WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing
property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow gas supplier’s instructions.
If you cannot reach your gas supplier, call fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
“This appliance is intended for supplemental heating.”
“This heater shall not be installed in a bedroom or bathroom.”
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or property
damage. Refer to this manual for correct installation and operational procedures. For assistance or additional
information consult a qualified installer, service agency or gas supplier.
WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed.
Provisions for adequate combustion and ventilation air must be provided. Refer to Air for Combustion andVentilation section on page 4 of this manual.
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing
property damage, personal injury or loss of life.
This appliance may be installed in an aftermarket*, permanently located, manufactured (mobile) home,
where not prohibited by state or local codes.
This appliance is only for use with the type of gas indicated on the rating plate.
This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
INSTALLER: Leave this manual with appliance.
CONSUMER: Retain this manual for future reference.
MANUFACTURED BY NEW BUCK
CORPORATION
200 ETHAN ALLEN DRIVE, PO BOX 69
SPRUCE PINE, N.C. 28777
www.buckstove.com
WARNING: Only New Buck Corporation
MA CVF714, may be used with the CVFB200
unit only.
PARTS LIST ..........................................................................................................................................23
REPLACEMENT PARTS .....................................................................................................................24
owner’s manual carefully and
completelybeforetryingto
assemble, operate or service this
heater.Improper use of this
heater can cause serious injury or
death from burns, fire, explosion,
electricalshockandcarbon
monoxide poisoning.
DANGER:Carbon monoxide
poisoning may lead to death!
NOTE: When burning any unit
or appliance that combusts fuel
for heat, such as coal, oil, wood
or natural and (L.P.) liquid
petroleumgas.Wehighly
recommend the use of smoke
and carbon monoxide detectors
in your home.
Carbon Monoxide Poisoning:
Early signs of carbon monoxide
poisoning resemble the flu, with
headaches, dizziness or nausea. If
you have these signs, heater may
not be working properly. Getfresh air at once! Have heater
serviced. Some people are more
affected by carbon monoxide than
others. These include pregnant
women, people with heart or lung
disease or anemia, those under
influence of alcohol and those at
high altitudes.
Makecertainyoureadand
understand all Warnings. Keep
this manual for reference. It is
your guide to safe and proper
operation of this heater.
WARNING: Any change to this
heater or its controls can be
dangerous.
WARNING: Do not allow fans
to blow directly into the stove.
Avoid any drafts that alter
burner flame patterns. Ceiling
fans can create drafts that alter
burner flame patterns. Altered
burnerpatternscancause
sooting.
WARNING: Donotuse a
blower insert, heat exchanger
insert or other accessory not
approved for use with this
heater.
Due tohigh temperaturesthe
appliance should be located out of
traffic and away from furniture and
draperies.
Do not place clothing or other
flammable material on or near
appliance. Never place any objects on
heater.
Stove becomes very hot when running
heater. Keep children and adults away
from hot surfaces to avoid burns or
clothing ignition. Stove will remain
hot for a time after shutdown. Allow
surfaces to cool before touching.
Carefully supervise young children
when they are in the room with
heater. When using handheld remote
accessory, keep selector switch in
OFF position to prevent children from
turning on burners with remote.
Keep appliance area clear and free
from combustible materials, gasoline
and other flammable vapors and
liquids.
1.This appliance is only for use
with the type of gas indicated on
rating plate. This appliance is not
convertible for use with other
gases.
2.If you smell gas
shut off gas supply
do not try to light any appliance
do not touch any electrical
switch: do not use any phone in
your building
immediatelycallyourgas
supplier from a neighbor’s phone.
Follow gas supplier’s instructions
if you cannot reach your gas
supplier, call fire department
3.This heater shall not be installed
in a bedroom or bathroom.
4.Do not use this stove as a wood
burning fireplace. Use only
models:
3.Donotaddextra logs or
ornaments such as pine cones,
vermiculite or rock wool. Using
these added items can cause
sooting.
CVFB200(LP),
CVFB200(NAT),
C100BA(LP) or
C100BA(NAT)
vent-free gas log heater.
series
6.During initial operation, slight
smoking could occur due to
heater burning manufacturing
residues.
7.To prevent creation of soot, follow
instructions in “Cleaning and
Maintenance”, page 19.
8.Before using furniture polish,
wax, carpet cleaners or similar
products, turn heater off. If heated,
vapors from these products may
create a white powder residue
within burner box or on adjacent
walls or furniture.
9.This heater has an Oxygen
Depletion Sensing (ODS) safety
shutoff system. The ODS shuts
down heater if not enough fresh
air is available. See “Air for
Combustion and Ventilation”,
pages 3 through 5. If heater keeps
shutting off, see“Troubleshooting”, pages 20 through 22.
10. Do not run heater
where flammable liquids or vapors
are used or stored
under dusty conditions
11. Do not use this stove to cook food
or burn paper or other objects.
12. Do not use heater if any part has
been exposed to or under water.
Immediately call a qualified
service technician to inspect room
heater and to replace any part of
control system and any gas control
which has been under water.
13. Do not operate heater if any log is
broken.
14. Turn heater off and let cool before
servicing. Only a qualified service
person should service and repair
heater.
15. Operating heater above elevations
of 4,500 feet could cause pilot
outage.
16. Do not place stove directly on
carpeting, vinyl tile or any
combustible material other than
wood. The stove must set on a
metal or wood panel extending the
full width and depth of the
appliance.
Page 1
Page 5
IDENTIFICATION NUMBERSAND DESCRIPTIONS FOR
VENT FREE STOVE SERIES
CVFB200 TOWNSEND II
ID#MODEL COLOR
CVFB200-AALMOND
CVFB200-BBLACK
CVFB200-GGREEN
CVFB200-RTERRACOTTA
CVFB200-PVVINTAGE COPPER
ID#TYPE OF GAS
CVFB200(LP)LIQUID PROPANE
CVFB200(NAT)NATURAL
ID#OPTIONAL BLOWER ASSEMBLY CVFB200 ONLY
MA CVF714BLOWER ASSEMBLY
C100BA HEPPLEWHITE
ID#MODEL COLOR
C100BA-AALMOND
C100BA-BBLACK
C100BA-GGREEN
C100BA-RTERRACOTTA
C100BA-PVVINTAGE COPPER
ID#TYPE OF GAS
C100BA(TLP)LIQUID PROPANE
C100BA(NAT)NATURAL
Page 2
Page 6
PRODUCT
INDENTIFICATION
MODELS C100BA(LP), C100BA(NAT) OR CVFB200(LP), CVFB200(NAT) MILLIVOLT
VENT FREE UNITS.
PRODUCT FEATURES
AUTO
NOTE: CVFB200 TOWNSEND II PICTURED
STOVE
BODY
OFF
MANUAL
( TOWNSEND II )
OPERATION
This heater is clean burning. It requires
no outside venting. There is no heat
loss out a vent or up a chimney. Heat is
generated by realistic, dancing yellow
flames. This heater is designed for vent
-free operation. State and local codes
in some areas prohibit the use of ventfree heaters.
SAFETY PILOT
AUTO
COVER DOOR
(SHOWN IN THE OPEN
POSITION)
OPTIONAL
REMOTE CONTROL
BRACKET
PIEZO IGNITOR
OFF
MANUAL
( HEPPLEWHIGHT )
VALVE
CONTROL KNOB
(FLAME) ADJUSTMENT
KNOB
LOCAL CODES
Install and use heater with care. Follow all local codes. In absence of local codes, use latest
edition of “The National Fuel Gas Code ANSI Z223.1”, also know as NFPA 54*.
