IF THIS HEATER IS NOT PROPERLY INSTALLED, A HOUSE FIRE MAY RESULT.
FOR YOUR SAFETY, FOLLOW THE INSTALLATION INSTRUCTIONS. CONTACT
THE AUTHORITY HAVING JURISDICTION (SUCH AS MUNICIPAL BUILDING
DEPARTMENT, FIRE DEPARTMENT, FIRE PREVENTION BUREAU, etc.)
CONSULT BEFORE INSTALLATION TO DETERMINE THE NEED TO OBTAIN A
PERMIT. KEEP THESE INSTRUCTIONS FOR FUTURE USE.
TESTED AND LISTED BY: ITS/WARNOCK HERSEY, MIDDLETON, WI
MANUFACTURED BY NEW BUCK CORPORATION
200 ETHAN ALLEN DRIVE
P.O. BOX 69
SPRUCE PINE, N.C. 28777
www.buckstove.com
JUN 2013
Page 2
Page 3
TABLE OF CONTENTS
Important Instructions ......................................................................................................................... 2
THIS UNIT GENERATES A LOT OF HEAT, SO TREAT UNIT WITH CARE. HOT
WHILE IN OPERATION. KEEP CHILDREN, CLOTHING AND FURNITURE AWAY.
CONTACT MAY CAUSE SKIN BURNS. DO NOT USE CHEMICALS OR FLUIDS TO
START FIRE. DO NOT BURN GARBAGE OR FLAMMABLE FLUIDS. DO NOT
CONNECT TO ANY DISTRIBUTION DUCT OR SYSTEM. READ ALL INSTRUCTIONS
BEFORE INSTALLING AND USING APPLIANCE. FAILURE TO FOLLOW
INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE, BODILY INJURY OR EVEN
DEATH. SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCES.
The New Buck Corp. non-catalytic systems have been tested by ITS, Warnock Hersey to
ANSI/UL Standards: UL 1482-2000: UL/ULC S627.
Install and operate your units according to instructions provided in this manual. Local
building codes may apply; therefore, contact your local building inspector or fire marshal
for necessary installation requirements and permits which may go beyond these instructions.
The authority having jurisdiction should be consulted before installation to determine the
need to obtain a permit.
MODEL 21 ELITE
If appliance is installed in mobile homes:
WARNING DO NOT INSTALL IN SLEEPING ROOMS.
CAUTION: The Structural Integrity Of the Mobile Home Floor, Wall And Ceiling/Roof
Must Be Maintained.
For space heaters installed in mobile homes, the necessity for attaching the space heater to
the structure. See (Page 16, Statement 16, Figure 18 ).
Install in accordance with 24 CFR, Part 3280 (HUD).
NOTE: When burning any unit or appliance that combusts fuel for heat, such as coal, oil,
wood or natural and (L.P.) liquid petroleum gas. We highly recommend the use of
smoke and carbon monoxide detectors in your home.
Incase of room air starvation, example; if there are exhaust fans running in the house for
kitchen, bathrooms, ect., enough negative pressure could be created in the house to cause
back drafting of smoke from the stove, an outside air kit may have to be used. For outside
air installation see (Page 15).
CAUTION
DO NOT USE MORE THAN ONE STOVE TO A CHIMNEY. DO NOT USE A FLUE
INTENDED FOR A GAS APPLIANCE.
Page 2
Page 5
CAUTION
YOUR CHIMNEY OR FLUE MUST BE CORRECTLY SIZED. A CHIMNEY OR FLUE
THAT IS TOO SMALL OR LARGE IN DIAMETER, OR TOO SHORT, CAN CAUSE
YOUR STOVE TO SPILL SMOKE WHEN DOOR IS OPENED.
SECTION I
INTRODUCTION
Your new MODEL 21 ELITE is a non-catalytic unit designed to meet the most stringent
emissions standards without the use of a catalytic combustor. This effect is achieved through
the use of secondary air which is mixed with primary air in the units firebox.
For peak performance, we suggest the use of hard seasoned natural wood, loading wood from
front to rear.
NOTE: Soft woods such as pine, create more creosote, clogging of chimney and produce a less efficient
burn performance.
You should not burn trash or garbage, artificial or paper logs, gift wrapping, treated or painted
wood or any type of coal.
DO NOT USE CHEMICALS OR FLUIDS TO START FIRE.
DO NOT BURN GARBAGE OR FLAMMABLE FLUIDS.
The primary air, which is controlled by the user, burns the wood. Secondary air is admitted into
the firebox through secondary air tubes at the top of the firebox. This secondary air burns the
impurities in the smoke released from the initial wood burning. The temperature necessary for
this combustion is maintained through the firebrick refractory. If any more technical
information is necessary, contact your local dealer.
Page 3
Page 6
RESIDENTIAL / MOBILE FREESTANDING
SECTION II
INSTALLATION AND CLEARANCES
Select an installation location that will give the best airflow from the front of the heater to
the remainder of the home
PREPARING THE STOVE FOR INSTALLATION
1. Inspect unit for any obvious physical damage.
2. Plug power cord into a 115V AC outlet to test motor and fan. Do not run cord under unit or
in high traffic areas.
3. Check primary air draft control to ensure that it slides freely.
4. Remove any items from within firebox.
AIR CONTROL
Figure 1
Chimney
This model is designed for connection to any listed 2100º UL103 HT chimneys and parts.
This room heater must be converted to a chimney complying with the requirements for Type
HT chimneys in the Standard for chimneys, Factory-Built, Residential, Type and
Building Heating Appliance, UL 103, or liner.
Page 4
Page 7
Floor Protection:
Floor protection must be 3/8” minimum thickness non-combustible material or equivalent.
How to use alternate materials and how to calculate equivalent thickness:
An easy means of determining if a proposed alternate floor protector meets requirements listed
in the appliance manual is to follow this procedure:
1. Convert specification to R-value:
R-value is given—no conversion is needed.
K-factor is given with a required thickness (T) in inches:
C-factor is given: R=1/C
2. Determine the R-value of the proposed alternate floor protector.
Use the formula in step (1) to convert values not expressed as “R”For multiple layers, add R-values of each layer to determine the overall R-value.
3. If the overall R-value of the system is grater than the R-value of the specified floor protector, the alternate is acceptable.
Example:
The specified floor protector should be 3/4” thick material with a K-factor of 0.84.
The proposed alternate is 4” brick with a C-factor of 1.25 over 1/8” mineral board with a
K-factor of 0.29.
