These installation and servicing instructions apply to:
Buderus wall-mounted condensing gas boilers
600 - 11R / 19R / 24R.
Model: C13, C33, C
Type: GB II
Fuse rating: 1.25 Ampere slow blow
Power rating: 230 VAC, 50 Hz, IPX4D
Important general instructions for use
Only use the boiler in accordance with its designated use and
the installation and servicing instructions. Servicing and repair
must be carried out by CORGI registered installer. Only use
the boiler in combinations and with the accessories and spare
parts indicated in the installation and servicing instructions.
Other combinations, accessories and consumables may only
be used if they are expressly provided for the designated use
and if system performance and safety are not affected in any
way.
The boiler is suitable for connection to fully pumped, open
vented or sealed water systems.
Adequate arrangements for completely draining the system by
provision of draining valves must be provided in the installation
pipework.
Subject to technical modifications.
As a result of our policy of constant development, there may be
small differences between illustrations, functional steps and
technical data.
All Boulter Buderus gas fired boilers now include an installation, commissioning and service record log book. The details
of the log book will be required in the event of any warranty
work being requested.
Please complete the appropriate sections on completion of the
installation and commissioning.
REMEMBER: Please hand the log book back to the user.
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
Installation and maintenance instructions wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/20043
Regulations and directives
It is law that all gas appliances are installed and serviced by a
CORGI registered installer in accordance with the regulations.
Failure to install appliances correctly could lead to prosecution.
It is in your own interest, and that of safety, to ensure the law
is complied with.
The installation must also be in accordance with the latest
I.E.E (BS.7671) Wiring Regulations, local building regulations,
water regulations, the building regulations and the Building
Standards (Scotland) and any relevant requirements of the
local authority.
Detailed recommendations are contained in the following
British Standard Codes of Practice:
BS. 5440:1 Flues (for gas appliances of rated input not
exceeding 70 kW).
BS. 5440:2 Ventilation (for gas appliances of rated input not
exceeding 70 kW).
BS. 5449Forced circulation hot water systems.
BS. 5546Installation of gas hot water supplies for domestic
purposes (2nd. family Gases).
BS. 6798Installation of gas fired hot water boilers of rated
input not exceeding 60 kW.
BS. 6891Low pressure installation pipes.
IGE/UP/1b Tightness testing and purging domestic sized gas
installations.
Health and & Safety Document No. 635.
The Electricity at Work Regulations, 1989.
The manufacturer's notes must not be taken, in any way, as
overriding statutory obligations.
The design and construction of the Buderus wall-mounted
condensing gas boiler 600 - 11R/19R/24R conforms to the
basic specifications listed in the European directive governing
gas-fired appliances 90/396/EEC, and with respect to EN 625,
EN 483 and EN 677.
NOTE
Observe the corresponding technical rules and
the building supervisory and statutory
regulations when installing and operating the
system.
WARNING!
Keep the burner-control unit housing CLOSED
when working on water-bearing components.
NOTE
It is mandatory to clean and service the system
once a year. This includes an inspection of the
entire system to see if it is in full working order.
Defects and faults must be eliminated
immediately.
NOTE
When instructions aren’t followed, warranty
expires.
Timber Framed Buildings
If the boiler is to be fitted in a timber framed building it should
be fitted in accordance with the Institute of Gas Engineering
document IGE/UP/7:1998.
Bathroom Installations
This appliance is rated IPX4D.
The boiler may be installed in any room or internal space,
although particular attention is drawn to the requirements of
the current IEE (BS.7671) Wiring Regulations and, in
Scotland, the electrical provisions of the building regulations
applicable in Scotland, with respect to the installation of the
boiler in a room or internal space containing a bath or shower.
If the appliance is to be installed in a room containing a bath or
shower then, providing water jets are not going to be used for
cleaning purposes (as in communal baths/showers), the
appliance can be installed in Zone 3, as detailed in BS.7671.
Compartment Installations
A compartment used to enclose the boiler should be designed
and constructed especially for this purpose.
An existing cupboard or compartment may be used, provided
that it is modified for the purpose.
In both cases, details of essential features of cupboard/
compartment design, including airing cupboard installation,
are to conform to the following:
BS 6798 (No cupboard ventilation is required - see 'Air Supply'
for details).
It is not necessary to have a purpose-provided air vent in the
room or internal space in which the boiler is installed. Neither
is it necessary to ventilate a cupboard or compartment in which
the boiler is installed, due to the low surface temperatures of
the boiler casing during operation; therefore the requirements
of BS 6798, Clause 12, and BS 5440:2 may be disregarded.
The position selected for installation MUST allow adequate
space for servicing in front of the boiler.
For the minimum clearances required for safety and
subsequent service, see the wall mounting template.
In addition, sufficient space may be required to allow lifting
access to the wall mounting plate.
Wall-mounted condensing gas boilers must only be operated
with the combustion air/flue gas systems especially devised
and authorised for this type of boiler.
Observe the relevant standards, regulations and legislation of
the country of final use.
CAUTION
Use this device for its intended purpose only.
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
4Installation and maintenance instructions wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
DANGER!
Notes relating to the heating system water.
Thoroughly flush the system before it is filled
with water. Use only untreated water or water
treatment product such as Sentinal X100 to fill
and top up the system.
When using water treatment, only products
suitable for use with Boulter Buderus heat
exchangers are permitted (e.g. Sentinel X100).
Your warranty is at risk if an incorrect water
treatment product is used in conjunction with
this appliance. For more information, contact
Boulter Buderus Product Support Department.
It is most important that the correct
concentration of the water treatment product is
maintained in accordance with the
manufacturer's instructions.
If the boiler is used in an existing system any
unsuitable additives MUST be removed by
thorough cleaning. BS.7593:1992 details the
steps necessary to clean a domestic central
heating system.
In hard water areas, treatment to prevent lime
scale may be necessary - however, the use of
artificially softened water is NOT permitted.
Under no circumstances should the boiler be
fired before the system has been thoroughly
flushed.
Do not use water softened in a salt bedding
exchanger.
Do not use anti-freeze or other additives.
The expansion vessel must be of sufficient
size.
When oxygen-permeable pipes are used (e. g.
for floor heating systems) the system must be
separated by means of heat exchangers.
Unsuitable heating water promotes sludge
formation and corrosion. This may cause
malfunctions and damage in the heat
exchanger.
This appliance is not suitable for gravity
central heating nor are they suitable for the
provision of gravity domestic hot water.
The boiler must be vented.
Drain cocks must be located in accessible
positions, which permits the draining of the
entire system. They should be at least ½" BSP
nominal size and be in accordance with
BS. 2879.
The hydraulic resistance of the boilers is
shown in the graph below.
graph 1
350
300
250
200
150
resistance (mbar)
100
50
0
00,10,20,30,40,50,60,70,80,911,11,21,3
flow (m /h)
resistance heat exchanger
3
NOTE:
Notes relating to domestic hot water.
The boiler must not be used for direct hot water
supply.
The hot water storage cylinder must be of the
indirect type.
Single feed, indirect cylinders are not
recommended and must not be used on sealed
systems.
The hotwater cylinder and ancillary pipework,
not forming part of the useful heating surface,
should be lagged to prevent heat loss and any
possible freezing - particularly wher pipes run
throughroof spaces and ventilated underfloor
spaces.
The domestic hot water service must be in
accordance with BS 5546 and BS 6700.
Safe handling of substances
Care should be taken when handling the boiler's insulation,
which can cause irritation to the skin.
No asbestos, mercury or CFCs are included in any part of the
boiler and its manufacture.
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/20045
Open vent system requirements
The system should be vented directly off the boiler flow pipe, as
close to the boiler as possible. The cold feed entry should be
inverted and MUST be positioned between the pump and the vent,
and not more than 150 mm (6") away from the vent connection.
NOTE
Combined feed and vent pipes may also be
fitted.
Feed / expansion
cistern
Wate r
level
(cold)
22 mm
open vent
15 mm
cold
feed
450 (18")
minimum
1000 (40")
minimum
150 (6")
max.
There should be a minimum height, 450 mm (18"), of open vent
above the cistern water level. The vertical distance between the
highest point of the system and the feed/expansion cistern water
level MUST not be less than 1000 mm (40"). The pump must be
fitted on the flow side of the boiler.
A suitable pump is a domestic circulator capable of providing a
maximum 11 °C (20 °F) temperature differential across the boiler
with the whole of the heating circuit open. With the minimum flow
circuit allowed by the controls the differential must not exceed
25 °C (see also the graph on page 5).
The vertical distance between the pump and feed/expansion
cistern MUST comply with the pump manufacturer’s minimum
requirements, to avoid cavitation. Should these conditions not
apply either lower the pump position or raise the cistern above the
minimum requirements specified by Boulter Buderus. The
isolation valves should be fitted as close to the pump as possible.
Schematic pipework and system balancing
The boiler does not normally need a bypass but at least some
radiators on the heating circuit, of load at least 10% of the
minimum boiler output, must be provided with twin lockshield
valves so that this minimum heating load is always available (see
footnote re. thermostatic radiator valves).
