Buderus Logano G115 WS US/CA, Logano G115/3 WS, Logano G115/4 WS, Logano G115/5 WS Installation And Service Instructions Manual

Page 1
For heating contractors
Please read carefully prior to installation and servicing.
Caution!
Observe the safety instructions of this installation and maintenance manual before placing the boiler in operation.
If installation, adjustment, modification, operation or maintenance of the heating system is carried out by an unqualified person, this may result in danger to life and limb or property damage. The directions of this installation and maintenance manual must be followed precisely. Contact a qualified service company or service pro­vider if support or additional information is required.
Caution!
The operating manual is a component of the techni­cal documentation and must be handed over to the operator of the heating system. Discuss the content of this manual with the owner or operator of the heating system to ensure that they are familiar with all information required for operation of the heating system.
Installation and Service Instructions
Low-temperature oil boiler
6 720 615 225-00.1RS
Logano G115 WS US/CA
6 720 615 225 - 08/2007 US/CA
Page 2
Contents
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
2
Contents
1 Safety Considerations and Symbol
Descriptions 3
1.1 Regarding this Manual 3
1.2 Explanation of symbols 3
1.3 Observe the following Symbols 3
1.3.1 Installation Guidelines 4
1.3.2 Boiler Room Guidelines 4
1.4 Tools, Materials and Accessories 4
1.5 Disposal 4
2 Product description 5
2.1 Intended use 5
2.2 Certification and testing mark 5
2.3 Notes on installation and operation 5
2.4 Heating system water quality 5
2.5 Product description 6
2.6 Pack contents 7
2.7 Dimensions Specifications 8
2.7.1 Logano G115 WS dimensions 8
2.8 Conditions for operation 9
2.8.1 General operating conditions 9
2.8.2 Conditions for the boiler room and the environment 10
2.8.3 Combustion air supply conditions 10
2.8.4 Conditions, Fuel 10
2.8.5 Conditions power supply 11
2.8.6 Conditions for hydraulic system and water quality 11
3Moving the boiler 12
3.1 Reducing boiler weight for transportation purposes 12
3.2 Lifting and carrying the boiler 13
3.3 Using transportation aids to transport the boiler 13
4 Installing the boiler 14
4.1 Wall clearances 14
4.2 Reversing boiler door 15
4.3 Mounting the adjustable feet (included with B-kit) 16
4.4 Positioning and leveling the boiler 16
5 Installing the boiler 17
5.1 Flue pipe installation 17
5.1.1 Chimney venting 17
5.2 Fitting the water connections 19
5.2.1 Fitting the B-kit 19
5.2.2 Installation of boiler drain (included in B-Kit) 20
5.2.3 Installing system components 20
5.3 Filling the heating system and checking for leaks 21
5.4 Mounting the burner 23
5.5 Connecting the fuel supply 23
5.6 Installing aquastat 24
5.7 Blocked vent switch (required in Canada) 24
5.8 Electrical connections 24
5.8.1 Fitting the controls 25
5.8.2 Fitting temperature sensor assembly and burner cable 26
5.8.3 Connecting the power supply and additional components 27
5.8.4 Fitting cable ties 27
5.9 Fitting outer casing panels 27
6 Commissioning the heating system 28
6.1 Bringing the system up to operating pressure 28
6.2 Checking the safety valve 28
6.3 Checking position of heat exchanger baffles 29
6.4 Preparing the heating system for operation 29
6.5 Starting up the control and the burner 29
6.6 Notes on commissioning the burner 30
6.7 Raising flue gas temperature 30
6.7.1 Adjusting the position of heat exchanger baffles 31
6.7.2 Removing heat exchanger baffles 31
6.7.3 Removing the heat exchanger barrier plate 32
6.8 Manual reset high limit (STB) 32
6.9 Installing the burner door jacket 32
6.10 Commissioning log 33
7 Shutting down the heating system 34
7.1 Shutting down normally 34
7.2 Shutting down the heating system in an emergency 34
7.2.1 What to do in an emergency 34
8 Heating system servicing 35
8.1 Why is regular maintenance important? 35
8.2 Preparing the boiler for servicing 35
8.3 Cleaning the boiler 36
8.3.1 Cleaning the boiler with brushes 36
8.3.2 Wet cleaning (chemical cleaning) 37
8.4 Checking heating system operating pressure 37
8.5 Testing relief valve 38
8.6 Servicing and maintenance logs 39
9 Troubleshooting 42
10 Installation examples 43
11 Parts lists 45
12 Circuit diagrams 50
Page 3
1
Safety Considerations and Symbol Descriptions
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
3
1 Safety Considerations and Symbol Descriptions
1.1 Regarding this Manual
This document contains important information regarding safe and proper installation, operation and maintenance of the boiler.
The high tech G115 WS boiler is designated as a hot water heating boiler.
The Installation and Maintenance Instructions are directed to the installing contractor who has professional knowl­edge regarding boiler installation and maintenance.
1.2 Explanation of symbols
Signal words are used to indicate the seriousness of the ensuing risk if measures for minimising damage are not taken.
Caution indicates that minor damage to property may
occur.
Warning indicates that minor personal injury or severe
damage to property may occur.
Danger means that severe personal injury may occur.
Very serious cases may result in death.
Notes contain important additional information.
Notes do not contain any warnings or information about hazards or risks.
1.3 Observe the following Symbols
All applicable local, state, and national codes and regula­tions must be observed for the installation of the boiler:
– The local building code requirements regarding place-
ment, combustion air and venting and chimney system
must be followed. – Follow applicable electrical code requirements. – Follow the local code and standards regarding safe
boiler operation.
Warnings are indicated by a warning triangle and a grey background.
Notes are identified in the text by this symbol. They are bounded by horizontal lines above and below the text.
NOTICE
Use only original Buderus spare parts. Buderus can not be held liable for damage caused by non-Buderus parts.
NOTICE
The boiler installation must be performed by a qualified installer in accordance with regu­lations put forth in NFPA-31 Installation of Oil-Burning Equipment. The installation must comply with all local and national codes, reg­ulations and authorities having jurisdiction re­garding the installation of oil fired boilers.
For Canada refer to the guidelines of CSA/ CGA-B139 Installation Codes.
Page 4
1
Safety Considerations and Symbol Descriptions
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
4
1.3.1 Installation Guidelines
1.3.2 Boiler Room Guidelines
1.4 Tools, Materials and Accessories
For the installation and maintenance of the boiler you will need typical tools used in this industry. In addition, the following components are useful:
– Hand truck with strap or Buderus boiler cart. – Wood blocking. – Cleaning brushes and/or chemical cleaning agents for
wet cleaning.
1.5 Disposal
V Please dispose of any trash in an environmentaly
friendly fashion.
V Please discard properly of any heating system related
components.
Caution: DANGER TO LIFE
from electric shock.
V Do not work on electrical components un-
less you have the required qualification.
V Do not work on electrical components un-
less you have the required qualification.
V Prior to opening the control: shut down
the power supply by turning off the emer­gency shut-off switch or disengaging the heating system circuit breaker, and pre­vent from accidental reactivation.
V Observe all applicable installation guide-
lines.
Caution: DANGER TO LIFE
from flue gas poisoning. Insufficient combustion air can result in dan­gerous operation if combustion air is taken from indoors.
V Please observe that combustion air open-
ings are not reduced in size or closed.
V Make sure that no mechanical air open-
ings or devices remove combustion air from the boiler room such as central vacu­um systems, dryers and air conditioning appliances.
V Make sure that the boiler is connected to
a chimney or horizontal venting system that is capable of handling the slight posi­tive breeching pressure.
V If any of these problems have not been
corrected, the boiler must not be operat­ed.
V Make the end-user aware of these guide-
lines and their potential danger.
Caution: FIRE DANGER
due to flammable or liquid materials.
V Make sure that flammable and liquid mate-
rials are not stored in the close vicinity of the boiler.
Page 5
2
Product description
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
5
2 Product description
This installation and maintenance manual contains impor­tant information for the safe and intended installation, ini­tial start-up and maintenance of this boiler.
The special oil fired boiler Logano G115 WS is generally referred to below as a boiler.
The installation and maintenance manual is provided for technicians who have been trained and have experience in working with heating systems and oil fired installations.
2.1 Intended use
The G115 WS is designed for central heating and domestic hot water (DHW) systems, for instance in resi­dential homes or apartment buildings, or small commer­cial applications.
2.2 Certification and testing mark
This appliance has been tested and certified to meet rules and regulations in place for the US and Canadian mar­kets.
2.3 Notes on installation and operation
When installing and operating the heating system, it is the installer's responsibility to meet all applicable federal, state, and local codes.
2.4 Heating system water quality
Poor water quality can damage heating systems due to scale formation and corrosion. Please refer to Chapter 2.8.6, Tab. 9 for further details of the water quality.
Caution: Risk of system damage due to un­suitable boiler water.
V If oxygen-permeable pipes are used, e.g.
for radiant heating systems, the systems must be separated from the boiler by a heat exchanger. Unsuitable heating sys­tem water promotes sludge formation and corrosion. This can result in heating sys­tem malfunction and boiler damage.
Page 6
2
Product description
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
6
2.5 Product description
The boiler is a low-temperature oil-fired appliance with automatic control panel or aquastat for boiler water tem­perature.
