Buderus 600 - 11S, 600 - 19S, 600 - 24S, 600 - 24C User Manual

Page 1
7209 6800 - 11/2003 GB(EN) For the user
Users manual
Wall-mounted condensing gas boiler
600 - 11S / 19S / 24S / 24C
U122 K
Please read thoroughly before operating the unit
Page 2
Preface
Introduction
Please read these instructions and follow them carefully for a safe and economical use of your boiler.
Important general instructions for use
This device should only be used for its intended purpose and in accordance with the operating instructions. It is the law and in your own interest, and that of safety that this boiler must be installed by a CORGI registered installer, in accordance with the relevant requirements of the current Gas Safety (Installation and Use) Regulations, The Building Regulations, current I.E.E. Wiring Regulations and the relevant British Standard Codes of Practice.
The device may only be used in combination with the units, accessories and spare parts listed in the installation and servicing instructions. Other combinations of units, accessories and consumables are only to be used if they completely fulfil the specifications involved, and if system performance and safety are not affected in any way.
Subject to technical modifications
As a result of our policy of constant development, there may be small differences with respect to illustrations, functional steps and technical data.
Cleaning
For normal cleaning simply dust with a dry cloth. To remove stubborn marks and stains, wipe with a damp
cloth and finish off with a dry cloth.
DO NOT use abrasive cleaning materials.
2
Operating instructions for 600 - 11S /19S / 24S / 24C • Edition 11/2003
Boulter Buderus Ltd. • http://www.boulter-boilers.com
Page 3
Operating Instructions
Dear Customer,
Your Buderus 600 Series wall-mounted condensing gas boiler has been designed and built in accordance with state-of-the-art technological standards and the recognised safety rules. Special focus has been placed on operator convenience in this respect.
Carefully read the safety instructions and operating manual to ensure safe, economic and ecologically beneficial use of the unit.
Due to the high efficiency of the boiler a plume of water vapour may form at the terminal during operation. This is normal.
1 Safety precautions
ADANGER!
If you smell gas:
1. No naked flames ! Do not smoke !
2. Avoid sparks ! Do not operate electrical switches. Do not use the telephone, plug-in devices of any kind or the doorbell!
3. Shut off the main gas supply!
4. Open windows and doors!
5. Warn building occupants and evacuate the building!
6. Call TRANSCO (under 'GAS' in the telephone directory) from outside the building!
INOTE
In the event of any other type of incident, shut off the main gas supply and electric supply to the appliance and seek assistance from a CORGI registered engineer.
3 Working in the heating
system
ADANGER !
Only a CORGI registered Engineer is to be entrusted with the installation of this boiler, the gas supply and the flue connection. Commissioning, Servicing and any Repairs must be carried out by a competent person i.e.: a CORGI Registered Engineer. All CORGI Registered Installers carry a CORGI identification card and have a registration number. Both should be recorded in your boiler logbook. You can check your installer/Engineer is registered by telephoning 01256 372300 or by writing to: CORGI, 1 Elmwood, Chineham Business Park, Crockford Lane, Basingstoke. RG24 8WG
INOTE
It is mandatory to clean and service the system once a year ! This includes an inspection of the entire system to see if it is in full working order. Any faults and defects found in the course of inspection must be rectified immediately.
It is recommended to enter into a service contract with a specialist company.
4 Functions of the system
and operating instructions
The installer should familiarize the user with the functions and operation of the heating system and ensure that a complete set of technical documentation is supplied.
2 Installation area / boiler
room
ADANGER!
The air intake and outlet openings must not be reduced in size or closed.
ADANGER!
Do not store or use inflammable materials or liquids near the heating boiler.
INOTE
To prevent the boiler from being damaged, care must be taken not to contaminate the combustion air with halogenated hydrocarbons (e. g. contained in aerosol sprays, solvents, detergents, paints, and adhesives), or with high quantities of dust. The room in which the boiler is installed must be frost-proof and be well ventilated.
5 Maintenance
The appliance should be serviced at least once a year by a CORGI registered installer.
Boulter Buderus Ltd. • http://www.boulter-boilers.comSubject to modifications resulting from technical improvements!
3Operating instructions for 600 - 11S /19S / 24S / 24C • Edition 11/2003
Page 4
Operating Instructions
6 Initial start-up
6.1 Preparing for operation
Please note also the operating instructions supplied with the control unit.
