, no special maintenance is necessary.
Nevertheless, depending on the configuration different options or accessories may be installed. In this case, follow the maintenance schedule in regular intervals.
Option peristaltic pump:
–
Option filter:
–
Option moisture detector:
–
During maintenance, remember:
– The equipment must be maintained by a professional familiar with the safety requirements and risks.
– Only perform maintenance work described in these operating and installation instructions.
– When performing maintenance of any type, observe the respective safety and operation regulations.
DANGERElectrical voltage
Checking the filter element
Checking the hoses
Calibrating the moisture detector
Electrocution hazard.
a) Disconnect the device from power supply.
b) Make sure that the equipment cannot be reconnected to mains unintentionally.
c) The device must be opened by trained staff only.
d) Regard correct mains voltage.
DANGERToxic, corrosive gas/condensate
Sample gas/condensate may be hazardous to health.
a) If necessary, ensure a safe gas/condensate discharge.
b) Always disconnect the gas supply when performing maintenance or repairs.
c) Protect yourself from toxic/corrosive gasses/condensate when performing mainten-
ance. Wear appropriate protective equipment.
26 Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
7 Service and repair
This chapter contains information on troubleshooting and correction should an error occur during operation.
Repairs to the unit must be performed by Bühler authorised personnel.
Please contact our Service Department with any questions:
Tel.: +49-(0)2102-498955
If the equipment is not functioning properly after correcting any malfunctions and switching on the power, it must be inspected
by the manufacturer. Please send the equipment inside suitable packaging to:
Bühler Technologies GmbH
- Reparatur/Service -
Harkortstraße 29
40880 Ratingen
Germany
Please also attach the completed and signed RMA decontamination statement to the packaging. We will otherwise be unable to
process your repair order.
You will find the form in the appendix of these instructions, or simply request it by e-mail:
service@buehler-technologies.com
or your agent
.
7.1 Troubleshooting
Problem / MalfunctionPossible causeAction
Condensate inside the gas
outlet
Reduced gas flow rate– Gas circuit clogged– Uninstall and clean heat exchanger
Excess temperature– Operating point not yet reached– Wait (max. 20 min)
Insufficient temperature– Faulty control– Send in cooler
– Installed fan stopped– Check and replace if necessary
– Flush in both directions
– if necessary, replace filter element
– Be sure the vents are not covered (heat
buildup)
– Maintain limits / install pre-separator
27Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
7.1.1 Error messages on the display
If an error occurs, the display will read "Err". Press the " " button to show the error number(s).
Error messages will appear until the unit has been restarted or the error is cleared using the "Func" button. It can only be cleared
if the cause for the error has been corrected.
Causes / Action: The following is a list of the most common causes and actions for the respective error. If the actions listed do
not resolve the problem, please contact Service.
Problem / MalfunctionPossible causeAction
No display– No voltage
– Loose connecting cable
– Display defective
D1.02(The software version for the display will ap-
(permanent)
Error– An error has occurred– Read the error number as described above
Error 40– General error temperature sensor 1– Sensor possibly defective
Error 41– Low temperature / short-circuit temperat-
ure sensor 1
Error 42– Excess temperature / short-circuit temper-
ature sensor 1
Error 43– Measurement fluctuation temperature
sensor 1
Error 50– General error temperature sensor 2– Sensor possibly defective
Error 51– Low temperature / short-circuit temperat-
ure sensor 2
Error 52– Excess temperature / short-circuit temper-
ature sensor 2
Error 53– Measurement fluctuation temperature
sensor 2
– Check temperature sensor connection
– Check temperature sensor connection
– Check temperature sensor connection
– Check temperature sensor connection
– Check temperature sensor connection
– Check temperature sensor connection
28 Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
Status textPossible causeAction
H2o.1– Moisture alarm moisture detector 1– Dry
– Check condensate trap
H2o.2– Moisture alarm moisture detector 2– Dry
– Check condensate trap
init– Initialisation phase– Wait
PuMP– Pumps deactivated– Reactive pumps via menu
dtActive Delta T control only: The block temperat-
ure is outside the defined temperature range.
– Cooler is still in the "break-in phase"
– Fluctuating ambient temperature
– Insufficient cooling capacity
– Excess/low temperature– see chapter “Troubleshooting”
(Flashing)
– Wait to see if the target temperature will be
– Check the ambient temperature / power sup-
– Process-related: Adjust alarm limits
7.2 Safety instructions
– The device must be operated within its specifications.