Balancing
1. Set the programmer to ON for both CH and HW. Turn the
cylinder thermostat down. Close the manual or thermostatic
valves on all radiators leaving the twin lockshield valves (on
the radiators referred to above) in the open position. Turn up
the room thermostat and adjust these lockshield valves to give
boiler flow and return temperatures not more than 20 °C apart.
These valves should now be left as set.
2. Open all manual or thermostatic radiator valves and adjust the
lockshield valves on remaining radiators to give around 11 °C
temperature drop at each radiator.
3. Turn up the cylinder thermostat and adjust the cylinder
balancing valve so that the cylinder achieves a maximum flow
consistent with adequate flow to the radiators. Check that with
only the domestic hot water loop in circuit a differential
temperature of 20 °C across the boiler is not exceeded.
4. Adjust room and cylinder thermostats and programmer to
NORMAL settings.
System
flow to
pump
Connection
to boilers
fig. 1Open vent system
22 mm
open vent
15 mm
cold
feed
Elbow
then
tee
Flow
Return
BOILER
fig. 2Schematic pipework and system
System
return
Air vent
Alternative
2x2 port
valves
Radiators
Inverted cold
feed entry
3 port
valve
Cylinder
balancing
valve
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
6Installation and maintenance instructions wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
Thermostatic radiator valves
k
Boulter Buderus support the recommendations made in
BS. 5449, and by leading manufacturers of domestic heating
controls, that heating systems utilising the thermostatic
radiator valve control of temperature in individual rooms shall
also be fitted with a room thermostat, controlling the
temperature in a space served by radiators not fitted with such
a valve.
Such an arrangement will provide for potentially more efficient
control of the environment and will also avoid the continuous
running of the circulation pump during programmed heating
ON periods - thus saving electrical energy.
It is, therefore, strongly recommended that, when thermostatic
radiator valves are used, space heating temperature control
over a living/dining area or a hallway having a heating
requirement of at least 10% of the minimum boiler heat output,
is achieved using a room thermostat whilst other rooms are
individually controlled by thermostatic radiator valves.
Sealed system requirements
NOTE
The method of filling, refilling, topping up or
flushing sealed hot water circuit from the mains
via a temporary hose connection is only
allowed if acceptable to the local water
authority.
1. General
The installation must comply with the requirements of
BS. 6798 and BS. 5449.
The installation should be designed to work with flow
temperatures of up to 80 °C.
All components of the system, including the heat exchanger of
the indirect cylinder, must be suitable for a working pressure of
3 bar (45 lb/in
2
) and temperature of 110 °C. Care should be
taken in making all connections so that the risk of leakage is
minimised.\
2. Safety valve
A spring loaded safety valve complying with the relevant
requirements of BS. 6759 must be fitted in the flow pipe as
close to the boiler as possible and with no intervening valve or
restriction. The valve should have the following features:
– A non-adjustable preset lift pressure not exceeding 3 bar
(45 lb/in
2
);
– A manual testing device;
– Provision for connection of a discharge pipe. The valve or
discharge pipe should be positioned so that the discharge
of water or steam cannot create a hazard to the occupants
of the premises or cause damage to electrical components
and wiring.
Make-up vessel
(max. capacity 3 litres)
Hose union
bib tap
Water
supply
Hose connector
Nonreturn
valve
Automatic
air vent
Hosepipe
(disconnect
after refilling)
BS. 1010:2
stop tap
HEATING
CIRCUIT
Test cock
Air vent
Pump
Double check valve
Pressure gauge
Expansion
vessel
Safety valve
BOILER
Drain coc
fig. 3Sealed system
3. Pressure gauge
A pressure gauge covering at least the range of 0-4 bar
(0-60 lb/in
2
) must be fitted to the system. The gauge should be
easily seen from the filling point and should preferably be
connected at the same point as the expansion vessel.
4. Expansion vessel
A diaphragm type expansion vessel must be connected to a
point close to the inlet side of the pump, the connecting pipe
being not less than 15 mm (½" nominal) size and not
incorporating valves of any sort.
The vessel capacity must be adequate to accept the
expansion of the system water when heated to 110 °C
(230° F).
The charge pressure must not be less than the static water
head above the vessel. The pressure attained in the system
when heated to 110 °C (230° F) should be at least 0.35 bar
2
(5 lb/in
) less than the lift pressure of the safety valve.
For guidance on vessel sizing refer to table 1.
For further details refer to BS. 5449 and BS. 7074:1 and the
British Gas Corporation publication: "Material and Installation
Specifications for Domestic Central Heating and Hot Water".
5. Cylinder
The cylinder must be either of the indirect coil type or a direct
cylinder fitted with an immersion calorifier which is suitable for
operating on a gauge of 0.35 bar (5 lb/in
2
) in excess of the
safety valve setting. Single feed indirect cylinders are not
suitable for sealed systems.
6. Make-up water
provision must be made for replacing water loss from the
system, either:
– from a manually filled make-up vessel with a readily visible
water level. The vessel should be mounted at least 150 mm
(6") above the highest point of the system, and be
connected through a non-return valve to the system, filled
at least 300 mm (12") below the make-up vessel on the
return side of the domestic hot water cylinder or radiators.
or
– where access to a make-up vessel would be difficult by
pre-pressurisation of the system. Refer to "Filling", below.
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/20047
7. Mains Connection
There must be no direct connection to the mains water supply
or to the water storage tank supplying domestic water, even
through a non-return valve, without the approval of the local
water authority.
8. Filling
The system may be filled by one of the following methods:
a. Through a cistern, used for no other purpose, via a ball
valve permanently connected directly to a service pipe
and/or a cold water distributing pipe. The static head
available from the cistern should be adequate to provide
the desired initial system design pressure. The cold feed
pipe from the cistern should include a non-return valve and
a stop valve with an automatic air vent connected between
them, the stop valve being located between the system and
the automatic air vent. The stop valve may remain open
during normal operation of the system if automatic water
make-up is required.
b. Through a self-contained unit comprising a cistern,
pressure booster pump (if required) and, if necessary, an
automatic pressure reducing valve and flow restrictor. The
cistern should be supplied through a temporary connection
from a service pipe or cold water distributing pipe.
This unit may remain permanently connected to the
heating system to provide limited automatic water makeup. Where the temporary connection is supplied from a
service pipe or distributing pipe which also supplies other
draw-off points at a lower level then a double check valve
shall be installed upstream of the draw-off point.
c. Through a temporary hose connection from a draw-off tap
supplied from a servicing pipe under mains pressure.
Where the mains pressure is excessive a pressure
reducing valve shall be used to facilitate filling.
The following fittings shall form a permanent part of the system
and shall be fitted in the order stated:
– A stop valve complying with the requirements of
BS. 1010, Part 2 (the hose from the draw-off tap shall
be connected to this fitting);
– A test cock;
– A double check valve of an approved type.
z Thoroughly flush out the whole of the system with cold
water, without the pump in position.
z With the pump filled, fill and vent the system until the
pressure gauge registers 1.5 bar (21.5 lb/in
2
). Examine
for leaks.
z Check the operation of the safety valve by manually
raising the water pressure until the valve lifts. This
should occur within ± 0.3 bar (4.3 lb/in
2
) of the preset lift
pressure.
z Release water from the system until the initial system
design pressure is reached.
z Light the boiler and heat the system to the maximum
working temperature. Examine for leaks.
z Turn off the boiler and drain the system while still hot.
z Refill and vent the system.
z Adjust the initial pressure to the required valve.
Sizing procedure for expansion vessel
The volume of the expansion vessel (litres) fitted to a sealed
system shall not be less than that given by the table below,
multiplied by a factor of 0.8 (for flow temperatures of less than
80 °C).
Safety valve setting3.0 bar2.5 bar2.0 bar
Vessel charge and initial system
pressure
Total water content of system (litres)Expansion vessel volume litres
252.12.73.92.33.35.92.85.0
504.25.47.84.76.711.85.610.0
756.38.211.77.010.017.78.415.0
1008.310.915.69.413.423.711.320.0
12510.413.619.511.716.729.614.125.0
15012.516.323.414.120.135.516.930.0
17514.619.127.316.423.441.419.735.0
20016.721.831.218.826.847.422.640.0
22518.724.535.121.130.153.325.445.0
25020.827.239.023.533.559.228.250.0
27522.930.042.925.836.865.131.055.0
30025.032.746.828.240.271.133.960.0
Multiplying factors for other
system volumes
Table 1Expansion vessel volumes
0.51.01.50.51.01.50.51.0
barbarbarbarbarbarbarbar
0.08330.1090.1560.0940.1340.2370.1130.20
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
8Installation and maintenance instructions wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
Installation1
1Installation
1.1Dimensions and connections
CH FLOW
CH RETURN
460 mm (18")
290 mm (11,4")
105 mm (4")
230 mm (9")
50 (2")
70 (2.8")
130 (5")
145 (5,7")
619 mm (24")
604 mm (23,7")
Ø100 (4")
3
Ø60 (2 ")
328 mm (13")
376 mm (15")
25 mm (1")
8
20 (0.8")
700 mm (27½")
119 mm (4,7")
82 mm (3")
CWDO
GAS
CH Flow=Ø22 mm Compression (0.87")
CH return=Ø22 mm Compression (0.87")
GAS=Gas connection G½" INSIDE
CWDO=Condensate water drainage outlet Ø21.5 mm (0.8") OUTSIDE
NOTE
See the wall-mounting template for the necessary clearances.