6.1.1 Check water pressure
z Open the control panel cover.
z Check the water pressure (fig. 1, item 1).
Optimum filling pressure is 1.0 to 1.2 bar, max. water pressure is 1.5 bar.
If pressure is below 1.0 bar, proceed as described in “Topping up the heating system”, otherwise continue as described in Section 6.1.3 “Temperature-setting adjustments”.
3
4
120
2
60
°C
bar
1
1
20
0
11
I 0
1
KW
01
12
10
1
10
1
10
Topping up the heating system
AWARNING!
The wall-mounted condensing gas boiler must not be activated at this stage.
The system should be filled with untreated mains water.
z Set three-way valve to the middle setting (applicable
for 24C only). This is done by pushing the lever on the three-way valve (fig. 2) with a screwdriver to the middle setting.
Fig. 1 Pressure display
4
Operating instructions for 600 - 11S /19S / 24S / 24C • Edition 11/2003
Fig. 2 Three-way valve
Boulter Buderus Ltd. • http://www.boulter-boilers.com
Page 5
z If necessary open the CH flow and CH return
maintenance valves (fig. 3, item 1 and 2).
Operating Instructions
z Connect temporary hose (fig. 4).
z Open both stop valves.
1
CH Flow
DHW Hot
(combi only)
Gas
Fig. 3 Maintenance shutoff valves
stop
valve
double
check
valve
DHW
temporary
hose
cold
CH Return
DHW Cold
(combi only)
stop
valve
CH
return
2
z Fill the system to a pressure of 1.0 to 1.2 bar
(fig. 5, item 1). Max. water pressure is 1.5 bar.
z Shut both stop valves and disconnect the filling loop.
Fig. 4 Connecting temporary hose
3
4
120
2
60
°C
bar
1
1
20
0
11
I 0
1
KW
01
12
10
1
10
1
10
Fig. 5 Pressure display
Boulter Buderus Ltd. • http://www.boulter-boilers.comSubject to modifications resulting from technical improvements!
5Operating instructions for 600 - 11S /19S / 24S / 24C • Edition 11/2003
Page 6
Operating Instructions
6.1.2 Purging the heating-water circuit
z Unscrew the four screws at the top and bottom of the
ventilation cover (fig. 6, item 1) and remove the ventilation cover.
1
Fig. 6 Remove ventilation cover
z Open the cap on the automatic vent unit (fig. 7) by
one turn to allow any residual air to escape.
z If the air purging operation causes the pressure to
drop, top up with water.
z Refit the ventilation cover.
z Remove the hose from the filling and draining valve,
unscrew the hose spigot and screw the cover cap back on.
z Purging the system at the radiator bleed-valves.
INOTE
If there are frequent water losses, have the system examined and repaired by a CORGI registered installer. Have the inhibitor concentration checked every year.
Fig. 7 Automatic air vent unit
6
Operating instructions for 600 - 11S /19S / 24S / 24C • Edition 11/2003
Boulter Buderus Ltd. • http://www.boulter-boilers.com
Page 7
6.1.3 Temperature-setting adjustments
z Set flow temperature at the control unit (fig. 8, item 6)
(see table 1).
z Set hot-water temperature for 600 - 24 C with
integrated hot-water supply at knob (fig. 8, item 3) (see table 2). For energy saving (no heat-retention function) move knob (fig. 8, item 3) to cold-start-setting “1”. Set outlet temperature, at the same time, to 60 °C.
z Set hot-water temperature for 600 Series with
external tank at control unit (fig. 8, item 3) using table 3.
z Adjust room temperature to maximum setting at the
control unit.
z Open the gas service valve by pushing in and turning
anticlockwise into a vertical position (fig. 8, item 4).
z Push the mains power switch (fig. 8, item 1) to “I”.
The boiler runs through the start-up programme and the burner is ignited after approx. 30 seconds.
z Adjust room temperature to desired setting at the
control unit.
Operating Instructions
2
11
1
6
I
0
1
10
5
Fig. 8 Control panel, pressure display, gas service valve,
temperature indicator
KW
01
12
1
10
1
10
3
4
Control unit Range of application Controller position / boiler flow temperature
Buderus
iRT30 Floor heating
13 (48 °C, max. factory-adjusted setting for floor
heating)
Radiator heating
17 (67 °C, min. factory-adjusted setting for radiator
heating)
ON/OFF temperature controller, 24 V
* Basic setting: Have the specific system settings of the Buderus control system and burner-control unit control panel adjusted by
a specialist heating system company.
