Buderus AM10 Installation And Operating Instructions Manual

Page 1
For the contractor
Please read these instructions care­fully
Installation and Operating Instructions
Controller
Modulating Outdoor Reset Control
°F
72186100-00N
AM10
7218 6100 (07/2010) US/CA
US-listed
Page 2
Contents
AM10 - We reserve the right to make any changes due to technical modifications!
2
Contents
1 Installation manual . . . . . . . . . . . . . . . . . . . . . 3
1.1 Description of Module . . . . . . . . . . . . . . . . 3
1.2 Outdoor reset . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Mounting of the AM10 . . . . . . . . . . . . . . . . 4
1.4 Positioning outdoor sensor . . . . . . . . . . . . 6
1.5 Single Boiler Control . . . . . . . . . . . . . . . . . 6
1.6 Cascade Boiler Control . . . . . . . . . . . . . . . 8
2 User Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2 Heating curve . . . . . . . . . . . . . . . . . . . . . . . 9
2.3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.4 Settings description . . . . . . . . . . . . . . . . 10
2.4.1 1st menu, idle display . . . . . . . . . . . . . . . 10
2.4.2 2nd menu, supply temperature set point. 10
2.4.3 3th menu, target point of heating curves. 10
2.4.4 4th menu, base point of heating curves 11
2.4.5 5th menu, warm weather shut down . . . 11
2.5 Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.5.1 Fault code 5H . . . . . . . . . . . . . . . . . . . . . 12
2.5.2 Sensor fault/emergency operation . . . . 12
Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Page 3
AM10 - We reserve the right to make any changes due to technical modifications!
3
Installation manual
1
1 Installation manual
1.1 Description of Module
Product description
The AM10 is a modulating control for Buderus boilers equipped with the EMS bus. It sets the supply water temperature based on outdoor temperature. The boiler fires, runs and modulates based on the information received from the AM10, and the delta temperature between supply and return. An ON/OFF signal from 3th party room thermostats or zone controllers is used to communicate a heat demand. The AM10 offers warm weather shutdown when the outdoor temperature rises above an adjustabletemperature. To control and stage multiple boilers, combine the AM10 with an MCM10 module.
Fig. 1 Included items
2 x
2 x
2 x
4 x
3 x
mode
°F
72186100-01N
Page 4
Installation manual
AM10 - We reserve the right to make any changes due to technical modifications!
4
1
1.2 Outdoor reset
Outdoor reset is a smart way to economically control space heating based on outdoor temperature. It functions based on the fact that the colder the weather the greater the heat loss of a structure, and the higher the supply water temperature needed to heat the house. On a warmer day with smaller losses a lower water temperature will be able to heat the house.
Outdoor reset is the preferred control when using multiple zones, as the boiler supply water temperature is not dictated by a master or largest zone, but solely based on the heat loss of the structure.
Heating curve
The AM10 has a built in linear heating curve that sets the supply water temperature in relation to the outdoor temperature.
The maximum supply water temperature is set on the boiler dial works as a high limit. The boiler will follow the heating curve in the AM10 up to the high limit.
1.3 Mounting of the AM10
Mount the AM10 module inside a Buderus boiler. For detailed instructions see the installation manual of your boiler.
For connecting the AM10 to the EMS-Bus: (Æfig. 5).
Setting
Outside
temperature
[°F]
Supply
temperature
[°F]
Default 14 167 Example 1 0 170 Example 2 -10 175 Example 3 -20 180
Tab. 1 Heating curve
Page 5
AM10 - We reserve the right to make any changes due to technical modifications!
5
Installation manual
1
Fig. 2 Thermostat
Fig. 3 Outdoor sensor
On/Off
mode
°F
L
L ≤ 100 ft.
R ≤ 100 Ω
Ø = 18 AWG
Ø
72186100-02N
mode
°F
L
L ≤ 100 ft.
