Important general instructions for use
This device should only be operated in accordance with its
designated use and the indications given in the servicing
instructions. All maintenance and repair operations must be
carried out by a qualified service technician.
Always operate in conjunction with original accessories, and
use only genuine spare parts. Other combinations of units,
accessories and consumables are only to be used if they
completely fulfil the specifications involved, and if system
performance and safety are not affected in any way.
Note that all the servicing tasks described here must be carried
out by a qualified maintenance firm. Work on gas pipes and
fittings must only be carried out by a CORGI registered
engineer.
Subject to technical modifications
As a result of our policy of constant development, there may be
small differences between illustrations, functional steps and
technical data.
The boiler meets the basic requirements of the
appropriate standards and directives.
Conformity has been substantiated by the
proper documents which - together with the
declaration of conformity - are filed with the
manufacturer.
BENCHMARK' Log Book
All Buderus gas boilers now include an Installation, Commissioning and Service record log book. The details of the log
book will be required in the event of any warranty work being
requested.
Please complete the appropriate section at each service visit.
REMEMBER: Please hand the log book back to the user.
Subject to modifications resulting from technical improvements! Buderus Ltd. • http://www.buderus-domestic.co.uk
2Servicing manual for wall-mounted condensing gas boiler 600 Series 11S/19S/24S/24C • Issued 02/2006
Messages – Universal Automatic Burner (UBA)1
Buderus
U122 K
1Messages – Universal Automatic Burner (UBA)
1.1UBA status display
Operational condition and error messages appear on the
display of the Universal Automatic Burner (UBA).
The message consists of two characters.
The first character is displayed automatically.
Fig. 1600 Series 11S / 19S / 24S / 24C: Display
To display the second character:
z Hinge the control panel cover to the left to open.
z Press the "Service" button.
Fig. 2600 Series 11S / 19S / 24S / 24C:
Open the control panel cover
Fig. 3"Service" button
Subject to modifications resulting from technical improvements! Buderus Ltd. • http://www.buderus-domestic.co.uk
Servicing manual for wall-mounted condensing gas boiler 600 Series 11S/19S/24S/24C • Issued 02/20063
Messages – Universal Automatic Burner (UBA)1
1.2UBA operating level 1.5
UBA operating level 1.5 (fig. 4).
Key:
Item 1:Display
Item 2:Service button
Item 3:Reset button
Item 4:Boiler flow temperature
Item 5:Hot-water temperature
Item 6:Power adjustment
Item 7:Pump overrun switch
Item 8:Chimney-sweep switch
Item 9:11 kW jumper
1
2
3
4
5
Fig. 4UBA operating level 1.5
9
8
7
6
1.3Service tool
The service tool allows you to determine the operating status
of the boiler, check components and carry out fast fault diagnosis.
z Open the cover at the front of the boiler unit and insert the
twin plug connector of the service tool into the sockets
provided (fig. 5, item 1).
1
11
KW
I
0
Fig. 5Service tool connection
01
12
1
10
1
10
Subject to modifications resulting from technical improvements! Buderus Ltd. • http://www.buderus-domestic.co.uk
4Servicing manual for wall-mounted condensing gas boiler 600 Series 11S/19S/24S/24C • Issued 02/2006
Messages – Universal Automatic Burner (UBA)1
1.4Operating messages
Display after
Display
pressing the
service button
Meaning
-.
=.