– All repairs must be carried out by Bühler authorised personnel only.
– Only perform modifications, servicing or mounting described in this manual.
– Only use original spare parts.
DANGERElectrical voltage
Electrocution hazard.
a) Disconnect the device from power supply.
b) Make sure that the equipment cannot be reconnected to mains unintentionally.
c) The device must be opened by trained staff only.
d) Regard correct mains voltage.
reached
plied
DANGERToxic, corrosive gas/condensate
Sample gas/condensate may be hazardous to health.
a) If necessary, ensure a safe gas/condensate discharge.
b) Always disconnect the gas supply when performing maintenance or repairs.
c) Protect yourself from toxic/corrosive gasses/condensate when performing mainten-
ance. Wear appropriate protective equipment.
CAUTIONHealth hazard if the heat exchanger leaks
The heat exchanger is charged with glycol-based coolant.
In the event of a heat exchanger leak:
a) Avoid contact with the skin and eyes.
b) In the event of a leak, do not restart the cooler under any circumstances The cooler
must be repaired by the manufacturer.
29Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
7.3 Cleaning and removal of the heat exchanger
Heat exchangers only need to be replaced or maintained if clogged or damaged. If they are clogged, we recommend checking if
using a filter will avoid future occurrences.
– Close gas supply.
– Switch off device and disconnect all plugs (e.g. connector plug alarm output, supply input, etc.).
– Disconnect gas connections and condensate drain.
– Pull the heat exchanger up and out.
– Clean the heat exchanger hole (hole inside the cooler block), as the heat exchangers are installed with silicone grease.
– Flush the heat exchanger until all contaminants have been removed.
– Grease the cooled outside surface external surface with silicone grease.
– Reinsert the heat exchanger into the cooling nest with a rotating movement.
– Reconnect the gas supply and condensate drain. The gas inlet is marked red.
– Restore power/gas supply and wait for unit to be ready for operation.
– Open gas supply.
7.4 Replacing the hoses of the peristaltic pump (option)
– Turn off gas supply.
– Switch the device off and disconnect power supply.
– Remove the supplying and draining hoses from the pump (
– Loosen the centre knurled screw but do not remove it. Push the screw downwards.
– Pull off the cover.
– Pull the connections sidewards and remove the hose.
– Replace the hose and remount the pump in reverse order.
– Reconnect power supply.
Take care of the safety instructions!
).
7.5 Replacing the filter element (option)
CAUTIONGas leakage
The filter should not be dismantled under pressure.
Don’t use damaged parts again.
– Close the gas supply.
– Switch off and unplug the device.
– Pull the bracket, holding on to the filter glass.
– Whilst holding the filter head, move the glass back and forth and carefully remove downward.
– Remove the filter element and insert a new one.
– Check for leaks and replace, if necessary.
– Whilst holding the filter head, move the glass back and forth and carefully reattach the filter head, attach the bracket, and
ensure it is seated securely.
– Restore the power and gas supply.
NOTICE!Please observe legal regulations when disposing of filter elements.
30 Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
7.6 Drying of the moisture detector (option)
The moisture detector must be dried if moisture enters.
– Close the gas supply.
– Switch off and unplug the device.
– Loosen the swivel nut for the moisture detector connection line and disconnect the line.
– Unscrew the moisture detector counter-clockwise and remove.
– Dry moisture detector.
– Reinsert the moisture detector and carefully tighten the screw connection.
– Connect the connection line and tighten the swivel nut.
– Restore the power and gas supply.
7.7 Calibration of the moisture detector (option)
– When replacing the moisture detectors, they must be recalibrated.
– Be sure dry gas flows through the cooler.
– Select cooler menu and confirm.
or
– Select menu item moisture detector.
– The display shows (Reset).
– Confirm the display to calibrate the moisture detectors.
For a detailed overview of menu navigation, refer to chapter "Operation and Control".
7.8 Spare parts and accessories
Please also specify the model and serial number when ordering parts.
Upgrade and expansion parts can be found in our catalog.
The heat exchanger is charged with glycol-based coolant.