The boiler consists of: – Boiler heat exchanger with insulation – Boiler jacket – Control panel or aquastat
The controls monitor and control all electrical boiler com­ponents.
The boiler can alternatively be fitted with a simple aqua­stat control.
The boiler jacket prevents heat loss and acts as a noise insulator.
The boiler heat exchanger transfers the heat generated by the burner to the heating water. The insulation prevents energy loss.
Suitable burners
Fig. 1 Boiler without burner
1 Control panel 2 Boiler jacket 3 Boiler heat exchanger with insulation 4 Burner door 5 Burner door panel
Caution: Risk of system damage from use
of incorrect burner. V Only the burner provided may be em-
ployed with this boiler.
6 720 615 225-01.1RS
1
2
3
4
5
Page 7
2
Product description
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
7
2.6 Pack contents
Upon delivery, check that the packaging is complete and undamaged.
Component Qty Packaging
Boiler heat exchanger 1 1 pallet
Boiler casing, factory-fit­ted to boiler heat exchanger
Burner door and burner door panel, factory-fitted to boiler heat exchanger
B-kit components:
– 1 Supply manifold
G115"US"
– elbow 90 ° 1-1/4"
– elbow 90 ° 3/4"
– double nipple R1-1/4"-
1-1/4" NPT x 75
– boiler drain 3/4"
– relief valve 3/4" x 3/4"
30PSI
– temperature/pressure
gauge
– Bolt set B-Kit
G115"US"
– adjustable boiler feet
M10 x 51 packed
1 1 foil package
1)
1) in the combustion chamber in the boiler
Controller or, alternatively, Aquastat
2)
2) Aquastat may be supplied with burner
11 box
Technical documentation 1 foil package
Tab. 1 Package Contents
Page 8
2
Product description
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
8
2.7 Dimensions Specifications
2.7.1 Logano G115 WS dimensions
Fig. 2 Connections and dimensions (measurements in inches)
VK = Boiler supply RK = Boiler return EL = Boiler drain (connection for drain valve)
Connections and dimensions:
7 747 019 141-02.1RS
23
5/8"
L
VK
L
K
F
L
39
5/8"
30
3/8"
1
3/4"
2
7/8"
8
7/8"
8
7/8"
Rp1
1/4"
EL
Rp
3/4"2 7/8"
25
1/4"
RK
1" NPT
3
1/4"
Ø 5"
20"
10
3/8"
12
1/4"
5
7/8"
4
3/8"
5/8"
- 1"
Boiler model Unit G115/3 WS G115/4 WS G115/5 WS
Boiler sections 345 Heating capacity (gross output) MBtu/hr 85 109 136 Thermal output (net IBR output) MBtu/hr 74 95 119 Boiler water content Gal 8.7 10.8 12.9 Gas capacity cu.ft. 1.20 1.75 2.21 Oil firing rate GPH 0.7 0.9 1.0 Flue gas back-pressure W.C. 0.04" - 0.06" Permissible flow temperatureSafety
1)
1) Limit (safety temperature limiter, STB) Maximum permitted flow temperature = Safety limit (STB) - 32 °F Example: Safety limit (STB) = 212 °F, maximum permitted flow temperature = 212 ° - 32 ° = 180 °F The safety limit must meet the national regulations of the country concerned.
°F 230
Allowable operating pressure psi 58 Maximum time constant of thermostat and high limit safety cut-out (STB)
s 40
Tab. 2 Technical data for boilers without burners
Boiler model Unit G115/3 WS G115/4 WS G115/5 WS
Boiler overall length (L) Inch 23-5/8" 28-5/8" 33-3/8" Boiler block length (LK) Inch 21-1/8" 25-¾" 30-½" Combustion chamber length Inch 16" 20-½" 25-¼" Combustion chamber length Inch 10-5/8" Burner door thickness Inch 3-5/8" Distance between boiler feet (FL) Inch 10-3/8" 16-1/8" 20-7/8" Net weight1)– Lbs 330 403 476
Tab. 3 Dimensions, weight and other data for boilers without burners
1) Incl. packaging material approx. 6-8 % more
Page 9
2
Product description
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
9
2.8 Conditions for operation
Maintaining the specified operating conditions will enable the boiler to provide a high level of reliability and long serv­ice life. Some details relate only to operation with Buderus Logamatic control panels.
2.8.1 General operating conditions
Caution: Ri sk of sys te m da ma ge if op er at in g
conditions are not maintained. Irreversible damage to individual compo-
nents of the boiler as a whole or the heating system may occur.
V The information on the rating plate is bind-
ing and must be observed.
Operating conditions
Min. boiler water tempera-
ture
Operating interruption
(complete boiler shutdown)
heating circuit with
heating circuit mixing valve
1)
Min. return temperature
In combination with Logamatic control for variable low-temperature operating modes, such as Logamatic 2107
no requirements operating
temperatures are ensured by
the Logamatic controls
2)
Automatically by Logamatic controls not required but recommended with
low-temperature heating system design 130/113 °F
Required with:
– Underfloor heating systems
– Systems with high water content:
> 115° gal/MBH (1 MBH = 100.000 Btu/hr)
In conjunction with a Logamatic controls for constant boiler water temperatures, e.g. Logamatic 2109 or with supplementary exter-
nal programmer and aquastat
150 °F
3)
possible if, after interruption of the operation, there is at least 3 hours
heating operation
required Required with:
– Systems with high water content
> 115 gal/MBH: 130 °F
Tab. 4 General operating conditions
1) A heating circuit with a mixing valve improves controllability and is specifically recommended for systems with several heating zones.
2) If heating zones or a boiler circuit actuator cannot be regulated via the control device (for example pump logic), an operating temperature of
122 °F must be reached within 10 min of switching the burner ON by restricting the water volume flow.
3) Boiler water temperature control setting: when the boiler is in ON mode, the minimum boiler water temperature in the boiler must be reached
within 10 minutes, e.g. by flow rate limitation, and maintained as the minimum temperature.
Page 10
2
Product description
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
10
2.8.2 Conditions for the boiler room and the environment
2.8.3 Combustion air supply conditions
If the burner is to be operated with sealed combustion by drawing its combustion air solely from the outdoors, follow burner manufacturer's specification.
2.8.4 Conditions, Fuel
Operating conditions Notes – Requirement in greater detail
Temperature in the boiler room +40 to +104 °F relative humidity max. 90 % No condensation or precipitation inside the boiler room Dust/airborne particles Excessive dust inside the boiler room must be avoided when the boiler is operat-
ing, e. g.:
– Dust from building work
Combustion air supplied from outside must not be excessively loaded with dust or airborne particles; if necessary, air filters should be fitted in case:
– Air supply contaminated with dust from dirt roads and paths.
– Air supply contaminated with dust from production and processing facilities, e. g. quar-
ries, mines, etc.
– Airborne particles from thistles and similar Halogenated-hydrocarbon com­pounds
The combustion air must be free from halogenated-hydrocarbon compounds.
– Identify the source of halogen-hydrocarbon compounds and seal it off. Where this is
impossible, route combustion air from areas that are not contaminated by halogen-
hydrocarbon compounds. Fans that extract air from the boiler room.
During burner operation, no mechanical air handling equipment may be operated that could extract combustion air from the boiler room, e.g.:
–Exhaust hood
– Tumble dryer
– Ventilation equipment
Small animals Prevent small animals from entering the boiler room, particularly through the air inlet vents –
by fitting them with screens.
Fire safety Maintain clearances between the boiler and flammable materials in accordance with local
regulations. A minimum clearance of 16" is required. Never store flammable materials or liquids in the vicinity of the boiler.
Flooding In case of an acute risk of flooding, disconnect the boiler in time from its fuel and power
supply before water enters the room. Any components or control equipment, which came in contact with flood water, must be replaced before re-commissioning.
Tab. 5 Boiler room and ambient conditions
Operating conditions
Boiler output (in case of
multi-boiler systems = total output)
Ventilation air cross-section in square inches
(unrestricted aperture)
Air intake flow cross-section for combustion air drawn from out­side (divided between max. 2 apertures)
< 170,000 Btu/hr At least 23.25 square inches
Tab. 6 Observe national regulations for boilers which draw their air supply from the boiler room.
Operating conditions Notes – Requirement in greater detail
Permissible fuels for boilers with­out integral burners
This boiler can be operated with #2 Fuel Oil ASTM D396-05 Type 2. Select a burner that is suitable for this fuel typ.
Contamination Free of contaminants (for example dust, mist, humidity), i. e. a constant operation will not
lead to accumulation of deposits, in valves, strainers and filters and could lead to service calls.
Tab. 7 Fuels
Page 11
2
Product description
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
11
2.8.5 Conditions power supply
2.8.6 Conditions for hydraulic system and water quality
Operating conditions Notes – Requirement in greater detail
Power supply voltage 120 V
AC nominal
Observe the voltage range of the burner and controls used. The outer casing/boiler must
be grounded for safety reasons and in order to function correctly. Circuit breaker 10 A Frequency 60 Hz Enclosure rating IP 40 (protected against contact by entry of foreign objects > 0.04 inches Ø
(> 1 mm Ø ), no water proofing)
Tab. 8 Power supply
Operating conditions Notes – Requirement in greater detail
Operating pressure (above atmospheric)
15–58psi Maximum 30 psi with the supplied safety valve.