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/20049
Installation1
1.2Boiler assembly - exploded view
Single unit (11R / 19R / 24R)
350
10
380
310
340
420
440
360
320
290
330
250
370
280
260
270
120
520
510
400
390
410
430
450
460
470
480
480
20
Legend
10. Casing
230
110
130
230
250
240
300
200
70
60
100
500
80
170
530
180
40
560
540
160
90
190
210
220
490
140
150
240
290
50
30
20. Door complete
30. Ventilation cover
40. Bracket
50. Concentric adaptor
60. Clip adaptor
70. Lipring 100mm
80. Fan
90. Sealing Fan / Venturi
100. Lipring 60mm
110. Flue gas pipe
120. Condensate collector
130. Seal flue gas pipe
140. Flue gas sensor
150. Condensate trap
160. Suction pipe
170. Lipring 50mm
180. Gas valve
190. Rectifier
200. Venturi
210. Gas pipe
220. Gas service valve
550
230. Pipe return/flow top
240. Pipe connection
250. Clip
260. Return pipe
270. Drain cock
280. Connection return
290. Sensor
300. Flow pipe
310. Connection supply
320. Hairpin heat exchanger
330. Automatic air vent
340. O-ring
350. Lipring
360. Safety sensor
370. Sealing ring
380. Backpart heat
exchanger
390. Seal heat exchanger
400. Insulation backpart heat
exchanger
410. Burner 11 kW
Burner 19 kW
Burner 24 kW
420. Sealing burner
430. Heat exchanger helix
440. Combustion divider
450. Insulation front heat exchanger
460. Frontpart heat exchanger
470. Sight glass
480. Fasteners
490. UBA
500. Main switch
510. Hot surface ignitor
520. Ionisation electrode
530. Cable fan
540. Cable harness
550. Frame
560. RTH converter 230V
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
10Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
Installation1
1.3Flue Installation
1.3.1Siting the flue terminal
The flue must be installed in accordance with the
recommendations of BS. 5440-1:2000.
Pluming will occur at the terminal so terminal positions where
this could cause a nuisance should be avoided.
The air supply and the flue gas exhaust must meet the
applicable general regulations. Please consult the instructions
provided with the flue terminal kits prior to installation.
The boiler MUST be installed so that the terminal is exposed
to external air.
It is important that the position of the terminal allows the free
passage of air at all times.
Minimum acceptable spacing from the terminal to obstructions
and ventilation openings are specified in table 1.
If the terminal is fitted within 1000 mm of a plastic or painted
gutter or within 500 mm of painted eaves, an aluminium shield
of at least 1000 mm long should be fitted to the underside of
the gutter or painted surface.
If the lowest part of the terminal is less than 2 metres above the
level of the ground, balcony, flat roof or place to which any
person has access, the terminal must be protected by a guard.
Protective guards are available from Quinnell Barrett and
Quinnell, Old Kent Road, London.
Ensure that the guard is fitted centrally.
The flue assembly shall be so placed or shielded as to prevent
ignition or damage to any part of the building.
The air inlet/products outlet duct and the terminal of the boiler
MUST NOT be closer than 25 mm (1'') to combustible material.
Detailed recommendations on the protection of combustible
material are given in BS. 5440 - 1:2000.
NOTE
It is absolutely essential to ensure, in practice,
that products of combustion discharging from
the terminal cannot re-enter the building or any
other adjacent building through ventilators,
windows, doors, other sources of natural air
infiltration, or forced ventilation/airconditioning.
If this could occur the appliance MUST be turned off (with the
owners permission), and labelled as unsafe until corrective
action can be taken.
A
B,C
M
A
F
M
G
under carport
H, I
B,C
K
F
F
G
D
K
G
Fig. 1Flue terminal position
Terminal Position
A. Directly below or alongside an opening
window, air vent or other ventilation opening
B. Below guttering, drain pipes or soil pipes
C. Below eaves
D. Below balconies or a car port roof
E. From vertical drain pipes or soil pipes
F. From internal or external corners
G. Above adjacent ground, roof or balcony level
H. From a surface facing the terminal
I. From a terminal facing a terminal
J. From an opening in a car port (e.g. door or
window) into dwelling
K. Vertically from a terminal on the same wall
L. Horizontally from a terminal on the wall
M. Adjacent to opening
C
K
L
L
K
G
FJ
Minimum
Spacing
300 mm (12")
75 mm (3")
200 mm (8")
200 mm (8")
150 mm (6")
300 mm (12")
300 mm (12")
600 mm (24")
1200 mm (48")
1200 mm (48")
1500 mm (60")
300 mm (12")
300 mm (12")
Table 1Balanced flue terminal position
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/200411
Installation1
1.3.2Air supply and flue gas exhaust in a closed
installation
A ventilation cover is integrated into the 600 Series condensing
gas boilers. This cover houses a number of components, such
as the burner and the heat exchanger. Since this ventilation
cover is part of the air supply system, it is vital that it is always
installed correctly.
To ensure optimal operation, the 600 Series appliances must
be connected to a Buderus wall-mounted or roof-mounted flue
terminal. These terminals have been developed specifically for
the 600 Series condensing gas boilers and have been
comprehensively tested. The Buderus wall and roof-mounted
flue terminal kits ensure trouble-free operation.
The following items for the flue (see fig. 2) are included in the
delivery of the boiler:
– pos. 1: 1 Concentric bend 60/100;
– pos. 2: 1 Horizontal flue terminal 60/100;
– pos. 3: 1 Flue finishing kit.
1.3.3Maximum Flue length
The maximum pipe length of the air supply and flue gas
exhaust pipes for the 600 Series condensing gas boilers (see
table 2) is determined by the total pressure loss of all
components in the flue gas exhaust / air supply system.
1
Fig. 2Horizontal flue pack
2
3
L
550 mm
50 mm
Take the flue conduit clearances into account when planning
the layout of the place of installation (see subsection 1.3.1:
"Siting the flue terminal" on page 11).
Maximum wall thickness without extensions is 550 mm.
Maintain a minimum side wall clearance of 50 mm (see fig. 3).
1.3.4Additional flue parts
Additional flue parts (see table 3) can be ordered from your
supplier.
Fig. 3Side flue and rear flue installation
Boiler
600 SeriesL = 7.5 m1.2 m
Table 2Pipe length
Flue partsOrder No.
Concentric pipe, 500 mm long, adjustableNE 83703
Concentric pipe, 1000 mm long, not adjustableNE 83704
Concentric bend 90°NE 83705
Concentric bend 45°NE 83706
Table 3Additional flue parts
Maximum
pipe length
For every 90° bend the
maximum pipe length has
to be reduced by
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
12Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
Installation1
1.4Items supplied with unit
z Check the contents against the packing list to ensure that
nothing is missing.
Key to fig. 4:
1: Wall-mounted condensing gas boiler
2: Wall bracket
3: Technical documents
4: CH Flow connection pipe
5: CH Return connection pipe
6: Gas service valve
7: Plastic bag containing the following accessories:
2 x wall fixing-screws
2 x wall plugs
2 x washers
Seals (2 x ¾“)
Square wrench
Initial start-up sticker
Second identification plate
Requirements to be met by the place of installation
NOTE
Observe all statutory building regulations
applying to the place of installation.
1
Fig. 4Items supplied with unit
2
5
4
3
6
7
1
2
DANGER!
Inflammable materials or liquids must not be
stored or used near wall-mounted condensing
gas boilers. The site of installation must be
frost-protected.
1.5Transport
The boiler is transported in a horizontal position.
z Open the box and remove the four foam supports (fig. 5,
item 1). The casing is not attached to the boiler.
z Take out the casing (fig. 5, item 2) and put aside during
installation.
CAUTION!
Do not carry the boiler by the casing at any
time.
z Take out the wall bracket (fig. 4, item 2) and attach to the
wall using the wall mounting template.
z Take out the condensing gas boiler (fig. 5, item 3) and
hang onto the wall bracket (fig. 6).
z Dispose of packaging.
3
Fig. 5Unpacking the box
Fig. 6Installation
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/200413
Installation1
1.6Pipe connections
CAUTION!
Ensure that all pipework is routed so as to
minimise any strain on the boiler fittings.
1.6.1Gas Supply
The gas installation must be installed in accordance with
BS.6891.
CAUTION!
Pipework from the meter to the boiler MUST be
of adequate size.
The complete installation MUST be tested for gas tightness
and purged as described in IGE/UP/1b.
