Buderus Logano G315 Installation And Service Instructions Manual

Installation and Service Instructions
Low-temperature oil/gas boiler
WARNING: If installation, adjustment, modification, oper-
ation or maintenance of the heating system is carried out by an unqualified person, this may result in personal injury or property damage. The directions of this installation manual must be followed precisely. If support or additional information is required, contact a qualified service company, service provider or the gas company.
WARNING:
Observe the safety instructions of this installation manual before placing the heating appliance in operation. The operating manual is a component of the technical documentation and must be handed over to the operator of the heating system. Explain to the owner or operator how to use the heating system using the operating instructions. Make sure that he has been familiarized with all information required for the operation of the heating system.
Logano G315
Boilers for oil/gas-fired power burners
NOTICE: If the heating appliance will be installed in Mas-
sachusetts, it must be installed by an installer or dealer who is registered there.
This manual is available in the English and French language. Please keep this manual for future reference.
For contractors
Read carefully prior to installation and maintenance
6 720 647 211 (12/2010) US/CA
Contents
About this manual
The appliance has been tested to meet all national requirements in effect on the date of manufacture. The conformity has been confirmed. The corresponding documentation and the original Declaration of Conformity are on file with the manufacturer.
This installation and maintenance instructions contain important information for the safe and proper installation, initial start-up and maintenance of the oil/gas-fired boiler Logano G315.
These installation and maintenance instructions are designed for specialists, who, due to their vocational training and experience, are knowledgeable in handling heating systems and oil and gas installations.
The oil/gas-fired boiler Logano G315 is available in two variants (disassembled and assembled).
These installation and maintenance instructions explain the installation and maintenance of both boiler types.
Contents
1 Guideline to symbols and safety instructions 4
1.1 Explanation of symbols . . . . . . . . . . . . . . . . 4
1.2 Safety instructions . . . . . . . . . . . . . . . . . . . 4
2 Product description . . . . . . . . . . . . . . . . . . . . . . 6
2.1 Designated use . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Operating conditions . . . . . . . . . . . . . . . . . 8
2.3 Compliance with standards
and regulations . . . . . . . . . . . . . . . . . . . . . 8
2.4 Additional regulations for installations in the Commonwealth of Massachusetts 10
3 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . 14
4.1 Logano G315 - delivery as a
pre-assembled block . . . . . . . . . . . . . . . . 14
4.2 Logano G315 – delivery unassembled . . 14
5 Transporting the boiler . . . . . . . . . . . . . . . . . . 14
6 Positioning the boiler . . . . . . . . . . . . . . . . . . . . 15
6.1 Tools and auxiliary materials . . . . . . . . . . 15
6.1.1 Boiler assembly tool size 2.3 . . . . . . . . . . 15
6.2 Recommended wall clearances . . . . . . . . 16
6.3 Installing the boiler on a boiler base or
foundation . . . . . . . . . . . . . . . . . . . . . . . . . 17
7 Boiler block assembly . . . . . . . . . . . . . . . . . . . 18
7.1 Assembly of a boiler block from sections 18
7.2 Joining the boiler block assembly
(delivery unassembled) . . . . . . . . . . . . . . 19
7.3 Setting up the boiler block (assembled
block) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
7.4 Sliding the supply pipe into place . . . . . . 24
7.5 Sealing the immersion sleeve . . . . . . . . . 24
7.6 Leak test . . . . . . . . . . . . . . . . . . . . . . . . . . 25
7.6.1 Carrying out leak test . . . . . . . . . . . . . . . . 25
7.6.2 Sealing leaks . . . . . . . . . . . . . . . . . . . . . . . 25
7.6.3 Supply flange with safety components,
return flange . . . . . . . . . . . . . . . . . . . . . . . 26
7.7 Boiler water connections . . . . . . . . . . . . . 26
2
Logano G315 - Subject to technical modifications
Contents
7.8 Installing fittings and burner door . . . . . . 27
7.8.1 Positioning the draft diverter . . . . . . . . . . 27
7.8.2 Screwing cleanout cover onto rear
section . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
7.8.3 Inserting the flue gas baffle plates . . . . . . 28
7.8.4 Fitting burner door panel . . . . . . . . . . . . . 28
7.9 Boiler outer casing . . . . . . . . . . . . . . . . . . 29
7.9.1 Fitting the profile rails . . . . . . . . . . . . . . . . 29
7.9.2 Attaching the thermal insulation . . . . . . . 29
7.9.3 Fitting side panels and top covers . . . . . 31
8 Connecting the boiler on the flue gas side 33
8.1 Installing a vent pipe sealing collar
(accessory) . . . . . . . . . . . . . . . . . . . . . . . . 33
8.1.1 Installing a flue gas temperature sensor