Step (a): Use formula above to convert specification to R-value. R= 1/K x T = 1/0.84 x .75 =
0.893
Step (b): Calculate R of proposed system. 4” brick of C=1.25, therefore Rbrick = 1/C = 1/1.25
=0.80 1/8” mineral board of K = 0.29, therefore Rmin.bd. =1/029 x0.125 = 0.431
Step (c): Compare proposed system R of 1.231 to specified R of 0.893. Since proposed
system R is greater than required , the system is acceptable.
Definitions:
Thermal conductance = C =
Btu
(hr)(ft²)(°F) (m²)(°K)
=
W
Thermal conductance = K =
(Btu)(inch)
(hr)(ft²)(°F) (m)(°K)(hr)(ft)(°F)
=
W
=
(Btu)
Thermal conductance = R =
(ft²)(hr)(°F)
BtuW
(m²)(°K)
=
Install in accordance with 24 CFR, Part 3280 (HUD).
Page 5
Page 8
PREPARING THE ROOM HEATER LOCATION
1. Select an installation location that will give the best airflow from the front of heater to
remainder of home.
2. Place protective floor pad in position.
3. Place unit on pad making sure the minimum clearance specifications are met.
4. If connecting to an existing masonry flue, first ensure that the flue conforms to the NFPA-211 Code and/or consult your local code for proper procedures.
NOTE: This model is designed for connection to: any Listed 2100° UL 103 HT. TYP chimney
also any Listed UL DVL Close Clearance pipe or single wall minimum 24 ga. blued or black
pipe. Follow pipe manufacturers instructions carefully.
CHIMNEY
This room heater must be converted to a chimney complying with the requirements for Type HT
chimneys in the Standard for Chimneys, Factory-Built, Residential, Type and Building Heating
Appliance, UL 103.
The chimney size should not be less than or more than the cross-section area of the flue collar.
These methods should be employed when connecting the room heater to a masonry chimney,
factory-built chimney or masonry fireplace, when the connection from the room heater to a
masonry chimney is made through a combustible wall.
A chimney connector shall not pass through an attic, roof space, closet, floor, ceiling or similar
concealed space. Where passage through a wall or partition of combustible construction is
desired, the installation shall conform with CAN/CSA-B365.
Installing a thimble through combustible wall
Chimney Connector Systems and Clearances from Combustible Walls for
Residential Heating Appliances
A) Minimum 3.5-in thick brick
masonry all framed into
combustible wall with a minimum
of 12-in brick separation from clay
liner to combustibles. The fireclay
liner shall run from outer surface of
brick wall to, but not beyond, the
inner surface of chimney flue liner
and shall be firmly cemented in
place.
B) Solid-insulated factory-built
chimney length of the same inside
diameter as chimney connector
and having 1-in. or more of
insulation with a minimum 9-in. air
space between outer wall of
chimney length and combustibles
Page 6
Page 9
C) Sheet steel chimney connector,
minimum 24 gauge in thickness, with a
ventilated thimble, minimum 24 gauge in
thickness, having two 1-in. air channels,
separated from combustibles. by a
minimum of 6-in. of fiber insulation.
Opening shall be covered, and thimble
supported with a sheet steel support,
minimum 24 gauge in thickness.
D) Solid insulated, listed factory-built
chimney length with an inside diameter 2
-in. larger than chimney connector and
having 1-in. or more of insulation,
serving as a pass-through for a single
wall sheet steel chimney connector of
minimum 24 gauge thickness, with a
minimum 2-in. air space between outer
wall of chimney section and
combustibles. Minimum length of
chimney section shall be 12-in. chimney
section spaced 1-in. away from
connector
CAUTION:Certain installation types require the use of certain chimney types.
Please follow these instructions exactly.
.
HOW TO LOCATE CHIMNEY EXIT AND INSTALL
Residential Installation
A. Vertical Exit using (6" Single wall minimum 24 ga. blued or black pipe and any
Listed 2100° UL 103 HT. Chimney).
Without optional close clearance shield and pipe shield.
NOTE: For minimum clearances (See Page 8, Figure 4).
1. Suspend a plumb bob from ceiling above unit so that weight is hanging in center of flue
exit. (A small weight on a string will serve as a plumb bob). Mark ceiling where string
is suspended to locate center of chimney.
2. After locating center of hole, install ceiling support box, chimney or chimney connector,
flashing and rain cap, per chimney manufacturers instructions and local building codes
for installation through combustible walls or ceilings.
3. Now connect stove and ceiling support box using 6" Single Wall minimum 24 ga. blued
or black pipe (DO NOT USE GALVANIZED PIPE). Connect each section so crimped
end faces downward and secure each section to each other using at least three (3) sheet
metal screws or rivets. Single wall pipe is to be connected with (3) sheet metal screws
or rivets to connector collar on heater.
(See Page 8, Figure 5).
Page 7
Page 10
C
C
BACKWALL
A
E
B
F
C
C
D
G
A. Vertical exit using
pipe
and any listed 2100° UL 103 HT. TYPE Chimney).
(6" Single wall minimum 24 ga. blued or black
Without optional pipe shield.
Model 21 Elite minimum clearance to combustibles.
SIDE WALL
A B C D E F G
25” 13" 13" 15.5" 8" 6" 16"
NOTE: All clearances are to combustibles without pipe shield, using 6" single wall minimum 24 ga.
blued or black pipe and minimum floor protector. The clearances above may be reduced. Follow
NFPA-211 codes if available or follow instructions on (Pages 11, and 12).
Figure 4.
BACK WALL
B
PROTECTOR PAD
E
A
C
MODEL 21 ELITE
D
Figure 5.
CONTEMPORARY CAP
F
LISTED 2100° UL 103 HT
TYP. CHIMNEY
DONOTOBSTRUCT
CAULK
STORM COLLAR
G
RADIATION SHIELD
LISTED 2100° UL 103 HT TYP.
INSTALLATION
CEILING
SIDE
WALL
C
FLASHING
CEILING SUPPORT
SINGLE WALL
CONNECTOR PIPE
Pipe Shield
Page 8
Page 11
HOW TO LOCATE CHIMNEY EXIT AND INSTALL
Residential Installation
B. Vertical Wall Exit using (6" Single Wall minimum 24 ga. blued or black pipe with el-
bow and any Listed 2100° UL HT chimney and Listed 2100° UL HT. T-Box assembly).
Without optional close clearance shields and pipe shield.
NOTE: For minimum clearances (See Page 10, Figure 6).
1. Mark plumb line on wall directly behind center of heater.
(See Page 10, Figure 6).
NOTE: When using 6" Single Wall minimum 24ga. blued or black pipe.
Maintain 18" minimum clearances between pipe and ceiling.
2. Place vertical portion of heater pipe and elbow in position and project a point onto
plumb line level with center of elbow.
