Buderus Logano G125 BE US/CA, Logano G125/21-BE, Logano G125/28-BE, Logano G125/34-BE Installation And Service Instructions Manual

Installation and Service Instructions
Low Emissions and High Efficiency Oil Boiler
C
Logano G125 BE US/CA
Read carefully prior to installation, maintenance and service.
6 720 804 880 (2012/10) EN-US
Table of Contents
1 Safety Considerations and Symbol Descriptions . . . . . . . . . . . . . . . . . . . 4
1.1 Regarding this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Guideline of Notices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Observe the following Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3.1 Installation Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3.2 Boiler Room Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4 Tools, Materials and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.5 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 Product Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1 Product Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2 Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Technical Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1 Technical Data less Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2 Operating Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.2.1 General Operating Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4 Packaging and Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5 Moving the Boiler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.1 Reducing Boiler Weight for Transportation. . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.2 Lifting and Carrying the Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.3 Moving the Boiler with the Boiler Cart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6 Placing the Boiler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.1 Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.2 Reversing the Burner Door Swing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.3 Installation of boiler Feet (Components of B-Kit) . . . . . . . . . . . . . . . . . . . . . . . 17
6.4 Placement of the Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7 Boiler Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
7.1 Installation of Venting Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
7.1.1 Vertical Venting Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
7.1.2 Horizontal Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
7.2 Installation of Combustion Air Supply System. . . . . . . . . . . . . . . . . . . . . . . . . 28
7.3 Installation of Water Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
7.3.1 B-Kit Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
7.3.2 Installation of Boiler Drain (B-Kit Component) . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.3.3 Installation of System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.4 Filling and Checking for Water Leaks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
7.5 Installation of Oil Line. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.6 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
7.6.1 Installation of Aquasmart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
7.6.2 Control System Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
7.6.5 Strain Relief Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.6.6 Top Rear Panel Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
2
Logano G125 BE - Specifications subject to change without notice.
Table of Contents
8 Placing the Boiler in Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
8.1 Setting the Initial System Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
8.2 Checking the Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
8.3 Check Position of Flue Baffles (Room Air Operation). . . . . . . . . . . . . . . . . . . . . 40
8.4 Check Position of Flue baffle Plates (Outside Air Operation) . . . . . . . . . . . . . . . . 41
8.5 Prepare System for Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
8.6 Start-up of Control and Burner. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
8.7 Guidelines for Burner Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
8.8 Adjusting Stack Temperatures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
8.8.1 Adjusting/Removing Flue Baffles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
8.8.2 Removing Flue Blocking Plate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
8.9 Testing of the Manual Reset High Limit (STB) of Logamatic controls . . . . . . . . . . . 44
8.10 Installation of Front Burner Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
8.11 Detailed Start-up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
9 Taking the Boiler Out of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
9.1 Normal Boiler Shut-down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
9.2 Emergency Shut-down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
10 Boiler Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
10.1 Why do maintenance?. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
10.2 Prepare Boiler for Cleaning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
10.3 Boiler Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
10.3.1Cleaning the Boiler with Brushes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
10.3.2Wet Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
10.3.3Inspecting the combustion air hose (sealed combustion only) . . . . . . . . . . . . . . . . . . 50
10.4 Testing System Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
10.5 Testing Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
10.6 Inspection and Maintenance Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
11 Restoring System Lock-outs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
12 Piping Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
13 Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
14 Burner Wiring Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
15 Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Logano G125 BE - Specifications subject to change without notice.
3
1
Î
Safety Considerations and Symbol Descriptions
1 Safety Considerations and Symbol Descriptions
1.1 Regarding this Manual
This document contains important information regarding safe and proper installation, operation and maintenance of the boiler.
The high tech G125 BE boiler is designated as a hot wa­ter heating boiler.
The Installation and Maintenance Instructions are direct­ed to the installing contractor who has professional knowledge regarding boiler installation and mainte­nance.
1.2 Guideline of Notices
Two levels of danger are identified by the following warning labels:
DANGER
Denotes a possible severely dangerous
WARNING!
CAUTION!
situation where, without proper caution, bodily injury or loss of life may result.
DANGER OF INJURY/SYSTEM DAMAGE
Denotes a possible dangerous situation that can lead to mild to moderate bodily in­jury or physical damage.
1.3 Observe the following Symbols
The local and state codes and regulations must be ob­served during the installation of the boiler:
– The local building code requirements regarding
placement, combustion air and venting and chimney system must be followed.