*Available from:
This heater has a pilot with an Oxygen
Depletion Sensing (ODS) safety
shutoff system. The ODS/pilot is a
required feature for vent-free room
heaters. The ODS/pilot shuts off the
heater if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This heater has a piezo ignitor. This
system requires no matches, batteries,
or other sources to light heater.
American National Standards Institute Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
Page 3
Page 7
AIR FOR
COMBUSTION AND
VENTILATION FOR
C100BA, CFVB200 VENT
FREE STOVE SERIES
WARNING: This heater shall
not be installed in a unusually
tightconstructionunless
provisionsareprovidedfor
adequatecombustionand
ventilationair.Readthe
following instructions to ensure
proper fresh air for this and
other fuel-burning appliances in
your home.
Today’s homes are built more energy efficient than ever. New materials, increased
insulation and new construction methods
help reduce heat lossin homes. Home
owners weather strip and caulk around
windows and doors to keep the cold air
out and the warm air in. During heating
months, home owners want their homes as
airtight as possible.
While it is good to make your home
energy efficient, your home needs to
breathe. Fresh air must enter your home.
All fuel-burning appliances need fresh air
for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers
and fuel burning appliances draw air from
the house to operate. You must provide
adequate fresh air for these appliances.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from
National Fuel Gas Code, NFPA 54/
ANSI Z223.1, Section 5.3, Air for
Combustion and Ventilation.
All spaces in homes fall into one of
thetwofollowingventilation
classifications:
1.Unusually Tight Construction
2.Unconfined Space
The information on pages 4 through 5
will help you classify your space and
provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and
windows may provide enough fresh
air for combustion and ventilation.
However, in buildings of unusually
tight construction, you must provide
additional fresh air.
Unusuallytightconstructionis
defined as construction where:
aWalls and ceilings exposed to
the outside atmosphere have a
continuous water vapor retarder with a rating of one
perm (6 x 10
m2)or lesswithopenings
gasketed or sealed and
bWeather stripping has been
added on openable windows
and doors and
cCaulkingorsealantsare
applied to areas such as joints
aroundwindowanddoor
frames, between sole plates and
floors,betweenwall-ceiling
joints, between wall panels, at
penetrationsforplumbing,
electrical and gas lines and at
other openings.
If your home meets all of the two
criteria above, you must provide
additional fresh air. See VentilationAir From Outdoors, page 5.
If your home does not meet all of
the three criteria above, proceed to
Determining Fresh-Air Flow For
Heater Location, page 4.
-11
kg per pa-sec-
Unusually Tight Construction or
Unconfined Space
The National Fuel Gas Code, ANSI
Z223.1 defines a unusually tight
construction as a space whose volume
is less than 50 cubic feet per 1,000 Btu
per hour (4.8 m3per kw) of the
aggregate input rating of all appliances
installed in that space; and unconfinedspace as a space whose volume is not
less than 50 cubic feet per 1,000 Btu
per hour (4.8 m3per kw) of the
aggregate input rating of all appliances
installed in thatspace. Rooms
communicating directly with the space
in which the appliances are installed*,
through openings not furnished with
doors, are considered a part of the
unconfined space.
This heater shall not be installed in a
unusually tight construction unless
provisions are provided for adequate
combustion and ventilation air.
*Adjoining rooms are communicating
only if there are doorless passageways
or ventilation grills between them.
Installation and repair should be done
by a qualified service person. The
appliance should be inspected before
each use and at least annually by a
professional service person. More
frequent cleaning may be required due
to excessive lint from carpeting,
bedding material, pet hair, etc. It is
imperative that control compartments,
burnersa ndcircu latingair
passageways of the appliance be kept
clean.
WARNING:Any change to
this heater or its controls can be
dangerous.
“WARNING: IF THE AREA IN WHICH THE HEATER MAY BE OPERATED DOES NOT MEET THE REQUIRED
VOLUME FOR INDOOR COMBUSTION AIR, COMBUSTION AND VENTILATION AIR SHALL BE PROVIDED BY
ONE OF THE METHODS DESCRIBED IN THE NATIONAL FUEL GAS CODE, ANSI Z223.1/NFPA 54, THE INTERNA-TIONAL FUEL GAS CODE, OR APPLICABLE CODES.”
Page 4
Page 8
AIR FOR
vent draws combustion air from the outdoors and vents to
COMBUSTION AND
VENTILATION
Continued
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have A Unusually Tight Construction or Unconfined Space
Use this work sheet to determine if you have a unusually tight construction or unconfined space.
Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways
or ventilation grills between the rooms.
1. Determine the volume of the space (length x width x height).
Length x Width x Height = ____________________ cu. Ft. (volume of space)
Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. Ft. (volume of space)
if additional ventilation to adjoining room is supplied with grills or openings, add the volume of these
rooms to the total volume of the space.
2. Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.
____________________ (volume of space) / 50 cu. Ft. = (maximum Btu/Hr the space can support)
Example: 2560 cu. Ft. (volume of space) / 50 cu. Ft. = 51,200 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free heater________________ Btu/Hr
Gas water heater*________________ Btu/Hr
Gas furnace________________ Btu/HrExample:
Vented gas heater________________ Btu/HrGas water heater40,000 Btu/Hr
Gas fireplace logs________________ Btu/HrVent-free heater + 30,000 Btu/Hr
Other gas appliances* +________________ Btu/HrTotal= 70,000 Btu/Hr
Total=________________ Btu/Hr
* Do not include direct-vent gas appliances. Directthe outdoors.
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
______________ Btu/Hr (maximum the space can support)
______________ Btu/Hr (actual amount of Btu/Hr used)
Example: 51,200 Btu/Hr (maximum the space can support)
70,000 Btu/Hr (actual amount of Btu/Hr used)
The space in the above example is a unusually tight construction because the actual Btu/Hr used is more than
the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as
follows:
A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined
space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air FromInside Building, page 5.
B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 5.
C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined
space. You will need no additional fresh air ventilation.
“Warning: If the area in which the heater my be operated does not meet the required volume for indoor
combustion air, combustion and ventilation airs hall be provided by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, the International Fuel Gas Code or applicable local
codes.”
Page 5
Page 9
AIR FOR
COMBUSTION AND
VENTILATION
Continued
VENTILATION AIR
VENTILATIONAIRFROM
INSIDE BUILDING
This fresh air would come from an
adjoining unconfined space. When
ventilating to an adjoining unconfined
space,you mustprovide two
permanent openings; one within 12"
of the ceiling and one within 12" of
the floor on wall connecting the two
spaces (See Options 1 and 2, Figure
2). You can also remove door into
adjoining room (See Option 3, Figure
2). Follow the National Fuel Gas
Code, NFPA 54/ANSI Z223.1, Section
5.3,Airfor Combustionand
Ventilation for required size of
ventilation grills or ducts.
12"
Option (2)
Option (1)
Ventilation
Grills Into
Adjoining Room
Option (3)
Remove
Door into
Adjoining
Room
12”
Ventilation Grills Into
Adjoining Room
FIGURE 2 - VENTILATION AIR FROM INSIDE BUILDING
WARNING:Rework worksheet, adding the space of the
adjoining unconfined space.
The combined spaces must
haveenoughfreshairto
supply all appliances in both
spaces.