Dispose of parts so as not to endanger the health or environment. Follow the laws in the country of use for disposing of electronic components and devices as well as hazardous materials during disposal.
33Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
9 Appendices
9.1 Gas cooler technical data
TC-Standard X2
Gas Cooler Technical Data
Ready for operationafter max. 10 minutes
Ambient temperature5 °C to 50 °C
Gas outlet dew temperature
preset:
adjustable:
Protection classIP 20
Mechanical loadTested to DNVGL-CG-0339, Table 6
HousingStainless steel, brushed
Packaging dimensionsapprox. 355 x 220 x 205 mm
Weight incl. heat exchangerapprox. 7.5 kg
Electrical dataUnit without add-onUnit with add-on
Recommended fuse
(characteristic: delayed action)
Status output switching capacitymax. 250 V AC, 150 V DC
Electrical connectionsPlug per EN 175301-803
Gas connections and condensate outletHeat exchanger see table "Heat Exchanger Overview"
Parts in contact with mediums
Filter:
Moisture detector:
Heat exchanger:
Peristaltic pump:
Tubing:
Markings:FM18ATEX0012X: II 3 G Ex ec nC IIC T4 Gc
5 °C
2 °C…20 °C or Delta T-control
2 Hz-13.2 Hz Amplitude ± 1.0 mm
13.2 Hz -100 Hz acceleration
approx. 6 kg (for 24 V DC)
approx. 9 kg fully upgraded
(1 peristaltic pump)
24 V DC230 V AC115 V AC24 V DC230 V AC115 V AC
5 A0.6 A1.2 A5.5 A0.7 A1.4 A
120 W110 W / 140 VA130 W130 W / 160 VA
6,3 A1,25 A2,5 A6,3 A1,25 A2,5 A
2 A, 50 VA, potential-free
Filter, moisture detector adapter G1/4 or NPT 1/4"
see "Technical Data - Options"
see "Technical Data - Options"
see table "Heat Exchanger Overview"
see "Technical Data - Options"
PTFE/Viton
IECEx FMG 18.0005X: Ex ec nC IIC T4 Gc
FM18US0021X/FM18CA0010X: CL I DIV 2 GP ABCD
34 Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
TC-Standard+ X2
Gas Cooler Technical Data
Ready for operationafter max. 10 minutes
Ambient temperature5 °C to 50 °C
Gas outlet dew temperature
preset:
adjustable:
Protection classIP 20
Mechanical loadTested to DNVGL-CG-0339, Table 6
HousingStainless steel, brushed
Packaging dimensionsapprox. 355 x 220 x 205 mm
Weight incl. heat exchangerapprox. 7.5 kg
Electrical dataUnit without add-onUnit with add-on
Recommended fuse
(characteristic: delayed action)
Status output switching capacitymax. 250 V AC, 150 V DC
Electrical connectionsPlug per EN 175301-803
Gas connections and condensate outletHeat exchanger see table "Heat Exchanger Overview"
Parts in contact with mediums
Filter:
Moisture detector:
Heat exchanger:
Peristaltic pump:
Tubing:
Markings:FM18ATEX0012X: II 3 G Ex ec nC IIC T4 Gc
5 °C
2 °C…20°C
2 Hz-13.2 Hz Amplitude ± 1.0 mm
13.2 Hz -100 Hz acceleration
approx. 6 kg (for 24 V DC)
approx. 9 kg fully upgraded
(1 peristaltic pump)
24 V DC230 V AC115 V AC24 V DC230 V AC115 V AC
5 A0.6 A1.2 A5.5 A0.7 A1.4 A
120 W110 W / 140 VA130 W130 W / 160 VA
6, 3 A1,25 A2,5 A6,3 A1,25 A2,5 A
2 A, 50 VA, potential-free
Filter, moisture detector adapter G1/4 or NPT 1/4"
see "Technical Data - Options"
see "Technical Data - Options"
see table "Heat Exchanger Overview"
see "Technical Data - Options"
PTFE/Viton
IECEx FMG 18.0005X: Ex ec nC IIC T4 Gc
FM18US0021X/FM18CA0010X: CL I DIV 2 GP ABCD
9.2 Technical Data - Options
Analogue Output Cooler Temperature Technical Data
Signal4-20mA or 2-10V
corresponds to -20°C to +60°C cooler temperature
ConnectionM12x1 plug, DIN EN 61076-2-101
Technical Data FF-3-N Moisture Detector
Ambient temperature3 °C to 50 °C
max. operating pressure with FF-3-N2 bar
MaterialPVDF, PTFE, epoxy resin, stainless steel 1.4571, 1.4576
35Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
Technical Data peristaltic pumps CPsingle X2 / CPdouble X2
Ambient temperature0°C to 50 °C
Flow rate0.3 L/h (50 Hz) / 0.36 L/h (60 Hz) with standard hose
Vacuum inletmax. 0.8 bar
Pressure inletmax. 1 bar
Outlet pressure1 bar
Hose4 x 1.6 mm
Condensate outletHose nipple Ø6 mm
Note: The limit curves for the heat exchangers MTV-2 and MTG-2 apply to a dew point of 50 °C.