Follow applicable electrical code requirements.
Follow the local code and standards regarding safe
boiler operation.
NOTICE
Use only original Buderus spare parts. Buderus can not be held liable for dam­age caused by non-Buderus parts.
NOTICE
The boiler installation must be performed by a qualified installer in accordance with regulations put forth in NFPA-31 Installa­tion of Oil-Burning Equipment. The instal­lation must comply with all local and national codes, regulations and authori­ties having jurisdiction regarding the in­stallation of oil fired boilers.
For Canada refer to the guidelines of CSA/CGA-B149.1 and 2 Installation Codes.
NOTICE
Application comment for optimum use of equipment and adjustment as well as useful information.
Cross reference
Designated by means of an arrow Î , refers to a notice in another document.
4
Logano G125 BE - Specification s subject to change without notice.
Safety Considerations and Symbol Descriptions
1
1.3.1 Installation Guidelines
DANGER TO LIFE
from electric shock
CAUTION!
z Do not work on electrical components
unless you have the required qualifica­tion and applicable certification.
z Do not work on electrical components
unless you have the required qualifica­tion and applicable certification.
z Prior to opening the control: shut
down the power supply and prevent from accidental reactivation.
z Observe all applicable installation
guidelines.
1.3.2 Boiler Room Guidelines
DANGER TO LIFE
from poisoning.
CAUTION!
Insufficient combustion air can result in dangerous operation if combustion air is taken from indoors.
1.4 Tools, Materials and Accessories
For the installation and maintenance of the boiler you will need typical tools used in .
In addition, the following components are useful:
Boiler cart with rope or Buderus boiler cart.
Wood blocking.
Cleaning brushes and/or chemical cleaning agents
for wet cleaning.
1.5 Disposal
z Please dispose of any trash in an environmentaly
friendly fashion.
z Please discard properly of any heating system relat-
ed components.
CAUTION!
z Please observe that combustion air
openings are not reduced in size or closed.
z Make sure that no mechanical air
openings or devices remove combus­tion air from the boiler room such as central vacuum systems, dryers and air conditioning appliances.
z Make sure that the boiler is connected
to a chimney or horizontal venting sys­tem that is capable of handling the slight positive breeching pressure.
z If any of these problems have not been
corrected, one cannot operate the boil­er.
z Make the end-user aware of these
guidelines and their potential danger.
FIRE DANGER
due to flammable or liquid materials.
z Make sure that flammable and liquid
materials are not in the close vicinity of the boiler.
Logano G125 BE - Specifications subject to change without notice.
5
2
Product Description
2 Product Description
2.1 Product Applications
The boiler is designated for use as a hot water heating boiler for space heating applications and to heat domes­tic hot water by means of an indirect fired tank for single and multi-family homes and small commercial heating applications.
Please observe the technical data on the rating label and technical information (Î Chapter 3, page 7), to en­sure proper application of this product.
2.2 Product Description
The G125 BE is a oil fired low temperature boiler with boiler water temperature regulation.
The boiler consists of:
Optional Logamatic control
Boiler jacket
Boiler block with insulation
Burner
The optional Logamatic control manages most control functions in a heating system.
As an alternative, a Aquasmart control can be used for boiler control.
The boiler jacket serves to reduce energy loss and as a noise reducing agent.
The boiler block transfers the heat generated by the burner to the boiler water. The insulation reduces the stand-by losses.
1
Fig. 1 Boiler G125 BE US/CA
1 Control panel
2 Boiler jacket
3 Boiler block with insulation
4 Burner door cover
5 Burner
2
3
5
4
7 747 010 678-01.1RS
6
Logano G125 BE - Specification subject to change without notice.
3 Technical Information
3.1 Technical Data less Burner
25 1/2"
23 1/2"
14 1/2"
Technical Information
12 1/4"
3
Fig. 2 Dimensions and connections (measurements in inches)
Connections (For Measurements see following tables):
VK = Boiler supply VS = Connection (plugged) RK = Boiler return RS = Connection (plugged) EL = Boiler drain (Connection for drain valve) VSL = Connection (plugged)
Boiler Model G125/21-BE G125/28-BE G125/34-BE
Number of boiler blocks 34 5
Heating Capacity (Gross Output) MBtu/hr 72 96 116
Net IBR MBtu/hr 63 83 101
Boiler water content Gal 8.7 10.8 12.9
Fireside volume cu.ft. 1.20 1.75 2.21
Oil firing rate GPH .60 .80 1.0
Fireside pressure drop psi 0.00058 – 0.00145
Permissible max. supply temperature
1
°F 230
Allowable operating pressure psi 58
Maximum Reset High Limit for temperature
s 40
sensor and overheat thermostat (STB)
Table 1 Technical Data for G125 BE less burner
1
High limit (overheat thermostat STB) Permissible maximum supply temperature = High limit (STB) – 32 °F e.g.: High limit (STB) = 212 °F, maximum permissible supply temperature = 212 – 32 = 180 °F Select your high limit (STB setting) according to your local codes and requirements.