1.6.2Gas connection
12
z A gas service valve is supplied with the unit. Take it out of
the box and connect it to the boiler see fig. 7, item 3 with
P.T.F.E.-tape. Connect to gas supply according to the
relevant standards.
1.6.3Heating system connections
The central heating system should be in accordance with
BS.6798 and, in addition, for smallbore and microbore
systems, BS.5449.
z Take the CH flow connection pipe and the CH return
connection pipe out of the box and connect to the
condensing gas boiler seefig. 7, item 1 and 2.
z Connect the central heating system to these pipe
connections according to the relevant standards.
1.6.4Condensate drain
A condensate drain is integrated in the boiler. The drain outlet
is a standard (21.5 mm) overflow pipe. This drain needs to be
connected to a drainage point. All pipework and fittings in the
condensate drainage system MUST be made of plastic - no
other materials may be used.
The routing of the drain must be made to allow a minimum fall
of 1 in 20 away from the boiler, throughtout its length.
4
Fig. 7Pipe connections
Key to fig. 7:
1: CH flow
2: CH return
3: Gas
4: Condensate water drainage outlet (CWDO)
3
Excessive external pipe runs should be avoided in order to
prevent possible freezing.
Any external pipework should be a minimum of 32 mm internal
diameter.
WARNING!
Any external run must be insulated.
Ensure that the condensate trap is filled with water.
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
14Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
Installation1
1.7Flue installation
The only flue systems that may be used are those supplied by
Boulter Buderus. The flue system must be installed in
accordance with the requirements of BS.5440:1. 2000.
Standard 100 mm flue systems
The standard concentric flue system provides for a max.
horizontal straight length of upto 7.5 m (see subsection 1.3.3).
Full instructions for fitting this flue are in subsection 1.7.2:
"Installation of the horizontal flue" on page 15.
IMPORTANT
Any horizontal flue system fitted to a
condensing boiler must be inclined towards the
appliance at an angle of 3% (30 mm per metre
length) to prevent condensate dripping from
the flue terminal.
This means that the clearance above the
appliance must be increased to match the duct
length. See figure on page 9.
1.7.1Connecting the vertical flue gas duct
z Fit the vertical flue gas duct (fig. 8) onto the appliance flue
connector.
z For remaining installation of the vertical flue assembly,
refer to the relevant installation instructions.
1.7.2Installation of the horizontal flue
The standard 100 mm diameter horizontal flue system is
siutable for lengths upto 560 mm (see fig. 10).
For longer flue runs upto 7.5 m, extension air/flue ducts are
available (see page 12, table 3).
NOTE
Use the wall-mounting template to help you
mark the position of the side flue opening
Flue gas
testing point
Fig. 8Vertical flue connection
Flue gas
testing point
Fig. 9Elbow with flue gas testing point
Flue
Turret
Maximum 560 mm
No Clamp
Terminal
assembly
Outer
Wall
Fig. 10 Standard flue
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/200415
Installation1
1.7.3Flue duct preparation and assembly
z Measure the flue length L. Refer to figures 11 and 12.
NOTE
The flue must be inclined to the boiler.
z Mark of the lengths shown onto the ducts and cut the
length. The cuts must be square and free from burrs.
Terminal assembly outer (air) duct - L-70 mm, inner (flue)
duct - L-50 mm. The measurement is made from the ridge
at the terminal indicating the outer face of the wall.
Refer to figure 13.
Extension air duct - L-70 mm, flue duct - L-50 mm.
The measurement is from the formed end.
z Assemble flue system completely. Push the ducts fully
together. The slope of the terminal outlet must be face
downwards.
The assembly will be made easier if a solvent free grease
is lightly applied to the male end of the ducts.
NOTE
An inner wall sealing plate is provided which
should be fitted to the ducts before assembly.
L
105
Fig. 11 Flue length - rear
L
z Push the assembly through the wall and slide the turret
onto the flue connector. Refer to figure 9.
z Ensure that the turret is fully entered into the socket on the
boiler. From the outside fix the flue finishing kit to the
terminal and, after ensuring the duct is properly inclined
towards the boiler, fix the finishing kit to the wall.
If the terminal is within 2 m of the ground where there is
access then an approved terminal guard must be fitted.
The guard must give a clearance of at least 50 mm around
the terminal and be fixed with corrosion resistant screws.
Fig. 12 Flue length - side
Outer
Wall
Face
Fig. 13 Flue terminal position
Flue Terminal
Raised Ring
locating the
terminal relative
to the outside
wall face
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
16Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
Installation1
1.8Electrical connections
1.8.1Mains connection
CAUTION
This appliance MUST be earthed.
A mains supply of 230 V - 50Hz is required.
External controls are suitable for volt free or 230 V installation.
Wiring to the boiler MUST be in accordance with the current
I.E.E. (BS.7671) Wiring Regulations and any local regulations.
Wiring should be a 3 core PVC insulated cable, not less than
0.75 mm
Connection must be made in a way that allows complete
isolation of the electrical supply such as a double pole switch
having 3 mm (1/8'') contact seperation in both poles, or a plug
and socket, serving only the boiler and system controls. This
boiler is equipped with a double pole switch see fig. 14, item 1.
The means of isolation must be accessible to the user after
installation.
The electrical connection to the mains supply should be readily
accessible and adjacent to the boiler.
If the supply cord is damaged, it must be replaced by a
registered Corgi installer to avoid a hazard.
2
(24 x 0.2 mm), and to BS.6500 Table 16.
1
Fig. 14 UBA
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/200417
Installation1
1.8.2Wiring Diagram
4
123
18-pin connection strip
FS
FR
PA
Burner-control unit (UBA)
Flame-monitoring electrode
ignitor
Hot surface
STB
Fuse, main switch, emergency OFF switches and
safety measures to comply with local regulations and standards
The wires inthis mains lead are coloured in accordance with the following code:
GREEN AND YELLOW - EARTH ; BLUE - NEUTRAL ; BROWN - LIVE
As the colours of the wires in the mains lead of of the appliance may not correspond with the coloured markings identifying the terminals in your plug proceed as follows:
The wire coloured green and yellow must be connected to the terminal on the plug marked with the letter E or by the earth symbol or coloured green or green-and-yellow. The wire coloured brown must be connected to the terminal marked with
the letter L or coloured red. The wire coloured blue must be connected to the terminal marked with the letter N or coloured black.
FOR LOCATION OF INDIVIDUAL COMPONENTS, SEE TROUBLESHOOTING GUIDE IN THE SERVICE SECTION OF THIS MANUAL.".
WARNING
THIS APPLIANCE MUST BE EARTHED
Ensure that your appliance is connected correctly - if you are in any doubt consult a qualified electrician.
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
18Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
Installation1
1.9Timing and temperature control
The wall-mounted condensing gas boiler can be fitted with the
following control devices:
– ON/OFF temperature controller, volt free;
– A room-temperature control device at 230V connected to
the RTH converter see fig. 15, item 2.
1.9.1230V Room-temperature control device
connection
CAUTION
DO NOT activate the condensing gas boiler at
this stage.
z Lead the 230V control device wire through the cable lead
(see fig. 15, item 1).
z Fix the 230V wire to position 1 and 2 of the 230V
connection (see fig. 15, item 2).
z Secure the 230V wire with the bracket and the two screws
onto the RTH converter.
1.9.2Volt free room-temperature control device
connection
z Remove the cover of the connextion box (fig. 16, item 1).
z Lead the control device wire through the cable lead
(see fig. 16, item 2).
z Fix the wire to position 1 and 2 of the volt free connection
(see fig. 16, item 3).
z Secure the wire with the bracket and the two screws onto
the RTH converter (see fig. 16, item 4).
Fig. 15 Connecting the control device
2
1
1
2
3
Fig. 16 RTH converter - Volt free connection
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/200419
Initial start-up2
12
10
01
11
KW
10
1
1
2Initial start-up
2.1Preparing the boiler for operation
CAUTION
DO NOT operate the condensing gas boiler if
large amounts of dust are present, e.g. due to
building work in and around the place of
installation.
2.1.1Checking for leaks
z Disconnect the system from the power supply.
z Check all sections of gas pipework and connections for
signs of leaks before starting up system for the first time.
If a leak is detected during tightness testing, use an
approved leak detector to check all connections for
possible escapes. The product must be certified as a gas
leak-testing agent. DO NOT allow the product to come into
contact with electrical wiring.
Fig. 17 Unscrew ventilation cover
2.1.2Purging air from the gas supply system
z Loosen the 4 crosshead screws on the ventilation cover
(fig. 17).
z Remove the ventilation cover.
z Close the gas service valve.
z Unscrew the sealing closure of the gas connection-
pressure testing nipple by two turns (fig. 18).
z Purge system and appliance as per relevent procedures,
IGE/UP/1b. Ensuring all safety requirments are met.
z Open gas service valve.
z Close the gas service valve once more.
z Shut the sealing closure of the test nipple once more.
z Open cover for 2nd operating level (fig. 19, item 1).
z Make sure that system pump is running.
z Start boiler up and move chimney sweep switch (fig. 19,
item 3) to position “1”.
