5 643 983 – 3/2005 - updated 8/2007
Instruction for High Altitude
Conversion Kit for 124X Series Boilers
This kit and instruction are for converting the
G124X Series Boilers for use at elevations
above 8500ft.
REQUIRED INPUT RATES
G124X-18
66,660
BTU/H
THE CONVERSION SHALL BE
PERFORMED BY A
MANUFACTURER’S AUTHORIZED
REPRESENTATIVE IN
ACCORDANCE WITH THE
REQUIREMENTS OF THE
MANUFACTURES, PROVINCIAL OR
TERRITORIAL AUTHORITIES
HAVING JURISDICTION AND IN
ACCORDANCE WITH THE
REQUIREMENTS OF THE Can/CGAB149.1 or Can/CGA-B149.2
INSTALLATION CODES.
G124X-25
92,700
BTU/H
G124X-32
119,250
BTU/H
Notice: This manual must be retained for future reference!

5 643 983 – 3/2005 - update 8/2007
Parts list for converting the boilers for high
altitude installations
This kit contains the following parts:
Main Gas Burner orifice and gaskets
Conversion data plate to be filled out ands affixed to the
appliance
Conversion instructions
TO CONVERT THE BOILER FOR USE AT HIGH
ALTITUDE, THE FOLLOWING INSTRUCTIONS
SHALL BE ADHERED TO.
The boiler shall be converted prior to installation
1. Remove Control Access Panel from the boiler, fig 1.
2. Remove main gas orifices and washers from the burner
assembly, fig 2.
3. Install new orifices and washers supplied with kit. Ensure
orifices are the proper size for your boiler application per
the following
4. Fill out the required information on the conversion plate
and affix the plate to the outside of the boiler jacket as
close as possible to the existing rating plate.
5. If the boiler has not been placed into operation, follow the
installation instruction in “the installation, Operation and
Maintenance Manual” supplied with the boiler.
tables:
Fig. 1
Model
G124X-18 1.80mm
G124X-25 1.75mm
G124X-32 1.70mm
Model
G124X-32 2.70mm
Orifice Size Kit Number Orifice Size Kit Number
Orifice Size Kit Number Orifice Size Kit Number
Orifice Sizes — Propane
0-8500 8501-12000
0-8500 8501-12000
Elevation in feet
G124x18P85
G124x25P85I
G124x32P85I
Orifice Sizes — Natural Gas
Elevation in feet
Standard
Version
I
Manifold Pressure
In inch wc
Model G124X-18 G124X-25 G124X-32
Natural 3.6 3.5 3.6
Propane 9.8 10.3 10.0
1.75mm
1.70mm
1.65mm
mm08.2mm58.281-X421G
mm07.2mm57.252-X421G
2.65mm
Fig.2
G124X18P12000I
G124X25P12000I
G124X32P12000I
G124X18N1200
G124X25N12000
G124X32N12000