(accessory) . . . . . . . . . . . . . . . . . . . . . . . . 33
9 Installing the control panel . . . . . . . . . . . . . . . 34
9.1 Installing the control panel . . . . . . . . . . . . 34
9.2 Fitting temperature sensor assembly . . . 34
10 Mounting the burner . . . . . . . . . . . . . . . . . . . . . 36
14 Troubleshooting burner faults . . . . . . . . . . . . 50
15 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
11 System start-up . . . . . . . . . . . . . . . . . . . . . . . . . 37
11.1 Filling the system . . . . . . . . . . . . . . . . . . . . 37
11.2 Commissioning the system . . . . . . . . . . . 38
11.3 Start up the control panel . . . . . . . . . . . . . 38
11.4 Initial burner start-up . . . . . . . . . . . . . . . . . 38
11.5 Raising flue gas temperature . . . . . . . . . . 38
11.6 Commissioning log . . . . . . . . . . . . . . . . . . 39
12 Shutting down the system . . . . . . . . . . . . . . . . 40
12.1 Shutting down the heating system via
the control panel . . . . . . . . . . . . . . . . . . . 40
12.2 Shutting down the system in an
emergency . . . . . . . . . . . . . . . . . . . . . . . . 40
13 System inspection and maintenance . . . . . . 41
13.1 General information . . . . . . . . . . . . . . . . . 41
13.2 Why is regular maintenance important? 41
13.3 Cleaning the boiler with cleaning
brushes . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
13.4 Wet-cleaning the boiler . . . . . . . . . . . . . . 43
13.5 Checking the operating pressure . . . . . . 44
13.6 Refilling with boiler water and purging
the system . . . . . . . . . . . . . . . . . . . . . . . . 45
13.7 Inspection and maintenance reports . . . . 46
Logano G315 - Subject to technical modifications
3
1
Guideline to symbols and safety instructions
1 Guideline to symbols and safety instructions
1.1 Explanation of symbols
Warnings
Warnings are indicated in the text by a warning triangle and a gray background.
In case of danger from electric shock, the exclamation point on the warning triangle is replaced with a lightning symbol.
Signal words at the beginning of a warning are used to indicate the type and seriousness of the ensuing risk if measures for minimizing damage are not taken.
NOTICE indicates that material losses may occur.
CAUTION indicates that minor to medium injury may occur.
WARNING indicates possible severe personal injury.
DANGER indicates a risk to life.
Important information
Important information that presents no risk to people or property is indicated with this symbol. It is separated by horizontal lines above and below the text.
Additional symbols
Symbol Function
B
Æ
Listing/list entry
Listing/list entry (2nd level)
Tab. 1
Sequence of steps
Cross-reference to other points in this document or to other documents
1.2 Safety instructions
Danger from failing to consider your own safety in an emergency such as a fire
B Never risk your own life. Your own safety must always
take the highest priority.
Risk due to oil leaks
B When using oil as the fuel, national regulations hold the
operator responsible for immediately asking a specialist contractor to remedy oil leaks the moment they are discovered.
If you smell gas
B Close the gas shut-off valve. B If you hear gas escaping, evacuate the affected area
immediately.
B Open the windows. B Do not operate any electrical switches or equipment
such as telephones, power plugs and doorbells.
B Extinguish all open flames. B Do not smoke.
Do not use lighters.
B Warn all occupants of the building, but do not ring
doorbells.
B Call your gas utility company and your local heating
contractor from outside the building. If necessary, notify police or the fire department.
If you smell flue gas
B Switch OFF the appliance. B Open windows and doors. B Inform a trained and certified heating contractor.
Danger of electric shock when the control panel is open
B Always de-energize the connection before working on
electrical parts (circuit breaker). Take measures to prevent accidental reconnection.
B Take provisions against unintentional reconnection.
4
Logano G315 - Subject to technical modifications
Guideline to symbols and safety instructions
1
Danger of poisoning from flue gas if supply of combustion air is insufficient
B Safeguard supply of combustion air. B Do not cover or reduce the size of ventilation openings
in doors, windows and walls.
B Safeguard sufficient supply of combustion air also for
appliances installed at a later date, e.g. kitchen exhaust fans, clothes dryers, and air conditioning units with vent to the outside.
B Never operate the appliance if the supply of
combustion air is insufficient.
Combustion air / room air
To prevent corrosion, keep the supply of combustion air / room air free of corrosive substances (e.g. halogenated hydrocarbons that contain chlorine or fluorine compounds).
Danger of explosion of flammable gases
B Only employ a trained and certified contractor to carry
out work on the gas train.
Explosive and easily combustible materials
Never use or store easily combustible materials (paper, thinners, paints, etc.) near the appliance.