The display shows (fig. 19, item 2) “
-.” or “ =.” to indicate that
the gas supply system is purged of air. Return chimney sweep
switch to position “0”.
Fig. 18 Purging air from the gas supply system
2
3
1
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
20Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
Fig. 19 Display and chimney-sweep switch
Initial start-up2
2.1.3Check combustion air/flue gas connection
Check to ensure that the correct combustion air/flue gas
system has been fitted.
Check that the instructions included in the appropriate flue gas
system installation manual have been followed.
2.1.4Checking the type of gas and supply
CAUTION
The burner must only be put into operation with
the correct nozzles (table 5).
Type of gasFactory settings of gas burners
When delivered ready for operation
and set to Wobbe index 14.1 kWh/m
(referred to 15 °C, 1,013 mbar),
Natural gas H
applicable for Wobbe index range
11.3 to 15.2 kWh/m
3
.
Inscription on gas-type indicating
label:
Category setting: G 20 - 2E_20 mbar
After adaptation by a CORGI
registered installer, the unit can be
Propane P
run on propane.
Inscription on gas-type indicating
label: 3P G 31_30-50 mbar
Table 4Gas-supply types
Type of gas
supply
Natural gas H
(G20)
Gas nozzles ∅ [mm]
11R19R/24R
Venturi
tubes
5.556.5Standard
3
NOTE
Observe stickers attached to Venturi tubes.
Propane P3.404.15Standard
Table 5Gas-nozzle diameter
Controller settingFlow temperature [°C]
140
244
348
453
558
662
767
871
976
1080
Table 6Flow temperature
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/200421
Initial start-up2
12
10
01
11
KW
10
1
1
2.1.5Adjusting the flow temperature
z Open the cover to the 2nd operating level (fig. 20, item 1).
z Adjust the knob (fig. 20, item 2) to the desired flow
temperature (table 6) for your particular installation.
NOTE
Factory setting of the controller is "10"
(around 83 °C).
NOTE
If the flow temperature is set too low, there is
the risc that an external hot water cylinder
cannot achieve a comfortable enough
temperature.
2
1
Fig. 20 Control box
Key to Fig. 20:
1: Cover for second operating level
2: Flow temperature knob
3: Heat-capacity jumper
4: Heating capacity knob
5: only used when boiler is in service mode
6: only used when boiler is in service mode
3
56
4
2.1.6Setting the heating capacity
Set the heating capacity (table 7), according to the amount of
heat required, at the controller (fig. 20, item 4).
NOTE
The controller is factory-adjusted to position “6”
Controller
setting
Heating capacity [kW] (±5 %)
11 R19 R 24 R
14.99.79.7
25.610.711.3
36.311.812.9
46.912.814.5
57.613.816.0
68.314.917.6
79.015.919.2
89.616.920.8
910.318.022.4
1011.019.024.0
Table 7Heating capacity
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
22Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
Initial start-up2
12
10
01
11
KW
10
1
1
2.1.7Measure gas-supply pressure (flow pressure)
z Open at least one radiator thermostat valve.
CAUTION
The condensing gas boiler must not be
activated at this stage.
z Make sure that the system pump is running.
z Turn the chimney-sweep switch (fig. 21, item 4) to
position “1”.
z Loosen the screw plug on the gas test nipple (fig. 22) by
two turns.
z Attach the pressure-gauge connection hose to the gas test
nipple (fig. 23).
z Slowly open the gas service valve.
z Turn the power switch (fig. 21, item 2) to position “I”.
The burner should ignite after about 30 seconds.
z Measure the gas connection pressure and note it down on
the report form.
The gas-connection pressure must be
for natural gas H min. 17 mbar, max. 25 mbar, nominal
connection pressure 20 mbar.
for propane P min. 30 mbar, max. 50 mbar, nominal
connection pressure 37 mbar.
z Detach the gauge-connection tube once more and close
the test nipple at the screw plug.
.
NOTE
If the required connection pressure is not
available or too high, contact your gas supplier
or TRANSCO.
Ensure all disturbed joints and connections are checked for
gas tightness on completion of tasks.
3
4
2
1
Fig. 21 Mains switch, service button and chimney-sweep
switch
Fig. 22 Measure the gas connection pressure
2.1.8Check the gas/air ratio and adjust as required
z Turn mains power switch (fig. 21, item 2) and chimney-
sweep switch (fig. 21, item 4) to “0”.
z Unscrew the sealing closure of the burner-pressure testing
nipple by one turn (fig. 22).
z Connect the positive port of the pressure gauge with a
hose to the burner pressure measuring nipple (fig. 23).
z Make sure that the system pump is running.
z Turn mains power switch to “I” and chimney-sweep switch
to “1”.
z If the burner has fired after approx. 30 seconds, keep the
service button (fig. 21, item 3) pressed until “Y” appears on
the display.
z Turn the hot-water temperature controller (fig. 21, item 1)
Fig. 23 Check the gas/air ratio
to “1”.
z Read the differential pressure.
The differential pressure (p
(±5 Pa = 0,05 bar) (display on measuring gauge: -10 Pa to
GAS–pAIR
) should total -5 Pa
0Pa).
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/200423
Initial start-up2
z If the gas/air ratio does not conform to specifications,
readjust at the setscrew (fig. 23, item 1).
z Turn mains power switch and chimney-sweep switch to “0”.
z Remove the measuring equipment and retighten the screw
in the burner-pressure measuring nipple.
z Readjust the hot-water temperature controller to its original
setting.
z Turn the mains power switch to “I”.
2.1.9Record readings
z Unscrew the corresponding sealing closure (fig. 24) on the
connection adapter for the combustion-air/flue-gas system
and replace it once the measuring operation in question
has been carried out.
Carbon monoxide content
CAUTION
The carbon monoxide values under vacuum
must be smaller than 400 ppm or 0.04 Vol%.
Values around or exceeding 400 ppm indicate
a faulty burner adjustment, a dirty gas burner
or heat exchanger, or a defective burner.
Ensure that the cause of the fault is remedied
immediately.
2.1.10 Function testing
NOTE
During initial start-up and annual servicing,
make sure that all control, regulating and
safety devices are in full working order and, if
applicable, check for correct adjustment.
Measuring the ionisation current (fig. 25)
z Disconnect the system from the power supply.
z Loosen the plug-and-socket connector of the ionisation
electrode and connect the multimeter in series.
On the measuring device, select the µ-direct current range.
The measuring device must have a resolution of at
least 1 µA.
z Make sure that the system pump is running.
z Reconnect the system to the power supply and turn the
chimney-sweep switch to “1”.
z Measuring the ionisation current. The ionisation current
being checked must measure >2 µA direct current.
z Enter the reading on the report form.
z Disconnect the system from the power supply.
z Remove multimeter and restore the plug-and-socket
connection to its original state.
z Turn the chimney sweep switch to position “0”.
z Reconnect the system to the power supply.
When the display shows “7” and the service button is
pressed, the display turns to “c”. Press the Reset button.
The display shows “r”.
Fig. 24 Measuring points on exhaust conduit
Key to Fig. 24:
1: Exhaust-fume temperature, CO
2: Combustion-air temperature
, CO, NO
2
x
Fig. 25 Measuring the ionisation current
12
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
24Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
Initial start-up2
z Place the casing (see fig. 26, item 1).
z Tighten the fixing screw (see fig. 26, item 2).
2.1.11 Handing over
After completing the installation and commissioning of the
system the installer should hand over to the householder by
the following actions:
z Hand the User Manual to the householder and explain
his/her responsibilities under the relevant national
regulations.
z Explain and demonstrate the lighting and shutting down
procedures.
z The operation of the boiler and the use and adjustment of
all system controls should be fully explained to the
householder, to ensure the greatest possible fuel economy
consistent with the household requirements of heating.
Advise the user of the precautions necessary to prevent
damage to the system and to the building in the event of the
system remaining inoperative during frosty conditions.
z Explain the function and the use of the boiler heating
controls.
z Explain the function of the boiler fault mode. Emphasise
that if a fault is indicated, the boiler should be turned off and
a registered local heating installer consulted.
z Explain and demonstrate the function of time and
temperature controls, radiator valves etc., for the economic
use of the system.
Fig. 26 Place casing
1
2
Loss of system water pressure
z Explain that when there is a significant loss of pressure the
user should contact a Corgi registered installer.
WARNING
Do not fire the boiler if the pressure has
reduced to zero from the original setting.
z After installation, commissioning and customer handover
instructions please complete the BENCHMARK appliance
log book and leave this with the customer.
z IMPORTANT
A comprehensive service should be carried out annually.
Stress the importance of regular servicing by a Corgi
registered installer.
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/200425
Inspection3
3Inspection
3.1Preparing the heating boiler for
inspection
z Disconnect the system.