Dew point fluctuations
static
in the entire specification range
Temperature difference between heat exchangers
± 0.1 K
± 1.5 K
< 0.5 K
9.5 Heat exchanger
9.5.1 Heat exchanger description
The energy content of the sample gas and the required cooling capacity of the gas cooler is determined by three parameters: gas
temperature ϑG, dew point τe (moisture content) and volume flow v. The outlet dew point rises with increasing energy content of
the gas. The following limits for the maximum flow are specified for a standard operating point of τe = 40 °C and ϑG = 70 °C. Indicated is the maximum flow v
gas inlet temperatures. However, the physical facts are so vast we decided to omit the illustration. Please contact our experts for
clarification or refer to our design program.
in Nl/h of cooled air, so after moisture has condensed. Values may differ for other dew points and
max
38 Bühler Technologies GmbHBE440023 ◦ 10/2018
TC-Standard (+) X2
9.5.2 Heat exchanger overview
TC-Standard
Heat exchangerPTS
PTS-I
2)
PTG
PTG
PTV
PTV-I
2)
MTS
MTS-I
3)
2) 3)
MTG
MTG
3)
3)
MTV
MTV-I
3)
2) 3)
Version / MaterialStainless steelGlassPVDFStainless steelGlassPVDF
Flow rate v
Inlet dew point τ
Gas inlet temperature ϑ
Max. Cooling capacity Q
Gas pressure p
max
1)
1)
e,max
max
G,max
max
1)
450 Nl/h250 Nl/h250 Nl/h300 Nl/h210 Nl/h190 Nl/h
65 °C65 °C65 °C65 °C65 °C65 °C
180 °C140 °C140 °C140 °C140 °C140 °C
150 kJ/h90 kJ/h90 kJ/h95 kJ/h80 kJ/h65 kJ/h
160 bar3 bar2 bar25 bar3 bar2 bar
Pressure drop Δp (v=150 L/h)10 mbar10 mbar10 mbar20 mbar19 mbar18 mbar
Dead volume V
tot
Gas connections (metric)6 mmGL 14 (6 mm)
Gas connections (US)1/4"GL 14 (1/4")
Condensate out connections (metric)G3/8GL 25 (12 mm)
Condensate out connections (US)NPT 3/8"GL 25 (1/2")
1)
Max. cooling capacity of the cooler must be considered
2)
Models marked I have NPT threads or US tubes, respectively.
3)
Passive discharge via automatic condensate drains or traps not applicable for MTG heat exchangers. For passive discharge on
29 ml29 ml57 ml19 ml18 ml17 ml
4)
DN 4/66 mm tube GL14 (6 mm)DN 4/6
4)
1/4"-1/6"1/4" tubeGL14 (1/4")1/4"-1/6"
4)
G3/8G1/4GL18 (8 mm)G1/4
4)
NPT 3/8"NPT 1/4"GL18 (8 mm)NPT 1/4"
the MTS and MTV heat exchangers, use a screw connection with a clearance of at least 7 mm (see accessories).
4)
Gasket inside diameter
TC-Standard+
Heat exchanger2x MTG-2
3)
2x MTV-2
2x MTV-2-I
3)
2) 3)
Version / MaterialGlassPVDF
Flow rate v
Inlet dew point τ
Gas inlet temperature ϑ
Max. Cooling capacity Q
Gas pressure p
max
1)
1)
e,max
max
G,max
max
1)
210 Nl/h190 Nl/h
70 °C70 °C
140 °C140 °C
80 kJ/h65 kJ/h
3 bar2 bar
Pressure drop Δp (v=150 L/h)19 mbar18 mbar
Dead volume V
tot
Gas connections (metric)GL14 (6 mm)
Gas connections (US)GL14 (1/4")
Condensate out connections (metric)GL18 (8 mm)
Condensate out connections (US)GL18 (8 mm)
1)
Max. cooling capacity of the cooler must be considered.