Disposal
B Dispose of packaging in an environmentally
responsible manner.
B All heating system components that have to be
replaced should be disposed of in environmentally­responsible manner at an authorized disposal site.
Other important information
B If the system overheats or the gas supply does not shut
off, do not switch off or disconnect the power supply to the pump. Instead, shut off the gas supply somewhere else separate from the heating system.
Installation, conversion
Only have the appliance installed or modified by a trained and certified heating contractor.
Never modify any parts that carry flue gas.
Never close the outlet of safety valves. Water may be expelled from any safety valve during heat-up.
Inspection and maintenance
The operator is responsible for safety and environmental compliance of the heating system.
Sign a maintenance and inspection contract with a trained and certified contractor, covering an annual inspection and demand-dependent maintenance. This guarantees high efficiency and environmentally sound combustion.
Instructing the customer
B Instruct customers about the functions and operation
of the appliance.
B Inform the customer that they must not carry out any
modifications or repairs.
B Only use the boiler for its intended purpose and only
when it is in working order.
Logano G315 - Subject to technical modifications
5
2
Product description
2 Product description
NOTICE: Risk of system damage from use of
incorrect burner. B Only use burners that meet the technical
requirements of the oil/gas-fired boiler Logano G315 (Æ chapter 3, page 11).
The oil/gas-fired boiler Logano G315 has been developed and built employing the latest technologies and safety regulations.
Particular emphasis is placed on ease of operation. Please observe the safety instructions and the operating instructions to ensure optimum safe, economical and environmentally-friendly utilization of your system.
The main components of the Logano G315 oil/gas-fired boiler are:
• Boiler block (Æ Fig. 1, [3]) The boiler block transfers the heat generated by the burner to the boiler water.
• Boiler shell (jacket Æ Fig 1 and 2, [1]), thermal insulation (Æ Fig 1, [2]) The boiler jacket and thermal insulation minimize energy loss.
• Control panel (Æ Fig 1, [4]) The control panel is designed to monitor and control all electrical components of the oil/gas-fired boiler Logano G315.
4
2
3
1
Fig. 1 Oil/gas-fired boiler Logano G315
1 Boiler shell (jacket) 2 Thermal insulation 3 Boiler heat exchanger 4 Control Panel Assembly
1
6 720 642 622-01.1o
Observe all standards and guidelines applicable to the installation and operation of the system in your country.
Please observe the information on the boiler rating plate. These are definitive and must be observed.
To prevent boiler contamination, we recommend installing a dirt trap in the water system.
As a basic rule, flush existing systems before connecting the boiler.
Install a desludging unit in the boiler return to prevent damage to the boiler.
1
1
6 720 642 622-02.1o
Fig. 2 Front jacket
1 Boiler shell (jacket)
6
Logano G315 - Subject to technical modifications
Logano G315 Remarks
Heating oil Liquid propane (LPG) Natural Gas (NG) The Logano G315 boiler can be operated with the specified fuels. Select a burner suitable for use with the fuels specified for the Logano G315 boiler.
The output figures shown in the Table “Technical Data” are nominal power figures.
Carry out maintenance and cleaning procedures annually. Check that the entire system is functioning correctly. Immediately remedy faults.
If heating oil is used, shorter maintenance intervals may be necessary depending on the operating time.
Tab. 2
2.1 Designated use
The Logano G315 oil/gas-fired boilers have been designed for the heating of water.
The Logano G315 can be operated with oil, gas, and combination burners. For a list of the approved burners, please contact Bosch Thermotechnology Corp.
This boiler can be operated with an aquastat, the Logamatic 4000, and other control systems.
Fuels
Product description
2
Logano G315 - Subject to technical modifications
7
2
Product description
2.2 Operating conditions
Thermostream technology is a unique feature of Buderus cast iron boilers. Return water is preheated and mixed within the boiler before it comes in contact with the heating surface of the combustion chamber. The Thermostream technology ensures there is an even temperature distribution in the boiler and avoids condensate forming within the combustion chamber. This unique feature reduces thermal stress, the main cause of
Minimum flow rate none
Minimum return temperature °F ( °C) none
Minimum operating temperature oil boiler
Minimum operating temperature gas boiler
Maximum supply temperature °F ( °C) 2123)/2484) (1003)/1204))
Maximum operating pressure PSI (bar) 87–(6)
For operation with two-stage oil and gas burners Set the partial load stage to 60 %
Time constant of the temperature controller sec 40
Time constant of the monitor/limiter sec 40
1)
1)
°F ( °C) 122–(50)
°F ( °C) 122–(50)
failure of traditional cast iron boilers. The advantage of this technology is the maintenance of the minimum operating temperature of the boiler (Æ Tab. 3); this makes the installation of a shunt pump unnecessary. This way, the costs for the pump itself and its power consumption, as well as possible failure costs are saved. The minimum boiler operating temperature as shown in the table below must be reached within 10 minutes and then be maintained while the burner is running.