DANGER OF FATAL INJURY
due to electric shock when system is
opened.
z Before opening the system:
disconnect the heating unit at the
emergency OFF switch or the
corresponding circuit breaker of the house
power supply.
z Ensure that the heating system cannot be
reconnected by accident.
z Remove the burner housing or cover from the heating
boiler.
NOTE
If the gas supply pipes are to be disconnected
from the burner, the housing MUST ONLY be
removed by a qualified service technician and
checked for tightness on reassembly.
For further information, please refer to subsection 8.2
"Inspection and maintenance reports" on page 54 and fill out
the Benchmark.
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
26Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
Maintenance4
4Maintenance
For further information, please refer to subsection 8.2
"Inspection and maintenance reports" on page 54 and fill out
the Benchmark.
4.1Clean the heat exchanger, burner and
condensate trap
NOTE
The cleaning of the burner and heat exchanger
described here should be carried out whenever
there are signs of heavy soiling on the wallmounted condensing gas boiler. It is sufficient,
during annual servicing, to clean the burner
and heat exchanger with the help of an
appropriate cleaning product and a soft brush
and compressed-air hose (see following
section).
The heat exchanger can be dismantled
completely for thorough cleaning if required
(see “Cleaning the heat exchanger after
dismantling” on page 28).
Fig. 27 Loosen the union nut and remove the cable
4.1.1Cleaning the heat exchanger without dismantling
z Disconnect the system from the power supply.
z Close the gas service valve.
z Loosen the fixing screws, remove casing and ventilation
cover.
z Release plug-in connection of fan power lead (fig. 27,
item 1), burner-control unit fan control lead (fig. 27, item 2)
and gas-burner assembly (fig. 27, item 3).
z Loosen union nut on gas valve assembly (fig. 27, item 4).
z Push safety plate out of way.
z Turn air suction tube and pull off from below.
z Swivel the air combination unit forward (fig. 28, item 1).
z Pull the air combination unit up and out of bayonet
connector (fig. 28, item 2) and remove via front of unit.
z Remove burner gasket (fig. 29, item 1).
z Remove rubber seal in heat exchanger by pushing
upwards from inside (fig. 29, item 2).
2
Fig. 28 Remove the air combination unit
1
Fig. 29 Remove burner gasket and rubber seal
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/200427
Maintenance4
z Remove heat exchanger by pulling upwards through the
opening (fig. 30).
NOTE
Maintain the specified clearance of approx.
25 cm between the ceiling and the ventilation
cover.
z Remove the front of the heat exchanger. This is done by
releasing the four snap catches at the sides.
z Remove the hot surface ignitor (fig. 31, item 1) and
ionisation electrode (fig. 31, item 2).
In the case of the hot surface ignitor: loosen the fixing
screw of the hot surface ignitor, detach both earth (ground)
leads and remove the retaining plate of the hot surface
ignitor by pulling it upwards, withdraw the hot surface
ignitor by pulling it upwards.
In the case of the ionisation electrode: Swivel the
retaining plate to one side and carefully remove the
ionisation electrode by pulling it upwards.
z Clean the burner and both parts of the heat exchanger with
compressed-air or brush.
z Refit the heat exchanger by following the above procedure
in reverse order.
CAUTION
The gasket between the two halves of the
casing shell should normally be replaced.
Fit the new gasket by pressing in from the top
on both sides, and without stretching.
DO NOT attempt to cut the gasket to size.
Fig. 30 Remove burner
1
2
CAUTION
The burner gasket must match the shape of
the groove in the housing.
CAUTION
Check the heat-exchanger for leaks BEFORE
reassembling the casing shells.
4.1.2Cleaning the heat exchanger after dismantling
z Disconnect the system from the power supply.
z Close the gas service valve.
z Loosen the retaining screw and remove the casing.
z Close the heating shutoff valves and drain the system.
CAUTION
Cut hot water on supply side by closing the
heating shutoff valve.
Fig. 31 Remove the hot surface ignitor and ionisation
electrode
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
28Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
Maintenance4
To drain the boiler take the following steps:
z First drain the system.
z In case of frost, drain the boiler.
z Loosen the draining nipple with a screwdriver see fig. 32.
z Attach temporary hose to the nipple. Connect the other
side of the temporary hose to a draining pipe.
z When the boiler is drained then tighten the draining nipple
screw.
z Release plug-in connection of fan power lead (fig. 27,
item 1, page 27), burner-control unit fan control lead
(fig. 27, item 2, page 27) and gas-burner assembly (fig. 27,
item 3, page 27).
z Loosen union nut on gas valve assembly (fig. 27, item 4,
page 27).
z Push safety plate out of way.
z Turn air suction tube and pull off from below.
z Swivel the air combination unit forward (fig. 28, item 1,
page 27).
z Pull the air combination unit up and out of bayonet
connector (fig. 28, item 2, page 27) and remove via front of
unit.
z Remove rubber seal in combustion chamber from top
(fig. 29, item 2, page 27).
Fig. 32 Draining the boiler
z Remove burner and burner gasket (fig. 29, item 1,
page 27) by pulling upwards through the opening (fig. 33,
item 1).
z Remove the front of the heat exchanger by releasing the
four retaining clips (fig. 33, item 2).
z Remove the hot surface ignitor (fig. 31, item 1) and
ionisation electrode (fig. 31, item 2).
In the case of the hot surface ignitor:
Loosen the fixing screw of the hot surface ignitor, detach
both earth (ground) leads and remove the retaining plate of
the hot surface ignitor by pulling it upwards, withdraw the
hot surface ignitor by pulling it upwards.
In the case of the ionisation electrode:
Swivel the retaining plate to one side and carefully remove
the ionisation electrode by pulling it upwards.
z Remove securing pin on flow and return connection
conduit (fig. 34) of heat exchanger.
z Remove spiral heat exchanger by pulling towards front
(fig. 34). Drain any water remaining in the heat exchanger
into the condensate trap.
1
2
Fig. 33 Remove burner and release retaining clips
Fig. 34 Securing pin on spiral heat exchanger
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/200429
Maintenance4
z Remove the diffusion head (fig. 35, item 2) on the
underside of the heat exchanger by withdrawing the
securing pin (fig. 35, item 1) and unscrewing the diffusion
head.
z Clean the front and back cover of the heat exchanger and
the heat exchanger with water or compressed air.
z Clean the burner with compressed air only.
Take care not to damage the fins of the heat exchanger.
Refitting (fig. 36) :
NOTE
Excessive flue gas temperatures may be an
indication of an incorrectly-fitted diffusion
head.
12
z Screw the diffusion head in as far as it will go on the
underside of the heat exchanger (the final turn of the heat
exchanger increases the clearance between the pipes) and
insert securing pin.
CAUTION
Take care not to damage the insulation on the
diffusion head.
z Check to ensure that the heat exchanger has been fitted
the right way round. The upper securing-pin groove must
be horizontal (fig. 36, item 1).
z Refit the heat exchanger by following the above procedure
in reverse. Note the following:
z The gasket between the front and back cover of the heat
exchanger should normally be replaced. Fit the new gasket
by pressing in from the top on both sides, and without
stretching. DO NOT attempt to cut the gasket to size.
z Check the heat exchanger for leaks BEFORE
reassembling the front and back cover of the heat
exchanger.
z Check O-ring seals (spiral), and replace as required.
z Smear the O-ring seal with a thin layer of silicone grease.
Fig. 35 Removing the diffusion head
1
Fig. 36 Refitting the heat exchanger
4.1.3Cleaning the condensate trap
z Remove the trap and withdraw it from the outlet see fig. 37.
z Clean the condensate trap.
z Fill the condensate trap with water and then reassemble in
reverse order.
z Measuring the gas input pressure (flow pressure).
z Check the gas/air ratio.
z Leak test in operational condition.
z Measuring the carbon monoxide content.
z Carry out function testing.
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
30Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
Fig. 37 Removing the condensate trap
Servicing5
5Servicing
5.1Operating codes
NOTE
If the code displayed on the burner-control unit
is not listed under the operating codes or fault
warnings, the burner-control unit itself is
malfunctioning.
DisplayDisplay after
pressing the
service
button
0Buderus 600 - 11R / 19R / 24R is ready for operation
ABurner interval circuit, 10 min. from burner start-up
HStandby activated, Buderus 600 - 11R / 19R / 24R ready to provide heat
LInitial safety period: self-testing of burner-control unit during burner start-up
z Check flue gas sensor for continuity. If continuity is not
present, the flue gas sensor is defective.
z Replace any flue gas sensor found to be defective.
Ensure you use only genuine Boulter Buderus spare parts.
z If the flue gas sensor is working correctly, plug it in once
more.
5.3.2Replacing the flue gas sensor
z Unscrew the flow-backup mounting.
z Detach the cable plug at the flue gas sensor.
z Loosen both retaining screws on the flue gas sensor.
z Remove the flue gas sensor and replace with a new unit
(fig. 38).
z Retighten the retaining screws.
z Reconnect the cable plug.
z Screw the mounting into place.