Table 1 Flow temperature
Radiator heating 15 (58 °C, new building) up to
10 (80 °C, old building)*
Boulter Buderus Ltd. • http://www.boulter-boilers.comSubject to modifications resulting from technical improvements!
7Operating instructions for 600 - 11S /19S / 24S / 24C • Edition 11/2003
Page 8
Operating Instructions
12
10
1
01
11 KW
10
10
1
Controller position DWH-storage temperature [°C] Outlet temperature [°C]
1–60
2 60
34040
4 43 43
54646
6 49 49
75252
8 55 55
95858
10 60 60
Tab. 2 Hot-water temperature for 600 - 24 C
Range of application Controller position Water temperature in external tanks
Minor convenience, small heat losses 1 27 °C
Average convenience, medium heat losses 5 41 °C
Optimum convenience, normal heat losses 10 60 °C
Table 3 Hot-water temperature in external tanks
6.2 Combustion fuels
Natural gas or propane.
6.3 Frost hazard for the heating system
In the event of any risk of the heating system freezing up:
z Open the control panel cover.
z Open cover for 2nd control box (fig. 9, item 1).
z Move switch to position “2” (pump post-purge
period 24 h) (fig. 9, item 5).
z Shut cover for 2nd control box and control panel.
2
11
0 I
KW
01
12
4
3
5
8
1
10
1
10
1
10
1
Fig. 9 2nd control box
Boulter Buderus Ltd. • http://www.boulter-boilers.com
Operating instructions for 600 - 11S /19S / 24S / 24C • Edition 11/2003
Page 9
6.4 Operational and fault codes (table 4)
12
10
1
01
11 KW
10
10
1
Operating conditions and possible faults are shown on the display (fig. 10, item 4). The codes consists of two characters. Press the Service button (fig. 10, item 3) to display the second character.
Operating Instructions
2
4
3
All codes not contained in table 4 should be noted down
5
separately. These are malfunctions that require the presence of a specialist technician.
11
0 I
1
10
1
KW
01
12
10
1
10
1
Fig. 10 Operational and fault codes
Display Display after pressing
Meaning Rectification
the service button
0 A, H, L, P, U, Y Boiler is ready for operation
6* A Burner not ignited Press reset button (fig. 10, item 2).
If the burner fails to ignite after several unblocking operations, consult a specialist company.
-. H Normal heating mode
=. H Normal hot water mode
* Flashing after three start-up attempts.
Table 4 Operational and fault codes
Boulter Buderus Ltd. • http://www.boulter-boilers.comSubject to modifications resulting from technical improvements!
9Operating instructions for 600 - 11S /19S / 24S / 24C • Edition 11/2003
Page 10
Operating Instructions
7 Taking the system out of
service
z Open the control panel cover.
z Push the mains power switch (fig. 11, item 1) to “0”.
z Close the gas service valve by turning it clockwise
(fig. 11, item 2).
z Close the control panel cover.
Frost hazard for the heating system
z Turn the mains switch to “I” and leave the gas service
valve open.
z Adjust room temperature to minimum (or frost-
protection) setting at regulating device or on remote control unit.
INOTE
If you intend to shut down the system fully under frost hazard conditions, note that the system must be drained entirely of water.
11 KW
1
1
10
1
01
12
10
1
10
2
Fig. 11 Mains switch, gas service valve
7.1 Draining the system
z Close the DHW cold and the CH return valve.
z Connect temporary hose (fig. 12).
z Open the CH return stop valve to drain the system.
Stop valve
CH Flow
Fig. 12 Draining the system
Drain
DHW Cold
(combi only)
CH Return
Stop valve
temporary hose
10
Operating instructions for 600 - 11S /19S / 24S / 24C • Edition 11/2003
Boulter Buderus Ltd. • http://www.boulter-boilers.com
Page 11
Notes
Boulter Buderus Ltd. • http://www.boulter-boilers.comSubject to modifications resulting from technical improvements!
11Operating instructions for 600 - 11S /19S / 24S / 24C • Edition 11/2003
Page 12
Heating system specialist:
Boulter Buderus Ltd.
Magnet House
Whitehouse Road
Ipswich
Suffolk, IP1 5JA
http://www.boulter-boilers.com
720.968A - 3939 - 11/2003
Loading...