Ventilation Air From Outdoors
Provide extra fresh air by using
ventilation grills or ducts. You must
provide two permanent openings: one
within 12" of the ceiling and one
within 12" of the floor. Connect these
items directly to outdoors or spaces
open to outdoors. These spaces
include attics and crawl spaces.
Follow the National Fuel Gas Code,
NFPA 54/ANSI Z223.1, Section 5.3,
Air for Combustion and Ventilation
for required size of ventilation grills or
ducts.(See Figure 3).
OUTLET
AIR
INLET
AIR
NOTE: TYPICAL STOVE CABINET MODEL
OUTLET AIR
INLET AIR
VENTILATED
ATTIC
VENTILATED
TO ATTIC
VENTILATED
TO CRAWL
VENTILATED
CRAWL SPACE
SPACE
IMPORTANT:Do not provide
openings for inlet or outlet air into
attic, if attic has a thermostatcontrolled power vent. Heated air
entering the attic will activate the
power vent.
FIGURE 3 - VENTILATION AIR FROM OUTDOORS
Page 6
Page 10
UNPACKING STOVE
ASSEMBLY FOR
CVFB200, C100BA VENT
FREE STOVE SERIES
1. Carefully remove corrugated box
enclosing stove, leaving unit on
pallet at this time. Remove box that
contains logs,also remove Top
Grate
from stove and set aside. Top
Grate
will be placed on unit after
being installed in desired location
2. Using phillips head screwdriver,
move screws from hold down
brackets on two of the legs.
3. Using drop cloth or blanket to
protect floor, carefully lay stove
body on back. Remove hold down
brackets from the two legs by
unscrewing two bolts holding
brackets. Now replace two bolts in
bottom of legs. The bolts are used
for leveling adjusters. Place unit in
upright position. .(See Figure 4).
NOTE: TYPICAL STOVE CABINET MODEL
FRONT OF
STOVE
BACK
LEVELING BOLTS
BACK OF
STOVE
TOPOF
SIDE
FIGURE 4
Page 7
Page 11
INSTALLATION OF OPTIONAL BLOWER ASSEMBLY FOR
VENT FREE STOVE SERIES MODEL CVFB200(LP) OR CVFB200(NAT)
TOWNSEND II ONLY.
NOTE: If optional blower assembly is to be used
with heater , install blower assembly before putting
unit in chosen location and connecting gas supply.
WARNING: Failure to position the parts in
accordance with this diagram or failure to use
only parts specifically approved may result in
improper functions or property damage or
personal injury.
CAUTION: The Blower Assembly is equipped
with a Power Cord. Make sure that the Power Cord
does not get under Blower Assembly or become
damaged while being installed.
WARNING: Electrical Grounding
Instructions: This appliance is equipped with a
three prong (grounding) plug for your
protection against shock hazard and should be
plugged directly into a properly grounded three
-prong receptacle. DO NOT cut or remove the
grounding from this plug.
BLOWER ASSEMBLY MODEL (MA CVF714)
1.Remove rear shield from top rear of unit before installing optional
Blower Assembly (MA CVF714).
2.Remove Blower Assembly from carton. Remove all protective
packaging applied to Blower Assembly for shipment.
3.Check all items for any shipping damage. If damaged, promptly
inform dealer where you purchased the Blower Assembly.
4.From the rear of the Fire Box, align four (4) notches in Blower
Assembly with (4) holes in rear of Fire Box. This will ensure
centering of Blower Assembly on the Fire Box. Attach Blower
Assembly to Fire Box using four (4) #8 x 1/2" self-piercing mounting
screws provided. (See Figure 5).
VENT FREE STOVE SERIES MODEL CVFB200(LP) or
CVFB200(NAT) TOWNSEND II ONLY.
REMOVE REAR SHIELD BEFORE
ATTACHING BLOWER ASSEMBLY
FOUR (4) NOTCHES IN
BLOWER ASSEMBLY FOR
MOUNTING
CAUTION: Label all wires prior to
disconnection when servicing controls. Wiring
errors can cause improper and dangerous
operation.
Verify proper operation after servicing.
If any of the original wire as supplied with the
appliance must be replaced, it must be replaced
with a wire of at least a 105€ temperature rating.
WARNING: Only New Buck Corporation
approved blower assembly, part number MA
CVF714, may be used with Vent Free Stove
Series CVFB200(LP) or CVFB200(NAT)
Townsend II only.
NOTE: Do not run power cord underneath
heater or in walk way or heavy traffic areas.
FOUR (4) HOLES
FOR MOUNTING
BLOWER ASSEMBLY
BLOWER ASSEMBLY
OPTIONAL BLOWER ASSEMBLY
FIRE BOX
FIGURE 5 - LOCATION OF OPTIONAL BLOWER ASSEMBLY
Page 8
(MA CVF714) FOR VENT FREE STOVE SERIES
TOWNSEND II FIREBOX (MODEL CVFB200LP,
CVFB200NAT) ONLY
Page 12
INSTALLATION OF VENT FREE STOVE SERIES CFVB200, C100BA
NOTE:
Place freestanding stove in desired
position in room. Be sure to maintain
clearances to combustibles as outlined
in Minimum Wall and Ceiling
Clearances on this page.
*NOTICE:Thisheateris
intended for use as supplemental
heat. Use this heater along with your
primary heating system. Do not install
this heater as your primary heat
source. Do not run ceiling fan while
heater is running. In the event of a
power outage, you can use this heater
as your primary heat source.
WARNING: A qualified service
person must install heater. Follow
all local codes.
WARNING: Never install the
heater
in a bedroom or bathroom
in a recreational vehicle
wherecurtains,furniture,
clothing or other flammable
objects are less than 48 inches
from the front, top or sides of
the heater
in high traffic areas
in windy or drafty areas
CAUTION: This heater creates
warm air currents. These currents
move heat to wall surfaces next to
heater. Installing heater next to vinyl
or cloth wall coverings or operating
heater where impurities (such as
tobacco smoke, aromatic candles,
cleaning fluids, oil or kerosene lamps,
etc.) in the air exist, may discolor
walls.
IMPORTANT: Vent-free heaters
add moisture to the air. Although this
is beneficial, installing heater in rooms
without enough ventilation air may
cause mildew to form from too much
moisture. See Air for Combustion andVentilation, pages 4 through 5.
Maintain adequate clearances for
accessibility for the purpose of
servicing and proper operation.
GAS CONNECTION
Check gas type. Use only the type of
gasindicated on the valve rating
plate. If the type of gas listed on the
plate is not your type of gas supply,
DO NOT INSTALL. Contact your
dealer for proper model.
Always use an external regulator for
all LP heaters to reduce the supply
tank pressure to a maximum of 13"
W.C. This is in addition to the
regulator furnished with the heater.
Warning: Connection directly to an
unregulated LP tank can cause an
explosion.
The normal gas connection is 3/8"
NPT made at the right rear side facing
stove. If a left side connection is
desired, the connecting pipe may be
routed under the rear of the burner
base to terminate at the right hand
side for connection to the inlet of the
valve.
NOTE: The connecting pipe must be
internally treated for protection from
sulfur compounds if copper tubing is
used for natural gas.
Test for leaks using a solution of soap
and water after completing the
connection. DO NOT USE OPEN
FLAME.
CLEARANCES TO
COMBUSTIBLES
(Vent-Free Operation Only)
WARNING:Maintainthe
minimum clearances. If you can,
provide greater clearances from
floor, ceiling and adjoining side and
back walls.