Permissible site test pressure 45 – 75 psi Safety temperature limitation by TR temperature control
122–194°F
Safety temperature limitation by manual reset high limit (STB)
212 – 248 °F On some controls adjustable on site from 212 to 248 °F.
Water quality The heating system may only be filled and topped up with water of domestic water quality.
We recommend a pH value of 8.2 – 9.5.
Tab. 9 System configuration and water quality
Page 12
3
Moving the boiler
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
12
3 Moving the boiler
This chapter details how to move the boiler safely.
3.1 Reducing boiler weight for transportation purposes
If required, you can reduce the weight of the boiler by removing the burner hood and door.
V Unscrew the burner door-panel screws. V Lift burner door panel slightly and draw forward to
remove.
Fig. 3 Removing burner door panel
V Unscrew two hex-head bolts at the sides. V Open burner door. V Lift the burner door off its hinges.
Fig. 4 Removing the burner door
Caution: Risk of system damage from im­pact.
Fragile components could be damaged.
V Observe the transport instructions on the
packaging.
Protect boiler connections from damage and dirt if the boiler is not installed immediately.
Dispose of packaging in an environmentally responsible manner.
6 720 615 225-02.1RS
Prevent the burner door from falling over and damaging the burner and blast tube.
7 747 019 141-04.1RS
Page 13
3
Moving the boiler
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
13
3.2 Lifting and carrying the boiler
The boiler can be held and carried at the grip positions shown.
V Undo the transit screws.
Fig. 5 Lifting and carrying the boiler
3.3 Using transportation aids to transport the boiler
Moving the boiler with hand truck V Place the hand truck (e.g. boiler trolley or sack truck) at
the back of the boiler.
V Secure boiler to hand truck using the boiler bolts or
strapping.
V Move the boiler to the installation location.
Fig. 6 Moving the boiler with a boiler hand truck
The boiler is secured to the pallet by 2 screws for transportation purposes.
Caution: Risk of injury from carrying heavy loads.
V Always lift and move the equipment with
the assistance of another person using the handle positions shown.
7 747 019 141-05.1RS
Caution: Risk of injury if load is inadequately secured during transportation.
V Use suitable means of transportation, e.g.
the Buderus boiler hand truck with strap.
V Secure the load against falling.
You can order the boiler hand truck from your Buderus distributor.
The boiler trolley can also be used to facilitate work underneath the boiler, e.g. fitting the ad­justable feet (Æ Chapter 4.3, page 16).
7 747 019 141-06.1RS
Page 14
4
Installing the boiler
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
14
4 Installing the boiler
This chapter describes how to install and place the boiler in the boiler room.
4.1 Wall clearances
Position the boiler with the recommended wall clear­ances. Reducing the minimum clearances makes the boiler more difficult to access during installation, mainte­nance and cleaning.
The boiler base or foundation must be perfectly flat and level.
The burner door is factory-fitted with the hinges on the right. The burner door can be converted to open to the left (Chapter 4.2, page 15).
Fig. 7 Boiler room clearances (boiler positioned on the
l.h. or r.h. side)
Caution:
Risk of system damage from freezing.
V Install the heating system in a frost-free
room.
Dimen­sion
Wall clearance
A Recommended 51-1/8"
minimum 39-3/8"
B Recommended 27-½"
minimum 15-¾"
C Recommended 15-¾"
minimum 3-7/8"
L
K
Æ Chapter 2.7.1 "Logano G115 WS
dimensions", page 8
Tab. 10 Recommended and minimum wall clearances
(dimensions in inches).
7 747 019 141-07.1RS
The boilers are designed for a side clearance of 6". Where applicable, allow extra wall clearanc­es for additional components such as DHW tank, pipe connections, flue gas silencer or other flue components, etc.
Caution: Risk of fire from flammable materi­als or liquids.
V Clearances less than 6" must comply with
local and statutory codes.
V Make sure that there is a sufficient clear-
ance between combustible materials and the chimney connection as specified by NFPA 31 (distance of 18 ").
V The floor must comply with the require-
ments of NFPA 31.
Page 15
4
Installing the boiler
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
15
4.2 Reversing boiler door
The burner door is factory-fitted with the hinges on the right – the burner door opens to the right.You can change the burner door hinges over to the left-hand side if desired to suit the installation site.
Remove the burner hood/burner door panel first (Æ Chapter 3.1, page 12).
V Removing the burner door (Æ Chapter 3.1, page 12). V Unscrew the hinge bolts and remove the hinges. V Mount the hinges on the left-hand side of the boiler
using the hinge bolts.
Fig. 8 Reversing the burner door (boiler heat
exchanger attachments)
1 Hinge bolts 2 Hinges
V First remove the hinge lobe bolts and then the hinge
lobes. Mount the hinge barrels on the left-hand side of the boiler using the hinge-barrel bolts.
V Hook the burner door with the hinge lobes onto the
hinges.
V Check that the heat exchanger baffles are placed hori-
zontally (Æ Chapter 6.3, page 29).
V Close the burner door and secure with the two hexa-
gon-head bolts.Tighten the hexagon-head bolts evenly (approx. 90 Lbs/inch) so that the burner door seals properly.
Fig. 9 Reversing the burner door (door attachments)
1 Hinge-barrel bolts 2 Hinge lobes 3 Burner door 4 Hinges 5 Heat exchanger baffle plates
7 747 019 141-08.1RS
12 21
If the burner door hinges have been changed over to the left-hand side, the burner cable must be disconnected from the burner before opening the burner door.
7 747 019 141-09.1RS
1
4
5
2
3
Page 16
4
Installing the boiler
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
16
4.3 Mounting the adjustable feet (included with B-kit)
Level the boiler with the adjustable feet to prevent air pockets forming inside the boiler.
Requirement: the burner hood/burner door panel must have been removed first (Æ Chapter 3.1, page 12).
V Tilt the boiler with the aid of a hand truck or trolley
(Æ Chapter 3.3, page 13) or place a wooden batten underneath it.
V Screw in adjustable feet ¼" – 3/8". V Gently set the boiler down.
Fig. 10 Fitting adjustable feet
1 Angle bracket 2 Adjustable feet
4.4 Positioning and leveling the boiler
V Position the boiler in its final location. V Level the boiler horizontally by turning the adjustable
feet and using a level.
Fig. 11 Leveling the boiler horizontally
If the boiler is mounted on top of a horizontal hot water tank, the adjustable feet are not needed.
7 747 019 141-10.1RS
1
2
Protect boiler connections from damage and dirt if the boiler is not installed immediately.
7 747 019 141-11.1RS
Page 17
5
Installing the boiler
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
17
5 Installing the boiler
This chapter details how to install your boiler correctly. The individual steps involved are:
– Connecting the flue – Connecting the water pipes – Making the electrical connections – Fitting the burner – Connecting the fuel supply
5.1 Flue pipe installation
5.1.1 Chimney venting
Connect boiler to vertical chimney with a 5" vent pipe. Use only venting systems that comply with local codes and regulations.
If local codes are not existent, refer the the following reg­ulations:
– NFPA 31, Installation of Oil-Burning Equipment, – NFPA 211, Standard for Chimneys, Fire Places and
Solid Fuel Burning Appliances,
– In Canada refer to CSA B139, Installation Code for Oil-
Burning Equipment,
– NFPA 211 requires chimney to be lined before con-
necting boiler.
Inspecting and cleaning existing flue
Before installing the new boiler, check and clean the old flue system.
V Remove blockages and dirt from the chimney. V Clean chimney. V Repair or replace faulty sections. V If necessary, repair chimney with mortar and joints.
Down drafts
To prevent down drafts extend chimney at least 3 feet above the roof opening and at least 2 feet above any part of the roof within a radius of 10 feet.
Page 18
5
Installing the boiler
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
18
Minimum clearances to combustible material
Minimum size of chimney
The minimum recommended chimney size is 8" x 8" (6 ¾" x 6 ¾" inside liner) or 6" diameter with a minimum height of 15 feet. Use a 5" flue pipe for connection to an existing chimney.
Installing the flue pipe
V Insert flue pipe 5" onto the breach and secure with
3 screws.
V Install flue connections between boiler and chimney to
slope up at least ¼" per foot to the chimney.
V Connect the flue pipe to the chimney above the bottom
of the chimney to prevent blockages.
V Install cleaning and service hatches.
After starting the burner, set breeching draft to -0.01 to
-0.02 inches WC using a draft gauge. The overfire pres­sure can be positive. If necessary, install a barometric damper in the flue system to maintain the underpressure in the system or to meet code requirements. Always install the draft controller in vertical position. Use a draft gauge when making adjustments.
Fig. 12 Installing the flue pipe
1 Flue pipe 2 Boiler flue socket
Flue pipe Type Minimum clearance
Double-wall L 6"
Single-wall L 18"
Tab. 11 Minimum clearances to combustible objects for
flue systems
Danger: Risk of death from escaping flue gases.
If the resistance to flue gas flow is too great and/or the flue pipe diameter is smaller than the recommended size and/or the flue pipe is too short:
V Seal all vent pipe joints. V Install a CO alarm. Positive pressure com-
bustion ensures that the flue gas can exit the flue system.