R ≤ 100 Ω
Ø = 18 AWG
Ø
72186100-03N
[°F] [k Ω] [°F] [k Ω] [°F] [k Ω] [°F] [k Ω]
-40 336.5 5 72.9 50 19.9 95 6.5
-31 242.6 14 55.3 59 15.7 104 5.3
-22 177.0 23 42.3 68 12.5 113 4.4
-13 130.4 32 32.7 77 10.0 122 3.6
-4 97.1 41 25.4 86 8.1
Tab. 2 Sensor resistance table
Page 6
Installation manual
AM10 - We reserve the right to make any changes due to technical modifications!
6
1
1.4 Positioning outdoor sensor
For best performance the outdoor sensor is to be positioned where the sun can never reach it. Mount only on a north facing wall of the building, out of the sunlight, with at least 1 foot (30 cm) above snow line. Keep the sensor away from heat sources like dryer, water heater, or boiler vents, windows, etc.
Fig. 4 Sensor location
1.5 Single Boiler Control
To equip a single Buderus with outdoor reset control, required items are:
ON/OFF thermostat for every heating
zone with individual zone pump or zone valve
•Pump relay
Wiring
72186100-04N
Page 7
AM10 - We reserve the right to make any changes due to technical modifications!
7
Installation manual
1
Fig. 5 Wiring detail
If there are multiple zones, wire all thermostats in parallel for calls for heat from any thermostat to produce a heat demand.
Outdoor
sensor
N
Pump Relay
H C1 C2 X X
T T
Dedicated
120 VAC
15 Amp Circuit
Neutral
Zone valve
Line
120 VAC
Field wiring
Low Voltage
Field wiring
AM10 Module
EV
1
2
FW
1 21 2
WA
1 2
FA
1 2
RC
DHW Tank
Sensor
Factory
Installed
Jumper
RC 10/20
Outdoor
sensor
T T
Connection
DHW
Sensor
Safety
Limit
Orange Blue Lt Green Lt Gray Red
Wire terminal strip
Terminals FA and WA
not used in this
application
1
2
1
2
On / Off 1 2
72186100-05N
Do not install RC10 module when using this configuration.
Page 8
Installation manual
AM10 - We reserve the right to make any changes due to technical modifications!
8
1
1.6 Cascade Boiler Control
In a Buderus cascade with an MCM10 the AM10 is used as a modulating control based on outdoor temperature. The MCM10 will determine which boiler or boilers need to fire and at what modulation. The MCM10 also rotates the boilers for equal run time. For details on the MCM10 module, consult the MCM10 manual.
Do not install RC10 module when using this configuration.
Page 9
AM10 - We reserve the right to make any changes due to technical modifications!
9
User Manual
2
2 User Manual
2.1 Introduction
The AM10 is an outdoor temperature­dependent controller with a linear heating curve. The heat demand is communicated using a dry contact input.
2.2 Heating curve
The heating curve indicates the relationship between the outdoor temperature and the supply temperature. This concerns a straight line which can be described by 2 points (A and B). Point A is the supply temperature at an outdoor temperature of 14 °F and point B is the supply temperature at an outdoor temperature of 68 °F. C is the high limit supply temperature set on the boiler (Æfig. 6).
The supply temperature requested by the AM10 can never be higher than the high limit supply temperature of the boiler. For this reason it is recommended to set the supply temperature on the boiler (line C) to the maximum value, unless you deliberately want to compensate the heating curve, for example for a radiant floor heating system.
Fig. 6 Heating curve
1 Supply temperature [ °F] 2 Outdoor temperature [ °F]
2.3 Operation
Use the Mode key (Æ fig. 7, [1]) to go through the various menu items(Æ fig. 7, [4]) ; a line (Æ fig. 7, [2]) on the display indicates the active menu item.
The value of a menu item which can be set will flash. The value can then be changed using the plus + and minus – (Æ fig. 7, [3]) keys. The settings will not be lost if there is a power outage.
Fig. 7 Display view
B
+68 +14 -40
C
A
72186100-07N
2
1
°F
mode
1 3
72186100-08N
2
4
Page 10
User Manual
AM10 - We reserve the right to make any changes due to technical modifications!