0
A
C
H
L
U
y
A
H
y
600 Series 11S / 19S / 24S / 24C is ready for operation
Burner interval circuit, 10 min from burner start-up
Waiting for the three-way valve and/or pump to switch
Standby activated, 600 Series 11S / 19S / 24S / 24C ready to provide heat or hot water
Initial safety period: self-testing of UBA during burner start-up
Post- or pre-flushing period of fan unit
Flow temperature at adjustment setting
600 Series 11S / 19S / 24S / 24C running in heating mode
“Chimney-sweep” mode, flow-temperature controller bypassed,
600 Series 11S / 19S / 24S / 24C heating to previously-entered flow temperature
Normal heating mode
Service mode
600 Series 11S / 19S / 24S / 24C running in hot-water mode
H
r
Table 1Displayed UBA operating messages
Normal hot water mode
Reset
Subject to modifications resulting from technical improvements! Buderus Ltd. • http://www.buderus-domestic.co.uk
Servicing manual for wall-mounted condensing gas boiler 600 Series 11S/19S/24S/24C • Issued 02/20065
Messages – Universal Automatic Burner (UBA)1
1.5Fault messages
Display
2
3
4
Display after
pressing the
service button
C
P
C
A
C
F
H
Trouble-
Meaning
Water flow
Safety sensor exceeds 100 °Cpage 10
Excessive temperature increase at safety sensorpage 11
Air volume flow
Bad plug-in connection at cable loom, or damaged wiringpage 12
Temperatures
Feed sensor above 100 °Cpage 13
F2 fuse malfunction, or exhaust-gas sensor tripped
Safety sensor exceeds 100 °Cpage 17
Dripping tappage 18
shooting
flow diagram
page 15
L
P
U
y
5
C
6
A
C
H
L
Short circuit in safety sensorpage 19
Safety sensor, loose contact or defectivepage 20
Short circuit in feed sensorpage 21
Feed sensor, loose contact or defectivepage 22
Communication
600 series has switched off after disconnection of diagnosis plug
Flame monitoring
F1 fuse defective, or no ionisation message after ignitionpage 24
Ionisation message, but no flamepage 28
Flame dies out after gas valve is openedpage 29
Flame goes out during warm-up phasepage 30
page 23
Subject to modifications resulting from technical improvements! Buderus Ltd. • http://www.buderus-domestic.co.uk
6Servicing manual for wall-mounted condensing gas boiler 600 Series 11S/19S/24S/24C • Issued 02/2006
Messages – Universal Automatic Burner (UBA)1
Display
7
8
9
Display after
pressing the
service button
A
C
F
H
L
y
A
Trouble-
Meaning
Mains voltage
Voltage in UBA too low or too highpage 31
Mains voltage interrupted following a fault warning messagepage 32
F3 fuse defect, or UBA system errorpage 33
Voltage peaks in UBApage 34
UBA timer errorpage 35
General fault/gas-pressure
External switching contact, e.g. temperature monitor for floor heating, has
been tripped
System error
System errorpage 37
shooting
flow diagram
page 36
C
F, H, P
L
U
E
Any indication,
except
Incorrect cable connection at KIM, or KIM defectivepage 38
System error (UBA defective)page 39
Wiring to gas-burner assembly incorrect, or loose wiring connections
in UBA
KIM defectivepage 41
UBA system fault
UBA system fault
P
P
Table 2Displayed UBA fault warning messages
Non-compatible UBA fittedpage 42
page 40
Subject to modifications resulting from technical improvements! Buderus Ltd. • http://www.buderus-domestic.co.uk
Servicing manual for wall-mounted condensing gas boiler 600 Series 11S/19S/24S/24C • Issued 02/20067
Faults that the UBA does not display2
2Faults that the UBA does not display
Hot-water mode
Although the UBA is apparently ready for use, situations may
arise where a hot-water tap is opened and no hot water flows
out, or flows out for only a short period.
Troubleshooting flow diagram:
page 43/44.
Heating mode
Although the UBA is apparently ready for use, and the room
temperature has not yet reached the preset level, the
600 Series 11S / 19S / 24S / 24C wall-mounted condensing
gas boiler fails to go into heating mode.
Troubleshooting flow diagram:
page 45.
Subject to modifications resulting from technical improvements! Buderus Ltd. • http://www.buderus-domestic.co.uk
8Servicing manual for wall-mounted condensing gas boiler 600 Series 11S/19S/24S/24C • Issued 02/2006
Troubleshooting3
3Troubleshooting
The following flow diagrams are provided for the purpose of
systematic troubleshooting.
Take the opportunity, while carrying out fault diagnosis, to
check that all that plugs and wiring terminals on the UBA are
connected correctly.
WARNING
Switch off the 600 Series 11S / 19S / 24S / 24C
BEFORE checking the connections.
Each time a fault has been rectified, push the “reset”
button "" to unblock the UBA and return it to standby mode.
NOTE
The system cannot be reset by disconnecting
at the master switch.
Certain troubleshooting tasks must be carried out with the
600 Series 11S / 19S / 24S / 24C in heating mode.
When doing so, the chimney-sweep switch should be set to "1"
(fig. 6).
Remember to return the chimney-sweep switch to “0” once
work is complete.
01
Fig. 6Chimney sweeper switch on UBA
Subject to modifications resulting from technical improvements! Buderus Ltd. • http://www.buderus-domestic.co.uk
Servicing manual for wall-mounted condensing gas boiler 600 Series 11S/19S/24S/24C • Issued 02/20069
Troubleshooting3
2
Safety sensor temp. exceeds
100 °C
Wait approx. 30 sec for the boiler to return
automatically to normal operation
New fault warning message
2C?
Check system and heat exchanger, as
indicated in the installation and servicing
instructions, for signs of airlocks and dirt -
purge and/or clean as required
Are all
maintenance shutoff
valves open?
Is the water
pressure in the system at
least 1 bar?
C
Yes
Yes
No
No
No
Open maintenance shutoff valves
Fill up with water as indicated in the
installation and servicing instruc-
tions, and purge the system of air
Yes
Is at least one
thermostatic valve open (to
control the amount of water