Avoid long horizontal flue pipe runs and keep the number of elbows to a minimum.
Page 19
5
Installing the boiler
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
19
5.2 Fitting the water connections
5.2.1 Fitting the B-kit
The safety relief valve and the pressure/temperature gauge are mounted on the supply manifold (included in B­Kit) on the VK boiler supply connection as follows:
V Fit and seal unmarked end of double nipple into con-
nection VK on the boiler.
V Converter is paint-marked pink and stamped with the
designation NPT on the end with the 1¼" NPT thread.
Fig. 13 Checking thread length on double nipple
V Seal 90° 1¼" NPT street elbow on double nipple. V Fit and seal manifold to 90° elbow. The manifold can
face in different directions (Æ Fig. 14).
V Seal pressure/temperature gauge to supply manifold.
Fig. 14 Installing B-Kit
1 90° 1¼" NPT street elbow 2 Double nipple 3 Supply manifold 4 Pressure/temperature gauge 5 Pressure relief valve 6 90° ¾" NPT elbow
Caution: Risk of system damage from leak-
ing connections. V Support the pipes to the boiler to prevent
them from being under stress.
Do not fit the safety valve until the leak test (Æ Chapter 5.3, page 21) has been com­pleted. The relief valve must be installed in a vertical position.
We recommend installing a dirt filter (option­al) in the boiler return connection to reduce build-up of debris on the water side.
Page 20
5
Installing the boiler
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
20
5.2.2 Installation of boiler drain (included in B-Kit)
V Seal boiler drain to connection EL.
Fig. 15 Installation of boiler drain
RK Return EL Drain
5.2.3 Installing system components
See the installation diagram for installation of the heating system components.
For more installation examples refer to Æ Chapter 10, page 43.
Fig. 16 Installation diagram
1 Pressure relief valve 2 Pressure/temperature gauge 3 Ball or stop valve 4 Air eliminator (in main supply) 5 System pump 6 Flow check valve 7 Expansion tank 8 Automatic feed valve 9 Flow check valve 10 Purge station 11 Water feed VK Boiler supply EL Drain RK Return
Install a fill connection in the supply piping to the boiler.
7 747 019 141-15.1RS
RK
EL
7 747 019 141-16.1RS
1
2
33 563
3
7
3
98
VK
RK
11
EL
4
10
Page 21
5
Installing the boiler
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
21
5.3 Filling the heating system and checking for leaks
The boiler is tested for leaks at the factory. Before putting the heating system into operation, it must be checked to ensure that no leaks will occur during operation.
Carry out the leak test at 1.5 times the standard operating pressure and in accordance with the codes.
V Seal pressure relief valve connection (Æ Fig. 14
"Installing B-Kit", page 19) and all other open connec­tion with blind plugs.
V Isolate the expansion tank from the system by closing
the valve.
V Open the mixing and shut-off valves on the heating
water (primary) side.
V Slowly fill the boiler with tap water.
Fig. 17 Pressure/temperature gauge
Caution: Risk of system damage from ex­cess pressure when testing for leaks.
Pressure, control and safety equipment may be damaged by excessive pressure.
V When you carry out a leakage test, make
sure that no pressure, control or safety equipment that cannot be isolated from the boiler water chamber is fitted.
Caution: Risk of damage to system due to temperature stresses.
If you fill the heating system when it is hot, the resulting temperature stresses can cause stress cracks. The boiler will then leak.
V Only fill the heating system when cold (the
flow temperature should be no more than 100 °F).
V Pay attention to the water quality as spec-
ified in the operator's log, and record the volume and quality of the water used to fill the system.
Maximum operating pressure
Maximum on-site testing pressure
30 psi (with safety valve supplied)
45 psi
58 psi (with 50 psi relief valve)
75 psi
Tab. 12 Maximum testing pressure
7 747 019 141-17.1RS
Page 22
5
Installing the boiler
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
22
V Open the cap of the automatic air vent by one full turn
to allow air to escape.
V Slowly fill the heating system. Observe the pressure
gauge whilst filling.
V Check the connections and pipework for leaks. V Bleed the system via the radiator bleed valves if appli-
cable.
V Top with water if the pressure drops as a result of
bleeding the system.
V Installing pressure relief valve (Æ Fig. 14 "Installing B-
Kit", page 19)
Caution: Health risk from contaminated do­mestic water.
V Always observe the regulations and stand-
ards applicable in your jurisdiction for the prevention of contamination of drinking water (e.g. by water from heating sys­tems).
Page 23
5
Installing the boiler
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
23
5.4 Mounting the burner
Only burners that comply with the boiler specification can be used with this boiler. (Æ Chapter 2.7, page 8).
V Screw studs included with the B-Kit to the burner door.
V Install burner with the correct nozzle and settings (air,
pump pressure, turbulator settings, flange position).
V Place the seal on the studs and secure the burner with
the included nuts.
V Follow the manufacturer’s direction for installation, fine
adjustment and regular maintenance procedures.
Fig. 18 Burner door mounting holes
5.5 Connecting the fuel supply
Make the fuel connection in accordance with all applica­ble local and national codes and regulations. We recom­mend fitting a fuel filter and de-aerator.
V Visually inspect the fuel pipe and clean or replace, if
necessary.
V Install a shut-off valve into the fuel supply pipe. V Connect the fuel pipe free of stress to the boiler. V Check the fuel line for leaks.
Caution: Risk of system damage from use of incorrect fuel.
V Only use burners which meet the techni-
cal boiler requirements.
Approved burners with accessories (such as aquastat and circulator) are also available as a package from Buderus.
For details of the correct burner settings
Æ flue system documentation and Æ burner documentation.
7 747 019 141-18.1RS
Page 24
5
Installing the boiler
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
24
5.6 Installing aquastat
An aquastat controls the boiler supply temperature.
V Install aquastats in the sensor well as specified by the
installation manual.
For operating the boiler with aquastat Æ Chapter 6, page 28.
Fig. 19 Aquastat installation
1 Immersion sleeve
5.7 Blocked vent switch (required in Canada)
For Canadian installations fit a blocked vent switch per the vent switch manufacturer’s instructions and as close as possible to the boiler breach.
See pages 50 - 52 for wiring diagrams.
5.8 Electrical connections
This section only applies to boilers using Buderus con­trols.
V Remove rear boiler jacket.
– Unscrew the fixing screws.
V Remove cover panel. Wiring from the control panel to
the burner is passed through the hole in the front boiler top panel.
Fig. 20 Removing rear boiler cover and cover plate.
1
7 747 019 141-19.1RS
Danger: Risk of death from electric shock.
V Electrical work may only be carried out by
qualified technicians. Before opening any electrical equipment, isolate it from the power supply by turning off the emergen­cy shut-off switch or disengaging the heat­ing system circuit breaker, and prevent from accidental reactivation. Follow the in­stallation instructions.
Page 25
5
Installing the boiler
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
25
5.8.1 Fitting the controls
V Position the tabs of the controls in the slots. V Slide the controls forwards towards the burner door. V Let the flexible hooks of the control panel click into the
openings by pushing the control panel down.
Fig. 21 Fitting the controls
1 Flexible catches 2 Locating tabs 3 Slots 4 Locating holes
V Remove the controls cover.
– Unscrew the cover screws.
V Secure the controls with self-tapping screws.
Fig. 22 Cover, removing
1 Cover screws 2 Self-tapping screws
1
2
3
7 747 019 141-21.1RS
1
2
7 747 019 141-22.1RS
Page 26
5
Installing the boiler
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
26
5.8.2 Fitting temperature sensor assembly and burner cable
V Route capillary tubes and sensor wiring through the
cable opening of the front boiler jacket and connect to test port.
V Roll up surplus capillary tubes and sensor lead and lay
them on the thermal insulation.
V Route the burner cable through the cable entry in the
front boiler cover to the control panel.
V Connect the burner cable to the control in accordance
with the terminal markings.
Fig. 23 Routing and connecting cables
1 Cable entry in the front boiler cover 2 Capillary tube and sensor cable 3 Immersion well (sensing point) 4 Burner cable
V Insert the temperature sensor assembly and balancing
spring in the immersion well and insert completely. The plastic spiral is then pushed back automatically.
V Push the sensor retaining clip (supplied with the con-
trols) onto the top of the immersion well from the side.
Fig. 24 Fitting the temperature sensor assembly
1 Immersion well (sensing point) 2 Plastic coil 3 Balancing spring 4 Sensor retaining clip
Caution: Risk of system damage due to se-
vere kinking or sharp burrs on capillary tubes. Capillary tubes can get damaged from se-
vere kinking or sharp burrs.
V Route capillary tubes carefully, avoiding
bending them excessively.
The boiler comes factory equipped with the sensor immersion well for the Aquastat.
V If a Buderus Logamatic controls is being
installed, the factory-fitted immersion well must be replaced by the Logamatic well supplied with the controls.
Ensure good contact between the sensor surfaces and the sensor well to achieve accu­rate readings. Use the balancing spring.
1
1
4
2
3
7 747 019 141-24.1RS
Page 27
5
Installing the boiler
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
27
5.8.3 Connecting the power supply and additional components
Establish a permanent connection to the mains power supply in accordance with the locally applicable regula­tions.