10
2
If the display receives no user's input for 10 seconds, it will automatically switch over to its idle display (outdoor temperature). The display code is shown (flashing) when the appliance is locked. Otherwise the following symbols are implemented:
2.4 Settings description
2.4.1 1st menu, idle display
The current outdoor temperature is shown (64 °F); the corresponding symbol is marked. A heat demand has been registered on the AM10; the appliance is in heating mode .
Fig. 8 Idle display
2.4.2 2
nd
menu, supply temperature
set point
Use the Mode key to select the 2
nd
menu
item: the supply temperature setpoint .
Range: 32 - 194 °F.
Fig. 9 Supply temperature on the boiler
2.4.3 3
rd
menu, target point of
heating curve
Use the Mode key to select the symbol. This concerns the target point of the heating curve corresponding with an outdoor temperature of 14 °F. The value will flash and can be changed using the + and – keys.
Adjustment range: 68 - 194 °F. Factory setting: 167 °F.
Fig. 10 Target point of heating curve
Symbol Icon Meaning
Flame Appliance in
heating mode
Switch
contact
AM10 received a
heat demand
Engineer‘s
wrench
Appliance locked
Tab. 3 Mode key icons
°F
72186100-09N
°F
72186100-10N
°F
72186100-11N
Page 11
AM10 - We reserve the right to make any changes due to technical modifications!
11
User Manual
2
2.4.4 4th menu, base point of heating curve
Use the Mode key used to select the symbol. This concerns the base point of the heating curve corresponding with an outdoor temperature of 68 °F. The value will flash and can be changed using the plus + and minus – keys.
Adjustment range: 68 - 194 °F. Factory setting: 86 °F.
Fig. 11 Display of 4
th
menu item
2.4.5 5
th
menu, warm weather shut
down
Use the Mode key to select the warm weather shut down temperature . This concerns the maximum outdoor temperature at which the heating is still operational. The value will flash and can be changed using the plus + and minus – keys.
Adjustment range: 32 - 86 °F. Factory setting: 70 °F.
Fig. 12 Display of 5
th
menu item
2.5 Faults
The appliance is locked. When the appliance is in idle mode, a flashing appliance display code is shown instead of the outdoor temperature and the key symbol is displayed. Adjustments can still be made by selecting the relevant parameter using the Mode key. However, the appliance will be in idle mode and the display code will show for as long as the system detects a fault.
The meanings of the various codes and the relevant troubleshooting procedures are detailed in the boiler's installation instructions.
°F
72186100-12N
°F
72186100-13N
Page 12
User Manual
AM10 - We reserve the right to make any changes due to technical modifications!
12
2
2.5.1 Fault code 5H
This is a communication fault. Check the connection to the boiler.
Fig. 13 Fault indication
2.5.2 Sensor fault/emergency operation
If no sensor is detected on the AM10, dashes are shown in the numerical field instead of the outdoor temperature.
If there is a heat request (the display will show ), the AM10 will request 122 °F, if this is permitted by the high limit.
Fig. 14 Sensor fault display
°C
72186100-14N
°F
72186100-15N
Page 13
AM10 - We reserve the right to make any changes due to technical modifications!
13
2
Notes
Page 14
AM10 - We reserve the right to make any changes due to technical modifications!
14
2
Notes
Page 15
AM10 - We reserve the right to make any changes due to technical modifications!
15
2
Notes
Page 16
United States and Canada
Bosch Thermotechnology Corp. 50 Wentworth Avenue Londonderry, NH 03053 Tel. 603-552-1100 Fax 603-584-1681 www.buderus.us U.S.A.
Products manufactured by Bosch Thermotechnik GmbH Sophienstrasse 30-32 D-35576 Wetzlar www.buderus.com
Bosch Thermotechnology Corp. reserves the right to make changes without notice due to continuing engineering and technological advances.
Loading...