Control of all heating
zones with Buderus 4000
2)
External controls (BMS) or
Aquastat control
140–(60)
Tab. 3
1) This temperature has to be reached within ten minutes of the burner starting and has to be maintained whilst the burner is firing.
2) 65 °C with partial load < 60 %
3) The maximum supply temperature is 212 °F (100 °C), if the boiler is operated as hot water boiler.
4) The maximum supply temperature is 248 °F (120 °C), if the boiler is operated as a hot water generator.
2)
A heating zone with a mixing valve improves controllability and is specifically recommended for systems with differing water temperature zones.
This operating condition can be easily achieved by the controls monitoring the boiler temperature and reducing the flow rate through the boiler until the required temperature is reached. This is then maintained by continuing to control flow based on the boiler water temperature. The controls can reduce the flow rate by closing the valves on the mixed heating circuits, modulating the boiler primary pumps, closing the motorized butterfly valves or by having a motorized valve in the boiler return on a single boiler installation. The Buderus 4000 series controls can manage this process or it can be completed by the BMS.
If it is not possible for the control panel to regulate the flow sufficiently to meet this operating condition, then a shunt pump circuit must be fitted to avoid the type of thermal stress that all boilers would experience in these conditions. This shunt pump circuit can be controlled either with a Buderus 4000 control panel or with a third­party controller. Failure to ensure that the operating condition is maintained may lead to thermal stress in the boiler and eventual failure of the sections which would be outside the scope of the warranty.
8
Logano G315 - Subject to technical modifications
2.3 Compliance with standards and regulations
Installation and operation of the system must comply with all applicable codes, regulations and statutory requirements.
Installation, connection of the fuel supply and flue connector, commissioning, connection of the electrical power supply, servicing and repair may only be carried out by a trained or certified heating contractor. Only registered gas fitters may carry out work on the gas train.
The system must be cleaned and serviced once a year. The operation of the complete system must be tested at the same time. Any faults must be corrected immediately.
The design and mode of operation of this boiler must comply with the American National Standard ANSI Z21.13/CSA4.9, latest edition for Gas Fired Low Pressure Steam and Hot Water Boilers.
Other confirmed approvals and certifications are indicated by labels on the boiler.
The heat exchanger has been designed and certified in accordance with the ASME Boiler and Vessel Code, Section IV.
Installation of the boiler must comply with all applicable codes and regulations imposed by the national, Federal or local authorities and bodies. If no specific requirements are defined, in the USA, the latest edition of the National Fuel Gas Code ANSI Z223.1/NFPA 54 applies. In Canada, installation must comply in all respects with the latest edition of the Installation Code for Gas Burning Appliances and Equipment, CAN/CSA-B.149 and the applicable local regulations and requirements for the appliance category. The relevant authorities and regulatory bodies must be informed before installation starts.
Where required by local regulations, the system must comply with the American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers (ASME CSD-1).
The hot water distribution system must comply with all applicable codes and regulations. When replacing an existing boiler, it is important to check the condition of the entire hot water distribution system to ensure safe operation.
In the Commonwealth of Massachusetts, this appliance must be installed by a licensed plumber and gas fitter. Valves external to the boiler must be fitted with T-handles and condensate piping must be installed in accordance with the State Plumbing Code.
Product description
2
Logano G315 - Subject to technical modifications
9
2
Product description
2.4 Additional regulations for installations in the Commonwealth of Massachusetts
(a) For all side wall horizontally vented gas fueled
equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
• INSTALLATION OF CARBON MONOXIDE
DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
– In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
– In the event that the requirements of this subdivision
cannot be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
• APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NPA 720 and be ANSI/UL 2034 listed and IAS certified.
• SIGNAGE. A metal or plastic identification plate shall
be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (½) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
• INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspections, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CRM 5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CRM 5.08(2)(a) 1 through 4:
• The equipment listed in Section 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the board; and
• Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURERS REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM REQUIRED. When the manufacturer of Product Approved side wall horizontally mounted gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for the installation of the equipment and venting shall include:
• Detailed instructions for the installation of the venting system or the venting system components; and
• A complete parts list for the venting system design or venting system.
(d) MANUFACTURERS REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for the venting of flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:
• The referenced “special venting systems” shall be included with the appliance or equipment installation instructions; and
• The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or venting design instructions shall remain with the appliance or equipment at the completion of the installation.