V Route all cables through the cable entries to the control
panel and connect in accordance with the wiring dia­gram.
5.8.4 Fitting cable ties
Secure all cable runs with cable ties (included with the control):
V Insert the cable ties together with the cable from the
top into the slots in the frame (step 1).
V Slide the cable ties downward (step 2). V Push against the ties (step 3). V Flip the toggle up (step 4).
Fig. 25 Securing cables with cable ties
5.9 Fitting outer casing panels
V Position and secure the control device cover. V Fit the rear boiler cover. V Secure by reinstalling cover screws and jacket panel
screws.
Fig. 26 Fitting the rear boiler cover
1 Controls cover 2 Rear boiler cover
Warning: Fire hazard from hot boiler compo-
nents. Hot boiler components may damage electri-
cal cables.
V Ensure that all wiring is routed in the ducts
provided or on the boiler insulation.
7 747 019 141-25.1RS
Page 28
6
Commissioning the heating system
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
28
6 Commissioning the heating system
This chapter describes the initial start-up procedure regardless of the installed control device.
V Complete the start-up protocol during this process
(Æ Chapter 6.10, page 33).
Further information on boiler room layout and clearances, combustion air requirements and venting systems and boiler operational requirements can be found in Æ Chapter 2.8, page 9.
6.1 Bringing the system up to operating pressure
Bring the system up to the normal operating pressure before commissioning.
V Top up the heating water or drain via the boiler drain
valve until the required operating pressure has been reached: minimum 15 psi, maximum 30 psi pressure.
V Bleed air from the heating system while filling.
6.2 Checking the safety valve
V Make sure that no persons are in the discharge area of
the pressure relief valve.
V Raise the lever on the pressure relief valve.
The pressure relief valve must open and release pressure. If the pressure relief valve does not discharge, it must be replaced, because system components can be damaged by excessive pressure.
Fig. 27 Pressure/temperature gauge for showing oper-
ating pressure and supply temperature
Caution: Risk of boiler damage from exces­sive dust and airborne particle levels.
V Do not operate the boiler when there is a
lot of dust in the boiler room, e.g. due to construction work.
V Install an air filter if the combustion air sup-
ply is very dusty (e.g. due to dirt roads and paths or dust-generating working environ­ments such as quarries, mines etc.) or contains airborne seeds from composite plants.
Caution: Risk of damage to system due to material stresses caused by temperature dif­ferentials.
V Only fill the heating system when cold (the
flow temperature should be no more than 100 °F).
7 747 019 141-17.1RS
Page 29
6
Commissioning the heating system
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
29
6.3 Checking position of heat exchanger baffles
Prior to commissioning, check that the heat exchanger baffles are in a horizontal position:
V Open burner door by removing the two hexagon-head
bolts at the sides.
V Slightly withdraw the flue gas baffles from the heat
exchanger.
V Adjust the heat exchanger baffles to a horizontal posi-
tion and push them back into the heat exchanger.
V Close burner door with the two hexagon bolts (approx.
90 inch-lbs). Tighten the hexagon bolts evenly to prop­erly seal the burner door.
Fig. 28 Opening the burner door
1 Flue gas baffles in the heat exchanger
6.4 Preparing the heating system for operation
V Open the fuel supply at the main shut-off valve. V Switch on the heating system emergency shut-off
switch and/or the appropriate circuit-breaker.
6.5 Starting up the control and the burner
For further start-up steps, follow the burner start-up sequence.To do so, it is essential that you consult the burner Æ documentation.
Use the on/off switch on the controls to switch the heat­ing system on. The burner starts up if the system is calling for heat or if you set the controls to manual mode. Æ service instructions for the controls.
V Select "Manual" mode . V Set the boiler water temperature control to the desired
temperature.
V Switch the on/off switch on (position "I").
Fig. 29 Switching on the controller
(e. g. Logamatic 2000)
1 Boiler water thermostat 2 On/off switch
1
7 747 019 141-27.1RS
1
2
7 747 019 141-28.1RS
Page 30
6
Commissioning the heating system
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
30
6.6 Notes on commissioning the burner
Allow burner to operate for 15 to 20 minutes before per­forming a combustion test. Earlier combustion tests can lead to incorrect readings as a result of burning off the sealing rope. We recommend rechecking the burner after a few weeks of operation.
Required instruments: –CO
2
measuring equipment – Draft measuring equipment – Oil pressure gauge – Stack thermometer –Smoke tester
V Check the combustion chamber pressure at the test
port.
V Check the breeching draft at a test port drilled in the
vent connector (chimney vent models only).
Fig. 30 Pressure test port on burner door
1 Pressure test port
6.7 Raising flue gas temperature
For the set flue gas temperature for the boiler see the technical data (Æ Chapter 2.7, page 8).
You may raise the flue gas temperature if you discover during tests that the flue gas temperature is too low for the type of chimney used (risk of condensation) by one or several of the following measures:
Incorrect burner adjustment can cause con­tamination of the boiler (e.g. soot), leading to low efficiency, high emissions, and a greater risk of service calls.
V Always check combustion with the follow-
ing instruments.
V Never adjust burner visually.
1
7 747 019 141-29.1RS
Caution: Risk of burning by touching hot boiler parts.
V Wear appropriate protective gloves or use
pliers.
Page 31
6
Commissioning the heating system
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
31
V Adjusting the position of heat exchanger baffles
-or­V Removing heat exchanger baffles
-or­V Removing the heat exchanger barrier plate
6.7.1 Adjusting the position of heat exchanger baffles
Only adjust or remove heat the exchanger baffles in pairs. V Open burner door by removing the two hexagon-head
bolts at the sides.
V Adjusting the position of heat exchanger baffles. V Slightly withdraw the flue gas baffles from the heat
exchanger.
V Turn the heat exchanger baffles to a slanting position
and push them back into the heat exchanger.
V Close burner door with the two hexagon bolts (approx.
90 inch-lbs). Tighten the hexagon bolts evenly to prop­erly seal the burner door.
V Re-check the flue gas temperature.
Fig. 31 Adjusting the position of heat exchanger baffles
6.7.2 Removing heat exchanger baffles
You can remove the baffle plates in pairs to raise the flue gas temperature.
V Open burner door by removing the two hexagon-head
bolts at the sides.
V Remove the baffle plates towards the front. V Close burner door with the two hexagon bolts (approx.
90 inch-lbs) Tighten the hexagon bolts evenly to prop­erly seal the burner door.
V Re-check the flue gas temperature.
Fig. 32 Removing heat exchanger baffles
7 747 019 141-30.1RS
7 747 019 141-31.1RS
Page 32
6
Commissioning the heating system
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
32
6.7.3 Removing the heat exchanger barrier plate
You can remove the blocking plate to further raise the flue gas temperature if the flue gas temperature is still too low after removing of the baffles.
V Open burner door by removing the two hexagon-head
bolts at the sides.
V Remove diverter plate by loosening bolt. V Re-check the flue gas temperature.
Fig. 33 Removing the heat exchanger barrier plate
6.8 Manual reset high limit (STB)
The manual reset high limit interrupts the power supply if the maximum permissible flow temperature is exceeded.
To enable a boiler reset and re-starting, the fault must be removed and the system temperature must have fallen below the limit.
V Check the function of the manual reset high limit
(Æ controls maintenance instructions).
6.9 Installing the burner door jacket
V Position the burner door panel on the hooks on the
boiler casing.
V Secure the burner door panel with the two screws at
the sides.
V The Logano G115 WS must be fitted with a burner that
has an operating range that matches the specifications of the Logano G115 WS.
V Mount the selected burner to the hole circle in the
burner door.
V Connect burner cable to burner. (Æ Installation instruc-
tions of burner).
Fig. 34 Installing the burner door jacket
7 747 019 141-32.1RS
Danger: Risk of fatal injury from electric shock.
V Only operate the boiler with the burner
hood/door panel fitted.
Caution: Risk of system damage from use of incorrect fuel.
V Only use burners which meet the techni-
cal requirements of the Logano G115 WS (Æ Chapter 2.7, page 8).
7 720 615 225-03.1RS
Page 33
6
Commissioning the heating system
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
33
6.10 Commissioning log
V Initial and date the commissioning steps carried out.
Commissioning operations Page Readings taken Comments
1. Fill heating system and check for leaks 21
____________ psi
– Heating system pressure
2. Bringing the system up to operating pressure
V bleeding heating system
V Testing relief valve
V adjust the expansion tank pressure (Æ see the expansion tank
manufacturer’s documentation)
28
____________ psi
3. Checking combustion air supply and flue system
4. Checking position of heat exchanger baffles 29
5. Switching on the controls and burner (Æ controls' documenta­tion)
29
6. Checking flue gas temperature and raising if required 30
____________ °F
7. Checking the manual reset high limit (STB) 32
8. Adjusting the controls settings to suit the customer's require­ments (Æ controls' documentation)
9. Informing the end user and handing over technical documentation
Confirmation of properly completed commissioning Company stamp/signature/date
Inform the customer about the correct fuel and correct operating pressure. Enter the de­tails in the table (Æ boiler operating instruc­tions).
Page 34
7
Shutting down the heating system
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
34
7 Shutting down the heating system
7.1 Shutting down normally
V With Buderus controls: switch off the on/off switch on
the controls (position "0"). This switches off the boiler and all its components (e.g. burner).