2)
Models marked I have NPT threads or US tubes, respectively.
3)
Passive discharge via automatic condensate drains or traps not applicable for MTG-2 heat exchangers. For passive discharge on
38 ml36 ml
4)
DN 4/6
4)
1/4"-1/6"
4)
4)
G1/4
NPT 1/4"
the MTV-2 heat exchangers, use a screw connection with a clearance of at least 7 mm (see accessories).
conditions of use specified in the schedule to this certificate.
Approvals surveillance audit program has further determ ined that the manufactur ing processes and quality
control procedures in place are satisfactory to manufacture the product as examined, tested and Approved.
X2; TC-Double X2 & TC-Double+ X2
Ratingen, D-40880
Germany
th
October 2018
TC-Standard Models:
Non-incendive for Class I, Division 2, Groups A, B, C and D; T4 hazardous locations with an ambient
temperature rating of 0°C of up to 50°C.
VP, Manager, Electrical Systems
To verify the availability of the Approved product, please refer towww.approvalguide.com
THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals LLC. 1151 Boston-Providence Turnpike, Norwood, MA 02062 USA
T: +1 (1) 781 762 4300 F: +1 (1) 781 762 9375 E-mail: information@fmapprovals.comwww.fmapprovals.com
Canadian Certificate Of Conformity No: FM18CA0010X
Non-incendive for Class I, Division 2, Groups A, B, C and D; T4 hazardous (classified) locations with an
ambient temperature rating of 0°C of up to 60°C.
TC-Standard Models:
Class I Division 2, Groups A, B, C, D; T4 Ta = 0°C to 50°C
TC-MIDI and TC-Double Models:
Class I Division 2, Groups A, B, C, D; T4 Ta = 0°C to 60°C
General - The TC-6 sample gas chillers are intended to cool and dry the sample gas before going into the
gas analysers. Sample gases contain vapour which has to be withdrawn before it reaches the gas analyser.
The Gas flows through a heat exchanger (impinger) inserted into a cooling block. The latter then is cooled
to a preset temperature (5°C mostly).
Depending on the required cooling capacity the size of the heat exchanger and therefore chiller is chosen
and depending on the kind of gas to be cooled different heat exchanger materials are provided (stainless
steel, glass or PVDF).
A gas cooler (chiller) might be prepared for more than one heat exchanger. The cooling block is cooled by
different combinations of Peltier-elements. The temperature is sensed by an RTD.
Construction – The equipment is housed in a brushed stainsteel IP20 enclosure.
Ratings - TC-Standard operate at 24VDC, 115 VAC or 230 VAC, selectable by ordering, with an ambient
temperature rating of 0°C of up to 50°C. and TC-MIDI and TC-Double Models operate at 115 VAC or 230 VAC,
selectable by ordering, with an ambient temperature rating of 0°C of up to 60°C.
4496 211b2d1fgh0jkl0n0 TC-Standard X2 - Sample Gas Cooler (fitted with 1 heat exchangers)
b = Gas cooler model: 1 or 2
d, = Supply voltage; 1, 2 or 4
f & g = Heat exchanger; 10, 15, 20, 25, 30, or 35
h = Peristaltic Pumps; 0, 1, 3
j & k = Moisture detector / Filter; 00, 01,10, or 11
l = Status Outputs; 0 or 1
n = Delta T control; 0 or 1
4496 212b2d2fgh0jkl0n0 TC-Standard X2 - Sample Gas Cooler (fitted with 2 heat exchangers)
b = Gas cooler model: 1 or 2
d = Supply voltage; 1, 2 or 4
f & g = Heat exchanger; 10, 15, 20, 25, 30, or 35
h = Peristaltic Pumps; 0, 2, or 4
THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals LLC. 1151 Boston-Providence Turnpike, Norwood, MA 02062 USA
T: +1 (1) 781 762 4300 F: +1 (1) 781 762 9375 E-mail: information@fmapprovals.comwww.fmapprovals.com
F 348 (Mar 16) Page 2 of 4
l = Status Outputs; 0 or 1
n = Delta T control; 0 or 1
k,l = Status output; 00 or 10
4496 212b2d2fgh0jkl0n0 TC-Standard+ X2 - Sample Gas Cooler (with 2 heat exchangers in
series)
b = Gas cooler model: 1 or 2
d = Supply voltage; 1, 2 or 4
f & g = Heat exchanger; 22, 27, 32 & 37
h = Peristaltic Pumps; 0, 2, 4
j & k = Moisture detector / Filter; 00, 01,10, or 11
l = Status Outputs; 0 or 1
n = no value assigned.