Logano G125 BE - Specifications subject to change without notice.
7
3
Technical Information
Boiler Model G125/21-BE G125/28-BE G125/34-BE
Total boiler length (L) 34 5/8” 39 3/8” 44”
Boiler block length (LK) 21 1/8” 25 3/4” 30 1/2”
Combustion chanber length 16” 20 1/2” 25 1/4”
Firebox diameter 10 5/8”
Burner door thickness 3 1/2”
Distance between boiler feet (FL) 11 3/8” 16 1/8” 20 7/8”
Dry weight
Table 2 Dimensions, Weight and other Data for G125 BE less burner
1
Weight incl. packaging material approx 6 – 8% more.
1
386lbs 459lbs 513lbs
3.2 Operating Conditions
Maintain the operating requirements listed on the follow­ing page for long and trouble free operation of the boiler. Proper and timely maintenance procedures must be fol­lowed.
SYSTEM DAMAGE
CAUTION!
If these operating requirements are not followed, it can lead to premature failure can result and cause permanent damage to the boiler.
z Follow the instructions on the rating la-
bel and those in the manual.
8
Logano G125 BE - Specifications subject to change without notice.
Technical Information
3.2.1 General Operating Requirements
Operating Conditions
Minimum Boiler tempera-
ture
Systems controlled by R2107 controls for outdoor reset operation
No requirements
Operating conditions are met
with R2107 control
150 °F
2
3
Table 3 General Operating Requirements
1
A heating circuit equipped with a motorized mixing valve improves the controllability of that sub-system and is specifically recommended when requiring different water temperatures.
2
In case the control system has no influence over the flow in a heating circuit (for instance using the Pumplogic feature of the R2107), then one should achieve a minimum supply temperature of 122 °F within 10 minutes after burner start-up by means of reducing (or interrupting) the water flow through the boiler.
3
Minimum setting on the adjustable high limit or Aquasmart: During burner operation one should achieve the minimum boiler temperature within 10 minutes after burner start-up by means of flow reduction and one should maintain this temperature.
Boiler Shutdown Boiler Shutdown/
Mixed temperature
Automatic with Logamatic
R2107
No requirement, yet beneficial with low temperature boiler with 130/113 °F system design
Necessary with:
Radiant floor applications
Systems with large water con-
tent > 115 gal/100,000 Btu/hr
Systems controlled by Aquasmart or R2109
Possible, provided the boiler op-
erates after total shut-down for
at least 3 hours.
1
Minimum return temperature
No requirement
Necessary Necessary for:
– Systems with large water
content > 115 gal/100,000 Btu/hr: 130 °F
– Firing with modulating burn-
ers: 130 °F
3
Logano G125 BE - Specifications subject to change without notice.
9
3
Technical Information
3.2.2 Requirements for Boiler Room and Surroundings
Operating Conditions Comments – Detailed Information
Boiler room temperature +40 to +104 °F
Relative humidity max. 90 % No condensate or dampness in boiler room.
Dust No excess amounts of dust should be present in the boiler room, e.g.:
– No sheet rock or construction dust.
The available combustion air can not contain dust or other particles/ use of an air filter might be needed, e.g.:
Combustion air from nearby roads with high dust levels.
Combustion air from nearby production facilities such as chemical plants &
shops.
– Airborne particulates.
Halogenated Hydrocarbons contamination
Fans, removing air from boiler room
Animals The boiler room and especially the air inlet openings for combustion air must be
Fire Protection Maintain proper clearances to combustible materials as required per local code.
Flood Zone Conditions Separate the fuel supply and electrical power supply from the boiler during flood
Combustion air must be free of halogenated hydrocarbons components.