10
Logano G315 - Subject to technical modifications
3 Specifications
34-41/64"
34 41/64" (880 mm)
40 3/4"
40-3/4"
17-23/32"
17 23/32"
(450 mm)
47 3/64"
47-3/64"
(1195 mm)
(1035 mm)
2-13/64"
2 13/64" (56 mm)
VK
6 7/64"
(155 mm)
36 59/64"
(938 mm)
36-59/64"
32-13/64"
Specifications
VK
32 13/64"
(818 mm)
4 11/64"
4-11/64"
(180 mm)
(106 mm)
3
RK
EL
7"
L
K
L
Fig. 3 Technical data for Logano G315 (dimensions in inches (mm))
EL Drain valve (Rp ¾) LKBoiler heat exchanger length L Overall boiler length RK Return connection on the boiler VK Supply connection on the boiler
1) With the drain valve (EL), you may only drain the system, not fill it.
2) The filling of the boiler and the system must be undertaken on a separate connector on the return line.
3) The flange corresponds to the order reduced to 212 (DN100), 176 (DN80) or 149 (DN65).
1)
2)
3)
6 720 642 621-48.1o
Logano G315 - Subject to technical modifications
11
3
Specifications
Logano G315
Boiler capacity Unit 105 140 170 200 230
Number of boiler sections 5 6 7 8 9
Nominal output Btu/hr
(kW )
Combustion output Btu/hr
(kW)
Boiler overall length (L) inches
(mm)
Boiler block length (L
) inches
K
(mm)
Fitting clearance, boiler section (width × height × depth)
Fitting clearance, boiler block (width × height × length)
inches
(mm)
inches
(mm)
Combustion chamber length inches
(mm)
Combustion chamber diameter
inches
(mm)
293.500 –
358.000
(86 – 105)
314.300 –
387.300
(92.1 –
113.5)
44-19/64
(1125)
38-3/16
(970)
31-7/64
(790)
362.000 –
477.800
(106 – 140)
387.300 –
516.700
(113.5 –
151.4)
50-19/32
(1285)
44-31/64
(1130)
481.000 –
580.200
(141 – 170)
515.300 –
625.900
(151.0 –
183.4)
56-57/64
(1445)
50-25/32
(1290)
28-1/32 × 36-25/32 × 6-19/64
(712 × 934 × 160)
28-1/32 × 39-1/8 × L
(712 × 994 × LK)
37-13/32
(950)
43-45/64
(1110)
15 3/4
(400)
583.600 –
682.600
(171 – 200)
624.900 –
734.100
(183.1 –
215.1)
63-3/16
(1605)
57-3/32
(1450)
K
50
(1270)
686.000 –
784.990
(201 – 230)
734.400 –
846.000
(215.2 –
247.9)
69-31/64
(1765)
63-25/64
(1610)
56-19/64
(1430)
Burner door thickness inches
(mm)
Vent connection diameter inches
(mm)
Weight, net
1)
Boiler water content gal.
Gas capacity gal.
Flue gas temperature, partial load (60 %)
(°C)
Tab. 4
12
lb.
(kg)
(l)
(l)
°F
1.20
(543)
37.75
143
38.83
147
178.6
(137)
1.395
(631)
45.25
171
47.82
181
280.4
(138)
4-59/64
(125)
7"
(178)
1.59
(719)
52.5
199
56.8
215
176.8
(136)
1.78
(807)
60
227
65.78
249
269.6
(132)
1.975
(895)
67.5
255
69.48
263
285.8
(141)
Logano G315 - Subject to technical modifications
Specifications
Logano G315
Boiler capacity Unit 105 140 170 200 230
3
Flue gas temperature, full load
°F
(°C)
323.6 – 365
(162 – 185)
309.2 –
359.6
321.8 – 356
(161 – 180)
(154 – 182)
Flue gas mass flow rate, oil, partial load (60 %)
Flue gas mass flow rate oil,
2)
full load
Flue gas mass flow rate, gas, partial load (60%)
Flue gas mass flow, gas,
2)
full load
CO
content, oil % 13.0
2
lb./s
(kg/s)
lb./s
(kg/s)
lb./s
(kg/s)
lb./s
(kg/s)
0.0624
(0.0283)
0.0862 –
0.1063
(0.0391 –
0.0482)
0.0626
(0.0284)
0.0864 –
0.1067
(0.0392 –
0.0484)
0.0831
(0.0377)
0.1063 –
0.1418
(0.0482 –
0.0643)
0.0836
(0.0379)
0.1067 –
0.1422
(0.0484 –
0.0645)
0.101
(0.0458)
0.1413 –
0.1717
(0.0641 –
0.0779)
0.1014
(0.0460)
0.1418 –
0.1722
(0.0643 –
0.0781)
CO2 content, gas % 10
Required draft PSI
(Pa)
(0)
316.4 –
348.8
334.4 – 374
(168 – 190)
(158 – 176)
0.1188
(0.0539)
0.1713 –
0.2013
(0.0777 –
0.0913)
0.1193
(0.0541)
0.172 –
0.2019
(0.0780 –
0.0916)
0.1367
(0.0620)
0.2013 –
0.2319
(0.0913 –
0.1052)
0.1371
(0.0622)
0.2022 –
0.2328
(0.0917 –
0.1056)
0
Fireside pressure drop in. W.C.