3. Measure up so there will be at least 1/4" rise per foot of horizontal connector pipe,
maintaining clearances to the ceiling as noted in page 9, figure 5. This will give you
center of hole for chimney penetration.
4. After locating center of penetration, install the tee-box and chimney, as per the chimney
manufacturers specifications.
5. Connect chimney collar to tee-box using 6" Single Wall minimum 24 ga. blued or
black pipe. (DO NOT USE GALVANIZED PIPE). Connect each section so crimped
end faces downward and secure each section to each other using three (3) sheet metal
screws or rivets. Single wall pipe is to be connected with three (3) sheet metal screws
rivets to connector collar on heater.
(See Page 10, Figure 7).
Page 9
Page 12
B. Vertical wall exit using
C
C
BACKWALL
A
E
B
F
C
C
D
G
black pipe with elbow
(6" Single wall minimum 24 ga. blued or
and any listed 2100° UL 103 HT.
TYPE Chimney and
Model 21 Elite minimum clearance to combustibles.
BACK WALL
SIDE WALL
E
PROTECTOR PAD
A
H
B
D
A B C D E F G
MODEL 21 ELITE 25” 13" 13" 15.5" 8" 6” 16"
Listed 2100° UL HT. T-Box assembly
With optional pipe shield.
Figure 6.
F
G
).
C
C
NOTE: All clearances are to combustibles with pipe shield, 6" Single Wall minimum 24 ga.
blued or black pipe with elbow and minimum floor protector. Clearances above may be
reduced. Follow NFPA-211 codes if available or follow instructions on (Pages 13, and 14).
LISTED 2100° UL 103 HT TYP.
NOTE:
CEILING
Maintain 18"Minimum Clearance
SINGLE WALL
CONNECTOR
CENTER LINE
OF ELBOW
MARK PLUMB
LINE ON WALL
Figure 7.
ELBOW PIPE
Pipe Shield
INSTALLATION INSTRUCTION
IN
SIDE
WALL
WALL
PASS-THROUGH
CONNECTOR
CHIMNEY REFER TO
MANUFACTURER’S
LISTED 2100° UL 103 HT
TYP. CHIMNEY T-BOX
ASSEMBLY REFER TO
MANUFACTURER’S
INSTALLATION
INSTRUCTION
Page 10
Page 13
HOW TO LOCATE CHIMNEY EXIT AND INSTALL
Residential and Mobile Home Installation
C. Vertical Exit using (6" DVL Close Clearance pipe and any Listed 2100° UL 103 HT
chimney). With optional close clearance shield and pipe shield.
NOTE: For installation of optional pipe shield (See Page 23).
NOTE: For minimum clearances (See Page 12, Figure 8).
For Required Out Side Air in Mobile Homes (See Page 15).
1. Suspend a plumb bob from ceiling above unit so that weight is hanging in center of flue
exit. (A small weight on a string will serve as a plumb bob). Mark ceiling where string is
suspended to locate center of the chimney.
2. After locating center of hole, install ceiling support box, chimney or chimney connector,
flashing and rain cap, per chimney manufacturer’s instructions and local building codes
for installation through combustible walls or ceilings.
3. Now connect stove and ceiling support box using DVL close clearance pipe. Connect
each section, per manufacturer’s instructions. Secure each section to each other using
minimum (3) sheet metal screws or rivets.
DVL close clearance is to be connected with (3) sheet metal screws or rivets to
connector collar on heater (See Page 12,Figure 9).
If appliance is installed in mobile homes:
WARNING:DO NOT INSTALL IN SLEEPING ROOMS.
Page 11
Page 14
C
C
BACKWALL
A
E
B
F
C
C
D
G
C. Vertical exit using (6" DVL Close Clearance pipe and
any listed 2100° UL 103 HT. TYPE Chimney). With pipe shield.
Model 21 Elite minimum clearance to combustibles.
Figure 8.
BACK WALL
SIDE WALL
E
A
B
PROTECTOR PAD
F
D
G
LISTED 2100° UL 103 HT
TYP. CHIMNEY
DONOTOBSTRUCT
RADIATION SHIELD
LISTED 2100° UL 103 HT
TYP. CHIMNEY
Figure 9.
CONTEMPORARY CAP
CAULK
STORM COLLAR
FLASHING
INSTALLATION
CEILING
C
C
SIDE
WALL
A B C D E F G
MODEL 21 19”7" 7"8.5" 8" 6" 16"
NOTE: All clearances are to combustibles with optional close clearance shields and pipe shield,
using DVL Close Clearance pipe, and minimum floor protector.
CEILING SUPPORT
DVL CLOSE
CLEARANCE PIPE
Pipe Shield.
Page 12
Page 15
HOW TO LOCATE CHIMNEY EXIT AND INSTALL
Residential and Mobile Home Installation
D. Vertical Wall Exit using (6" DVL Close Clearance Pipe and elbow and any Listed 2100°
UL HT chimney and Listed 2100° UL HT T-Box assembly).
With optional pipe shield.
NOTE: For installation of optional pipe shield (See Page 23).
NOTE: For minimum clearances (See Page 14, Figure 10).
For Required Out Side Air in Mobile Homes (See Page 15).
1. Mark plumb line on wall directly behind center of heater.
(See Page 14, Figure 9).
NOTE: When using DVL Close Clearance Pipe, maintain manufacturer’s minimum
clearances between pipe and ceiling.
2. Place vertical portion of heater pipe and elbow in position and project a point onto plumb
line level with center of elbow.
3. Measure up so there will be at least 1/4" rise per foot of horizontal connector pipe, maintaining clearances to ceiling as noted in (Page 13, Figure 9). This will give you the center
of hole for chimney penetration.
4. After locating center of penetration, install the tee-box and chimney, per chimney
manufacturer's specifications.
5. Connect the DVL close clearance pipe to tee-box, per manufacturer’s instructions.
DVL close clearance pipe is to be connected with (3) sheet metal screws or rivets to
connector collar on heater.(See Page 14, Figure 11).
If appliance is installed in mobile homes:
WARNING: DO NOT INSTALL IN SLEEPING ROOMS.
Page 13
Page 16
D.
C
C
BACKWALL
A
E
B
F
C
C
D
G
Vertical wall exit using (6" DVL Close Clearance pipe with elbow
and any listed 2100° UL 103 HT. TYPE Chimney
and
Listed 2100° UL HT T-Box assembly
). With pipe shield.
Model 21 Elite minimum clearance to combustibles.
BACK WALL
SIDE WALL
PROTECTOR PAD
E
A
B
F
H
D
G
A B C D E F G
MODEL 21 ELITE 19” 7" 7" 8.5" 8" 6" 16"
Figure 10.