5.3.3Replacing the UBA
z Disconnect the system from the power supply.
z Loosen the two screws on the UBA (fig. 39, item 1).
z Carefully turn the UBA around with the backside facing up
(fig. 40).
z Note the position of the cable plugs, disconnect all cable
plugs.
z Fit a new UBA.
z Reconnect all plug-in cables to their correct sockets.
z Turn the UBA around and place back onto the bracket.
z Tighten the two screws.
z Connect system to mains power supply.
Fig. 38 Buderus 600 - 11R / 19R / 24R :
replacing the flue gas sensor
1
Fig. 39 Replacing the UBA
Fig. 40 Backside of the UBA
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
40Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
Servicing5
5.3.4Checking the fan
z Set the mains switch to “0”.
z Disconnect the fan's plug and socket connection.
z Connect a multimeter (230 V AC).
z Turn the mains power switch to “I”.
z Take voltage reading at measuring device.
If the voltage reading is 230 V, the power supply is in order.
z Set the mains switch to “0”.
z If the power supply is in order, plug the unit in once more.
z Turn the mains power switch to “I”.
z If the fan now fails to run, it must be replaced.
z If the fan runs at only partial load (i.e. effective operation of
the boiler is not possible), troubleshooting should start at
the connection cable to the UBA or UBA.
5.3.5Replacing the fan
Fig. 41 Checking the fan
z Shut the gas valve.
z Disconnect the system from the power supply.
z Disconnect the fan, using the plug and socket from the
power supply (fig. 42, item 1), loosen the UBA control line
at the fan (fig. 42, item 2) and the gas burner fitting (fig. 42,
item 3).
z Loosen the union nut (fig. 42, item 4) on the gas burner
fitting.
z Push the safety plate out of the way (fig. 43, item 1).
z Turn air suction tube and pull off from below.
1
2
3
4
Fig. 42 Replacing the fan on the 600 Series:
loosen plug and union nut
1
Fig. 43 Replacing the fan on the 600 Series:
remove the air suction tube
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/200441
Servicing5
z Swivel the gas combination unit forward (fig. 44, item 1)
z Remove the gas combination unit from its bayonet
connector and pull upwards to detach (fig. 44, item 2).
z Detach the fan by loosening the 2 x 2 screws on the
connection unit.
z Replace the fan.
z Refit by following the above procedure in reverse.
2
Fig. 44 Replacing the fan on the 600 Series:
remove the gas connection unit
1
NOTE
Once installation has been completed
successfully, carry out leak testing as per
subsection 2.1.1.
5.3.6Checking the wiring connections of the UBA
z Disconnect the system from the power supply.
z Loosen the two fixing screws and carefully turn the UBA
around (fig. 39, item 1, page 40).
z Check all cable terminals for tightness and
resecure/retighten as required.
z Turn the UBA around and place back onto the bracket.
z Tighten the two screws.
z Connect system to mains power supply.
Fig. 45 Replacing the fan on the 600 Series:
replace the fan
Fig. 46 Checking the wiring connections of the UBA
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
42Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
Servicing5
5.3.7Checking the miniature fuses
z Disconnect the system from the power supply.
z Loosen the two fixing screws and carefully turn the UBA
around.
z Check miniature fuses (fig. 47) for correct functioning,
or carry out visual inspection. If defective, fit new fuse
(1.25 AT).
FuseFunction
1Hot surface ingitor
2UBA, sensors, thermostat valve
3UBA
z Turn the UBA around and place back onto the bracket.
z Tighten the two screws.
z Connect system to mains power supply.
5.3.8Checking the safety sensor
z Unplug cable connection from sensor.
z Measure resistance of sensor (fig. 48, item 1).
z Use a second-reading thermometer to measure the
temperature around the sensor.
z Compare readings with values shown in table 8 on
page 44. If there is any mismatch (i.e. > 5%), the sensor is
defective.
z If the sensor is working correctly, plug it in once more.
2
3
Fig. 47 Checking the miniature fuse
1
Fig. 48 Buderus 600 - 11R / 19R / 24R:
checking the safety sensor
5.3.9Replacing the safety sensor
z Shut the servicing valve.
z Drain the Buderus 600 - 11R / 19R / 24R as per the
"Installation and Servicing Instructions".
z Loosen the plug-in connection (fig. 49, item 1).
z Unscrew the sensor (fig. 49, item 2) and replace with a new
unit.
z Plug in cable connection.
z Open servicing valves.
NOTE
Fill the Buderus 600 - 11R / 19R / 24R and
purge the system of air.
Fig. 49 Buderus 600 - 11R / 19R / 24R:
replacing the safety sensor
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/200443
Servicing5
5.3.10 Checking the safety sensor connection lead
Check to ensure that all plug-in connections on the sensor and
UBA are in order. Note that an incorrectly-inserted plug can
lead to the generation of error messages. Start up the boiler by
pressing the “reset” button.
z Set the mains switch to “0”.
z Disconnect the system from the power supply.
z Unplug cable connection from flow sensor.
z Disconnect 18-pin plug from UBA.
z Use a continuity tester to check the cable between the
plug-in connection and the 18-pin plug in the UBA.
The test should be carried out on connections 06-18 and
08-18 (fig. 50).
z If the cables are in order, plug them in.
z Connect system to mains power supply.
z Turn the mains power switch to “I”.
Fig. 50 Buderus 600 - 11R / 19R / 24R:
checking the safety sensor connection lead
5.3.11 Checking the flow sensor
z Unplug cable connection from sensor.
z Measure resistance of sensor (fig. 51, item 1).
z Use a second-reading thermometer to measure the
temperature around the sensor.
z Compare readings with values shown in table 8. If there is
any mismatch (i.e. > 5%), the sensor is defective.
z If the sensor is working correctly, plug it in once more.
1
Fig. 51 Buderus 600 - 11R / 19R / 24R:
checking the flow sensor
Temp.
[°C]
029,490
523,462553,271.0
1018,787602,760.0
1515,136652,339.0
2012,268701,990.0
2510,000751,700.0
308,197801,458.0
356,754851,255.0
405,594901,084.0
454,656951,939.6
503,8931001,817.2
Table 8Resistance values for hot water / boiler sensor
Resistance
[Ω]
(approximate values)
Temp.
[°C]
Resistance
[Ω]
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
44Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
Servicing5
5.3.12 Replacing the flow sensor
z Shut the servicing valve.
z Drain the Buderus 600 - 11R / 19R / 24R as per the
"Installation and Servicing Instructions".
z Loosen the plug-in connection (fig. 52, item 1).
z Unscrew the sensor (fig. 52, item 2) and replace with a new
unit.
z Plug in cable connection.
z Open servicing valves.
NOTE
Fill the Buderus 600 - 11R / 19R / 24R and
purge the system of air.
5.3.13 Checking the flow sensor connection lead
Check to ensure that all plug-in connections on the sensor and
UBA are in order. Note that an incorrectly-inserted plug can
lead to the generation of error messages. Start up the boiler by
pressing the “reset” button.
z Set the mains switch to “0”.
z Disconnect the system from the power supply.
z Unplug cable connection from flow sensor.
z Disconnect 20-pin plug from UBA.
z Use a continuity tester to check the cable between the
plug-in connection and the 20-pin plug in the UBA.
The test should be carried out on connections 05-20 and
18-20 (fig. 53).
z If the cables are in order, plug them in.
z Connect system to mains power supply.
z Turn the mains power switch to “I”.
1
1
2
Fig. 52 Buderus 600 - 11R / 19R / 24R:
replacing the flow sensor
UBA
1
11
Fig. 53 Buderus 600 - 11R / 19R / 24R:
checking the flow sensor connection lead
10
20
5.3.14 Checking the hot surface ingitor
z Disconnect the system from the power supply.
z Loosen the two fixing screws and carefully turn the UBA
around.
z Unplug and remove hot surface ingitor from UBA housing
(fig. 54).
z Check hot surface ingitor for free throughput.
If throughput is free, the hot surface ingitor is in order.
z If the hot surface ingitor is in order, plug the cable into the
UBA housing.
z Turn the UBA around and place back onto the bracket.
z Tighten the two screws.
z Connect system to mains power supply.
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/200445
Fig. 54 Checking the hot surface ingitor
Servicing5
5.3.15 Replacing the hot surface ingitor
z Disconnect the system from the power supply.
z Remove burner cover.
z Remove the earth (ground) lead from the hot surface
ingitor (fig. 55, item 1).
z Loosen the two screws on the UBA and carefully turn the
UBA around with the backside facing up.
z Unplug hot surface ingitor connection cable from UBA
(fig. 56).
z Loosen nut on clamp used to secure earth (ground) lead
(fig. 55, item 2).
z Detach retaining plate of hot surface ingitor (fig. 55, item 3)
and remove hot surface ingitor.
1
3
2
Fig. 55 Replacing the hot surface ingitor
5.3.16 Measuring the ionisation current
z Disconnect the system from the power supply.
z Loosen the plug-and-socket connector of the monitoring
cable and connect the measuring device in series.
Select the µA direct current range on the multimeter.