(mbar)
Maximum permissible supply temperature
3)
Maximum permissible operating pressure
°F
(°C)
PSI
(bar)
0.112 –
0.165
(0.28 – 0.41)
0.185 –
0.317
(0.46 –
0.79)
0.285 –
0.522
(0.71 –
1.30)
248
(120)
87
(6)
0.538 –
0.715
(1.34 –
1.78)
Tab. 4
1) Weight with packaging approx. 6 – 8 % higher.
2) The details relate to the upper and lower rated output range.
3) Safety limit (high limit safety cut-out). Maximum possible supply temperature = safety limit (STB) – 32 °F ( – 18 K). Example: Safety limit (STB) = 212 °F (100 °C), max. possible supply temperature = 212 – 32 = 180 °F (100 – 18 = 82 °C).
0.530 –
0.711
(1.32 –
1.77)
Logano G315 - Subject to technical modifications
13
4
Scope of delivery
4 Scope of delivery
The Logano G315 can be delivered either as a pre­assembled block or in loose sections.
B Check that the packaging is undamaged on delivery. B Check that the delivery is complete.
4.1 Logano G315 - delivery as a pre-assembled block
Component Qty Packaging
Boiler block with burner door and supply pipe
Jacket pack (according to boiler rating)
Thermal insulation 1 bag
Tab. 5
4.2 Logano G315 – delivery unassembled
Component Qty Packaging
Front and rear section, 3 intermediate sections as well as burner door
Intermediate sections – (depending on boiler size)
Fittings and draft diverter 1 Box
Tie rods and supply pipe 1 Bundle
Jacket pack (according to boiler rating)
Thermal insulation 1 Bag
Tab. 6
1 Pallet
1 Cartons
1 Pallet
1 Pallet
1Cartons
5 Transporting the boiler
Use suitable equipment to transport the individual boiler sections (delivery unassembled) and other individual parts.
WARNING: Risk of injury from improperly secured boiler sections.
B Use only suitable means of transportation
when handling the boiler sections, e.g. a heavy duty hand truck.
B Secure the individual boiler sections to
prevent them from sliding off during transport.
NOTICE: Risk of system damage from impacts.
B The standard delivery of the Logano G315
oil/gas-fired boiler contains components that are sensitive to shock.
B During handling protect all electronic and
other components against impact.
B Please observe the transport instructions
on the packaging.
NOTICE: Risk of system damage from contamination.
B If you intend to keep the boiler in storage
once it has been assembled, observe the following:
B Protect the boiler connections against
contamination by sealing them off or covering them.
Dispose of packaging in an environmentally responsible manner.
14
Logano G315 - Subject to technical modifications
6 Positioning the boiler
Positioning the boiler
6
This chapter describes how to properly position the Logano G315.
NOTICE: Risk of system damage from freezing.
B Install the system in a room free from the
danger of freezing.
6.1 Tools and auxiliary materials
The following tools and auxiliary materials are required for the boiler assembly (the listed items must be provided by the installer):
• Boiler assembly tool 2.3 (Æ Fig. 4)
• Installation kit (accessory)
• Steel hammer and wooden or rubber mallet
• Half-round bastard file
• Screwdriver (Philips and flat head)
• Flat chisel
• Metric wrenches
• Support wedge, flat iron
• Cleaning rags and cloth
• Fine emery cloth
•Wire brush
•3-in-1 oil
• Solvent (gasoline, mineral spirits)
• Spirit level, tape measure, chalk, straight edge
• Blanking flange with vent facility (for pressure test)
6.1.1 Boiler assembly tool size 2.3
4 5
L
2
L
1
L
2
6
3 2 1
Fig. 4 Boiler assembly tool size 2.3
1 Mating flange 2 Additional flange 3 Compression unit (pressure flange with clamping nut) 4 Tie rod 5 Extension 6 Wedge (size 2.3)
121-1/4" (3080 mm)
L
1
31-1/2" (800 mm)
L
2
Boiler
sections
Assembly tool(s) per boiler hub
Extension
piece per
boiler hub
6 720 642 623-03.1o
Length (total)
in inches
(mm)
Logano G315 - Subject to technical modifications
5 – 9 1 3
Tab. 7
For the correct arrangement of the flange when performing the assembly procedure, refer to page 22.