C
C
NOTE: All clearances are to combustibles with close clearance shields and pipe shield, DVL
Close Clearance pipe with elbow and minimum floor protector.
LISTED 2100° UL 103 HT TYP.
NOTE:
CENTER LINE
OF ELBOW
MARK PLUMB
LINE ON WALL
CEILING
Maintain 18"Minimum Clearance
DVL CLOSE
CLEARANCE
PIPE
Figure 11.
Pipe Shield
INSTALLATION INSTRUCTION
IN
SIDE
WALL
WALL
PASS-THROUGH
CONNECTOR
CHIMNEY REFER TO
MANUFACTURER’S
LISTED 2100° UL 103 HT
TYP. CHIMNEY T-BOX
ASSEMBLY REFER TO
MANUFACTURER’S
INSTALLATION
INSTRUCTION
Page 14
Page 17
OPTIONAL OUT SIDE AIR INSTALLATION
Select an installation location that will give the best airflow from the front
of the heater to the remainder of the home.
TOOLS FOR INSTALLATION:
Drop cloth: 3/32” Meal drill bit: 5/16” magnetic socket chuck adapter: 5/16” wrench (box or socket) or
adjustable wrench: jigsaw with masonry metal and wood blades.
1. Select an installation location that will give the best airflow from front of heater to remainder of
home.
2. Choose which installation you are going to use.
3. Place floor protector according to manufactures specification in manual.
THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR , WALL AND
CEILING/ROOF MUST BE MAINTAINED. MOVE SPACE OPENING
AND / OR REPOSITION HEATER LOCATION IF NECESSARY ) .
5. Now measure and mark on floor protector location of heater using minimum clearance to combustible
walls.
in which section you chose to install.
(See Section A page 7-8, Section B page 9-10, Section C page 11-12, Section D page 13-14,
6. Mark a 4 1/4” circle on floor protector. Cut out floor protector and continue all the way threw floor.
(See Figure 12).
OUTLINE OF UNIT LOCATION
Figure 12.
7. Obtain outside air duct and slip duct down through the 4 1/4” hole until the face of outside air duct
contacts pad. Secure outside air duct to pad using four #10 X1” screws provided.
.
8. You may hook out side air kit to dryer vent hose. NOTE: If home is underpinned, you must run duct
through underpin as shown.
(See Figure 14
CAUTION:
4 1/4’ HOLE FOR OUTSIDE AIR
).
PROTECTIVE PAD
(See Figure 13
)
).
NOTE: THE FLAP ON DRYER VENT OUTLET MUST BE LOCKED IN THE OPEN POSITION.
(HOSE MUST EXTEND THREW OUTSIDE WALL OF STRUCTURE.)
Figure 13
(4) #10x1
FLOOR PROTECTOR
UNDER SIDE OF MOBILE HOME
OUTSIDE AIR DUCT
OUTSIDE AIR DUCT THROUGH
FLOOR WHEN MOBILE HOME IS
NOT UNDERPINNED.
Page 15
Figure 14
OUTSIDE AIR DUCT
THROUGH UNDERPINNED.
FLAP ON
VENT
MUST BE
OPEN
Page 18
9. Your unit is equipped with 4 leveling legs located on outer bottom at each corner, you may have to adjust
24"min.(610mm)
RAINCAP
FLASHING
RADIATIONSHIELD
24"min.(610mm)
RAINCAP
FLASHING
RADIATIONSHIELD
36"TYP.
36"TYP.
20FT.MAX.
for your unit to sit level.
10. Place insulation tape onto the top four edges of floor duct.
(See Figure 18
Figure 15.
).
(See Figure 15
).
INSULATION TAPE
11. Place insulation tape onto edges of bottom outside air kit.
12. Now position unit in correct position, meeting the correct
minimum clearance.
13. Place bottom part of outside air kit on top of floor duct
and screw together. Fasten bottom air kit to back of
unit with the screws.
INSULATION TAPE
(See Figure 16
).
14. Place insulation tape onto edges of top outside air kit.
15. Place top part of outside air kit over bottom outside
air kit making sure to cover air channel extension.
Fasten top air kit to back of unit with the screws
(See Figure 17
).
INSULATION TAPE
COVER AIR CHANNEL EXTENSION
Figure 16.
BOTTOM AIR KIT
Figure 17.
16. Open screen doors, you will find 4 holes in outer bottom. These are there if you have to fasten unit to
floor. Drill threw holes and using leg bolts fasten to floor. If thicker floor protector is used you may have
to use longer leg bolts.
17. Now you may start installing your flue system. NOTE: FOLLOW PIPE MANUFACTURES
SPECIFICATION.
18. Remove any items from within firebox, check primary air draft control to ensure that it slides freely.
19. Plug power cord into a 115VC outlet, do not run power cord under unit. Your unit is equipped with
(See Figure 18
).
automatic thermostat, when stove gets hot enough this will activate your blower system. You may adjust
your fan speed by using the rheostat located on back left side facing unit
36" TYP.
FLASHING
RADIATION
SHIELD
20 ft. MAX
SECURING UNIT
HOLES FOR
Figure 18.
Figure14
RAIN CAP
24" min.(610mm)
Figure 19
FLOOR KIT
TOP AIR KIT
LEVELING LEGS
Page 16
Page 19
FINAL CHECK
1. Recheck specified clearances.
2. Remove all foreign material from firebox area.
3. Open primary air draft.
4. Plug power cord into a 115V AC outlet.
5. Place crumpled pieces of newspaper in the stove. Light it and close door. Ensure that stove
draws properly through primary draft.
6. Check for smoke leaks around door.
Open door and check for smoke escaping from front of stove. Smoking usually indicates a
defective or poorly positioned chimney. Some chimneys with a marginal draft can be
preheated by lighting newspaper and holding it near the open damper with a poker or
fire tong. Once chimney heats up, a proper draft can usually be obtained.
If a thorough review of the Troubleshooting Guide manual does not reveal problem, contact
your dealer for assistance.
The unit is painted with a specially formulated high temperature paint that cures during
the first two or three firings. You may notice a slight smoking effect and an odor of
burning pain when you build the first fires. This is normal and is not a cause for
alarm. In some cases, these fumes will activate a smoke alarm. Opening a window near
the unit will allow these fumes to escape. DO NOT build a large, roaring fire until this
curing is complete or the heater finish may be damaged.
CAUTION
CAUTION
Page 17
Page 20
SECTION III
ALCOVE INSTALLATION
AND CLEARANCES
Select an installation location that will give the best airflow from the front of the heater to
the remainder of the home.