4496 311 b2defghijklmno Thermoelectric Cooler, TC-MI DI + X2(fitted with 1 heat exchangers)
b = Gas cooler types 1 or 2
d = Supply Voltage; 1 or 2
e = Gas paths; 1or 2
f,g = Heat exchangers; 60,61, 65, 66, 70, 75, 80 or 85
h = Peristaltic pumps; 0, 2, or 4
i = Sample gas pumps; 0, 1, 2, 6, or 7
j,k = Moisture detector / Filter; 00, 01, 02, 10, 11, 20 21, or 22
l,m = Status output; 00 or 10
n,o = Delta T control; 00 or 10
4496 312 b2d1fghijklm00 Thermoelectric Cooler, TC-MIDI + X2(fitted with 2 heat ex changers)
b = Gas cooler types 1 or 2
d = Supply Voltage; 1 or 2
f,g = Heat exchangers; 22, 27, 32, or 37
h = Peristaltic pumps; 0, 2, or 4
i = Sample gas pumps; 0, 1, 2, 6, or 7
j,k = Moisture detector / Filter; 00, 01, 02, 10, or 11
l,m = Status output; 00 or 10
a = Gas cooler types 1 or 2
c = Voltage; 1 or 2
e,f = Heat exchangers; 10,15, 20,25,30, or 35
g = Peristaltic pumps; 0, 2, or 4
h = Sample gas pumps; 0, 1, or 2
i,j = Moisture Detector/Filter; 00, 01, 10, or 11
k,l = Status output; 00 or 10
a = Gas cooler types 1 or 2
c = Voltage; 1 or 2
e,f = Heat exchangers; 22, 27, 32, or 37
g = Peristaltic pumps; 0, 2, or 4
h = Sample gas pumps; 0, 1, or 2
i,j = Moisture Detector/Filter; 00, 01, 10, or 11
SCHEDULE
Canadian Certificate Of Conformity No: FM18CA0010X
THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals LLC. 1151 Boston-Providence Turnpike, Norwood, MA 02062 USA
T: +1 (1) 781 762 4300 F: +1 (1) 781 762 9375 E-mail: information@fmapprovals.comwww.fmapprovals.com
F 348 (Mar 16) Page 3 of 4
13.
Specific Conditions of Us e:
1. When installed as Class I Division 2 equipment, the thermoelec tric cooler shall be mounted within a
14.
Test and Assessment Procedure and Conditions:
This Certificate has been issued in accordance with FM Approvals Canadian Certification Scheme.
15.
Schedule Drawings
A copy of the technical documentation has been kept by FM Approvals.
16.
Certificate History
Details of the supplements to this certificate are described below:
SCHEDULE
Canadian Certificate Of Conformity No: FM18CA0010X
tool-secured IP54 enclosure.
4th October 2018 Original Issue.
Date Description
THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals LLC. 1151 Boston-Providence Turnpike, Norwood, MA 02062 USA
T: +1 (1) 781 762 4300 F: +1 (1) 781 762 9375 E-mail: information@fmapprovals.comwww.fmapprovals.com
F 348 (Mar 16) Page 4 of 4
1.
HAZARDOUS (CLASSIFIED) LOCATION ELECTRICAL EQUIPMENT PER US REQUIREMENTS
The examination and test results are recorded in confidential report number:
7.
FM Approvals LLC, certifies that the equipment described has been found to comply with the following Approval
8.
If the sign ‘X’ is placed after the certificate number, it indicates that the equipm ent is subject to specific
9.
This certificate relates to the design, examination and testing of the products specified herein. The FM
10.