121-1/4
(3080 mm)
15
6
Positioning the boiler
6.2 Recommended wall clearances
34-41/64"
34 41/64"
15-3/4"
15 3/4"
(400 mm)
(880 mm)
29 1/2"
29-1/2"
AB + 4"
(~ 750 mm)
Boiler capacity Clearance A in inches (mm)
Boiler
MBH (kW)
358 – 686
(105 – 230)
sections
5 – 9 59 (1500) 39-3/8 (1000)
Recommended Minimum
Tab. 8
If you do not observe the recommended minimum clearance (Æ Fig. 5), you will not be able to use the cleaning kit (accessory). Alternatively shorter cleaning devices or wet cleaning may be used.
K
L
(AB+100 mm)
AB
A
6 720 642 621-02.1o
Fig. 5 Installation room with boiler
Observe the recommended wall clearances for complete opening of the burner door, for boiler installation and for cleaning and maintenance Fig. 5.
The burner door can be hung with the hinges on the right or left.
When installing your boiler maintain the recommended minimum dimensions. Select the recommended clearances between wall and boiler for easy access for installation, maintenance and service work.
The wall clearance on the hinge side must be at least the burner projection (AB). A distance of AB +4 inches (AB + 100 mm) from the wall is recommended.
The length L or boiler rating Æ Spare parts, page 51.
depends on the number of boiler sections
K
16
Logano G315 - Subject to technical modifications
Positioning the boiler
6
6.3 Installing the boiler on a boiler base or foundation
When setting up the boiler, we recommend you observe the specified wall clearances for improved installation and maintenance (Fig. 5).
It is advisable to place the boiler on a 2 – 4 inch (50 – 80 mm) tall base (Fig. 6, [1]). The base should be completely flat and level. The front edge of the boiler should be flush with the edge of the base.
A silencing boiler base is available as optional equipment from Buderus.
If this optional boiler base is not used, a concrete foundation can be constructed on-site. When building the foundation, a 3 15/16 x 1 31/32 x 5/16 inches (100 x 50 x 8 mm) steel angle or 3 15/16 x 13/64 inches (100 x 5 mm) steel flat should be incorporated (Æ Fig. 6 and Tab. 9).
1
2...4"
34-3/4"
34 3/4"
(~ 880 mm)
L1
Number of
boiler sections
5 38-3/16 (970) 28-3/4 (730)
6 44-31/64 (1130) 35-1/32 (890)
7 50-25/32 (1290) 41-21/64 (1050)
8 57-3/32 (1450) 47-41/64 (1210)
9 63-25/64 (1610) 53-15/16 (1370)
(base)
in inch (mm)
L2
(steel section)
in inch (mm)
Tab. 9 Foundation dimensions and lengths of steel flats
or steel angles
(~ 50...80 mm)
4"
(100 mm)
4"
(100 mm)
21 1/4"
(540 mm)
Fig. 6 Base dimensions
2
L
3-/2"
3 1/2"
(~ 90 mm)
6 720 642 621-01.1o
1
L
Logano G315 - Subject to technical modifications
17
7
Boiler block assembly
7 Boiler block assembly
WARNING: Risk of injury from improperly
secured boiler sections. B Use only suitable means of transportation
when handling the boiler sections, e.g. a heavy duty hand truck. When handling, secure the boiler sections to the means of transport to prevent them slipping.
87
6
5
4
3
9
10
11
2
8
1
6 720 642 621-03.1o
Fig. 7 Boiler heat exchanger
Key to Fig. 7: 1 Boiler base or foundation
2 Draining 3 Exhaust Manifold 4 Rear section 5 Return connection 6 Supply connection 7 Intermediate sections 8 Tie rod 9 Directional arrow 10 Front section 11 Burner door with burner plate
Depending on the type of delivery, we distinguish between delivery unassembled and as a ready assembled block. When delivered as a ready­assembled block, the boiler is assembled and checked for leaks prior to despatch. If, because of physical limitations, a boiler block cannot be assembled as a complete unit, delivery unassembled would enable assembly on site.
For details of assembling the remainder of the
boiler if the heat exchanger is delivered pre­assembled, see Æ Chapter 7.3, page 23.
7.1 Assembly of a boiler block from sections
WARNING: Risk of injury from inadequately
secured boiler sections. B Secure boiler sections during assembly
and take measures to prevent them from tipping over. If a hoisting tool is available, this can be used to set up the boiler sections safely.
The boiler block is always installed starting from the rear with the rear section (Fig. 7, [4]) and working towards the front. The front section (Fig. 7, [10]) is always fitted last.