Fig. 35 Switching off the heating system
(Logamatic 2000)
1 On/off switch
V When using the aquastat: Shut off main heating system
by turning off the emergency shut-off switch (position "OFF"). This switches off the boiler with all its compo­nents.
V Further shut-down procedure Æ refer to aquastat doc-
umentation.
Fig. 36 Heating system emergency shut-off switch
V Shut off fuel supply by closing main valve.
7.2 Shutting down the heating system in an emergency
7.2.1 What to do in an emergency
Explain to the customer what to do in an emergency, e.g. a fire.
V Never put yourself at risk of fatal injury. Your own safety
must always take the highest priority.
V Disconnect the heating system from the electrical
power supply by means of the emergency shutoff switch or the heating system circuit-breaker.
Caution: Risk of system damage from freez­ing.
If the heating system has been switched off, it may freeze up in cold weather conditions.
V Leave the heating system switched on as
long as possible.
V Protect a disabled heating system from
freezing by draining the heating system and hot water pipes at the lowest point.
1
7 747 019 141-34.1RS
7 747 019 141-35.1RS
Use the heating system emergency shut-off switch located outside the boiler room or the heating system circuit-breaker for emergency shutdown.
Page 35
8
Heating system servicing
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
35
8 Heating system servicing
8.1 Why is regular maintenance important?
Heating systems should be regularly maintained for the following reasons:
– to achieve a high level of efficiency and to operate the
system economically (low fuel consumption), – to achieve a high level of operational reliability, – to maintain the cleanest possible combustion, – to ensure reliable operation and long service life.
Servicing work may only be carried out by a qualified serv­ice technician. If parts are replaced, only Buderus approved components may be used. A service must be carried out once a year. The results of the services must be recorded in the servicing and maintenance log.
8.2 Preparing the boiler for servicing
V Shut down the heating system. (Æ Chapter 7.1,
page 34) V Remove the burner door panel or the burner hood from
the boiler. (Æ Chapter 3.1, page 12) V Disconnect electrical supply to burner.
Spare parts can be ordered from Buderus us­ing the parts list.
Danger: Risk of death from electric shock. V Before working on the boiler and prior to
opening control panel: shut down the power supply by turning off the emergency shut-off switch or disen­gaging the heating system circuit breaker, and prevent from accidental reactivation.
Page 36
8
Heating system servicing
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
36
8.3 Cleaning the boiler
The boiler can be cleaned with brushes and/or by a wet method. Cleaning equipment is available as accessory.
V Open burner door by removing the two hexagon bolts
on the sides.
8.3.1 Cleaning the boiler with brushes
V Note the position of the heat exchanger baffles for later. V Remove the hot gas baffle plates from the hot gas pas-
sages.
V Clean the hot gas baffle plates with one of the two
cleaning brushes.
Fig. 37 After opening the burner door
1 Flue gas baffles in the heat exchanger
V Clean the hot gas passages by turning the round clean-
ing brush.
Fig. 38 Brushing out the hot gas flues
V Clean the combustion chamber with a flat brush.
Remove the debris from the combustion chamber, the hot gas flues and the flue connection.
V Refit the heat exchanger baffles in their original posi-
tions.
V Check sealing rope on burner door. Replace damaged
or hardened gasket cord.
V Close burner door with the two hexagon bolts (approx.
90 inch-lbs). Tighten the hexagon bolts evenly.
Fig. 39 Brushing out the combustion chamber
Caution: Risk of burning by touching hot boiler parts.
V Wear appropriate protective personal
safety equipment.
1
7 747 019 141-27.1RS
7 747 019 141-37.1RS
You can obtain suitable gasket cord from your local Buderus sales office.
7 747 019 141-38.1RS
Page 37
8
Heating system servicing
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
37
8.3.2 Wet cleaning (chemical cleaning)
For wet cleaning use a cleaning agent appropriate for the degree of soiling (soot or scale). Proceed with the wet cleaning in the same order as described for cleaning with brushes (Æ Chapter 8.3.1, page 36).
V Cover the control panel with plastic to prevent spray
from entering the control panel. V Spray cleaning agent evenly into the heat exchanger
heater passages.
V Close burner door and start up the heating system. V Heat the boiler to a temperature of at least 160 °F. V Shut down the heating system. V Brush out the heat exchanger heater.
8.4 Checking heating system operating pressure
The system pressure for closed systems must be 15 – 30 psi (1.0 – 2.1 bar).
V Check system pressure. V If the pressure gauge shows less than 15 psi, the pres-
sure is too low. Top up the system with water.
Fig. 40 Pressure/temperature gauge for showing oper-
ating pressure and feed temperature
Follow the instructions for the cleaning prod­uct. You may need to proceed differently from the method described here in some cir­cumstances.
Caution: Risk of system damage due to fre­quent topping up.
If you have to top up the heating water fre­quently, the heating system may suffer dam­age from corrosion or scaling, depending on the water quality.
V Ensure that your heating system is bled
properly.
V Check the heating system for leaks and
proper operation of the expansion vessel.
7 747 019 141-17.1RS
Page 38
8
Heating system servicing
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
38
V Add water through the feed valve. V Bleed the heating system. V Check the operating pressure again.
8.5 Testing relief valve
The functioning of the pressure relief valve must be checked at regular intervals (1-3 years as specified by local codes).
V Make sure that no persons are in the discharge area of
the pressure relief valve.
V Raise the lever on the pressure relief valve.
The pressure relief valve must open and release pressure. If the pressure relief valve does not discharge, it must be replaced, because system components may be damaged by excessive pressure.
Caution: Risk of damage to system due to material stresses caused by temperature dif­ferentials.
V Only fill the system when cold (the flow
temperature at the temperature/pressure gauge should be no more than 100 °F).
Page 39
8
Heating system servicing
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
39
8.6 Servicing and maintenance logs
V Initial and date the servicing operations completed. The inspection and servicing logs can also be used as
copy masters.
Service work Page Date:______ Date:______ Date:______
1. Check general condition of heating system
2. Visual inspection and function check of the heating system
3. Checking fuel and water-carrying components of the system for:
– leaks during operation
–leak test
– visible signs of corrosion
– signs of ageing
4. Check the combustion chamber and the heating sur­face for contamination; shut down the system for this step
34
5. Checking the burner (Æ burner documentation)
6. Check the combustion air supply and flue gas routing for function and safety
7. Check the operating pressure, relief valve and expan­sion tank inlet pressure
37
8. Checking function of DHW tank and sacrificial anode (Æ DHW tank documentation)
9. Checking controls settings (Æ controls' documenta­tion)
10. Record the final checks of the inspection work, incl. measurements and test results
Confirmation of properly completed servicing Company
stamp/signa­ture
Company stamp/signa­ture
Company stamp/signa­ture
Page 40
8
Heating system servicing
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
40
Date:______ Date:______ Date:______ Date:______ Date:______ Date:______ Date:______
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
Company stamp/signa­ture
Company stamp/signa­ture
Company stamp/signa­ture
Company stamp/signa­ture
Company stamp/signa­ture
Company stamp/signa­ture
Company stamp/signa­ture
If any condition requiring maintenance work is identified in the course of servicing, that work must be carried out as necessary to en­sure safe and proper operation.
Page 41
8
Heating system servicing
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
41
On-demand maintenance procedures Page Date:______ Date:______ Date:______
1. Shutting down the heating system 34
2. Removing and cleaning the heat exchanger baffles 36
3. Cleaning heat exchanger heater flue (heating surfaces)
and combustion chamber and afterwards refitting heat exchanger baffles in original positions
36
4. Checking seals/cord gaskets on burner door and
burner and replacing as necessary
36
5. Commissioning the heating system 29
6. Final check of the servicing work
7. Checking safe and proper operation
Confirmation of properly completed servicing Company
stamp/signa­ture
Company stamp/signa­ture
Company stamp/signa­ture
Date:______ Date:______ Date:______ Date:______ Date:______ Date:______ Date:______
1.
2.
3.
4.
5.
6.
7.
Company stamp/signa­ture
Company stamp/signa­ture
Company stamp/signa­ture
Company stamp/signa­ture
Company stamp/signa­ture
Company stamp/signa­ture
Company stamp/signa­ture
Page 42
9
Troubleshooting
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
42
9 Troubleshooting
Two type of fault are distinguished: – Burner faults and – Control and heating system faults.
If there is a burner fault the fault indicator lamp on the burner comes on (Æ burner documentation). Such faults can generally be reset by pressing the reset button on the burner. Controls and heating system faults are indicated on the controls display if it has one. For further information see Æ controls' documentation.
Correcting burner faults
V Press reset button on burner.
Fig. 41 Resetting the burner
1 Burner
Caution: Risk of system damage due to too
many resets Too many resets can damage the burner's ig-
nition transformer.
V Do not press the reset button more than
three times in a row.
V If the fault does not reset after the third at-
tempt, try to localize and rectify the fault with the help of the burner documentation.
V Notify a service engineer if necessary.
Caution: Risk of system damage from freez­ing.
The heating system can freeze up in cold weather if it has been disabled by a fault shutdown.
V Rectify the fault immediately and restart
the heating system.