– Eliminate any chemical compound such as paints, lacquers, thinners, clean-
ing agents. If not possible, provide fresh outside air for combustion.
Please observe the following:
Product information of Buderus catalog.
Also observe guidelines in K3 chapter of Buderus catalog.
Avoid forced air removal by mechanical means during boiler operation such as:
Bathroom exhaust fans
Dryer
Air-conditioning equipment
kept free from animals entering by means of grills.
Maintain a minimum distance of 16”. Do not store flammable materials near the boiler.
conditions. Replace the boiler components such as insulation, electrical and con­trol components afterwards.
Table 4 Boiler room and surroundings
3.2.3 Combustion Air Requirements
Operating Conditions Boiler capacity (combine total boiler ca-
pacity for multiple units)
Two air inlet openings from out­side: one top, one near bottom
Table 5 Observe local codes and regulations for combustion air requirements
< 170,000 Btu/hr At least 43 square inch
> 170,000 Btu/hr At least 43 square inch plus 2.5 square inch per 10,000
Btu/hr, if the output is higher than 170,000 Btu/hr.
3.2.4 Fuel Conditions
Country All Countries
Fuel #2 Fuel Oil ASTM D396-05 Type 2
Comments No other fuel may be used with this burner.
Burner requires annual service and cleaning. Verify each time that the complete heating system is in working order. Defects must be remedied immediately.
Table 6 Permitted fuel types
Cross area required
10
Logano G125 BE - Specifications subject to change without notice.
Technical Information
3
3.2.5 Requirements for Power Supply
Operating Conditions Comments – Detailed Information
Main power supply 120 V Provide proper grounding for equipment and personal protection.
High amp protection 10 A
Frequency 60 Hz
Protection Group all equipment per local code
Table 7 Power supply
3.2.6 Conditions Pertaining to Piping and Water Quality
Operating Conditions Comments – Detailed Information
Operating pressure (over pres­sure)
Allowable test pressure 45 – 75 psi
Adjustable temperature limit TR122 – 194 °F
Manual reset high limit 210 °F In combination with Beckett AquaSmart the limit value (210 °F) may not be excee-
Water quality Initial fill water and make-up water should be potable water type quality. A pH
12 – 58 psi Maximum pressure is 30 psi based on supplied relief valve
ded.
range of 8.2 to 9.5 is desired.
Table 8 Piping and water quality
Logano G125 BE - Specifications subject to change without notice.
11
4
Packaging and Components
4 Packaging and Components
z Check the packaging for concealed damage.
z Check the packaging for completeness. Contact your
wholesaler in case of missing parts.
Component Qty Packaging
Boiler block 1 Pallet
Boiler jacket, installed on boiler
Burner door and burner door cover installed on boiler block
Buderus oil burner mounted on cus­tomized burner door
B-Kit-Components: Supply manifold (1¼" NPT) 30 psi relief valve (¾") boiler drain Pressure/temperature gauge (1¼" NPT × R1¼) conversion nipple
(parallel to NPT) 90°-elbow (1¼" NPT) 90°-elbow (¾" NPT) Burner mounting studs and washers Screw in feet
14Plastic pack-
aging with boil­er
Control panel, alternative Aquas­mart control (ordered separately)
Tigerloop oil filter 1 included with
Taco 007 circulator pump w/flanges
Technical documents 1 Plastic pack-
Table 9 Packaging and components
Cardboard box
boiler package
aging w/boiler
12
Logano G125 BE - Specifications subject to change without notice.
5 Moving the Boiler
This chapter describes how to move the boiler.
SYSTEM DAMAGE
due to bumps.
CAUTION!
z Protect the boiler from bumps and
rough treatment.
NOTICE
z Protect the boiler from connections
from damage and dirt, when the boiler is not installed immediately.
NOTICE
Please dispose of the packaging in an en­vironmentally friendly fashion.
Moving the Boiler
5
5.1 Reducing Boiler Weight for Transportation
One can reduce boiler weight by removing the front cov­er and burner door itself.
z Remove the screws holding the front cover in place.
z Lift up the front cover slightly and remove.
z Disconnect burner cable from burner control before
removing the burner door.
z Open burner door by removing the two burner door
bolts.
z Lift burner door from hinges.
NOTICE
Fig. 3 Removing the front cover
z Protect the burner door and the burner
tube from damage and dirt when the burner door is removed from the boiler.
Logano G125 BE - Specifications subject to change without notice.