Equipment Ratings:
Certificate issued by:
4 October 2018
J. E. Marquedant
Date
CERTIFICATE OF CONFORMITY
(Type Reference and Name)
3062014 dated 4
standards and other documents:
FM Class 3600:2018, FM Class 3611:2018, FM Class 3810:2018,
ANSI/ISA-12.12.01-2015, ANSI/ISA 61010-1:2012
conditions of use specified in the schedule to this certificate.
Approvals surveillance audit program has further determ ined that the manufac turing processes and quality
control procedures in place are satisfactory to manufacture the product as examined, tested and Approved.
TC-Double X2 & TC-Double+ X2
Ratingen, D-40880
Germany
th
October 2018
TC-Standard Models:
Non-incendive for Class I, Division 2, Groups A, B, C and D; T4 hazardous (classified) locations with an
ambient temperature rating of 0°C to 50°C.
VP, Manager, Electrical Systems
To verify the availability of the Approved product, please refer towww.approvalguide.com
THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals LLC. 1151 Boston-Providence Turnpike, Norwood, MA 02062 USA
T: +1 (1) 781 762 4300 F: +1 (1) 781 762 9375 E-mail: information@fmapprovals.comwww.fmapprovals.com
F 347 (Mar 16) Page 1 of 4
11.
The marking of the equipment shall include:
12.
Description of Equipment:
General - The TC- Standard; TC-Midi & TC-Double sample gas chillers are intended to cool and dry the sample
reaches the gas analyzer. The Gas flows through a heat exchanger (impinger ) inse rted i nto a cool ing b lock. The
depending on the kind of gas to be cooled different heat e xchange r materi als a re pro vided (stai nless steel, glas s
exchangers)
SCHEDULE
US Certificate Of Conformity No: FM18US0021X
TC-MIDI and TC-Double Models:
Non-incendive for Class I, Division 2, Groups A, B, C and D; T4 hazardous (classified) locations with an
ambient temperature rating of 0°C to 60°C.
TC-Standard Models:
Class I Division 2, Groups A, B, C, D; T4 Ta = 0°C to 50°C
TC-MIDI and TC-Double Models:
Class I Division 2, Groups A, B, C, D; T4 Ta = 0°C to 60°C
gas before going into the gas analyzers. Sample gases contain vapor which has to be withdrawn before it
latter then is cooled to a pre-set temperature (5°C mostly).
Depending on the required cooling capacity the size of the heat exchanger and therefore chiller is chosen and
or PVDF).
A gas cooler (chiller) might be prepared f or more than one heat exc hanger. The cooling block is c ooled by
different combinations of Peltier-elements. The temperature is sensed by an RTD.
The TC-Standard X2 / TC-Midi X2 series of sample coolers are designed specifically for high c oolin g capa cities
and high ambient temperatures.
The TC-Standard+ X2 / TC-Midi+ X2 series are designed specifically for the requirements in automated
measuring systems (AMS) according to EN 15267-3. The series connection of the heat exchangers will cool in
two cy cles to minimize wash out effects.
The TC-Double X2 series are designed specifically for high cooling capacities, high ambient temperatures and
to cool in two cycles to minimize wash out effects.
The TC-Double+ X2 incorporates two cooling blocks that can be set do different temperatures.
Construction – The equipment is housed in a brushed stainsteel IP20 enclosure.
Ratings - TC-Standard operate at 24VDC, 115 VAC or 230 VAC, selectable by ordering, with an ambient
temperature rating of 0°C of up to 50°C. and TC-MIDI and TC-Double Models operate at 115 VAC or 230 VAC,
selectable by ordering, with an ambient temperature rating of 0°C of up to 60°C.