V If this is not possible, protect your heating
system from freezing by draining the heat­ing system and hot water pipes at the low­est point.
1
6 720 615 225-04.1RS
Page 43
10
Installation examples
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
43
10 Installation examples
Key to abbreviations
Fig. 42 Multiple circuits with circuit valves
1 Baseboard
Fig. 43 Multiple circuits with circuit valves
1 Baseboard
KR Check valve SH Heating circuit adjuster
MAG Expansion tank SV Pressure relief valve
PH System pump THV Thermostatic radiator valve
PW Hot water pump WH Water compensation pipe (diversion)
7 747 019 141-40.1RS
SV
PH
MAG
THV
G125 WS/NA
1
1
1
G115 WS/NA
7 747 019 141-41.1RS
SV
PH
KR
MAG
G125 WS/NA
1
1
1
G115 WS/NA
Page 44
10
Installation examples
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
44
Fig. 44 Multiple circuits of water diversion for systems with a high water volume
1 Radiator 2 Boiler bypass
Fig. 45 Multiple circuits with pumps and motor-actuated 3-way mixing valve
1 Baseboard
7 747 019 141-42.1RS
SV
PH
THV
MAG WH
G125 WS/NA
3/4"
1
1
1
2
G115 WS/NA
7 747 019 141-43.1RS
SV
R2107
PH
PH
SH
180˚
100˚
100˚120˚
160˚180˚
M
PS
KR
KR
MAG
G125 WS/NA
1
G115 WS/NA
Page 45
11
Parts lists
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
45
11 Parts lists
The following parts are available from Buderus. If there are several Buderus article numbers for one item number, the numbers for the various models are listed in the relevant columns. Otherwise the table shows the number of com­ponents for each model.
Legend for tables 13 and 14:
x = no spare part
(x) = component of a set, only available with set
0 = no picture available
Boiler block and burner door (Æ Fig. 46)
Item no. Description Part number
G115/3 WS
3 section
G115/4 WS
4 section
G115/5 WS
5 section
10 Boiler block G115 WS 63036027 63036028 63036029
Available front section components
21 Plug G1 1/4" right 86055310 22 Gasket D 41.7x55x1.5mm AFM 34, left 86159710 23 Barrier plate with countersunk bolt, M8x16 63015342 24 Countersunk bolt DIN 7991 -M 8 x 16 -Ms (x)
Available back section components
50 Gasket D33x44x2mm 63005462 51 Plug G 1 05317712 52 Stud bolt, M10x65 5.6 as per drawing 05555070 20 Spacer sleeve R3/8"x39 (x) 54 Hexagon nut ISO4032-M10-8-A3K (x) 55 Washer DIN115-A10.5-A3K (x) 57 Reducer nipple G1"xG3/4" 63027607
60 Sensor sleeve PMW -3 SEE (4 1/2")"US" 7747022364 70 Anchor bolt set, M8x310mm 05127574 - ­70 Anchor bolt set, M8x440mm - 05127578 ­70 Anchor bolt set, M8x555mm - - 05127580
80 Flue connection complete 05354074
Available flue connection components
81 Sealing rope 8x1050 GP 63020961 0 Gasket compound brown (cartridge 310 ml) for gluing sealing rope 63014361
90 Feed-in connector assy. 1 1/4-NPT1, G115/G115 WS 63028062 63028062 63028061 91 Seal 55x41.7x1.5 mm 05752540
Spare parts that are supplied with the spare boiler block
120 Heat exchanger baffle 05347085 05347087 05347089
130 Angle bracket 420mm long 7747000018 – 130 Angle bracket 540mm long 7747000019 – 130 Angle bracket 660mm long 7747000020 131 Washer DIN126-9 (x) 132 Hexagon bolt ISO 4017 -M8x25-8.8 (x) 133 Hexagon nut DIN 6923-M8-8.8-A3K (x)
140 Hinge bracket G105/G115 05327033 141 Washer DIN125-A10.5-A3K (x) 142 Hexagon bolt ISO4017-M10x25-8.8 (x) 150 Hexagon bolt ISO4014-M10x65-8.8 (x) 160 Washer DIN125-A10.5-A3K (x) 180 Boiler feet M10x51mm complete 05236440
190 Flue pipe sealing collarDN130 complete 05354010
Tab. 13 Boiler block and burner door
Page 46
11
Parts lists
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
46
200
Flue silencer DN130 complete, without condensate drain; higher sound absorption
05074020
or:
210
Flue silencer D130 with an adaptor of 100mm length, with condensate drain; lower sound absorption
05074022
Flue silencer components
190 Flue pipe sealing collarDN130 complete 05354010 220 Flue pipe sealing collar assy. DN130 (stepped) 05354030 230 Sealing rope 10x2000 GP 63020963
250 Burner door complete 63023858
Available burner door components
260 Hinge G 215 05327020 270 Washer DIN125 A10,5 A3K (x) 280 Hexagon bolt ISO4017 M10x25 8. (x) 290 Inspection window seal assy. V3 63023634
Obtainable individual parts of inspection window seal
300 Gasket 30x30x3 63014382 310 Inspection window glass, Tempax 30x30x3.3mm 05447620 320 Inspection window cover x 330 Hexagon bolt ISO4017 M6x12 8.8 A3K (x) 340 Pressure testing nozzle M6 SW10 V2 (x)
350 Heat insulation for burner door BE/non-Buderus burner size 21/334/5 63002401
Available heat insulation components
360 Heat insulation for burner door panel 24mm thick 63004169 370 Insulation ring for burner door panel 10mm thick 63004170 380 Washer DIN9021 A6,4 A3K (x) 390 Sheet metal screw DIN7981 C ST6,3x25 A3T (x)
400 Sealing rope 14x1650 GP 63020965 0 Gasket compound brown (cartridge 310 ml) for gluing sealing rope 63014361
(x)
Mounting material for boiler block G115 WS
63031288
Contents: 1 countersunk bolt M8x16 Ms 2 spacer sleeves R3/8"x39 2 hexagon nuts ISO4032 M10 8 A3K 8 washers DIN125 A10.5 A3K 4 washers DIN126 9 4 hexagon bolts ISO4017 M8x25 8.8 4 hexagon nuts DIN6923 M8 8.8 A3K 4 hexagon bolts ISO4017 M10x25 8.8 2 hexagon bolts DIN6921 M10x65 8.8 1 hexagon bolt ISO4017 M6x12 8.8A3K 2 washers DIN9021 A6.4 A3K 2 sheet metal screws DIN7981 C ST6,3x25 A3T
0
B-KIT G115 WS
63029762
Contents:
1 Supply manifold G115"US" 1 elbow 90DEG11/4 1 elbow 90DEG 3/4 I/A 1 double nipple R11/4-11/4NPTx75 1 boiler drain 3/4 1 relief valve 3/4Mx3/4F 30PSI 1 temperature/pressure gauge 1 / 4 NPT 1 Bolt set B-Kit G115"US" 1 adjustable boiler foot M10x51 packed
Item no. Description Part number
G115/3 WS
3 section
G115/4 WS
4 section
G115/5 WS
5 section
Tab. 13 Boiler block and burner door
Page 47
11
Parts lists
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
47
Fig. 46 Boiler block and burner door
7747102153-00-Kesselblock und Brennertür G125 WS NA
21
23
24
133
133
180
180
52
53
22
21
370
380
390
280
270
260
250
350
300
290
310
330
340
320
350
400
360
22
52
55
54
80
142
141
140
130
131
132
120
70
70
91
90
10
81
51
57
50
50
60
150
160
70
230
220
200
210
190
7747102153-00-Boiler block and burner door G115 WS NA
Page 48
11
Parts lists
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
48
Boiler jacket (Æ Fig. 47)
Item no. Description Part number
G115/3 WS
3 section
G115/4 WS
4 section
G115/5 WS
5 section
A complete outer panel set consists of: front panel, rating plate, front insulation, cross-member, 2 side panels, boiler insulation, retaining spring, front hood, rear hood, rear panel and fixings.
Available outer panel components
10 Front panel assembly G115 63046570 18 Logano G115 name plate 7747025928 20 Front insulation G115 63025265 40 hexagon bolt ISO4017-M8x12-8.8 (x) 50 Cross-member G115 63029209 60 Hexagon nut DIN555 M8 5 (x) 70 Washer DIN126 9 (x) 80 Side panel 445mm long 63029945 - ­80 Side panel 565mm long - 63029946 ­80 Side panel 685mm long - - 63029947 85 Sheet metal screw C ST3,9x13 A3T (x) 90 Flathead bolt 3,9x9,5 A3T (x) 95 Plug-in fuse (x)
100 Boiler block insulation G115 7747014842 - ­100 Boiler block insulation G115 - 7747014843 ­100 Boiler block insulation G115 - - 7747014844 110 Retaining spring for securing heat insulation 7747016084
120 Front hood G115/S105/S105U 63029948 125 Cover panel 300x160 cover front 63016429 130 Rear hood assembly G115 "US" 63029949 63029950 63029951 140 Rear panel G115/G115U 63036024 145 Rear panel insulation 63025264 150 Cable clamp 07060754 160 Washer DIN432 10,5 St A3E (x) 170 Hexagon nut DIN555 M10 5 (x)
(x)
Panel fixings G115, GC115, G134
05180842
Contents: 17 flathead bolts ea. 3.9x9.5-A3T 3 sheet metal screws C-St3,9x13-A3T Oval-headed screw DIN7985-M6x16-4.8-A3T 2 push-fit catches 4 hexagon bolts ISO4017-M8x12-8.8 1 hexagon nut DIN555 M8 5 4 washers DIN126 9 4 washers DIN432 10.5 St A3E 4 hexagon nuts DIN555 M10 5
Tab. 14 boiler jacket
Page 49
11
Parts lists
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
49
Fig. 47 boiler jacket
7747102154-00-Verkleidung G125 WS NA
85
80
40
70
40
70
40
70
80
60
50
85
20
100
10
18
90
130
120
90
90
125
90
140
145
150
170
160
170
160
90
95
110
7747102154-00-boiler jacket G125 WS NA
Page 50
12
Circuit diagrams
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
50
12 Circuit diagrams
Fig. 48 Circuit diagram 1
Riello F3 or F5 Series Oil Burner Wiring
Riello F3 or F5 Series Oil fired Burner
Using a L7248C1006 Aquastat –
1) Connect room thermostat or end switch wiring to the “T T” terminals of the L7248C aquastat.