Fig. 4 Removal of burner door
13
5
Moving the Boiler
5.2 Lifting and Carrying the Boiler
NOTICE
The boiler is secured to the pallet with two bolts.
z Remove the bolts from pallet before
lifting the boiler.
The boiler can be picked up at the hand grips located along the lower jacket panels.
BODILY DANGER
due to carrying of heavy loads.
CAUTION!
z Lift and carry the boiler with at least
two people at the designated hand grip positions.
5.3 Moving the Boiler with the Boiler Cart
BODILY DANGER
if the product is not properly secured to
CAUTION!
z Lift up the boiler from the rear side by using moving
equipment (e.g. Buderus card or other dolly).
z Secure the boiler to the cart.
z Move the boiler to the job location.
the cart.
z Use proper moving equipment such as
the Buderus cart or other dolly.
z Secure the boiler to the cart and move
the boiler to the job location.
Fig. 5 Lifting and carrying the boiler
NOTICE
By tipping the cart you can install the boil­er feet (Î Chapter 6.3, page 17).
You can order a Buderus cart from your local wholesaler.
14
Fig. 6 Moving the boiler with a Buderus cart
Logano G125 BE - Specifications subject to change without notice.
6 Placing the Boiler
This chapter discusses how to place the boiler in the boiler room.
SYSTEM DAMAGE
due to freezing temperatures
CAUTION!
6.1 Clearances
Position the boiler while observing the clearances in (Î Fig. 7). Access to the boiler is reduced when reduc­ing these clearances.
The boiler foundation must be level and sufficiently strong.
The burner door is factory installed right swinging. You­can reverse the door swing in the field.
z Place the boiler in a frost free room.
Placing the Boiler
6
Distance
A Recommended 51 1/8"
minimum 39 3/8"
B Recommended 27 1/2"
minimum 15 3/4"
C Recommended 15 3/4"
minimum 3 7/8"
L see Chapter 3 „Technical Information“
Table 10 Recommended and minimum clearances
(Measurement in Inches)
NOTICE
Smaller clearances must abide with state and local code. The boiler is approved for 6" side clearances. A minimum distance of 18" to combustible materials must be maintained per NFPA 31.
Floor material must comply with NFPA 31.
Fig. 7 Clearance dimensions for G125 boilers
NOTICE
Observe required distances to other com­ponents such as water piping, venting and other components.
Logano G125 BE - Specifications subject to change without notice.
15
6
Placing the Boiler
6.2 Reversing the Burner Door Swing
The burner door hinges are factory installed on the right handside the burner door swings to the right. You can adjust the hinges so that the burner door swings to the left in the field.
Note: the front panel must first be removed. (Î Chapter 5.1, page 13).
z Remove burner door (Î Chapter 5.1, page 13).
z Remove hex head bolts of burner door hinges and re-
move hinges.
z Install the hinges on the left side of the boiler with the
hex head bolts.
z Remove the eyelets from the burner door by remov-
ing the hex head bolts.
z Locate and secure with hex head bolts these eyelets
to the left side of the burner door.
z Hang the burner door on the hinges.
z Check to make sure that the flue baffle plates are
horizontally in the boiler (Î Chapter 8.3, page 40).
z Secure the burner door with the burner door bolts.
Make sure to tighten the burner door bolts evenly with about 7.5 ft-lbs torque.
NOTICE
When reversing the swing of the burner door, make sure to remove the burner ca­ble and oil line from the burner first.
2
1
Fig. 8 Reversing burner door (boiler block)
1 Hex head bolts for hinges
2 Door hinges
3
2
1
4
Fig. 9 Reversing burner door (on burner door)
1 Hex head bolts for door eyelets
2 Door eyelet
3 Burner door
4 Door hinges
5 Flue baffles
1
2
5
16
Logano G125 BE - Specifications subject to change without notice.
6.3 Installation of boiler Feet (Components of B-Kit)
You can level the boiler using the screw-in boiler feet, so that air can not collect in the boiler.
Requirement: remove front panel from boiler (Î Chapter 5.1, page 13).
NOTICE
When installing a G125 BE boiler on top of a horizontal Buderus DHW indirect tank, do not use the boiler feet on the boil­er, but rather use the feet to level the tank.
z Tip the boiler slightly using the boiler cart
(Î Chapter 5.3, page 14) or put a piece of wood un­der one side.
z Screw in the boiler feet 1/4" – 3/8".