Carefully follow these instructions.
(See Figure 6). This stove is a
freestanding unit designed to set
directly on the floor. Do not place
stove directly on carpeting, vinyl tile
or any combustible material other
than wood. The stove must set on a
metal or wood panel extending the
full width and depth of the appliance.
IMPORTANT: You must maintain
minimum wall and ceiling clearances
during installation. The minimum
clearances are shown in Figure 6.
Measure from outermost point of stove
top.
Minimum Wall and Ceiling
Clearances (See Figure 6)
A. Clearancesfromoutermost
point of stovetop to any
combustible side wall should
not be less than 4 inches.
B. Clearancesfromoutermost
point of stovetop to any
combustible back wall should
not be lessthan 4 inches
(Includes Corner Installations).
C. Clearances from the stove top
to the ceiling should not be less
than 48 inches.
CEILING
FRONT VIEW
SIDE
WALL
TOP VIEW
SIDE
WALL
MINIMUM
CORNER VIEW
WALL
4" MINIMUM
NOTE: TYPICAL STOVE CABINET MODEL
FIGURE 6 - MINIMUM CLEARANCES TO
WALLS AND CEILING
4"
48" MINIMUM
BACK WALL
4" MINIMUM
WALL
4"
MINIMUM
4" MINIMUM
SIDE
WALL
SIDE
WALL
Page 9
Page 13
INSTALLATION
Continued
After positioning stove in desired
position, connect gas supply and
complete all pressure checks. (See
below Connecting To Gas Supply)
CAUTION: Use only new, black
iron or steel pipe. Internallytinned copper tubing may be used
in certain areas. Check your local
codes. Use pipe of 1/2" diameter
or greater to allow proper gas
volume to heater.
CONNECTING TO GAS
SUPPLY
WARNING: This appliance is
equippedwitha3/8"NPT
(NationalPipeThread)inlet
connectiontothepressure
regulator.
WARNING: A qualified service
person must connect heater to gas
supply. Follow all local codes.
Installation Items Needed
Before installing heater, make sure you
have the items listed below:
piping (check local codes)
sealant (resistant to LP gas)
equipment shutoff valve
tests gauge connection
sediment trap
tee joint
pipe wrench
A CSA/AGA design-certified equipment shutoff valve with 1/8" NPT tap is
an acceptable alternative to test gauge
connection. Purchase the optional CSA/
AGAdesign-certifiedequipment
shutoff valve from your dealer. See
Accessories, page 23.
The gas inlet connection for the stove
heater is located on the lower rear right
-hand side when viewed from the front
of the unit. Make sure gas log heater is
secured to the stove cavity assembly.
NOTE: TYPICAL STOVE CABINET MODEL
BACK VIEW
BACK OF
STOVE
UNIT
SIDE VIEW
GAS
INLET
FRONT OF
STOVE
UNIT
Approved Flexible Gas
Hose (if allowed by local
codes)
CONNEC-
TION
ACCESS
FIGURE 7 - GAS REGULATOR LOCATION AND
GAS LINE ACCESS INTO STOVE CABINET
CSA/AGA DesignCertified Equipment
Shutoff Valve With
1/8” NPT Tap
Installation must include an equipment
shutoff valve, union and plugged 1/8"
NPT tap. Locate NPT tap within reach
for test gauge hook up. NPT tap must
be upstream from heater
(See Figure 8).
IMPORTANT: Install equipment
shutoff valve in an accessible location.
The equipment shutoff valve is for
turning on or shutting off the gas to the
appliance.
Apply pipe joint sealant lightly to male
threads. This will prevent excess
sealant from going into pipe. Excess
sealant in pipe could result in clogged
heater valves.
CAUTION:Usepipejoint
sealant that is resistant to liquid
petroleum (LP) gas.
From Gas Meter
(5” W.C.**to 10.5”
W.C. Pressure)
WARNING:Neverconnect
heater to private (non-utility) gas
wells.Thisgasiscommonly
known as wellhead gas.
Gas Control
Tee Joint
Pipe Nipple
Cap
3” Minimum
Sediment
Trap
FIGURE 8 - GAS CONNECTION
Page 10
Page 14
INSTALLATION
Continued
We recommend that you install a
sediment trap in supply line. Locate
sediment trap where it is within reach
for cleaning. Install in piping system
between fuel supply and heater. Locate
sediment trap where trapped matter is
not likely to freeze. A sediment trap
traps moisture and contaminants. This
keeps them from going into heater
controls. If sediment trap is not
installed or is installed wrong, heater
may not run properly.
CAUTION: Avoid damage to
regulator.Holdgasregulator
with wrench when connecting it
to gas piping and/or fittings.
CHECKING GAS
CONNECTIONS
WARNING: Test all gas piping
and connections for leaks after
installing or servicing. Correct all
leaks at once.
WARNING: Never use an open
flame to check for a leak. Apply a
mixture of liquid soap and water
to all joints. Bubbles forming
show a leak. Correct all leaks at
once.
4.Check all joints of gas supply
piping system. Apply mixture of
liquid soap and water to gas
joints. Bubbles forming show a
leak.
5.Correct all leaks at once.
6.Reconnect heater and equipment
shutoff valve to gas supply.
Check reconnected fittings for
leaks.
Test Pressures Equal To or Less
Than 1/2 psi (3.5 kPa)
1.Close equipment shutoff valve
(See Figure 9).
2.Pressurize supply piping system
by either using compressed air or
opening main gas valve located
on or near gas meter.
3.Check all joints from gas meter
to equipment shutoff valve (See
Figure 10). Apply mixture of
liquid soap and water to gas
joints. Bubbles forming show a
leak.
4.Correct all leaks at once.
EQUIPMENT
SHUTOFF
VALVE
FIGURE 9 - EQUIPMENT SHUTOFF
VALVE
OPEN
CLOSED
Pressure Testing Heater Gas
Connections
1.Open equipment shutoff valve (See
Figure 9).
2.Open main gas valve located on or
near gas meter.
3.Make sure control knob of heater is in
the OFF position.
4.Check all joints from equipment
shutoff valve to control valve (See
Figure 10). Apply mixture of liquid
soap and water to gas joints. Bubbles
forming show a leak.
5.Correct all leaks at once.
6.Light heater (See Operating Heater,
pages 17 through 19). Check all other
internal joints for leaks.
7.Turn off heater (See To Turn Off Gas
to Appliance on pages 17 through
19).
InputMinimumMaximum
Rating22,40032,000
Type of GasLP/PropaneNatural
Manifold
Pressure10.0"wc3.5"wc
*Min. Inlet10.5"wc4.5"wc
Max. Inlet13.0"wc10.5"wc
*For purpose of input adjustment.
The appliance must be isolated from the gas
supply piping system by closing its equipment
shutoff valve during any pressure testing of the
gas supply piping system at test pressures equal
to or less than ½ psi (3.5 kPa).
Pressure Testing Gas Supply
Piping System
Test Pressures In Excess of 1/2 psi
(3.5 kPa)
1.Disconnect appliance with its
appliance main gas valve (control
valve) and equipment shutoff valve
from gas supply piping system.
Pressures in excess of 1/2 psi will
damage heater regulator.
2.Cap off open end of gas pipe
where equipment shutoff valve
was connected.
3.Pressurize supply piping system by
either using compressed air or
opening main gas valve located on
or near gas meter.