PREPARING THE STOVE FOR INSTALLATION
Chimney
This model is designed for connection to any listed 2100º UL103 HT chimneys and parts.
This room heater must be converted to a chimney complying with the requirements for Type
HT chimneys in the Standard for chimneys, Factory-Built, Residential, Type and
Building Heating Appliance, UL 103.
1. Select an installation location that will give the best airflow from front of heater to
remainder of home.
2. Now choose which installation you are going to use.
3. Place floor protector according to manufactures specification in manual.
4. Now position unit in correct position, meeting the correct minimum clearance.
5. Your unit is equipped with 4 leveling legs located on outer bottom at each corner, you may
have to adjust for your unit to sit level.
6. Open screen doors, you will find 4 holes in outer bottom. These are there if you have to
fasten unit to floor. Drill threw holes. Using leg bolts fasten to floor. If thicker floor
protector is used you may have to use longer leg bolts.
7. Now you may start installing your flue system. NOTE; FOLLOW PIPE
MANUFACTURES SPECIFICATION.
8. Remove any items from within firebox, check primary air draft control to ensure that it
slides freely.
9. Plug power cord into a 115VC outlet, do not run power cord under unit. Your unit is
equipped with automatic thermostat, when stove gets hot enough this will activate your
blower system. You may adjust your fan speed by using the rheostat located on left side
front center facing unit.
(See Page 16, Figure 18
(See Page 16, Figure 19
).
).
Page 18
Page 21
Floor Protection:
Floor protection must be 3/8” minimum thickness non-combustible material or equivalent.
How to use alternate materials and how to calculate equivalent thickness
An easy means of determining if a proposed alternate floor protector meets requirements listed
in the appliance manual is to follow this procedure:
1. Convert specification to R-value:
R-value is given—no conversion is needed.
K-factor is given with a required thickness (T) in inches:
C-factor is given: R=1/C
2. Determine the R-value of the proposed alternate floor protector.
Use the formula in step (1) to convert values not expressed as “R”For multiple layers, add R-values of each layer to determine the overall R-value.
3. If the overall R-value of the system is grater than the R-value of the specified floor protec-
tor, the alternate is acceptable.
Example:
The specified floor protector should be 3/4” thick material with a K-factor of 0.84.
The proposed alternate is 4” brick with a C-factor of 1.25 over 1/8” mineral board with a
K-factor of 0.29.
Step (a): Use formula above to convert specification to R-value. R= 1/K x T = 1/0.84 x .75 =
0.893
Step (b): Calculate R of proposed system. 4” brick of C=1.25, therefore Rbrick = 1/C = 1/1.25
=0.80 1/8” mineral board of K = 0.29, therefore Rmin.bd. =1/029 x0.125 = 0.431
Step (c): Compare proposed system R of 1.231 to specified R of 0.893. Since proposed
system R is greater than required , the system is acceptable.
Definitions:
Thermal conductance = C =
Btu
(hr)(ft²)(°F) (m²)(°K)
=
W
Thermal conductance = K =
(Btu)(inch)
(hr)(ft²)(°F) (m)(°K)(hr)(ft)(°F)
=
W
=
(Btu)
Thermal conductance = R =
(ft²)(hr)(°F)
BtuW
(m²)(°K)
=
Install in accordance with 24 CFR, Part 3280 (HUD).
Page 19
Page 22
HOW TO LOCATE CHIMNEY EXIT AND INSTALL
Alcove Installation
Vertical Exit using (6" DVL Close Clearance pipe and any Listed 2100° UL 103 HT
chimney). Pipe shield must be used.
NOTE: For minimum clearances (See Page 21, Figure 20).
1. Suspend a plumb bob from the ceiling above unit so that weight is hanging in center of
flue exit. (A small weight on a string will serve as a plumb bob). Mark ceiling where
string is suspended to locate center of chimney.
2. After locating center of hole, install ceiling support box, chimney or chimney connector,
flashing and rain cap, per chimney manufacturer’s instructions and local building codes
for installation through combustible walls or ceilings.
3. Now connect stove and ceiling support box using DVL close clearance pipe. Connect
each section per manufacturer’s instructions.
4. Secure each section to each other using minimum (3) sheet metal screws or rivets.
DVL close clearance is to be connected with (3) sheet metal screws or rivets to
connector collar on heater.(See Page 21,Figure 21).
Page 20
Page 23
ALCOVE INSTALLATION
BACKWALL
A
E
B
F
C
C
D
G
D
AND CLEARANCES
Vertical exit using (6" DVL Close Clearance pipe and
any listed 2100° UL 103 HT. TYPE Chimney).
With optional pipe shield.
Model 21 Elite minimum clearance to combustibles.
Figure 20.
Figure 21.
A
PROTECTOR PAD
BACK WALL
B
D
F
LISTED 2100° UL 103 HT
TYP. CHIMNEY
H
DONOTOBSTRUCT
G
RADIATION SHIELD
LISTED 2100° UL 103 HT
TYP. CHIMNEY
INSTALLATION
CEILING
SIDE
WALL
C
SIDE WALL
A B C D E F G H
MODEL 21 19”7" 84"8.5" 8" 6" 16" 48"
NOTE: All clearances are to combustibles with pipe shield, using DVL Close Clearance pipe and
minimum floor protector.
E
CONTEMPORARY CAP
CAULK
STORM COLLAR
FLASHING
CEILING SUPPORT
DVL CLOSE
CLEARANCE PIPE
PIPE SHIELD
Page 21
Page 24
FINAL CHECK
1. Recheck specified clearances.
2. Remove all foreign material from firebox area.
3. Open primary air draft.
4. Plug the power cord into a 115V AC outlet.
5. Place crumpled pieces of newspaper in stove. Light it and close door. Ensure that
stove draws properly through primary draft.
6. Check for smoke leaks around door.
CAUTION
Open door and check for smoke escaping from the front of stove. Smoking usually
indicates a defective or poorly positioned chimney. Some chimneys with a marginal draft
can be preheated by lighting newspaper and holding it near open damper with a poker or
fire tong. Once chimney heats up, a proper draft can usually be obtained.
If a thorough review of Troubleshooting Guide in the manual does not reveal problem, contact
your dealer for assistance.
The unit is painted with a specially formulated high temperature paint that cures during
first two or three firings. You may notice a slight smoking effect and an odor of burning
paint when you build first fires. This is normal and is not a cause for alarm. In some
cases, these fumes will activate a smoke alarm. Opening a window near unit will allow
these fumes to escape. DO NOT build a large, roaring fire until this curing is complete or
heater finish may be damaged.