4496 211b2d1fgh0jkl0n0 TC-Standard X2 - Sample Gas Cooler (fitted with 1 heat
THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals LLC. 1151 Boston-Providence Turnpike, Norwood, MA 02062 USA
T: +1 (1) 781 762 4300 F: +1 (1) 781 762 9375 E-mail: information@fmapprovals.comwww.fmapprovals.com
F 347 (Mar 16) Page 2 of 4
US Certificate Of Conformity No: FM18US0021X
b = Gas cooler model: 1 or 2
d, = Supply voltage; 1, 2 or 4
f & g = Heat exchanger; 10, 15, 20, 25, 30, or 35
h = Peristaltic Pumps; 0, 1, 3
j & k = Moisture detector / Filter; 00, 01,10, or 11
l = Status Outputs; 0 or 1
n = Delta T control; 0 or 1
4496 212b2d2fgh0jkl0n0 TC-Standard X2 - Sample Gas Cooler (fitted with 2 heat
exchangers)
b = Gas cooler model: 1 or 2
d = Supply voltage; 1, 2 or 4
f & g = Heat exchanger; 10, 15, 20, 25, 30, or 35
h = Peristaltic Pumps; 0, 2, or 4
j & k = Moisture detector / Filter; 00, 01, 02, 10, 11, 20, 21, 22
l = Status Outputs; 0 or 1
n = Delta T control; 0 or 1
4496 212b2d2fgh0jkl0n0 TC-Standard+ X2 - Sample Gas Cooler (with 2 heat exchangers in
series)
b = Gas cooler model: 1 or 2
d = Supply voltage; 1, 2 or 4
f & g = Heat exchanger; 22, 27, 32 & 37
h = Peristaltic Pumps; 0, 2, 4
j & k = Moisture detector / Filter; 00, 01,10, or 11
l = Status Outputs; 0 or 1
n = no value assigned.
4496 311 b2defghijklmno Thermoelectric Cooler, TC-MI DI + X2(fitted with 1 heat
exchangers)
b = Gas cooler types 1 or 2
d = Supply Voltage; 1 or 2
e = Gas paths; 1or 2
f,g = Heat exchangers; 60,61, 65, 66, 70, 75, 80 or 85
h = Peristaltic pumps; 0, 2, or 4
i = Sample gas pumps; 0, 1, 2, 6, or 7
j,k = Moisture detector / Filter; 00, 01, 02, 10, 11, 20 21, or 22
l,m = Status output; 00 or 10
n,o = Delta T control; 00 or 10
b = Gas cooler types 1 or 2
d = Supply Voltage; 1 or 2
f,g = Heat exchangers; 22, 27, 32, or 37
h = Peristaltic pumps; 0, 2, or 4
i = Sample gas pumps; 0, 1, 2, 6, or 7
j,k = Moisture detector / Filter; 00, 01, 02, 10, or 11
l,m = Status output; 00 or 10
SCHEDULE
THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals LLC. 1151 Boston-Providence Turnpike, Norwood, MA 02062 USA
T: +1 (1) 781 762 4300 F: +1 (1) 781 762 9375 E-mail: information@fmapprovals.comwww.fmapprovals.com
1. When installed as Class I Division 2 equipment, the thermoelec tric c ooler shall be mounted within a
14.
Test and Assessment Procedure and Conditions:
This Certificate has been issued in accordance with FM Approvals US Certification Requirements.
15.
Schedule Drawings
A copy of the technical documentation has been kept by FM Approvals.
16.
Certificate History
Details of the supplements to this certificate are described below:
SCHEDULE
US Certificate Of Conformity No: FM18US0021X
a = Gas cooler types 1 or 2
c = Voltage; 1 or 2
e,f = Heat exchangers; 10,15, 20,25,30, or 35
g = Peristaltic pumps; 0, 2, or 4
h = Sample gas pumps; 0, 1, or 2
i,j = Moisture Detector/Filter; 00, 01, 10, or 11
k,l = Status output; 00 or 10
a = Gas cooler types 1 or 2
c = Voltage; 1 or 2
e,f = Heat exchangers; 22, 27, 32, or 37
g = Peristaltic pumps; 0, 2, or 4
h = Sample gas pumps; 0, 1, or 2
i,j = Moisture Detector/Filter; 00, 01, 10, or 11
k,l = Status output; 00 or 10
tool-secured IP54 enclosure which is capable of accepting one or more of the Class I Division 2 wiring
methods per the National Electric Code (ANSI/NFPA 70).
4th October 2018 Original Issue.
Date Description
THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals LLC. 1151 Boston-Providence Turnpike, Norwood, MA 02062 USA
T: +1 (1) 781 762 4300 F: +1 (1) 781 762 9375 E-mail: information@fmapprovals.comwww.fmapprovals.com
F 347 (Mar 16) Page 4 of 4
IECEx Certificate
4
of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com