NOTE: TYPICAL STOVE CABINET MODEL
EQUIPMENT
SHUTOFF
VALVE
GAS METER
CONTROL VALVE LOCATION
FIGURE 10 - CHECKING GAS JOINTS
Page 11
Page 15
INSTALLATION OF
LOGS FOR
TOWNSEND II
MODEL CVFB200(LP)
MODEL CVFB200(NAT)
NOTE: FOR INSTALLATION
OF C100BA HEPPLEWHITE
LOGS SEE PAGE 14.
1.Remove log access door on top of
unit buy removing two (4)phillips
screws. Set access doorand screws
aside. (See Figure 11).
2.Carefully insert logs though opening in
top of unit as described on ( Page 13,
figure 13).
3.After placing logs on base, light heater
making sure no logs are contacting
flames, if so, then turn flame off.
Reposition any log contacting flames
so there is no contact with flame.
Relight and check once more. If
correct, turn flame off.
4.Place access door on top of unit and
secure with the two (4) phillips screws.
5.Place the top grate on unit as shown.
(See Figure 12).
FOUR PHILLIPS SCREWS
ACCESS DOOR
FIGURE 11 - REMOVING ACCESS DOOR
TOP GRATE
FOUR PHILLIPS SCREWS
GAS LOGS
FIGURE 12 - REPLACING ACCESS DOOR AND INSTALL TOP GRATE
Page 12
Page 16
POSITIONING OF LOGS FOR VENT FREE STOVE SERIES
CVFB200(LP), CVFB200(NAT) TOWNSEND II
“LOG #2 PLACEMENT”
1
FIGURE 13
5
3
2
WARNING: POSITIONING LOGS IS VERY CRITICAL (SEE FIGURE 13).
LOG PLACEMENT FOR LOG SET
1) Place rear log (flat faced) #1 on rear log support. The log has alignment notches on each corner.
2) Place ember strip (wrapped in cardboard box ) #2 on front log supports. Center from side to side.
3) Next place middle log (with ember burn out) #3 over front burner tube. The two ends are notched out on bottom to ensure
proper fitting over ends of burner.
4) Right top log is a “y” shaped log #4. The round stem lays in the notched out space on the right corner of rear log. There is a
pin on the middle log, and a hole on the flattened end of the top left log. Place hole over pin.
5) Place one end of the left top log #5 in notch of left corner on rear log and the other end of the left top log in notch on top
middle log.
4
NOTE: When operated for the first time, the logs may emit a “paper burning” smell. This smell will gradually diminish and
will be totally eliminated after the first few hours of operation.
Page 13
Page 17
INSTALLATION
OF LOGS FOR
HEPPLEWHITE
MODEL C100BA(LP)
MODEL C100BA(NAT)
1.Carefully insert logs though
opening in top of unit, placing logs
on base as described on ( Page 15,
figure 15).
2.After placing logs on base, light
heater making sure no logs are
contacting flames, if so, then turn
flame off. Reposition any log
contacting flames so there is no
contact with flame. Relight and
check once more. If correct, turn
flame off.
3.Place the top grate on unit as
shown. (See Figure 14).
TOP GRATE
FIGURE 14 - INSTALL TOP GREAT
Page 14
Page 18
POSITIONING OF LOGS FOR VENT FREE STOVE SERIES
C100BA(LP), C100BA(NAT) HEPPLEWHITE
4
5
1
3
2
“LOG #2 PLACEMENT”
1
FIGURE 15
5
3
2
4
WARNING: POSITIONING LOGS IS VERY CRITICAL (SEE FIGURE 15).
LOG PLACEMENT FOR LOG SET
1) Place rear log (flat faced) #1 on rear log support. The log has alignment notches on each corner.
2) Place ember strip (wrapped in cardboard box ) #2 on front log supports. Center from side to side.
3) Next place middle log (with ember burn out) #3 over front burner tube. The two ends are notched out on bottom to ensure
proper fitting over ends of burner.
4) Right top log is a “y” shaped log #4. The round stem lays in the notched out space on the right corner of rear log. There is a
pin on the middle log, and a hole on the flattened end of the top left log. Place hole over pin.
5) Place one end of the left top log #5 in notch of left corner on rear log and the other end of the left top log in notch on top
middle log.
NOTE: When operated for the first time, the logs may emit a “paper burning” smell. This smell will gradually diminish and
will be totally eliminated after the first few hours of operation.
Page 15
Page 19
Turn control knob clockwise
OPERATING HEATER
FOR YOUR SAFETY
READ BEFORE
LIGHTING
WARNING: If you do not follow
these instructions exactly, a fire
or explosion may result causing
property damage, personal injury
or loss of life.
A. This appliance has a pilot which
must be lit by hand. When lighting
the pilot, follow these instructions
exactly. If piezo fails, then light
the pilot using matches. Refer to
Manual Lighting Procedures.
B. BEFORE OPERATING smell all
around the appliance area for gas.
Be sure to smell next to the floor
because some gas is heavier than
air and will settle on the floor.
WHAT TO DO IF YOU SMELL
GAS
Do not try to light any
appliance.
Do not touch any electric
switch; do not use any phone
in your building.
Immediately call your gas
supplier from a neighbor’s
phone.Followthegas
supplier’s instructions.
If you cannot reach your gas
supplier,callthefire
department.
C. Use only your hand to push in or
turn the gas control knob. Never
use tools. If the knob will not push
in or turn by hand, don’t try to
repair it, call a qualified service
technician or gas supplier. Force or
attempted repair may result in a
fire or explosion.
D. Do not use this appliance if any
part has been underwater.
Immediately call a qualified
service technician to inspect the
appliance and to replace any part
of the control system and any gas
control which has been under
water.
LIGHTING INSTRUCTIONS
SIT-MILLIVOLT VALVE
1.STOP! Read Safety Information.
2.Make sure manual shutoff valve is
fully open. Set thermostat to lowest setting.
3.Turn off all electrical power to the
appliance (if applies).
4.Turn control knob clockwise
to the “OFF” position.
5.Wait (5) five minutes to clear out
any gas. Then smell for gas, including near the floor. If you smell
gas, STOP and follow “B” in the
safety information! If you don’t
smell gas, go to the next step.
6.Turn control knob counterclockwiseto the “PILOT” position. Press in control knob for (15)
fifteen seconds.
NOTE: You may be running this
heater for the first time after hooking
up the gas supply. If so, the control
knob may need to be pressed in for (30)
thirty seconds. This will allow air to
bleed from the gas system.
7.With control knob pressed in, push
down and release ignitor button.
This will light the pilot. If needed,
keep repeating this step until pilot
lights. Pilot is located between
middle and rear logs. If pilot does
not light with piezo, light by hand
with a match.
8.Keep control knob pressed in for
(1) one minute after lighting pilot.
After (1) one minute, release control knob.
*Please refer to page 25 for location
and picture of pilot.
FLAME ADJUSTMENT KNOB
IGNITOR BUTTON
FIGURE 16 - CONTROL KNOB AND IGNITOR
SELECTOR
SWITCH
BUTTON LOCATION
CONTROL KNOB
*If knob does not pop up when
released, stop and immediately call
your service technician or gas supplier.
* If the pilot will not stay lit after
several tries, turn the gas control knob
to the “OFF” position and call your
service technician or gas supplier.
NOTE: If pilot goes out, repeat steps 4
through 8. Wait (5) five minutes before
attempting to light pilot again.