2) Connect incoming 120 Vac power source to L1 on the L7248C aquastat .
3) Connect a neutral to “L2” on the L7248C aquastat.
4) Connect black wire in wire harness to terminal B1 of the L7248C (the “L” terminal on the Riello burner terminal block).
5) Connect white wire in wire harness to terminal B2 of the L7248C (the “N” Terminal on the Riello burner terminal block).
6) Connect green wire to ground screw on L7248C (the ground connection on Riello Burner).
7) Red wire is not used in this application.
LN X
Terminal strip on Riello Burner
White wire
Red wire- NOT USED IN
THIS APPLICATION
Black wire
Ground
Quick connect
plug
Green wire
T
B1
Honeywell
Operating
Aquastat
(L7248C1006)
N
Neutral
Ground
T
Thermostat,
aquastat, or end
switch,
C1
C2
L1
B2
L2
Fuse
L
Hot
Service
Switch
Field wiring
Factory wired
Low Voltage
Field installed
WMO-1*)
*) Canadian installations: Install in series with start wire to the burner (phase).
Page 51
12
Circuit diagrams
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
51
Fig. 49 Circuit diagram 2
Carlin EZ-1 HP Burner Wiring with L7248C Aquastat
T
B1
Honeywell
Operating
Aquastat
(L7248C1006)
Carlin EZ-1 Wiring Schematic -
The Carlin EZ-1 Burner is equipped with the 60200 Series Primary Control with pre-purge.
Using a L7248C Aquastat –
1) Connect room thermostat or end switch wiring to the T & T terminals of the L7248C Aquastat.
Note: DO NOT CONNECT ROOM THERMOSTAT TO THE T – T TERMINALS OF THE CARLIN 60200 Control!
2) Connect 120 Vac power source to L1 on the L7248C aquastat.
3) Connect neutral source to L2 on the aquastat.
4) Connect red wire from wire harness to L1 on the L7248C (the red/white wire on the Carlin 60200 Control).
5) Connect black wire from wire harness to B1 on the L7248C (the black wire on the Carlin 60200 Control).
6) Connect white wire from wire harness to B2 on the L7248C ( the white wire on the Carlin 60200 Control).
7) Connect green wire to ground screw on the L7248C and to the ground connection on the Carlin Burner.
8) Install a jumper wire on the T T terminals of the 60200 Control.
9) The pink wires from the Carlin “In line heater” may be connected to a constant 120Vac power source or the red/white wire and the white wire in the Carlin 60200 Primary Control.
CCT 60200 Series Primary Control
Field
installed
jumper
Field wiring
Factory wired
Low Voltage
Field installed
Quick
connect
plug
White
Violet
Orange
Blue
Red/White
Black
T
F
T
F
A
A
CAD
Cell Eye
Red wire
Black wire
White wire
Green wire
Ground
Ground
T
Thermostat,
aquastat, or end
switch,
C1
C2
L1
B2
L2
Fuse
Service Switch
N
NeutralLHot
WMO-1*)
*) Canadian installations: Install in series with start wire to the burner (phase).
Page 52
12
Circuit diagrams
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
52
Fig. 50 Circuit diagram 3
Becket NX Burner Wiring
Becket NX Wiring Schematic -
With a L7248C1006 Aquastat –
1) Connect room thermostat or end switch wiring to the T T terminals of the L7248C Aquastat.
Note: DO NOT CONNECT ROOM THERMOSTAT TO THE “T T” TERMINALS OF THE R7184B OR 7505B PRIMARY CONTROL!
2) Connect 120 Vac power source to L1 on the L7248C aquastat.
3) Connect neutral source to L2 on the L7248C aquastat.
4) Connect the black wire in wire harness to B1 of the L7248C (the black wire on the R7184B or 7505B Primary Control).
5) Connect the white wire in wire harness to B2 of the L7248C (the white wire on the R7184B or 7505B Primary Control).
6) Connect the green wire in the wire harness to ground screw on the L7248C (the ground connection on the R7184B or 7505B Prima ry Control).
7) Install a jumper wire on the T T terminals of the R7184B or 7505B Primary Control.
Field wiring
Factory wired
Violet
Orange
Blue
Yellow
Black
Honeywell R7184B series Primary Control
or Beckett Genisys 7505B Primary Control
Low Voltage – Field
installed
T
T
A
A
Yellow
White
Burner Junction Box
Field installed
jumper
CAD
Cell
Green wire
Black wire
White wire
Quick
connect plug
Ground
T
B1
Honeywell
Operating
Aquastat
(L7248C1006)
Ground
T
Thermostat,
aquastat, or end
switch,
C1
C2
L1
B2
L2
Fuse
Service Switch
N
NeutralLHot
WMO-1*
Red
*) Canadian installations: Install in series with start wire to the burner.
Page 53
Index
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
53
Index
A
Aquastat.............................................................. 24
B
B-kit components ................................................... 7
Boiler output.......................................................... 8
Boiler room.......................................................... 10
Boiler type
............................................................. 8
Burner, notes on commissioning ............................ 30
C
Changing boiler hinges to left hand side ................. 15
Checking for leaks (CH system)
............................. 21
Cleaning heat exchanger
....................................... 36
Combustion air supply .......................................... 10
Commissioning
.................................................... 28
log
.................................................................. 33
Connecting power supply...................................... 27
Connecting the fuel supply .................................... 23
Connections
.......................................................... 8
Correcting burner faults........................................ 42
D
Dimensions............................................................ 8
Dirt trap
.............................................................. 19
E
Environment ........................................................ 10
F
Fitting B-kit.......................................................... 19
Fitting burner door panel ...................................... 27
Fitting cable ties................................................... 27
Fitting outer casing panels
.................................... 27
Fitting temperature sensor assembly...................... 26
Fitting the controls
............................................... 25
Flow temperature
................................................... 8
Fuel .................................................................... 10
H
Heat exchanger baffles, checking position .............. 29
Heating circuits, multiple ...................................... 43
Heating emergency stop switch
............................. 34
I
Installation diagram .............................................. 20
Installation examples ............................................ 43
Installation of boiler drain ..................................... 20
L
Log, commissioning .............................................. 33
Logs, servicing and maintenance
............................ 39
M
Main isolating cock ............................................... 29
Main isolating valve............................................... 29
Maintenance, regular
............................................ 35
Master switch ...................................................... 34
Mounting the adjustable feet ................................. 16
Mounting the burner
............................................. 23
O
On/Off switch ...................................................... 34
Onsite testing pressure ......................................... 21
Operating Conditions
............................................ 10
Operating conditions
.............................................. 9
P
Pack contents ........................................................ 7
Parts lists ............................................................ 45
Permissible operating pressure................................ 8
Power supply voltagePower supply
........................ 11
Pressure testing nozzle ......................................... 30
Pressure/temperature gauge ............................ 28, 37
R
Raising flue gas temperature ................................. 30
Rated heat output .................................................. 8
Removing burner door panel.................................. 12
Removing burner hood
.......................................... 24
Removing heat exchanger baffles ........................... 36
Replacing rope gasket........................................... 36
Reversing boiler door
............................................ 15
Routing burner cable ............................................ 26
S
Safety.................................................................... 3
Safety valve
.............................................. 19, 21, 28
Shutting down
..................................................... 34
Site test pressure ................................................. 11
Specifications
........................................................ 8
T
Temperature/pressure gauge ............................ 28, 37
Topping up
.......................................................... 37
Transporting with boiler trolley/sack truck .............. 13
Troubleshooting ................................................... 42
W
Wall clearances .................................................... 14
Water quality
....................................................... 11
Wet cleaning
........................................................ 37
Page 54
Notes
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
54
Page 55
Notes
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
55
Page 56
Bosch Thermotechnology Corporation 50 Wentworth Avenue Londonderry, NH 03053 Tel. 603-552-1100 Fax 603-584-1681 www.buderus.net
Products manufactured by Bosch Thermotechnik GmbH D-35573 Wetzlar www.buderus.de
Bosch Thermotechnology Corporation reserves the right to make changes without notice due to continu­ing engineering and technological advances.
Loading...