1
Placing the Boiler
6
2
z Level the boiler.
6.4 Placement of the Boiler
z Bring the boiler to its final location.
z Put a level on the boiler and adjust boiler feet to level
the boiler.
NOTICE
z Protect the boiler connections from
dust and debris, if the boiler will not be connected right away.
Fig. 10 Installation of boiler feet
1 Boiler rail
2 Boiler feet
Fig. 11 Leveling the boiler
Logano G125 BE - Specifications subject to change without notice.
17
7
Boiler Installation
7 Boiler Installation
7.1 Installation of Venting Systems
This chapter describes the installation of the venting system and the combustion air supply system for the G125 BE boiler. Following venting options are available:
Venting system Comment Draft Combustion air Chapter
Masonry chimney (no liner) Barometric
Masonry chimney w/ 5" liner
Vertical vent 5" 7.1.1.3, Page 21 Side wall Sealed vent Positive Outside air only 7.1.2, Page 22
Table. 11Venting options
damper required
Negative Outside air or room air 7.1.1.1, Page 19
7.1.1.2, Page 20
WARNING!
DANGER TO LIFE
from toxic flue gases.
z Never connect more than one appli-
ance to a venting system - regardless of vertical or horizontal venting.
z Common venting of appliances can
cause property damage and put life at risk.
z Chimney liners must be a single contin-
uous piece inside an existing chimney and can not have any connections in­side the chimney chase.
z The venting system shall not be routed
into, through, or within any other vent, such as an existing masonry or factory­built chimney that is used to vent any other appliance.
z Always follow vent manufacturer’s in-
structions.
NOTICE
WARNING!
FIRE DANGER
from insufficient clearance between vent system components and combustible sur­faces.
z Maintain 18" clearance to combustible
surfaces when using galvanized or stainless pipe in vertical or horizontal venting.
z Maintain 1" clearance to combustible
surfaces when using flexible oil vent for horizontal venting.
z Both the Aerocowl (AT-4) exhaust ter-
mination and Fields (FT-4) concentric exhaust/intake terminations are ap­proved with zero clearance to combus­tible surfaces.
NOTICE
The boiler installation must be performed by a qualified installer in accordance with regulations put forth in NFPA-31 Installa­tion of Oil-Burning Equipment. The instal­lation must comply with all local and national codes, regulations and authorities having jurisdiction regarding the installa­tion of oil fired boilers. For Canada refer to the guidelines of CSA/B139 Installation Codes.
18
z Avoid excessively long venting sys-
tems and keep the number of elbows to a minimum.
Logano G125 BE - Specifications subject to change without notice.
NOTICE
Due to tight construction of modern homes, Buderus recommends drawing combustion air from outdoors. The boiler is factory prepared for connecting 4" rigid pipe ducted directly to the increaser at the rear of the boiler. For further directions Î Chapter 7.2, page 28.
Except for direct venting, and provided ample combustion air is available in the boiler room, combustion air can also be drawn from the room (Î Chapter 7.2, page 28 for details).
NOTICE
For Canada the G125 BE is approved without a Blocked Vent Switch. Should local authorities require a Blocked Vent Switch Î Chapter Fig. 63, page 68.
Boiler Installation
7
7.1.1 Vertical Venting Systems
The G125 BE boiler can be vented vertically using an existing masonry chimney or a factory built All-Fuel or L­vent chimney.
7.1.1.1 Masonry Chimney
Venting system: Masonry Chimney
Comment Draft Combus-
tion air
Barometric damper required
Negative Outside air
or room air
Max. vent length
60 ft.
Refer to NFPA 31 for requirements on chimney venting. Old, cold or over-sized chimneys require the use of an approved 5" chimney liner (Î Page 20). The maximum vent length of a masonry chimney is 60 ft.
A masonry chimney is operated under slight negative pressure, and requires a barometric damper.
z Follow damper manufacturer’s instructions as to
placement.
z Adjust draft for negative 0.02 – 0.04" W.C.
DANGER TO LIFE
from toxic flue gases.
WARNING!
z Verify that all vent pipe connections
have been installed properly.
1
2
4
Fig. 12 Masonry chimney installation
1 Chimney
2 Barometric damper
3 Clean-out
4 Horizontal air connection for combustion air
(optional, see 7.2)
3
z Have the entire venting system cleaned
and inspected annually by a qualified service company.