CAUTION
Page 22
Page 25
Installation of Pipe Shield
1. Place pipe shield above top rear of stove cabinet. (See Figure 22).
2. Measure from the top of the back of stove and place the pipe shield 1” above stove top on
both sides keeping the pipe shield centered at the back. (See Figure 23).
3. Using the screws provided fasten pipe shield to the top back of stove cabinet and stove back
shield. (See Figure 23).
Figure 22.
PIPE SHIELD
STOVE REAR SHIELD
TOP REAR
CABINET
SCREWS
Figure 23.
1”
Page 23
Page 26
SECTION IV
OPERATION
This section of manual is to help you get maximum efficiency and maximum smoke
(particulate) reduction from your heater. If you should experience any difficulty or
have any questions concerning your heater, contact your dealer for assistance. The manufacturer
recommends that for maximum performance burn dried natural seasoned hard wood.
Build a fire for maximum efficiency. These models burn wood and extract heat so efficiently,
a large fire is not necessary. A large fire not only wastes energy, it usually results in home being
too warm for comfort.
BUILDING A FIRE
1. Open door.
2. Primary air control. The Primary Control Rod is located in front under the hearth.
FULL OPEN, push the primary control rod all the way in.
3/4 OPEN, pull 7/16”
1/2 OPEN, pull 7/8”
1/4 OPEN, pull 1 5/16 ”
FULL CLOSE, pull all the way 1 3/4 ”
FULL OPEN —-
7/16 3/4 —-
7/8 1/2 —-
1 5/16 1/4 -—
1 3/4 FULL CLOSE —-
FULL OPEN
CLOSE
PRIMARY CONTROL ROD
3. Twist two pieces of non-colored newspaper into a roll and place them on the floor of
firebox.
4. These models are not designed for use of grates, andirons or other methods of supporting
fuel.
NOTE: Do not use grate or elevate fire. Build wood fire directly on inner bottom of fire box.
5. Lay several pieces of dry kindling on top of newspaper.
6. Place three or four small pieces of firewood, 2-3" in diameter, on top of kindling.
7. Light newspaper in front. Close and latch door. Don't leave fire unattended at this point.
The draft system of heater should start quickly. It may be necessary to preheat chimney to
get draft started. To do this, open door and add newspaper to top backside of wood. Light or
let paper ignite and allow to burn while holding door slightly cracked. Once draft has
started, close and lock door. You are over heating unit if chimney and or connector glows
red.
8. After embers and a coal bed have been established, load heater with dried natural seasoned
hard wood.
NOTE: THE FUELING DOOR MUST REMAIN CLOSED DURING OPERATION.
NOTE: If blower is being used on the Model 21 Elite, your stove is equipped with a automatic
thermostat. When stove gets hot enough, thermostat will activate room air blower. Set
fan speed using rheostat according to desired heat output. Rheostat is located on back
left side facing unit.
NOTE: When refueling or removing ashes turn “OFF” room air blower. Be sure to turn room
air blower back on when finished.
NOTE: Do not run power cord underneath heater or in walk way or heavy traffic areas.
Page 24
Page 27
SECTION V
OPERATION FOR ROOM AIR BLOWER
AMD MAINTENANCE
Your heater is equipped with a room air blower. For operation and wiring see blow. (Figure 25).
Operation:
After heartier has warmed up the thermostat will automatically turn on blower. When the stove
cools off, thermostat will automatically shout off blower.
WIRE DIAGRAM
THERMOSTAT
MOTOR
GREEN
GROUND
BLACK
M
F
WHITE
BLACK
JUMPER
F
M
F
BLACK
JUMPER
Figure 25.
F
BLACK
JUMPER
WHITE
M
M
F
WHITE
F
F
M
BLACK
JUMPER
F
BLACK
M
GREEN
GROUND
BLACK
RHEOSTAT
POWER CORD
Page 25
Page 28
MAINTENANCE
DOOR GASKET REPLACEMENT (COLD HEATER)
To replace deteriorated gaskets, following steps must be taken to ensure proper installation of
gaskets.
1. Obtain proper gaskets and silicone glue from your local dealer.
2. Using pliers, remove any worn and deteriorated gaskets.
3. Using a scraper, wire brush and sandpaper or steel wool, clean glue and gasket residue from
door frame.
4. Measure and cut gaskets to length. Care should be taken not to stretch gaskets. What you
want is a full and loose gasket weave after attachment to framing.
5. Obtain silicone glue and run a 3/16” bead inside door frame.
6. Obtain gasket (s) and place in gasket channel areas starting at lower right corner, See below.
Use a technique which assures that gasket is applied in a loose like manner. DO NOT STRETCH GASKETS.
7. After gasket (s) are applied to glue, use your finger and go over all gasket gently pressing
gasket to the channel. Use same pressure against gasket so that final result is an evenly
applied gasket.
8. Leave door open and allow at least two (2) hours for glue to dry.
9. Once gaskets are checked, heater is ready for use.
10. This should be done annually. Allowing gaskets to deteriorate can cause over-firing and
shorten burn time.
START HERE
ROPE GASKET
21 ELITE LATCH
PS21E088
SILICONE
Page 26
Page 29
MAINTENANCE
CHECK CHIMNEY
A. Chimney should be inspected twice a year.
B. The chimney should be cleaned as necessary to remove creosote, soot, leaves, birds nests,
etc.
Before sweeping the chimney a few steps must be done.
1. Open feed door and remove the 1st Secondary Air Tube by removing cotter pin up in right
side facing stove. Remove air tube and cotter pin, set aside.
2. Gently remove the
3. Close feed door for cleaning chimney so debris don't fall out feed door while cleaning
chimney.
4. Creosote and debris will fall into the bottom of the stove unit from the cleaning.
5. Clean out all the creosote and debris from inside stove unit left from clean sweeping
chimney.
6. To replace Baffle Board and 1st Secondary Air Tube, reverse steps 1-2.
NOTE:
sparks and burning materials from escaping chimney and to keep birds and foreign materials from
!
entering.
NOTE: Some areas may require an approved spark arrestor.
A chimney cap should be installed to prevent moisture from entering chimney, to prevent
*
A. The heater should not be cleaned with any type of detergent as most all detergents have an
oil base and cannot be painted over.
B. The heater should be lightly sanded with fine sandpaper or steel wool, then repainted or
touched up with high temperature paint.
C. If the heater is located in a moist or damp location, check thoroughly for signs of
condensation during times when heater is not in use.
D. When heating season is over, heater should be cleaned out completely with a wire brush or
cloth to help eliminate ash and burned wood smell.
Baffle Board
INSULATION BLANKET
1ST SECONDARY AIR TUBE
and set aside.