The multimeter must have a resolution of at least 1 µA.
z Reconnect the system to the power supply, make sure that
the system pump is running and turn the chimney-sweep
switch to “1”.
z Measure the ionisation current.
The ionisation current must be > 2 µA DC.
z Enter the reading on the report form.
z Disconnect the system from the power supply.
z Remove the measuring device and restore the
plug-and-socket connection to its original state.
z Turn the chimney-sweep switch to position “0”.
z Refit the cover for 2nd operating level.
z Reconnect the system to the power supply. When the
display shows “7”, press the service button to display “c”.
Press the "reset" button. The display shows “r”.
Fig. 56 Disconnect the plug-in cable from the UBA housing
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
46Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
Servicing5
5.3.17 Replacing the ionisation electrode
z Remove the air combination unit.
z Loosen the plug-and-socket connection of the ionization
electrode.
z Loosen screw (fig. 57, item 1) by a half-turn and slide bar
to remove.
z Pull electrode to remove, and fit new unit.
z Reassemble by following the above procedure in reverse.
Fig. 57 Replacing the ionisation electrode
5.3.18 Checking KIM connections
z Locate Kim on the side of the UBA bracket.
z Check if 4 pin connector (fig. 58, item 1) is fitted and
secure.
1
NOTE
This is not a servicable part and any fault
identified with this component, contact Boulter
Buderus.
1
Fig. 58 KIM connections
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/200447
Conversion to another type of gas6
6Conversion to another type of gas
WARNING!
Work on components in contact with gas must
only be carried out by a registered CORGI
engineer.
Switch off the heating boiler
z Disconnect the system from the power supply.
z Close the gas service valve.
z Loosen the 4 crosshead screws on the ventilation cover
(fig. 59).
z Remove the ventilation cover.
Fig. 59 Unscrew ventilation cover
z Loosen union nut on gas valve assembly (fig. 60, item 4).
z Release plug-in connection of fan power lead (fig. 60,
item 1), burner-control unit fan control lead (fig. 60, item 2)
and gas-burner assembly (fig. 60, item 3).
z Push safety plate out of way (fig. 61, item 1).
z Turn air suction tube and pull off from below.
Fig. 60 Loosen the union nut and remove the cable
Fig. 61 Remove safety plate
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
48Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
Conversion to another type of gas6
sz Swivel the air combination unit forwards (fig. 62, item 1).
z Pull the air combination unit up and out of the bayonet
connector (fig. 62, item 2) and remove via the front of the
unit.
2
1
Type of gas
supply
Natural gas H
(G20)
Propane P3.404.15Standard
Table 9Gas-nozzle diameter
Replacing a gas nozzle
WARNING!
Conversion to another gas type is
implemented by installing/removing a gas
nozzle (fig. 63, item 3) of the appropriate gas
nozzle diameter (table 9).
z Undo the three screws (fig. 63, item 2) on the long side of
the gas fitting.
z Remove the gas nozzle and insert the correct gas nozzle
for the new gas type.
z Insert new seal (fig. 63, item 4).
z Remount all components in the reverse sequence.
z Cover stickers (fig. 64, item 1) with the new stickers
(2 pieces, included in conversion kit).
Gas nozzles ∅ [mm]
11R19R/24R
5.556.5Standard
Venturi
tubes
Fig. 62 Remove the air combination unit
Starting up
z Start up the appliance following the procedure described in
the mounting and maintenance instructions.
z Include all seal areas concerned during mounting in the
gas-tightness check when in operation.
z Refit all covers.
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
Fig. 63 Replacing a gaz nozzle
1
Fig. 64 Place new stickers
1
Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/200449
Appendix7
7Appendix
7.1Technical specifications
DimensionsUnit
Type of gas supply as established in
EN 437 (GB)
Rated heating capacity for system
temperature (modulating from 30° to 100°)
Heating curve 75/60 °C
Heating curve 40/30 °C
Seasonal efficiency (SEDBUK)%90.390.390.2
Central heating installation
Heating water temperature°C40 - 80
∆T at residual head of 200 mbarK<20
Max. operating overpressure of boilerbar3.0
Volume heat exchanger heating circuitl1.0
Pipe connections
GasG½" (outside) / R½" (inside)
Heating waterG¾" (device) / Ø 22 mm (accessory)
kW
kW
600 Series Buderus wall-mounted condensing gas boiler
11R19R24R
GB II
(natural gas H, propane P)
4.3 - 10.0
4.9 - 11.0
20 mbar, 37 mbar
2H3P
8.6 - 17.4
9.7 - 19.0
8.6 - 22.0
9.7 - 24.0
Condensate-water outletmmØ 21.5
Flue gas values
Condensate water quantity, natural gas,
40/30 °C
pH value of condensate waterapprox. 4.1
Flue gas mass-flow rate
Full load
Part-load
Flue gas temperature, full load
Heating curve 75/60 °C
Heating curve 40/30 °C
Flue gas temperature, part-load
Heating curve 75/60 °C
Heating curve 40/30 °C
full load, natural gas
CO
2
standard test gas G20%9.2
full load, natural gas
CO
2
standard test gas G31 propane%10.3
Standard emission factor COmg/kWh<22
Standard emission factor NO
Max. pressure drop permittedPa3560100
x
l/h0.71.31.6
g/s
g/s
°C
°C
°C
°C
mg/kWh<30
4.9
2.2
75
50
65
40
8.4
4.3
85
55
70
45
10.6
4.3
95
55
70
45
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
50Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
Appendix7
DimensionsUnit
Flue-gas system
Type of flue gas connectionC
Diameter of flue gas systemmm60/100
Electrical data
Mains connection voltageV230
Electrical power consumption
Full/Part loadW40/2540/2540/25
Electrical protection ratingIPX4D
Boiler dimensions and weight
Height x Width x Depthmm700 x 460 x 290
Weight (without casing)kg23.523.523.5
Casingkg5.55.55.5
600 Series Buderus wall-mounted condensing gas boiler
11R19R24R
, C33, C
13
53
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/200451
Appendix7
7.2Short list of spare parts
The following are parts commonly required due to damage or expendability. Their failure or absence is likely to affect safety or
performance of this appliance. For a pictorial representation of the part see the respective position number on the exploded view
pictures on page 10.
Pos.Art. no.Description
1075131Casing complete
2075130Door
3038470Ventilation cover
4038092Bracket
5077465Concentric adaptor
6038496Clip adaptor
7077464Lipring 100 mm
8073366Fan
9073565sSealing fan / venturi (set of 5 pieces)
73566sSealing ventilator (set of 5 pieces)
10073563Lipring 60 mm
11073743Flue gas pipe
12073630Condensate collector
13073579Seal flue gas pipe
14073376Flue gas sensor
15075969Condensate trap
16073573Suction pipe
17073574Lipring 50 mm
18073278Gas valve
19038355Rectifier
20073567Venturi 11 kW
20073568Venturi 19-24 kW
21076680Gas pipe
22076681Gas service valve
23075968sPipe return-flow top (set of 2 pieces)
24075970Pipe connection
78112Kim 165 (24 kw)
36404sPlate screw (set of 10 pieces)
36406sScrew 6x5/8" (set of 5 pieces)
38456Seal ventilation cover
38458sAssembly casing block (set of 2 pieces)
38460sCasing clamp (set of 5 pieces)
38462sAir seal bush (set of 5 pieces)
38463sAir seal bush (set of 4 pieces)
38474s
38475sClip (set of 5 pieces)
73591s
79058sPull relief (set of 5 pieces)
79084sSealing ring (set of 2 pieces)
75300Thermomanometer
73572sScrew M5 ( set of 10 pieces)
73054
73515Insulation divider
73560Cap
73586sSeal
73053Clip suction pipe
73570Gas air supply
73056sClip (set of 5 pieces)
73368sSealing ignitor (set of 10 pieces)
73488sGasket (set of 5 pieces)
73569sSealing venturi / gasket
75301230V cable
75882Swivel dreg with pinchring
73561Sealing
Clip CH tank (2) / clip sensorhousing
(2)
O-ring condensate trap
(set of 5 pieces)
Bracket ionisation electr. and glow
ignitor
Subject to modifications resulting from technical improvements!Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
52Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
Reports8
8Reports
8.1Start-up report
z Please check off the start-up tasks carried out and enter
the corresponding readings.
Initial start-up tasksRemarks or measurement readings
1. Note down gas characteristics:
Wobbe index
Operating heat value
2. Inspect to check for leaks
(See section 2.1.1 on page 20)
3. Check combustion air/flue gas connection
(See section 2.1.3 on page 21)
4. Checking the boiler equipment (change to another type of gas if
necessary) (See section 2.1.4 on page 21)
5. Carry out adjustment settings
(See section 2.1.5 on page 22)
6. Measure the gas connection pressure (flow pressure)
(See section 2.1.7 on page 23)
7. Checking and adjusting the gas/air -ratio
CO
-content: at full load
2
(See section 2.1.8 on page 23)
8. Leak test in operational condition
9. Measure carbon monoxide content (CO), vacuum
(See section 2.1.9 on page 24)