9.Turn control knob counterclockwi s eto “ON” position.
10. Ifusing unit withoutwall
thermostat place “AUTO/OFF/
MANUAL”switch into the
manual position. If using wall
thermostat place “AUTO/OFF/
MANUAL” switch into the auto
position and place thermostat to a
setting higher than the room
temperature.
11. Turn all electrical power on to the
appliance (if applies).
12. Your heater is equipped with a
“HI/LO” control. Turn clockwise
for Low and counterclockwise for
High.
TO TURN OFF
GAS TO APPLIANCE
SHUTTING OFF UNIT
1.Turn control knob clockwise
to the “OFF” position.
2.Turn off all electric power to the
appliance if service is to be performed.
SHUTTING OFF BURNER ONLY
(Pilot stays lit.)
1.
to the “PILOT” position.
CAUTION
Hot while in operation. Do Not Touch.
Keep children, clothing, furniture,
gasoline, and other liquids having
flammable vapors away.
CAUTION
DONOTTRYTOADJUST
HEATING LEVELS BY USING THE
MANUAL SHUTOFF VALVE.
THERMOCOUPLE
PILOT BURNER
IGNITOR ELECTRODE
FIGURE 17 - O.D.S PILOT
ASSEMBLY SHOWN AS L.P.
GAS.
Page 16
Page 20
OPERATING HEATER
Continued
WARNING: Improper installation,
adjustment, alteration, service or
maintenancecan causeproperty
damage, personal injury or loss of
life. Installation and service must be
performed by a qualified installer,
service agency or the gas supplier.
IMPROPER: Always operate the
appliance at the completely “ON” or
the completely “OFF” positions. Never
use the heater at a setting between these
positions as this can result in improper
combustion and excessive carbon
monoxide emissions.
Keep burner and control compartment
clean.
MANUAL LIGHTING
PROCEDURE
1. Follow steps 1 through 5 under
Lighting Instructions, page 16.
2. Depress control knob and light
pilot with match and lighter rod.
3. Keep control knob pressed in for
30 seconds after lighting pilot.
After 30 seconds, release control
knob. Now follow steps 8 through
11, page 16.
PILOT FLAME PATTERN
(MILLIVOLT)
Figure 18 shows a correct pilot flame
pattern. Figure 19 shows an incorrect
pilot flame pattern. The incorrect pilot
flame is not heating the thermocouple. This will cause the thermocouple to cool. When the thermocouple cools, the heater will shut
down.
If pilot flame pattern is incorrect, as
shown in Figure 18:
Turn heater off (see To turn Off
Gas to Appliance, page 16)
See Troubleshooting, pages 20
through 22.
THERMOPILE/
FIGURE 18 - CORRECT FLAME PATTERN L.P. OR NAT. GAS
OPTIONAL REMOTE
CONTROL
NOTE: All remote control accessories
must be purchased separately (see
Accessories). Follow instructions
included with the remote control.
NOTICE: You must light the pilot
before using the remote control unit.
See Lighting Instructions on page 16.
THERMOPILE/
FIGURE 19 - INCORRECT PILOT FLAME PATTERN L.P. OR NAT. GAS
Page 17
Page 21
FRONTACCESS TO
(SIT) MILLIVOLT
VALVE
When performing pressure checks or wiring
accessories such as remote control or wall
mounting thermostats it will be necessary to
access the front of the valve body. (See Figure 20).
To access the front of the valve body, you
must remove the face plate from the control
bracket. To remove the face plate you will
need to remove the two (2) Phillip head
screws which attach it. After removing the
screws, pull the face plate back from the
unit. This will give you the access you need.
When finished reattach the face plate to the
control bracket with the screws youremoved before operating the unit.
CAUTION
If unit has been in operation, allow the
unit time to cool before touching. Failure
to do so may result in personal injury.
CONTROL BRACKET
SCREWS
(SIT) MILLIVOLT VALVE WITH FACE PLATE ON
FACE PLATE
NOTE: To ensure proper
connection of switch refer
to pages 26 and 27. Make
sure the proper wires are
used for thermostat and
remotecontrolconnections, if not installed correctlythe unit will not
operate.
(SIT MILLIVOLT VALVE WITHOUT FACE PLATE)
FIGURE 20
Page 18
Page 22
INSPECTING
AND CLEANING
MAINTENANCE
WARNING: Turn off heater and
let cool before cleaning.
CAUTION:Youmustkeep
controlareas,burnerand
circulating air passageways of
heater clean. Inspect these areas
of heater before each use. Have
heater inspectedyearly bya
qualified service person. Heater
may need more frequent cleaning
duetoexcessivelintfrom
carpeting, pet hair and bedding
material, etc.
CLEANING BURNER
INJECTOR HOLDER AND
PILOT AIR INLET HOLE
The air shutter slots allow the proper
amount of air to mix with the gas. This
provides a clean burning flame. Keep
these slots clear of dust, dirt, lint and
pet hair. Clean these air inlet slots prior
to each heating season. Blocked air
slots will create soot. We recommend
that you clean the unit every three
months during operation and have
heater inspected yearly by a qualified
service person.
We also recommend that you keep the
burner tube and pilot assembly clean
and free of dust and dirt. To clean these
parts we recommend using compressed
air no greater than 30 PSI. Your local
computer store, hardware store or home
center may carry compressed air in a
can. You can use a vacuum cleaner in
the blow position. If using compressed
air in acan, please follow the
directions on can. If you don’t follow
directions on can, you could damage
the pilot assembly. NOTE:For
Townsend II See (Figure 11, page
12). For Hepplewhite See (Figure 14,
page 14). Removing access door and
top grates of your stove will make
cleaning easier.
1.Shut off unit, including pilot.
Allow unit to cool for at least thirty
minutes.
2.Inspect burner, pilot and slots in
air shutter for dust and dirt.
3.Using Phillips head driver loosen
set screw on air shutter and rotate
shutter toward rear of unit. NOTE:
Before rotating shutter mark the
position of shutter so you can
move it back to the correct position
after cleaning.
4. Opening the shutter as in step 3,
allows you to inspect the orifice.
After cleaning the area adjust air
shutter to the original position.
5. Blow air through the slots and
holes in the burner.
6. Blow air into the primary air holes
on the injector holder.
7. In case any large clumps of dust
have now been pushed into the burner
repeat steps 3 and 4.
Clean the pilot assembly also. A yellow tip on the pilot flame indicates
dust and dirt in the pilot assembly.
There is a small pilot air inlet hole
about two inches from where the pilot
flame comes out of the pilot assembly
(See Figure 22). With the unit off,
lightly blow air through the air inlet
hole. You may blow through a drinking straw if compressed air is not
available.
BURNER SLOTS
AIR SHUTTER
AIR SHUTTER SLOTS
FIGURE 21 - BURNER/ AIR SHUTTER
FIGURE 22 - PILOT ASSEMBLY
BURNER TUBE
PHILLIPS SCREW
O.D.S PILOT BURNER
LOGS
If you remove logs for cleaning,
refer to Installing Gas Logs.
Townsend II
13). For Hepplewhite (Figure 15,
page 15), to properly replace logs.
(Figure 13, page
For
MAIN BURNER
Periodically inspect all burner flame
ports with the heater running. All
slotted burner flame ports should be
open with flame present. Some burner
flame ports may become blocked by
debris or rust, with no flame present. If
so, turn off heater and let cool. Either
remove blockage or replace burner.