CLEANING THE HEATER
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
Page 27
Page 30
The glass door on your heater permits you to enjoy the beauty of the fire while retaining
efficiency of your heater. Although brand of glass used in heater door has well established and
recognized heat resistant and strength characteristics, it can be broken through improper care.
To achieve maximum utility and safety of your glass door, we advise that you observe
following use and safety tips:
1. Inspect glass regularly for cracks or breaks. If you detect a crack or break extinguish
fire immediately and return door to your dealer for glass replacement
before further use.
2. Do not slam heater door or otherwise impact glass. When closing door, make sure that
no logs or other objects protrude that would impact against glass.
3. Do not clean glass with materials which may scratch it (such as steel wool) or otherwise
The glass can be cleaned with a commercial oven cleaner, providing it does not contain
abrasives. A build-up on glass that has been there for a considerable length of time can be
burned off with a propane torch or straight razor blade. Use protective gloves when using razor.
To replace broken or cracked door glass fallow steps below.
damage glass. Scratches on the glass can develop into cracks or breaks.
NEVER SUBSTITUTE GLASS MATERIAL, USE ONLY CERTIFIED NEW BUCK CORP.
MAINTENANCE
CARE OF GLASS DOOR
(#PG2124GL)
#PG2124GL CERAMIC GLASS. IT MAY CAUSE DAMAGE AND VOID YOUR WARRANTY.
1. Please use caution and safety when handling broken glass and use safety glasses and
gloves.
2. Remove and dispose of any easily loose, broken glass from the stove and area before
starting any work with the door. Dispose of glass properly.
3. Lay a piece of card board or drop cloth large enough for door to lay face down on, place
door on card board or drop cloth to protect surface of door and to catch any lose or falling
glass.
4. Remove glass clips from back of door by removing glass clip screws holding clips and
dispose of the rest of any broken glass properly. Clean out all broken glass thoroughly.
5. Place new ceramic glass (SIZE CUSTOM FIT Part# PG2124GL BUCK STOVE CORP.) in
door frame and replace glass clips and secure with glass clip screws. Do not over tighten
screws or glass could crack.
6. Replace door onto unit.
DOOR FRAME
GLASS CLIPS
.
.
.
.
.
#PG2124GL GLASS
Page 28
.
.
.
.
.
Page 31
MAINTENANCE
To replace Thermostat:
1. NOTE: Make sure stove is cool and unplug power cord to unit.
2. Remove access plate located at the rear of unit on the top right side of stove back by
removing four (4) screws holding plate. (See Figure 29).
3. Unplug wires to thermostat.
4. Remove the thermostat buy unscrewing two (2) screws holding the thermostat.
5. Replace thermostat with # listed in replacement parts list.
6. To reinstall thermostat reverse step 4.
7. Plug wires back onto thermostat.
8. Replace access plate located at the rear of unit and plug power cord in receptacle outlet.
ACCESS PLATE
STOVE BACK
REAR
BACK
Figure 29.
RHEOSTAT
SCREWS
HOLDING
REAR
BACK
FRONT LEFT
SIDE CABINET
CABINET
DOOR ’ S
Figure 30.
THERMOSTAT
ACCESS PLATE
INNER BACK
OUTER BACK
REAR
BACK
MOTOR
SCREW HOLES
.
.
MOTOR
COVER
POWER CORD
To replace Motor from rear of unit:
1. NOTE: Make sure stove is cool and unplug power cord to unit.
2. To access motor, remove rear back by unscrewing the twelve (12) screws holding rear back to unit, lay a
side. (See Figure 29).
3. Remove two (2) screws holding motor cover and lay aside. (See Figure 30).
4. NOTE: Mark wires before unwiring motor.
5. Replace motor with new unit # MA5126715 .
7. If needed, See wiring diagram. (See Page 25, Figure 25).
6. To reinstall motor reverse steps 1-5. Plug power cord in receptacle outlet.
Page 29
Page 32
MAINTENANCE
To replace Motor from front of unit:
NOTE: If back of stove is close to wall, you may access motor from front cabinet doors.
1. NOTE: Make sure stove is cool and unplug power cord to unit.
2. To access motor, open cabinet doors. Motor cover is located in left upper rear. (See Figure 31).
3. Remove two (2) screws holding motor cover and lay aside. (See Figure 31).
4. NOTE: Mark wires before unwiring motor.
5. Replace motor with new unit # MA5126715.
7. If needed, See wiring diagram. (See Page 25, Figure 25).
6. To reinstall motor reverse steps 1-5. Plug power cord in receptacle outlet.
CABINET
DOOR ’ S
Figure 31.
MOTOR
SCREW HOLES
.
.
RHEOSTAT
MOTOR
COVER
Page 30
Page 33
21 ELITE
REPLACEMENT PARTS LIST
1 - SMALL DOOR WITH ROPING
2 - SMALL DOOR ASSEMBLY
1 - SMALL DOOR GLASS
1 - SMALL DOOR GLASS ROPING
4 - SMALL DOOR GLASS CLIPS
10- DOOR GLASS SCREWS
1 - DOOR HANDLE RETROFIT
1 - DOOR HANDLE LATCH 21 ELITE
1 - DOOR HANDLE BUSHING
1 - DOOR HANDLE SPACER
1 - DOOR HANDLE WASHER (FLAT)
1 - DOOR LATCH SCREW (PHILLIPS HEAD)
1 - SPRING HANDLE (FOR DOOR HANDLE)
2 - KNOB’S (FOR SCREEN DOORS)
1 - KNOB (FOR AIR CONTROL)
POBC413
3 - SECONDARY AIR TUBE’S
1 - BAFFLE BOARD
3 - COTTER PINS (FOR SECONDARY AIR TUBE’S)
- FULL FIRE BRICK 1 1/4”T X 4 1/2”W X 9”L
- CUT FIRE BRICK 1 1/4”T X 2 1/4”W X 9”L
1 - BLOWER MOTOR
1 - RHEOSTAT
1 - THERMOSTAT (110°)
1 - POWER CORD
1 - STRAIN RELEASE
- MALE TERMINALS
4 - JUMPER WIRE
1 - FAN SPEED CONTROL LABEL
1 - RHEOSTAT KNOB
PS210026
POBPFB01
PH182CPSS
PR900050
PR900050
PESBR085
PEBC204
PE400132
PE400240
PE400320
PE5X428
PE30JUMPER
Page 31
Page 34
SECTION VI
WOOD HEATER SAFETY
Certain safety hazards are inherent in any wood heater installation. You should be aware of
these so that a safe and proper installation can be made.