Observe the directional arrows (Fig. 7, [9]) during assembly and carry this out in accordance with the following instructions and illustrations.
Fig. 8 Rear section
18
Logano G315 - Subject to technical modifications
Boiler block assembly
7
7.2 Joining the boiler block assembly (delivery unassembled)
Remove nuts and washers from the studs on the hubs of the boiler sections before attaching the rear section and front section.
B Set up the rear section and secure it against tipping. B File down any burrs on the hubs (Æ Fig. 9).
Fig. 9 Remove burrs
B Clean the packing grooves where required using a wire
brush and cloth (Fig. 10, [3]).
B Clean the hub sealing faces (Fig. 10, [1 and 2]) with a
rag soaked in solvents or gasoline.
WARNING: Health hazard from noxious vapors released from material handling, such as solvents, primers or sealant.
B Ensure adequate ventilation of the
installation area.
B Please note the handling and safety
instructions of the product used.
B Evenly coat the hub sealing faces with sealant.
Fig. 10 Preparing the packing grooves and hubs
The next step involves preparing the nipples that will eventually seal the boiler sections.
B Clean nipple with a rag soaked in solvents or gasoline
and coat evenly with sealant.
B Insert the nipple straight into the upper (Sz. 2,119/50)
and lower (Sz. 0, 57/50) hub of the rear section and hammer home securely with alternate heavy blows. The upper nipple (Fig. 11, [1]) and the lower nipple (Fig. 11, [2]) should protrude approx. 28 mm out of the corresponding hub once they have been driven in.
B Remove any burrs with a file.
Logano G315 - Subject to technical modifications
Fig. 11 Driving nipples home
19
7
Boiler block assembly
The packing grooves (Fig. 12, [1]) must be clean and dry to enable the sealant rope to adhere properly.
B Coat the packing grooves with adhesive (primer).
Fig. 12 Coat the packing grooves with adhesive
B Insert the flexible sealant rope (Æ Fig. 13, [2]) on the
front of the rear section, starting around the upper hub, into the packing grooves (Æ Fig. 13, [1]) and press in lightly. At the butt joints, overlap the sealant rope by approx. 2 cm and press firmly together.
B Unroll the required length of sealant rope from the
spool supplied.
B Peel the backing paper from the sealant rope when
inserting into the packing groove (do not stretch).
Preparation of the first intermediate section:
B File down any burrs on the hubs (as shown in Fig. 9). B The packing springs must be clean and dry. Clean if
necessary.
B Clean the hub sealing faces with a rag soaked in
solvents or gasoline.
B Evenly coat the hub sealing faces with sealant (Fig. 14,
[1]).
B Coat the packing springs with adhesive (primer)
(Fig. 14, [2]).
Fig. 14 Preparing the centre section
To make installation easier, place the boiler section to be fitted onto the nipple on the upper hub first. Once this has been done, the boiler section can be aligned with the lower hub.
Fig. 13 Inserting sealant rope
20
Logano G315 - Subject to technical modifications
Boiler block assembly
7
The directional arrow (Æ Fig. 15, [3]) must point in the direction of the rear boiler section.
B Position the intermediate section so that the upper and
lower hubs (Æ Fig. 15, [2 and 4]) fit onto the nipples in the rear section.
B Pound first intermediate section onto the rear section
using a wooden or a rubber mallet (Æ Fig. 15, [1]).
2
1
3
4
6 720 642 621-11.1o
NOTICE: Assembly tool damage due to loose screw connections of the tie rods.
B Always check the tie rods before each use
and retighten as necessary. The tie rod is correctly positioned if it is fully inserted and no threads are showing (Æ Fig. 16, [2]).
B Always keep the threads (Æ Fig. 16, [1])
clean. Dirty threads may damage the assembly tool during compression.
Fig. 15 Pound intermediate section in place
Before the nipples are inserted in the next intermediate section, the part-assembled boiler block must be compressed using the boiler assembly tool.
NOTICE: The boiler can be damaged by pulling the boiler sections together incorrectly or due to excessive compression.
B Ensure that the nipples are positioned
straight in the boiler hubs after being pounded in and that they have not been compromised.
B Never compress more than one nipple
joint at a time.
B Stop compressing the sections when the
boiler hubs meet.
Fig. 16 Boiler assembly tool 2.3
CAUTION: Danger of accident from material fatigue. Improperly used or poorly maintained assembly tools may fail.
B Never work directly in front of the
assembly tool while it is being tensioned.
B Ensure that no one is standing in front of
the assembly tool.
NOTICE:
B Only boiler assembly tools size 2.3 may be
used (Fig. 4, page 15 and Fig. 17, [1 and 2]).
Logano G315 - Subject to technical modifications
21
Loading...
+ 47 hidden pages