Blocked burner flame holes will create
soot.
PILOT AIR HOLE
Page 19
Page 23
Replace battery in transmitter and
TROUBLESHOOTING
NOTE: All troubleshooting items are
listed in order of operation.
OBSERVED PROBLEM
When ignitor button is pressed, there is
no spark at ODS/pilot
WARNING: Turn off heater and
let cool before servicing. Only a
qualified servicepersonshould
service and repair heater.
POSSIBLE CAUSE
1.Ignitor electrode not connected to
ignitor cable
2.Ignitor cable pinched or wet
3.Broken ignitor cable
4.Bad piezo ignitor
5.Ignitor electrode broken
6.Ignitorelectrodepositioned
wrong
CAUTION:Never use a wire,
needle, or similar object to clean
ODS/pilot. This can damage ODS/
pilot unit.
REMEDY
1.Reconnect ignitor cable
2.Free ignitor cable if pinched by
any metal or tubing. Keep ignitor
cable dry
3.Replace ignitor cable
4.Replace piezo ignitor
5.Replace piezo ignitor
6.Replace piezo ignitor
When ignitor button is pressed, there is
spark at ODS/pilot but no ignition
ODS/pilot lights but flame goes out
when control knob is released
3.Control knob not pressed in while
in PILOT position
4.Air in gas lines when installed
5.ODS/pilot is clogged
6.Gas regulator setting is not
correct
1.Control knob not fully pressed in
2.Control knob not pressed in long
enough
3.Equipment shutoff valve not fully
open
4.Pilotflamenottouching
thermocouple,which allows
thermocouple to cool, causing
pilot flame to go out. This
problem could be caused by one
or both of the following:
A. Low gas pressure
B. Dirty or partially clogged
1.Turn on gas supply or open
equipment shutoff valve
2.Turn control knob to PILOT
position
3.Press in control knob while in
PILOT position
4.Continue holding down control
knob. Repeat igniting operation
until air is removed
5.Clean ODS/pilot (see Cleaningand Maintenance, page 19) or
replace ODS/pilot assembly
6.Replace gas control
1.Press in control knob fully
2.After ODS/pilot lights, keep control knob pressed in 30 seconds
3.Fully open equipment shutoff
valve
4.Contact local natural gas company
CleanODS/pilot(see
Cleaning and Maintenance,
page 19) or replace ODS/
pilot assembly
5.Hand tighten until snug, then
tighten 1/4 turn more
6.Replace thermocouple
7.Replace control valve
1.Clean burner (see Cleaning andMaintenance, page 19) or replace
burner orifice
2.Contact local gas company
3.Replace burner orifice
4.Reconnect leads
5.
receiver
Page 20
Page 24
TROUBLESHOOTING
Continued
OBSERVED PROBLEM
Delayed ignition burner
POSSIBLE CAUSE
1.Manifold pressure is too low
2.Burner orifice clogged
REMEDY
1.Contact local gas company
2.Clean burner (see Cleaning andMaintenance, page 19) or replace
burner orifice
Burner backfiring during combustion
Slight smoke or odor during initial operation
Moisture/condensation noticed on windows
Heater produces a whistling noise when
burner is lit
Dark residue on logs or inside of fireplace
1.Burner orifice is clogged or
damaged
2.Damaged burner
3.Gas regulator defective
1.Not enough air
2.Gas regulator defective
3.Residuesfrom manufacturing
processes and logs curing
1.Not enough combustion/ventila–
tion air
1.Turning control knob to HI
position when burner is cold
2.Air in gas line
3.Airpassageways on heater
blocked
4.Dirty or partially clogged burner
orifice
1.Improper log placement
2.Drafts or other air currents
affecting flame pattern
3.Air holes at burner inlet blocked
4.Burner flame holes blocked
1.Clean burner (see Cleaning andMaintenance, page 19) or replace
burner orifices
2.Replace damaged burner
3.Replace gas control
1.Check burner for dirt and debris.
If found, clean burner (see
Cleaning and Maintenance, page
19)
2.Replace gas control
3.Problem will stop after a few
hours of operation
1.Refer to Air for Combustion andVentilation requirements (page 4)
1.Turn control knob to LO position
and let warm up for a minute.
2.Operate burner until air is
removed from line. Have gas line
checked by local gas company
3.Observe minimum installation
clearances (see page 9)
4.Clean burner (see Cleaning andMaintenance, page 19) or replace
burner orifice
1.Properly locate logs (see Installing
Gas Logs, for TOWNSENDII see
page 13, for HEPPLWITE see
page 13)
2.Eliminate source of drafts around
heater
3.Clean out air holes at burner inlet.
Periodically repeat as needed
4.
Remove blockage or replace burner
White powder residue forming within burner
box or on adjacent walls or furniture
1.When heated, vapors from furniture polish, wax, carpet cleaners,
etc. turn into white powder
residue
Page 21
1.Turn heater off when using
furniture polish, wax, carpet
cleaners or similar products
Page 25
TROUBLESHOOTING
Continued
WARNING: If you smell gas
Shut off gas supply.
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in
your building.
Immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
IMPORTANT: Operating heater where impurities in air exist may create
odors. Cleaning supplies, paint, paint remover, cigarette smoke, cements
and glues, new carpet or textiles, etc., create fumes. These fumes may mix
with combustion air and create odors. These odors will disappear over time.
OBSERVED PROBLEM
Heater produces a clicking/ticking noise
just after burner is lit or shut off
Heater produces unwanted odors
Heater shuts off in use (ODS operates)
Gas odor even when control knob is in
OFF position
Gas odor during combustion
POSSIBLE CAUSE
1.Metal expanding while heating or
contracting while cooling
1.Heater burning vapors from paint,
hair spray, glues, cleaners chemicals,
new carpet, etc. (see IMPORTANT
statement above)
2.Gas leak. See WARNING
statement at top of page
1.Not enough fresh air is available
2.Low line pressure
3.ODS/pilot is partially clogged
1.Gas leak. See WARNING
statement at top of page
2.Control valve defective
1.Foreign matter between control
valve and burner
2.Gas leak. See WARNING
statement at top of page
REMEDY
1.This is common with most heaters.
If noise is excessive, contact qualified service person
1.Open window and ventilate room.
Stop using odor causing products
while heater is running
2.Locate and correct all leaks (see
Checking Gas Connections, page
11)
1.Open window and/or door for
ventilation
2.Contact local gas company
3.Clean ODS/pilot (see Cleaningand Maintenance, page 19)
1.Locate and correct all leaks (see
Checking Gas Connections, page
10)
2.Replace control valve
1.Take apart gas tubing and remove
foreign matter
2.Locate and correct all leaks (see
Checking Gas Connections, page
10)
Page 22
Page 26
(SIT) MILLIVOLT VALVENATURAL GAS
PARTS LIST
FOR MODELS CVFB200(LP), CVFB200(NAT) AND
C100BA(LP), C100BA(NAT)
MILLIVOLT (SIT)
KEY #PART #DESCRIPTION #
1PE 8204CPILOT ASSEMBLY NATURAL GAS
PE 8404CPILOT ASSEMBLY L.P.
2PO 10-2121-12FLEXIBLE SUPPLY LINE
3PE 820638
PE 820636(SIT) MILLIVOLT VALVE L.P.