Logano G125 BE - Specifications subject to change without notice.
19
7
Boiler Installation
7.1.1.2 Chimney with 5" Liner
Venting system: Chimney with 5" Liner
Comment Draft Combus-
tion air
Barometric damper required
Negative Outside air
or room air
Max. Vent length
60 ft.
Install liner according to manufacturer’s instructions. Follow all applicable local and national codes and regu­lations.
The maximum vent length of 5" liner in a masonry chim­ney is 60 ft. The 5" liner in a chimney is operated under slight nega­tive pressure, which requires a barometric damper.
z Follow damper manufacturer’s instructions as to
placement.
1
2
3
z Adjust draft for negative 0.02 – 0.04" W.C.
DANGER TO LIFE
from toxic flue gases.
WARNING!
z Verify that all vent pipe connections
have been installed properly.
z Have the entire venting system cleaned
and inspected annually by a qualified service company.
Fig. 13 5" Chimney liner installation
1 5" Chimney liner
2 Barometric damper
3 Horizontal air connection for combustion air
(optional, see 7.2)
20
Logano G125 BE - Specifications subject to change without notice.
7.1.1.3 Vertical Vent
Venting system: 5" Vertical Vent
Comment Draft Combus-
tion air
Barometric damper required
Negative Outside air
or room air
Max. Vent length
60 ft.
Extend the vertical vent pipe sufficiently far above the roof per NFPA 31. Follow all applicable local and nation­al codes and regulations.
Boiler Installation
7
1
2
3
The maximum length of the vertical 5" venting system is 60 ft.
The 5" vertical venting system operates under a slight negative pressure, which requires a barometric damper.
z Follow damper manufacturer’s instructions as to
placement.
z Adjust draft for negative 0.02 – 0.04" W.C.
DANGER TO LIFE
from toxic flue gases.
WARNING!
z Vertical vent pipe must have an ap-
proved fire stop at each ceiling penetra­tion and the stack must be properly supported at its base.
z Each venting section must be support-
ed at each elbow and at least every 48" of straight pipe.
DANGER TO LIFE
from toxic flue gases.
WARNING!
z Verify that all vent pipe connections
have been installed properly.
4
5
6
Fig. 14 Vertical venting system installation (supports are not
shown for clarity)
1 Roof Penetration
2 Fire stop
3 All-Fuel or L vent flue pipe
4 Barometric Damper
5 Clean-out
6 Horizontal air connection for combustion air
(optional, see 7.2)
z Have the entire venting system cleaned
and inspected annually by a qualified service company.
Logano G125 BE - Specifications subject to change without notice.
21
7
Boiler Installation
7.1.2 Horizontal Venting
Venting system: Side wall
Comment Draft Combus-
tion air
Sealed vent Positive Outside air
only
Max. Vent length
20 ft.
The maximum length of the direct vent system is 20 ft. of linear pipe including 3 x 90° elbows. With 4 elbows the maximum pipe length is 10 ft.
The following two direct vent terminations are approved with the G125 BE, and are available for purchase from your Buderus supplier.
Both exhaust terminations are approved for use with two different exhaust vent pipe options.
– Option 1:
Flexible, insulated 4" stainless steel oil vent. The in­sulated oil vent is rated for 1" clearance to combusti­bles. Wrap the adapters with 3" of ceramic wool covered with foil tape or sheet metal to maintain 1" clearance. For installation instructions Î Chapter „7.1.2.6 Installation of Insulated Flexible Oil Vent“, page 26.
– Option 2:
Standard, 26 gauge galvanized 4" vent pipe. Main­tain 18" clearance to combustibles with galvanized vent pipe (Î Chapter „7.1.2.7 Installation of Galva­nized Vent Pipe“, page 27).
NOTICE
Horizontal vent systems operate under positive pressure, which requires all seams to be sealed. Use high temperature silicone (500°F rated, G.E. 106 or equiva­lent) to seal any joints, screw penetrations, or combustion test holes, and seal at each pipe connection and all joints on adjust­able elbows. Refer to 7.1.2.2 for details.
NOTICE
Installations in Canada less than 7 ft. above ground are required to have a cage/screen over the termination to pre­vent injury from touching hot surfaces.
Fig. 15 Aerocowl (AT-4) and Concentric (FT-4) termination
22
Logano G125 BE - Specifications subject to change without notice.
Loading...
+ 50 hidden pages