1. FAULTY FLUE: An older flue should be thoroughly checked to be sure there are no holes
or weak spots which could allow sparks or hot gases to escape.
2. HEAT CONDUCTION: Placing combustible materials too close to a heater or chimney can
be a fire hazard.
By keeping these particular hazards in mind as you install and use your room heater you can
ensure a safe, reliable installation.
When burning wood the chimney and chimney connector should be inspected once every two
months during the heating season to determine if a creosote buildup has occurred. Any buildup of soot should be removed to prevent risk of a chimney fire. To remove chimney or chimney
connector: remove screws or fasteners then remove pipe and clean with steel brush. Replace
chimney or chimney connector and replace screws and/or fasteners.
NEVER USE GASOLINE, GASOLINE TYPE LANTERN FUEL KEROSENE,
CHARCOAL LIGHTER FLUID OR SIMILAR LIQUIDS TO START OR "FRESHEN
UP" A FIRE IN THE HEATER. KEEP ALL SUCH LIQUIDS WELL AWAY FROM
STOVE WHEN IT IS IN USE. ALL FLUIDS OF THIS TYPE GIVE OFF
VOLATILE FUMES AND CAN AND WILL EXPLODE! DON'T TAKE A CHANCE
WITH SAFETY OF YOUR HOME AND FAMILY.
CAUTION: Never remove ashes from heater with blower running.
DISPOSAL OF ASHES: Ashes should be placed in a metal container with a tight fitting lid.
The closed container of ashes should be placed on a noncombustible floor or on the ground,
well away from all combustible materials pending final disposal. If ashes are disposed of by
burial in soil or otherwise locally dispersed, they should be retained in closed container until all
cinders have thoroughly cooled.
CREOSOTE—FORMATION AND NEED FOR REMOVAL: When wood is burned
slowly, it produces tar and other organic vapors, which combine with expelled moisture to form
creosote.The creosote vapors condense in the relatively cool chimney flue of a slow-burning
fire. As a result, creosote residue accumulates on flue lining. When ignited this creosote makes
an extremely hot fire.
CAUTION
Page 32
Page 35
SECTION VII
TROUBLESHOOTING
PROBLEM POSSIBLE CAUSE SOLUTION
Sluggish HeaterObstruction in chimneyCheck for and remove
obstruction
High Fuel Consumption Improper regulation of draft
Wet or unseasoned wood
being burned.
Poor chimney draft Improper chimney height or
or inlet air
Burn dried natural seasoned
hard wood.
wrong size flue is being used.
Cooler temperatures caused
by external chimney.
(a) Close inlet air control as
much as possible to
maintain desired heat
output.
(b) Check gaskets, reinstall
fiberglass gasket around
doors and glass as
necessary
Backpuffing Gusts of Wind Chimney may need wind
Smoke rolls out when heater
door is opened.
Improper door fitting Check door gasket, check
adjustment of door latch.
diverts. Raise chimney for
better draft.
Wind gusts blowing down the
chimney
Opening heater door too fast Crack door for 15 seconds
Chimney may need wind
diverts. Raise chimney for
better draft.
before fully opening door.
Page 33
Page 36
NEW BUCK CORPORATION (NBC)
"LIMITED WARRANTY" FOR THE BUCK STOVE
PLEASE READ THIS WARRANTY CAREFULLY
PRODUCTS COVERED
This warranty covers the new Buck Stove heating unit, so long as it is owned by original
purchaser, including optional and standard accessories purchased at same time, subject to terms,
limitations, and conditions herein set out.
PRODUCTS NOT COVERED
This warranty does not cover the following:
Glass, Refractory Material, Firebrick or Gaskets.
This Warranty will not cover any damage and/or failure caused by abuse or improper installation
of products covered.
WARRANTY TIME PERIODS
(A) Period I
For one (1) year from the date of purchase, NBC will replace or repair, at its option, any
part defective in materials or workmanship. The costs of parts only are included. The
customer pays any labor or transportation charges required.
Thereafter,
(B) Period II
For a period after first year from date of purchase and extending for five (5) years as long as
the Buck Stove is owned by original purchaser, NBC will repair or replace, at
its option, any part defective in materials or workmanship, with exception of: electrical
motors, wiring, switches, components, optional and standard accessories and all parts not
permanently attached to heating unit. Parts not permanently attached to heating unit are
defined as those items designed to be removed from stove, including those removable with
common hand tools. The costs of parts only are included. The customer pays any labor or
transportation charges required.
.
PROCEDURE
Should you feel that your BUCK STOVE is defective, you should contact any Buck Stove
dealer for name of your nearest authorized Buck Stove service representative, who will instruct
you on proper procedure, depending on which Warranty Time Period (Period I or Period II)
applies.
Page 34
Page 37
If for any reason you are dissatisfied with suggested procedures, you may contact us in
writing at:
New Buck Corporation
Customer Service Department
P. O. Box 69
Spruce Pine, NC 28777
Email: info@buckstove.com
CONDITIONS AND EXCLUSIONS
(A) Replacement of parts may be in form of new or fully reconditioned parts, at NBC's option.
(B) There is no other express warranty. All implied warranties of merchantability and fitness for
use are limited to duration of Express Warranty.
(C) New Buck Corporation is not liable for indirect, incidental or consequential damages in
connection with use of product including any cost or expense of providing substitute
equipment or service during periods of malfunction or non-use.
Some states do not allow exclusion of incidental or consequential damages, so
above exclusion may not apply to you.
(D) All warranty repairs under this warranty must be performed by an authorized Buck Stove
service representative. Repairs or attempted repairs by anyone other than an authorized
service representative are not covered under this warranty. In addition, these unauthorized
repairs may result in additional malfunctions, correction of which is not covered by
warranty.
OTHER RIGHTS
This warranty gives you specific legal rights and you may also have other rights, which vary
from state to state.
OWNER REGISTRATION CARD
The attached Owner Registration Card must be completed in its entirety and mailed within 30
days from date of purchase or from date of installation, if installed by a factory certified
installer, to New Buck Corporation in order for warranty coverage to begin.
PLEASE NOTE: The Owner Registration Card must contain Authorized Buck Stove
Dealer Code Number and the Certified Installer's number (if applicable) for warranty coverage to
begin.
To be completed by selling distributor/ dealer/ customer:
Name ________________________________________________________________________
(Last) (First)
Address ______________________________________________________________________
City _______________________________________ State _________ Zip _________________
CUSTOMER EMAIL::_________________________________________________________
MODEL 21 ELITE
Serial Number _________________________________________________________________
Date of Installation: Day _______________ Month _________________ Year ______________
Installer’s Name _______________________________________________________________
Installer’s Certification Number __________________________________________________
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.