4PE 916188ON/OFF KNOB EXTENSION
5PE 916189HI/LO KNOB EXTENSION
6PE RC211RBAUTO/OFF/MANUAL
7PE 124461PIEZO STRIKER
8POT6-066" MANIFOLD SUPPLY LINE
8APOT6-1212" MANIFOLD SUPPLY LINE
9PO H- BURN00118" H-BURNER
10PO 64MVORFL.P. FRONT ORIFICE C100BA-CVFB200
PO 54MVORFL.P. REAR ORIFICE C100BA-CVFB200
PO 54MVORFNAT. FRONT ORIFICE C100BA-CVFB200
PO 44MVORFNAT. REAR ORIFICE C100BA-CVFB200
24
Page 23
Page 27
REPLACEMENT PARTS
OPTIONAL BLOWER ASSEMBLY (MA CVF714)
FOR USE WITH CVFB200
PART NO.DESCRIPTIONQTY.
PH 101612TEK#10-16 x 1/2" Self tapping Screws ( For Mounting Blower Assembly To Fire Box )4
PE A2-40-01WB Motor1
PE 400132Therm o disc1
PE 400240Power Cord1
PE 400320Strain Relief1
PE RA911VBON/OFF Switch1
Page 24
Page 28
ACCESSORIES
Purchase these heater accessories from
your local dealer. If they can not supply these accessories, call our Parts
Department at 1-828-765-6144 for referral information. You can also write
to the address listed on the back page
of this manual.
RECEIVER AND HAND-HELD
REMOTE CONTROL KIT
PART# PO FDC-504
For remote-ready models. Allows the
gas log heater to be turned on and off
by using a hand-held remote control.
WALL THERMOSTAT
PART# PE 400142
The desired comfort setting can be selected on the wall thermostat and the
log heater will automatically cycle
from pilot to the heat setting selected.
SERVICE HINTS
When Gas Pressure Is Too Low
Pilot will not stay lit
Burnerswillhave delayed
ignition
Heater will not produce specified
heat
When Gas Quality Is Bad
Pilot will not stay lit
Burners will produce flames and
soot
Heater will backfire when lit
You may feel your gas pressure is too
low or gas quality is bad. If so,
contact your local gas supplier.
REPLACEMENT
PARTS
NOTE: Use only original replacement
parts. This will protect your warranty
coverage for parts replaced under
warranty.
Page 25
Page 29
VENT FREE STOVE SERIES
CVFB200(LP), CVFB200(NAT) TOWNSEND II
WIRING DIAGRAM AND REMOTE OR WALL
THERMOSTAT INSTALLATION
THERMOPILE-GENERATOR
PILOT ASSEMBLY
FACTORY WIRING
AUTO/OFF/MANUAL
K
K
C
C
A
A
L
L
B
B
CONNECT THE TWO (2) WIRES FROM
REMOTE RECEIVER OR WALL
THERMOSTAT TO THE TWO (2) PREWIRED
AND MARKED REMOTE RECEIVER OR
WALL THERMOSTAT FEMALE TERMINALS
UNDERNEATH FRONT OF UNIT.
DATEREV.BY
SWITCH ON BACK OF UNIT
REDWIRE
FOROPTIONALREMOTECONTROL
ORWALLTHERMOSTAT
CUTANDADDTHERMOSTATWIRE
WITHWIRENUTS(NOTPROVIDED)
TOBOTHENDSOFREDWIRES.
SCREWTERMINALS
DISCRIPTION
NEWRELEASEM.B.DATE
APRVD
TERMINALS
REAR TERMINALS
SIDE VIEW OF VALVE
Page 26
FRONT TERMINALS
SWITCH
Page 30
VENT FREE STOVE SERIES
C100BA(LP), C100BA(NAT) HEPPLEWHITE
WIRING DIAGRAM AND REMOTE OR WALL
THERMOSTAT INSTALLATION
THERMOPILE-GENERATOR
PILOT ASSEMBLY
FACTORY WIRING
AUTO/OFF/MANUAL
SWITCH UNDERNEATH FRONT OF UNIT
K
K
C
C
A
A
L
L
B
B
CONNECT THE TWO (2) WIRES FROM
REMOTE RECEIVER OR WALL
THERMOSTAT TO THE TWO (2) PREWIRED
AND MARKED REMOTE RECEIVER OR
WALL THERMOSTAT FEMALE TERMINALS
UNDERNEATH FRONT OF UNIT.
DATEREV.BY
REDWIRE
FOROPTIONALREMOTECONTROL
ORWALLTHERMOSTAT
CUTANDADDTHERMOSTATWIRE
WITHWIRENUTS(NOTPROVIDED)
TOBOTHENDSOFREDWIRES.
SCREWTERMINALS
DISCRIPTION
NEWRELEASEM.B.DATE
APRVD
REAR TERMINALS
SIDE VIEW OF VALVE
Page 27
FRONT TERMINALS
SWITCHTERMINALS
Page 31
LIMITED WARRANTY
VENT-FREE NATURAL OR L.P. (LIQUID PROPANE)
GAS LOG HEATERS AND STOVE CHASSIS
WARRANTY INFORMATION
New Buck Corporation warrants this product to be free from defects in materials and components for two (2) year from the date
of first purchase provided that the product has been properly installed, operated and maintained in accordance with all applicable
instructions. To make a claim under this warranty the Bill of Sale or Cancelled check must be presented.
This warranty is extended only to the original retail purchaser. This warranty covers the cost of part(s) required to restore this
heater to proper operating condition and an allowance for labor when provided by a New Buck Corp. dealer. Warranty part (s)
MUST be obtained through authorized dealers of this product and / or New Buck Corp. who will provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty. The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit.
This warranty does not apply to parts that are not in original condition because of normal wear and tear, or parts that fail or become
damaged as a result of misuse, accidents, lack of proper maintenance or defects caused by improper installation. Travel diagnostic
cost, labor, transportation and any and all such other costs related to repairing a defective heater will be the responsibility of the
owner.
For a period of one (1) year from the date of purchase, New Buck Corp. will replace or repair at its option: electrical motor, wiring,
switches and optional accessories.
TO THE FULL EXTENT ALLOWED BY LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT:
THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND LIMITS THE DURATION OF ANY AND ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO TWO (2) YEARS ON ALL COMPONENTS FROM THE DATE OF PURCHASE:
AND NEW BUCK CORPORATION LIABILITY IS HEREBY LIMITED TO THE PURCHASE PRICE OF THE PRODUCT
AND NEW BUCK CORPORATION SHALL NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER INCLUDING
INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation of incidental or consequential damages, so the above limitation on implied warranties or exclusion or limitation on damages may not apply to you. This
warranty gives you specific legal rights and you may also have other rights that vary from state to state.
For information about this warranty write: NEW BUCK CORPORATION
P.O. BOX 69
SPRUCE PINE, NC 28777
www. buckstovecorp.com
Page 28
Page 32
Page 33
OWNER REGISTRATION
The attached owner registration card must be completed in its entirety and mailed within 30
days from date of installation in order for warranty coverage to begin to:
New Buck Corporation
P.O. Box 69
Spruce Pine, NC 28777
PLEASE NOTE:Owner Registration Card must contain Authorized Buck Stove Dealer
Number and Certified Installer’s number (if applicable) for warranty coverage to begin.
MODEL #: _________________________________________________
SERIAL #: _________________________________________________
DATE OF PURCHASE: ______________________________________
DATE OF INSTALLATION:___________________________________
INSTALLER’S NAME:_______________________________________
PURCHASED FROM: _______________________________________
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.